THE IMPORTANCE OF INDOOR AND OUTDOOR AIR-FILM COEFFICIENT MEASUREMENT TO SOLAR CALORIMETERY

Size: px
Start display at page:

Download "THE IMPORTANCE OF INDOOR AND OUTDOOR AIR-FILM COEFFICIENT MEASUREMENT TO SOLAR CALORIMETERY"

Transcription

1 SESCI 2004 Conference University of Waterloo Waterloo, Ontario, Canada August 21 st -25 th, 2004 THE IMPORTANCE OF INDOOR AND OUTDOOR AIR-FILM COEFFICIENT MEASUREMENT TO SOLAR CALORIMETERY M. Collins Dept. of Mechanical Engineering, University of Waterloo, Waterloo, Ontario, N2L 3G1, Canada ABSTRACT In advance of a new hotbox standard that deals specifically with solar calorimetry, the present analysis addresses the potential calculation errors associated with inaccurate and improper correction of the interior and exterior air-film coefficients. That standard, ASTM C Standard Test Method for Measuring the Solar Heat Gain Coefficient of Fenestration Systems using Calorimetry Hot Box Methods, has adopted the use of a Calibration Transfer Standard to determine the combine radiative and convective heat transfer coefficient on the indoor side of a test window, and a sol-air film coefficient meter on the outdoor side. The adaptation of these methods is discussed. Generally, the accepted hotbox calibration procedure is applicable with modification. The errors associated with improper calibration are also examined with respect to the standard test procedure. It is shown that in most cases, large errors in the thermal transmission (U-factor result in small errors in the calculated Solar Heat Gain Coefficient (SHGC. It was discovered, however, that incorrect calibration procedure could introduce significant errors in both the SHGC and thermal transmission (U-factor. Of note, tests conducted in still conditions, or those conducted when glass and air temperatures are similar, could produce errant results. NOMENCLATURE A = Area, m 2 F = View Factor, dimensionless G = Solar Radiation, W/m 2 h = Heat Transfer Coefficient, W/m 2 K k = Thermal Conductivity, W/mK N = Inward-Flowing Fraction, dimensionless Q = Energy Flow, W SHGC = Solar Heat Gain Coefficient, dimensionless T = Temperature, o C or K ΔT = Temperature Difference, o C or K U = Thermal Transmission, W/m 2 K α = Absorptivity, dimensionless ε = Emissivity, dimensionless η = Instantaneous Efficiency, dimensionless θ = Tilt Angle, degrees τ = Transmissivity, dimensionless Subscripts 30_8 = Case where h o = 30 and h i = 8 W/m 2 K abs = Absorber Panel 1

2 act = Actual aux = Calorimeter Auxiliary Power c = Glazing Cavity conv = Convective cor = CTS Core CTS = Calibration Transfer Standard error = Percent Error error,oper = Percent Error due to Operator error,test = Percent Error due to Off-Standard Test error,total = Total Percent Error g1 = Outdoor Glass g2 = Indoor Glass i = Indoor flow = Calorimeter Flow Loop mask = Calorimeter Mask Wall meas = Measured net = Net Gain o = Outdoor p = Plate (Sol-Air Heat Coefficient Meter sky = Sky surr = Surroundings walls = Calorimeter Walls x = Variable INTRODUCTION In recent years, responsible and sustainable energy use has been an important motivating factor in the design of new building products. Of particular note, the thermal and solar performance of windows will likely play a substantial role in energy efficient construction of the future [1]. Gas fills, spectrally selective coatings, a variety of shading devices, and so-called switchable glazings (electrochromic, thermochromic, or photochromic windows either currently provide, or show great promise, in providing substantial energy savings. The complex and varied nature of advanced window technologies also makes it difficult to assess the performance of these products. With the exception of gas fills and spectrally selective coatings, industry standard window analysis software [2,3] cannot analyze the thermal or solar performance of shaded or switchable glazings. Consequently, experimental methods (i.e., calorimetry stand to play an important role in the development and rating of new products. Window performance is evaluated using both hotbox testing (thermal, and solar calorimetry (solar and thermal. While hotbox methods are standardized and well documented [4,5,6], a standard test method for performing solar calorimetric testing, ASTM C [7], is only now being produced. One problem in developing this standard is that North American operators of solar calorimeters have each developed their own calorimeters, methods of calibration, and calorimetric test procedures. Inconsistencies exist not only in the quality of calorimeters and their calibration, but also in the applicability of a calibration or test procedure when applied to a specific calorimetric design. A further difficulty results from the transient nature of test conditions. To test the solar performance of a window, it is necessary to use the sun 1. Tracking the sun's position in the sky will result in a differing view of the foreground and incident direction of the wind as the calorimeter tracks, and over the course of a test day, changing air mass and spectrum. Furthermore, as the calorimeter is outdoors, changing wind speed, turbidity, and direction, outdoor temperature, and sky conditions can all introduce 1 With the exception of Solar Simulators. 2

3 transients into the analysis. In general, calorimeter operators aim to achieve quasi-stead-state conditions, and accept the aforementioned errors within reason. The desire of rating organizations to standardize those procedures, however, is the impetus for the current discussion. The present discussion will focus on one aspect of this calibration that is of critical importance to current solar calorimeter test procedures. Specifically, the use of a Calibration Transfer Standard (CTS and sol-air heat coefficient meter in determining the indoor and outdoor combined convective and radiative heat transfer (air-film coefficients respectively. The errors inherent in the misapplication of those devices are discussed and quantified as it applies to the accepted test procedures. CALORIMETRY Construction Existing calorimeters are unique in design and operating procedure. For the purposes of this discussion, however, only those calorimeters that attempt to achieve quasi-steady conditions will be discussed (i.e., tracking calorimeters. Such calorimeters are particularly useful for rating purposes. To facilitate solar tracking, and to increase calorimeter response time, tracking calorimeters are usually more compact designs (then those utilized by hot box facilities. By reducing size, the thermal mass is reduced, thereby reducing the response time of the calorimeter. As an added benefit, it is easier and cheaper to build a solar tracker if the calorimeter is small. Omitted are stationary test cells such as MoWitt [8] and the European PASSYS cells [9]. While those calorimeters can measure the solar performance of a window, they are better suited to investigations of overall day-to-day performance of test samples. Some examples of tracking calorimeters are shown in Figure 1. Both tracking and stationary calorimeters all have several common elements. In general, they consist of an insulated or guarded wall structure and an insulated surround panel, an absorber panel / flow loop system to remove thermal energy, and associated instrumentation. To measure net heat gain through a glazing system, a test window is first mounted in the surround panel (also called a mask wall. This wall covers the calorimeter aperture and serves as the interface between the interior and exterior environment. The mask wall is generally constructed of a thick homogenous slab of insulation, with an inner and outer protective skin that is painted flat white in order to reduce radiant loading. The wall construction of the solar calorimeter is designed to reduce heat loss either by adding insulation or through the use of a guard. By eliminating the temperature gradient across the wall using a guard (ΔT walls 0, it should be possible to eliminate heat flux. The interior walls are painted black for high emissivity (ε The absorber plate is the primary energy absorption device within the calorimeter. It is a plate heat exchanger placed within the calorimeter to intercept solar radiation. It is painted matte black to increase absorptivity, and is oriented to intercept and absorb all solar Figure 1: Queen's Solar Calorimeter, Queen's University, Kingston, Ontario, Canada. radiation incident in the chamber. The temperature of the fluid in the absorber serves to regulate the interior temperature of the calorimeter. Heat extraction (or addition, and interior temperature control is primarily accomplished through the calorimeter flow loop. Within the calorimeter, conditioned fluid is added to the internal circulating loop. This loop consists of an air-to-fluid heat exchanger, the solar absorber plate, and a circulation pump. 3

4 Test Procedure The instantaneous energy flow rate through the window, Q net, is known to be the difference between the gain due to incident solar radiation, G, and the heat loss due to the air-to-air temperature difference, ΔT = (T i T o (Figure 2. Therefore Q net = SHGC G A U ΔT A (1 Here, U represents the windows overall heat transfer coefficient or U-factor at the time of testing, and A is the projected area of the window. SHGC is the Solar Heat Gain Coefficient, and is given by the equation SHGC = τ + Nα (2 where τ and α are the transmissivity and absorptivity of the window, and N is the Inward-flowing fraction of absorbed solar radiation. For a particular test, G and ΔT will be measured, while Q net is determined through careful metering of the input and output energy flows in the calorimeter Q net = Q flow Qaux + Qwalls + Q (3 mask Q flow, Q aux, Q walls, and Q mask denote: the energy removed by the calorimeter flow loop, the auxiliary electrical power supplied to the calorimeter s internal fans and/or pumps, and heat lost through the walls and mask, respectively. G Solar (Short-Wave Radiation Thermal (Long-Wave Radiation / Convection Gρ g1 Gτ g1 T o 1/h r,o T g1 1/h r,g1_g2 1/h r,i T g2 T i G τ g1 ρ g2 Gτ g1 τ g2 1/h c,o 1/h c,s 1/h i Gα g1 Gα g2 Gα g Gα g Figure 2: Solar and thermal energy transfer in a shaded and unshaded window. Inter-reflection has been omitted for clarity. Terminology is presented in the nomenclature. The SHGC can be determined from a single calorimetric test, performed in the following manner: A calorimetric test is run to determine Q net from Eqn. (2 at a measured environmental condition of G and ΔT. Generally, the indoor air temperature, T i, is controlled to standard NFRC or ASHRAE indoor temperature (21 o C [10], while the outdoor air temperature, T o, is determined by the outdoor temperature at the time of testing. With a value of U predicted via external means, SHGC can be found using Eqn. (1. Of paramount importance to this procedure, is accuracy of the predicted U-factor. One option is to perform a second test at night. By this approach, the term SHGC G = 0 in Eqn. (1, and the window U- factor can be solved directly. In following this method, it is customary to "correct" the measured U-factor to account for differences in the indoor and outdoor air-film coefficients that occurred between tests. This correction does not account for changes in the cavity air-film coefficient due to differences in glass temperatures. Assuming that the air-film coefficients are measured on both the exterior and interior sides of the window, the correction is made using the equation U = U ( 1 adj = U x + hi, act hi, x + ho, act h (4 o, x Here, h i and h o are the indoor and outdoor air-film coefficients, respectively. The subscript adj refers to the approximation to actual conditions experienced during the daytime test, while the subscript x refers to the conditions during the nighttime test. An alternative option is to find U using window analysis software [2, 3]. The calorimeter operator can model the window; including the measured test conditions. 4

5 Alternatively, the operator can use standard test conditions in the model, and correct the results after the calorimetric test using Eqn. (4, where the subscript x would denote the standard air-film coefficients. The use of a modeled U-factor is preferred because it is far easier to implement. The operator, however, runs the risk that the model, for whatever reason, may not accurately represent the actual window. As was already noted, the main benefit of this method is that a single test is sufficient to determine the SHGC, thereby allowing the calorimeter operator to run several tests over the course of a test day. Since test days are only available when the weather permits, the method could offer a serious potential advantage when time is a consideration. The method is limited, however, by its dependence on an external means of calculating U. Incorrect measurement of the indoor and/or outdoor air-film coefficients, or even the failure to correct the U-factor, provides a significant opportunity to introduce error into the data analysis. It is the ultimate purpose of this paper to discuss the proper measurement and correction procedures, and to quantify the effects of errors introduced into the experimental method via the indoor and outdoor air-film coefficients. METHODOLOGY Calorimeter designs, test specimens, and the conditions under which a test occurs all contribute to making each situation unique. Real results are highly dependent on the situation at hand. As such, it would be difficult to quantify calculation error in an all-inclusive way. It is more useful, rather, to pick a limited number of realistic test situations and demonstrate the progression and impact of error. This investigation is based on a typical calorimeter, operating on a typical test day, testing a typical specimen. Additionally, the intent is not to perform an uncertainty analysis of calorimetric data. Those uncertainties are well documented for specific calorimeters and calorimetric procedures. The intent is only to examine the potential errors caused due to poor or inaccurate measurement of the indoor and outdoor air-film coefficients. The impact of errors in the air-film coefficients on the calculated U-factor and SHGC is examined, followed by a discussion of the ways in which those errors are likely to be introduced. The center-of-glass region of a double glazed window will be examined for two representative test situations. The sample window is composed of two 3.05 mm clear lites (ε = 0.84, τ = 0.83, k = 0.9 W/m K separated by a 12.7 mm air gap. The test situations are indicative of both a warm weather (T o = 35 o C and cold weather (T o = 5 o C calorimetric test conducted in full sunlight (G = 500 W/m 2. The inside condition in both cases is T i = 21 o C. Table 1 presents the test conditions encountered during the two typical test periods, for a range of indoor and outdoor air-film coefficients. Results were produced using the window analysis software VISION [3], which allows the user to manipulate window properties and construction, temperature and air-film coefficients, and irradiation levels. It is assumed that VISION produces accurate results, and a calorimetric test performed under identical conditions would result in the same U-factor and SHGC results. The actual U-value and SHGC are denoted and SHGC act for the given set of conditions. g1 and g2 refer to the outdoor and indoor glass, respectively. A few points are noted concerning Table 1. The U-factor changes largely due to changes in the indoor and outdoor air-film coefficients. However, as the indoor and outdoor glass temperatures also change, so does the air-film coefficient for the glazing cavity. It is this difference in temperatures that accounts for the differing U-factors between Cases 1 and 2. It is further noted that the absorbed solar energy in each glazing (Gα does not change. G is constant and the radiative properties of the glass are assumed constant for the range of conditions examined. Therefore, the change in the SHGC is not due to the level of transmitted solar radiation, but rather due to the absorbed solar radiation that enters the room by convection and thermal radiation (i.e., the inward-flowing fraction, N. 5

6 Table 1: Window performance as predicted by the VISION software [3] for various values of the air-film coefficient. Case 1: T i = 21 C, T o = 5 C, G = 500 W/m 2 h o h i T g1 T g2 (W/m 2 K (W/m 2 K (C (C (W/m 2 K (W/m 2 (W/m 2 (W/m 2 K SHGC act 5_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ h o h i h c Gα g1 Case 2: T i = 21 C, T o = 30 C, G = 500 W/m 2 T g1 T g2 (W/m 2 K (W/m 2 K (C (C (W/m 2 K (W/m 2 (W/m 2 (W/m 2 K SHGC act 5_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ANALYSIS AND DISCUSSION An examination of the errors in U and SHGC resulting from errors between the actual and expected air-film coefficients is performed. In performing this examination, the calorimeter operator has assumed that the indoor and outdoor air-film coefficients are 8 and 30 W/m 2 K, respectively. Under those circumstances, the U-values expected by the operator, U 30_8, would be 2.98 and 3.17 W/m 2 K for Cases 1 and 2, respectively. i.e., U 30_8 = at h o = 30 W/m 2 K and h i =8 W/m 2 K. For the time being, a discussion of the situations under which those film coefficients may be in error is omitted. It is easy to examine the error in the U-factor resulting from incorrect air-film coefficients. The percent error in the U-value used, U error, would be U 30 _ 8 U act U error = *100 (5 U act h c Gα g1 Gα g2 Gα g2 6

7 where is the actual U-factor that would have occurred at the time of testing, and U 30_8 is the U-factor for the conditions assumed by the operator. The error in the calculated SHGC cannot be determined in the same manner as U error. Referring to Figure 3 and Table 1, the actual heat flux measured by the calorimeter operator during a test would be Qnet = SHGC act G U act ( Ti To (6 A The operator, however, would have been using this value of Q net with the assumed value of U 30_8 to determine the SHGC. Therefore Qnet + U 30 _ 8 ( Ti To SHGC A meas = (7 G Here, SHGC meas is the SHGC resulting from the operators analysis for a particular test. Three errors can now be presented based on this result. The error between the calculated and actual SHGC, directly resulting from the operators assumption, is given by SHGCmeas SHGCact SHGCerror, oper = *100 (8 SHGCact The second and third errors are due to the fact that SHGCs should be presented at standard conditions. Referring again to Table 1, h o = 30 W/m 2 K and h i = 8 W/m 2 K are close to the standard conditions, and therefore the correct SHGC is approximately 0.75 for both cases. The error inherent in testing "offstandard", for this window, can be defined as SHGC act 0.75 SHGC error, test = *100 ( Similarly, the error between the calculated SHGC and standard value is given by SHGC meas 0.75 SHGC = *100 (10 error, total 0.75 The results of this analysis can been seen in Table 2. Figure 3 presents the error in the U-factor calculation as a function of changing air-film coefficient. Considering the outdoor air-film coefficients, the greatest potential for error is when h o is small. On a windless day. h o may drop to between 5 and 10 W/m 2 K. For this window, that results in a U error approaching 50%. Conversely, strong winds, and higher air-film coefficients, do not significantly change the outdoor air-film coefficient or the resultant U-factor. For a windy condition, 30 W/m 2 K corresponds to a wind speed of approximately 6 m/s (21.6 km/h. To reach 40 W/m 2 K, the wind speed would have to increase to 9 m/s (32.4 km/h. In fact, by inspection of Table 2, if the actual air-film coefficient was 10 W/m 2 K larger than the value of 30 W/m 2 K used assumed by the operator, s/he would still be within 3% of the actual U-factor. As the indoor environment of the calorimeter is relatively still, small variations between the expected and actual air-film coefficient will result in serious inaccuracies in data results. In reality, h i is strongly affected not only by air motion, but also by calorimeter tilt and the temperature of the absorber panel, and is not likely to be 8 W/m 2 K even if the air is still. In both of the example cases presented in Table 2, underestimating the indoor air-film coefficient by as few as 2 W/m 2 K has resulted in a value of U error of almost 10%. It is noted that ASTM C [7] will require calorimeter operators to measure the indoor air-film coefficient for a particular calorimeter. Neither of these results is surprising. It is well understood that changes in the air-film coefficients have the greatest affect on the U-factor when the air-film coefficients are small (Figure 4. This effect has long been recognized by calorimeter operators when considering the outdoor air-film coefficient. In the authors experience, calorimeter operators are not likely to operate on still days. The errors introduced into the data are simply too difficult to correct with any certainty. In light of this statement, it is ironic that many laboratories do not correct for the indoor air-film coefficient. In fact, many laboratories operate on 7

8 the premise that h i = 8 W/m 2 K (i.e., natural convection. While the measures introduced in ASTM C [7] will provide a better indication of the actual air-film coefficient, they cannot correct for the large variability inherent in the test situation. A far better solution, in the authors opinion, is to introduce and account for significant air motion inside the calorimeter, thereby moving to a more stable test situation. Table 2: Error in SHGC due to inaccurate U-factor calculation and testing off-standard conditions. The conditions of each case have been presented in Table 1. Case 1: T i = 21 C, T o = 5 C, G = 500 W/m 2 U 30_8 (W/m 2 K (W/m 2 K U error SHGC act SHGC meas SHGC error,oper SHGC error,test SHGC error,total 5_ % % 5.3% 9.4% 8_ % % 4.0% 6.6% 10_ % % 2.7% 4.6% 15_ % % 1.3% 2.4% 20_ % % 1.3% 1.9% 25_ % % 0.0% 0.2% 30_ % % 0.0% 0.0% 35_ % % 0.0% -0.2% 40_ % % 0.0% -0.3% 30_ % % -1.3% 1.0% 30_ % % 0.0% 0.0% 30_ % % 0.0% -1.1% 30_ % % 1.3% -1.4% 30_ % % 2.7% -1.1% 30_ % % 2.7% -1.8% 30_ % % 2.7% -2.2% 30_ % % 2.7% -2.6% 30_ % % 2.7% -2.9% U 30_8 Case 2: T i = 21 C, T o = 30 C, G = 500 W/m 2 (W/m 2 K (W/m 2 K U error SHGC act SHGC meas SHGC error,oper SHGC error,test SHGC error,total 5_ % % 5.3% 2.7% 8_ % % 4.0% 2.3% 10_ % % 2.7% 1.4% 15_ % % 1.3% 0.6% 20_ % % 1.3% 0.9% 25_ % % 0.0% -0.2% 30_ % % 0.0% 0.0% 35_ % % 0.0% 0.1% 40_ % % 0.0% 0.2% 30_ % % -1.3% -2.8% 30_ % % 0.0% 0.0% 30_ % % 0.0% 0.6% 30_ % % 1.3% 3.0% 30_ % % 2.7% 4.9% 30_ % % 2.7% 5.4% 30_ % % 2.7% 5.6% 30_ % % 2.7% 5.9% 30_ % % 2.7% 6.0% 8

9 60.0% 50.0% 40.0% 30.0% 20.0% U error (% 10.0% 0.0% % -20.0% -30.0% -40.0% Case 1: ho = hact Case 1: hi = hact Case 2: ho = hact Case 2: hi = hact h act (W/m 2 K Figure 3: U error as a function of differences between the actual and expected air-film coefficient for the given test cases. How U error translates to error in the calculated SHGC is also given in Table 2. An important characteristic of the results is that the errors associated with inaccurate measurement of the air-film coefficient are of the same magnitude as those caused by measuring off-standard conditions. Unfortunately, testing off-standard is not something that is easily corrected by the calorimeter operator. As was previously stated, a better solution is to simply avoid extreme situations where the errors are largest. For the given test cases, avoiding these extremes will reduce calculation errors to less than 3% in all cases. An unexpected result is how the errors offset one another in a predictable way. For Case 1, when T i > T o, errors due to h i offset off-standard measurement error. Similarly, for Case 2, T o > T i and errors due to h o offset off-standard measurement error. On one hand, a reduction in the indoor air-film coefficient, or increase in the outdoor air-film coefficient result in a reduction of the inward-flowing fraction and the SHGC. The effect that these changes have on the air-film coefficient, combined with the direction of heat flow, are similarly predictable. The operator is cautioned, however, against using this to reduce errors. It is uncertain if the relative errors will evenly offset for a different window. Many calorimeter operators do attempt to correct the measured values to account for differences in the air-film coefficient using Eqn. (4, and the measured or estimated air-film coefficients that occurred at the time of testing. This correction, however, does nothing to account for changes in the heat transfer coefficient of the glazing cavity (due to glass temperatures or due to testing off-standard conditions. By adjusting U 30_8 using Eqn. (4, and recalculating the analysis of Eqns (7 thru (12, Table 3 can be reformulated to examine the quality of this correction. After correction, operator error is significantly reduced. As a worst case, a still day, the projected U-factor error is only -1.9%. Of greater importance is the resulting error in the operators calculation. For all the cases presented, the error introduced by the operator is less than 0.2%. Unfortunately, correcting the U-factor does not account for testing at off-standard conditions. In some cases, the total error is actually increased because the offsetting of errors has been eliminated. 9

10 Table 3: Error in SHGC after standard U-factor correction due to changes in the cavity heat transfer coefficient and testing off-standard conditions. The conditions of each case have been presented in Table 1. Case 1: T i = 21 C, T o = 5 C, G = 500 W/m 2 U adj (W/m 2 K (W/m 2 K U error SHGC act SHGC meas SHGC error,oper SHGC error,test SHGC error,total 5_ % % 5.3% 5.2% 8_ % % 4.0% 3.8% 10_ % % 2.7% 2.5% 15_ % % 1.3% 1.3% 20_ % % 1.3% 1.3% 25_ % % 0.0% 0.0% 30_ % % 0.0% 0.0% 35_ % % 0.0% 0.0% 40_ % % 0.0% 0.0% 30_ % % -1.3% -1.3% 30_ % % 0.0% 0.0% 30_ % % 0.0% 0.0% 30_ % % 1.3% 1.3% 30_ % % 2.7% 2.6% 30_ % % 2.7% 2.5% 30_ % % 2.7% 2.5% 30_ % % 2.7% 2.5% 30_ % % 2.7% 2.5% U adj Case 2: T i = 21 C, T o = 30 C, G = 500 W/m 2 (W/m 2 K (W/m 2 K U error SHGC act SHGC meas SHGC error,oper SHGC error,test SHGC error,total 5_ % % 5.3% 5.4% 8_ % % 4.0% 4.0% 10_ % % 2.7% 2.7% 15_ % % 1.3% 1.3% 20_ % % 1.3% 1.3% 25_ % % 0.0% 0.0% 30_ % % 0.0% 0.0% 35_ % % 0.0% 0.0% 40_ % % 0.0% 0.0% 30_ % % -1.3% -1.3% 30_ % % 0.0% 0.0% 30_ % % 0.0% 0.0% 30_ % % 1.3% 1.3% 30_ % % 2.7% 2.6% 30_ % % 2.7% 2.5% 30_ % % 2.7% 2.5% 30_ % % 2.7% 2.5% 30_ % % 2.7% 2.5% It has also been mentioned that it is common for calorimeter operators to determine the U-factor by a second night time test. Assuming that air motion and temperature conditions do not change, the only difference would be the lack of absorbed solar radiation in each glazing of the window. To examine the effects of this, each of the situations presented in Table 1 have been remodeled using VISION [3] with G set to 0 W/m 2. Using the resulting U-factors, Table 3 has been reproduced and presented as Table 4. Using the night time U-factor does not introduce any significant error by virtue of differences in the level of irradiation. At worst, only -1.9% error exists between the actual and night time value. This small difference has a negligible effect on the resulting SHGC calculation. Night time determination of the U- factor, however, still does not account for testing at off-standard conditions. Further, it is rare that both temperature and air motion characteristics will remain constant between the day time and night time tests. This analysis does not attempt to gage those compounding factors. It is expected that while the night time measurement of U-factor can be corrected for differences in the air-film coefficients, the same cannot be 10

11 easily done for changes in temperature. Examination of Table 4, however, shows there is less than a 1% increase in the actual U-factors between Cases 1 and 2, despite a 25 o C increase in the ambient temperature. Since it has already been established that 1% error in the actual and expected U-factors translate to a negligible error in the calculated SHGC, and a 25 o C change in temperature is extreme, then slight changes in temperature are likely not a significant problem. The operator is cautioned, however, that there is no easy way to gage the magnitude of this error for other windows without performing some models. This being the case, s/he is better off resorting to a modeled U-factor, and not bothering with a night time test at all. Table 4: Error in SHGC using night time test to determine the U-factor. The conditions of each case have been presented in Table 1. Case 1: T i = 21 C, T o = 5 C, G = 500 W/m 2 U night (W/m 2 K (W/m 2 K U error SHGC act SHGC meas SHGC error,oper SHGC error,test SHGC error,total 5_ % % 5.3% 5.2% 8_ % % 4.0% 3.8% 10_ % % 2.7% 2.5% 15_ % % 1.3% 1.2% 20_ % % 1.3% 1.2% 25_ % % 0.0% -0.2% 30_ % % 0.0% -0.1% 35_ % % 0.0% -0.1% 40_ % % 0.0% -0.1% 30_ % % -1.3% -1.5% 30_ % % 0.0% -0.1% 30_ % % 0.0% -0.2% 30_ % % 1.3% 1.2% 30_ % % 2.7% 2.5% 30_ % % 2.7% 2.5% 30_ % % 2.7% 2.5% 30_ % % 2.7% 2.5% 30_ % % 2.7% 2.5% U night Case 2: T i = 21 C, T o = 30 C, G = 500 W/m 2 (W/m 2 K (W/m 2 K U error SHGC act SHGC meas SHGC error,oper SHGC error,test SHGC error,total 5_ % % 5.3% 5.4% 8_ % % 4.0% 4.1% 10_ % % 2.7% 2.8% 15_ % % 1.3% 1.4% 20_ % % 1.3% 1.4% 25_ % % 0.0% 0.1% 30_ % % 0.0% 0.1% 35_ % % 0.0% 0.1% 40_ % % 0.0% 0.1% 30_ % % -1.3% -1.3% 30_ % % 0.0% 0.1% 30_ % % 0.0% 0.1% 30_ % % 1.3% 1.4% 30_ % % 2.7% 2.8% 30_ % % 2.7% 2.8% 30_ % % 2.7% 2.8% 30_ % % 2.7% 2.8% 30_ % % 2.7% 2.8% 11

12 Two approaches are suggested to mitigate errors caused by testing at off-standard conditions. First, avoid testing at extreme conditions. No tests should be performed, for example, on a still day. For the given test gases, this would result in a maximum error of about 3% in the SHGC. Second, the operator should acknowledge the conditions of the test, and model the window using both standard and test conditions to gage the error. As long as the window model, performed using air-film coefficients measured during the test, agrees with test results, a reliable approximation of standard SHGC can be presented. Both of these measures assume that the operator performs a correction of the U-factor used in his/her data reduction. Air-Film Coefficient Measurement Having examined the progression of error from the air-film coefficients to the calculated values of U-factor and SHGC, it is now useful to focus on the methods of measuring these air-film coefficients. The preceding discussion has assumed that that both the indoor and outdoor coefficients can be measured, and corrections made. In the case of the outdoor air-film coefficient, h o, ASTM Standard [7] suggests that calorimeter operators install a sol-air heat coefficient meter. The meter is simply a blackened plate with an insulated back that sits in the plane of the window specimen. Measurement of the plate temperature, air temperature and irradiation, allows the sol-air heat transfer coefficient to be estimated using 4 4 Gα p ( Tp Tsurr ho, p = = hconv, o + ε pσ (11 ( Tp To ( Tp To where T p and T surr are the plate and surroundings temperatures, respectively. α p and ε p are the plate absorptivity and emissivity: both approximately 0.9. h conv,o is the convective part of the outdoor air-film coefficient. Potential problems may arise due to the application of this data. As per ASTM Standard [7], it is assumed that ε g ε p and T g1 T p, and therefore, h o,p h o,g1. While the assumption of similar emissivities is likely good, the outdoor glass and plate temperatures will be significantly different. In reality, the heat coefficient at the window would be different. However, it is suggested that the following correction factor be applied to the sol-air heat meter measurement ( Tp Tsurr ( Tg1 Tsurr ho, g1 = ho, p ε pσ + ε g1σ (15 ( Tp To ( Tg1 To Where the operator should estimate the surrounding temperature using an equation similar to that presented by Swinbank [11]. The determination of the indoor air-film coefficients is accomplished using a Calibration Transfer Standard (CTS [12]. This consists of a window specimen constructed using foam insulation as a core. Thermocouple sensors are placed in coincident locations on either side of the core, under the glass, to measure the temperature drop across the foam core. With knowledge of the foam core s thermal conductivity, and by inducing a temperature gradient across it, interior and exterior heat transfer coefficients, and heat flux, Q CTS, through the core can be determined from Q CTS = ACTS Ccor ( T g 2 T g1 (16 where C cor is the conductance of the polystyrene core and A CTS is the profile area of the calibration specimen. T' g2, T' g1 are the interior and exterior surface temperatures of the specimen core, respectively. The surface temperatures of the glass is then determined by Ccor T g 2 = T g 2 + ( T g 2 T g1 (17 C g 2 Ccor T g1 = T g1 ( T g 2 T g1 (18 C g1 Finally, the indoor air-film coefficient is found using 12

13 Q CTS i ( T T A i g 2 For solar calorimetric testing, determining h i is important. With the CTS installed in place of the window, ASTM Standard [7] specifies that h i be determined at three unspecified tilt angles at T i = 24 o C and T o = 32 o C. This procedure, however, cannot fully account for the air-film coefficients that may exist at the time of testing. The calibration test is performed in the absence of solar radiation, and therefore, very little energy enters the calorimeter when compared to an actual test situation. Because the absorber panel is used to control the interior temperature, it will almost certainly be run at warmer temperatures than those used during the CTS calibration test, and therefore, the radiative portion of the air-film coefficient will be affected. From the authors experience, the absorber temperature may be anywhere from 15 to 20 o C, depending on the calorimeter, specimen, and test conditions. The effect of calorimeter tilt is specific to the calorimeter, and cannot be quantified here. By inspection, however, increasing tilt is known to cause a reduction in the convective portion of the internal air-film coefficient. In the past, calorimeter operators have recognized this problem, and generally do not tilt test specimens more than 60 o from vertical [13]. Performing the calibration at 3 tilt angles, from 0 to 60 o, is likely sufficient. CONCLUSIONS It has been demonstrated that in addition to the careful and accurate correction of indoor and outdoor air-film coefficients, a knowledgeable calorimeter operator is important. In the preceding analysis, common test situations have been introduced that could significantly impact the accuracy of the test results. Of importance: Only large errors between the actual and expected U-factors result in significant error in the resulting SHGC calculation. e.g.,u error on the order of 20% or greater will result in SHGC error,oper of 4% and greater, depending on the situation. Large errors in the U-factor are incurred when testing under still-air conditions. It is recommended that tests never be run when the outdoor condition is still, and that precautions be taken so that air motion is induced in the calorimeter interior. If the operator corrects the results for the air-film coefficients that occurred at the time of testing, the SHGC results can be very accurate. However, it is noted that testing off-standard conditions may not result in the same SHGC that would be found during testing on-standard conditions. Determining U from software, is far better than using a separate night time test. The night time test takes more time, and will likely introduce it's own inaccuracies to the data analysis. By keeping these points in mind, the calorimeter operator should be capable of avoiding test situations that would result in errant results. The sol-air heat coefficient meter, specified in ASTM Standard [7], does a good job of measuring the exterior air-film coefficient. However, a more detailed correction equation was presented that would further improve its usefulness. A CTS is specified in ASTM Standard [7] to characterize the interior air-film coefficient during the commissioning of the calorimeter. A potential flaw was noted in this procedure in that the absorber plate would be much colder during an actual test, than it would be during the CTS calibration. As such, radiative heat transfer may have an unexpected impact on the data reduction. REFERENCES [1] Apte, J., Arasteh, D., and Huang, J., "Future Advanced Windows for Zero-Energy Homes", ASHRAE Transactions, Vol. 109 (2, 2003 [2] "Window 4.1, A PC Program for Analyzing Window Thermal Performance", Windows and Daylighting Group, Lawrence Berkeley Laboratory, University of California, CTS = h (19 13

14 [3] Wright, J.L., "Glazing System Thermal Analysis", CANMET, Advanced Glazing System Laboratory, VISION3, Minister of Supply and Services Canada, University of Waterloo, [4] ASTM C , Standard Test Method for the Thermal Performance of Building Assemblies by Means of a Hot Box. Annual Book of ASTM Standards, 2003 [5] National Fenestration Rating Council, "Procedure for Determining Fenestration Product Solar Heat Gain Coefficients at Normal Incidence" NFRC , Silver Spring, MD, [6] ASTM C , Standard Test Method for Steady-State Thermal Performance of Building Assemblies by Means of a Guarded Hot Box. Annual Book of ASTM Standards, [7] ASTM C , Standard Test Method for Measuring the Solar Heat Gain Coefficient of Fenestration Systems using Calorimetry Hot Box Methods. ASTM Draft Standard, [8] Klems, J.H., "Measurement of Fenestration Net Energy Performance: Considerations Leading to Development of the Mobile Window Thermal Test (MoWitt Facility", Transactions of the ASME, Vol. 110, pp , [9] Wouters, P., Vandaele, L., Voit, P. and Fisch, N., "The Use of Outdoor Test Cells for Thermal and Solar Building Research within the PASSYS Project", Building and the Environment, Vol. 28 (2, pp , [10] ASHRAE: Handbook of Fundamentals, American Society of Heating, Refrigeration, and Air Conditioning Engineers, Atlanta, GA, [11] Swinbank, W.C., "Long-Wave Radiation from Clear Skies", Quarterly Journal of the Royal Meteorological Society, Vol. 89, [12] Bowen, R. P. "DBR s Approach for Determining the Heat Transmission Characteristics of Windows", Division of Building Research, National Research Council Canada, [13] Collins, M.R., and Harrison, S.J., "Test of Measured Solar Heat Gain Variation with Respect to Test Specimen Tilt", ASHRAE Transactions, Vol. 107 (1, pp ,

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND Collins, M.R., and Harrison, S.J., "The Effects of Calorimeter Tilt on the Inward-Flowing Fraction of Absorbed Solar Radiation in a Venetian Blind", ASHRAE Transactions, Vol. 107 (1), pp. 677-683, 2001.

More information

TEST OF MEASURED SOLAR HEAT GAIN VARIATION WITH RESPECT TO TEST SPECIMEN TILT

TEST OF MEASURED SOLAR HEAT GAIN VARIATION WITH RESPECT TO TEST SPECIMEN TILT Collins, M.R., and Harrison, S.J., "Test of Measured Solar Heat Gain Variation with Respect to Test Specimen Tilt", SHRE Transactions, Vol. 107 (1), pp. 691-699, 2001. Copyright 2001, merican Society of

More information

Effect of Installing a Curved Venetian Blind to the Glass Window on Heat Transmission

Effect of Installing a Curved Venetian Blind to the Glass Window on Heat Transmission Effect of Installing a Curved Venetian Blind to the Glass Window on Heat Transmission Somsak Chaiyapinunt *1 and Nopparat Khamporn 2 1 Department of Mechanical Engineering, Faculty of Engineering, Chulalongkorn

More information

Glazing selection for solar design

Glazing selection for solar design Glazing selection for solar design Visible light transmittance: A measure of the amount of visible light that passes through the glazing material of a window, door, or skylight. Visible light transmittance,

More information

CAE 331/513 Building Science Fall 2016

CAE 331/513 Building Science Fall 2016 CAE 331/513 Building Science Fall 2016 Week 3: September 8, 2016 Heat transfer in buildings: Finish radiation, then solar radiation and windows Advancing energy, environmental, and sustainability research

More information

INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS

INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS Mark Luther 1, Timothy Anderson 2, and Tim Brain 3 1 School of Architecture and Building, Deakin University, Geelong, Australia 2 School

More information

NFRC SOLAR HEAT GAIN COEFFICIENT TEST REPORT. Rendered to: CLEAR FOCUS IMAGING

NFRC SOLAR HEAT GAIN COEFFICIENT TEST REPORT. Rendered to: CLEAR FOCUS IMAGING NFRC 201-2004 SOLAR HEAT GAIN COEFFICIENT TEST REPORT Rendered to: CLEAR FOCUS IMAGING SERIES/MODEL: SunSecure BASE WINDOW: 3/16" Clear Single Glazed PRODUCT TYPE: Window Film on the Interior of Clear

More information

Estimating the Solar Heat and Thermal Gain from a Window with an Interior Venetian Blind

Estimating the Solar Heat and Thermal Gain from a Window with an Interior Venetian Blind Collins, M.R., and Harrison, S.J., "Estimating the Solar Heat and Thermal Gain from a Window with an Interior Venetian Blind", ASHRAE Transactions, Vol. 110 (1), pp. 486 500, 004. Copyright 004, American

More information

AR/IA 241 LN 231 Lecture 4: Fundamental of Energy

AR/IA 241 LN 231 Lecture 4: Fundamental of Energy Faculty of Architecture and Planning Thammasat University A/IA 24 LN 23 Lecture 4: Fundamental of Energy Author: Asst. Prof. Chalermwat Tantasavasdi. Heat For a specific substance, the heat given to the

More information

Standard Test Method for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Using Hot Box Methods 1

Standard Test Method for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Using Hot Box Methods 1 Designation: 97 AMERICAN SOCIETY FOR TESTING AND MATERIALS 100 Barr Harbor Dr., West Conshohocken, PA 19428 Reprinted from the Annual Book of ASTM Standards. Copyright ASTM Standard Test Method for Measuring

More information

Simplified Collector Performance Model

Simplified Collector Performance Model Simplified Collector Performance Model Prediction of the thermal output of various solar collectors: The quantity of thermal energy produced by any solar collector can be described by the energy balance

More information

Design strategy for Low e windows with effective insulation

Design strategy for Low e windows with effective insulation Design strategy for Low e windows with effective insulation Michael P.C. Watts, Impattern Solutions, www.impattern.com Keywords; insulating windows. low emission glass, ABSTRACT Optimal window glass assemblies

More information

EFFECT OF INTERNAL LONG WAVE RADIATION AND CONVECTION ON FENESTRATION SIMULATION

EFFECT OF INTERNAL LONG WAVE RADIATION AND CONVECTION ON FENESTRATION SIMULATION EFFECT OF INTERNAL LONG WAVE RADIATION AND CONVECTION ON FENESTRATION SIMULATION Adelqui Fissore Sch. University of Concepción Mechanical Engineering Department Concepción - Chile ABSTRACT This paper presents

More information

5. AN INTRODUCTION TO BUILDING PHYSICS

5. AN INTRODUCTION TO BUILDING PHYSICS 5. AN INTRODUCTION TO BUILDING PHYSICS P. Wouters, S. Martin ABSTRACT This chapter places the System Identification Competition in a broader context of evaluating the thermal performances of building components.

More information

Solar Radiation 230 BTU s per Hr/SF. Performance Glazing Coatings, Layers & Gases

Solar Radiation 230 BTU s per Hr/SF. Performance Glazing Coatings, Layers & Gases Solar Radiation 230 BTU s per Hr/SF 89 83 82 90 Performance Glazing Coatings, Layers & Gases Learning Objectives After Viewing This Presentation You Will Understand: q The NFRC Labeling System q Light

More information

Solar Flat Plate Thermal Collector

Solar Flat Plate Thermal Collector Solar Flat Plate Thermal Collector INTRODUCTION: Solar heater is one of the simplest and basic technologies in the solar energy field. Collector is the heart of any solar heating system. It absorbs and

More information

PERFORMANCE EVALUATION OF REFLECTIVE COATINGS ON ROOFTOP UNITS

PERFORMANCE EVALUATION OF REFLECTIVE COATINGS ON ROOFTOP UNITS PERFORMANCE EVALUATION OF REFLECTIVE COATINGS ON ROOFTOP UNITS Report on DRAFT Prepared for: California Energy Commission 1516 9th Street Sacramento, CA 95814 Prepared by: Design & Engineering Services

More information

Energy flows and modelling approaches

Energy flows and modelling approaches Energy flows and modelling approaches Energy flows in buildings external convection infiltration & ventilation diffuse solar external long-wave radiation to sky and ground local generation fabric heat

More information

Winter Night. Thermos 6mm Outdoors # #

Winter Night. Thermos 6mm Outdoors # # February 26, 2016 By Gagnon, Stephan stephan@thermosrn.ca Thermos 3mm à 6mm vs Climaguard 80/70 Make-up Name Make-up Icon Transmittance Reflectance U-Value Visible (τ v %) (τ e %) Visible ρ v % out ρ v

More information

Heat Transfer Analysis of a Between-Panes Venetian Blind Using Effective Longwave Radiative Properties

Heat Transfer Analysis of a Between-Panes Venetian Blind Using Effective Longwave Radiative Properties AN-04-6-1 Heat Transfer Analysis of a Between-Panes Venetian Blind Using Effective Longwave Radiative Properties Darryl S. Yahoda John L. Wright, Ph.D, P.Eng. Member ASHRAE ABSTRACT Center-glass thermal

More information

The energy performance of an airflow window

The energy performance of an airflow window The energy performance of an airflow window B.(Bram) Kersten / id.nr. 0667606 University of Technology Eindhoven, department of Architecture Building and Planning, unit Building Physics and Systems. 10-08-2011

More information

QIRT th International Conference on Quantitative InfraRed Thermography

QIRT th International Conference on Quantitative InfraRed Thermography 10 th International Conference on Quantitative InfraRed Thermography July 27-30, 2010, Québec (Canada) Quantitative infrared wall inspection *CE Dept., Cracow University of Technology, Kraków, Poland,

More information

ADVANCED ROOF COATINGS: MATERIALS AND THEIR APPLICATIONS

ADVANCED ROOF COATINGS: MATERIALS AND THEIR APPLICATIONS ADVANCED ROOF COATINGS: MATERIALS AND THEIR APPLICATIONS Abstract J.M. Bell 1 and G.B. Smith 2 The use of low emittance and high solar reflectance coatings is widespread in window glazings, wall and roof

More information

Patrick H. Oosthuizen and J.T. Paul Queen s University Kingston, ON, Canada

Patrick H. Oosthuizen and J.T. Paul Queen s University Kingston, ON, Canada Proceedings of the ASME 2012 International Mechanical Engineering Congress & Exposition IMECE2012 November 9-15, 2012, Houston, Texas, USA IMECE2012-87735 A NUMERICAL STUDY OF THE EFFECT OF AN IRRADIATED

More information

SENSITIVITY OF THE SOLAR HEAT GAIN COEFFICIENT OF COMPLEX FENESTRATION SYSTEMS TO THE INDOOR CONVECTION COEFFICIENT

SENSITIVITY OF THE SOLAR HEAT GAIN COEFFICIENT OF COMPLEX FENESTRATION SYSTEMS TO THE INDOOR CONVECTION COEFFICIENT SENSITIVITY OF THE SOLAR HEAT GAIN COEFFICIENT OF COMPLEX FENESTRATION SYSTEMS TO THE INDOOR CONVECTION COEFFICIENT S.S.M. Foroushani 1, J.L. Wright 1, D. Naylor 2 1 Mechanical & Mechatronics Engineering,

More information

Assessing The Thermal Performance of Building Enclosure Materials Using A Medium-Size Hot Box Chamber Summer Meeting Torkan Fazli

Assessing The Thermal Performance of Building Enclosure Materials Using A Medium-Size Hot Box Chamber Summer Meeting Torkan Fazli Assessing The Thermal Performance of Building Enclosure Materials Using A Medium-Size Hot Box Chamber 2014 Summer Meeting Torkan Fazli Introduction The building construction industry consumes significant

More information

UNIT FOUR SOLAR COLLECTORS

UNIT FOUR SOLAR COLLECTORS ME 476 Solar Energy UNIT FOUR SOLAR COLLECTORS Flat Plate Collectors Outline 2 What are flat plate collectors? Types of flat plate collectors Applications of flat plate collectors Materials of construction

More information

Absorptivity, Reflectivity, and Transmissivity

Absorptivity, Reflectivity, and Transmissivity cen54261_ch21.qxd 1/25/4 11:32 AM Page 97 97 where f l1 and f l2 are blackbody functions corresponding to l 1 T and l 2 T. These functions are determined from Table 21 2 to be l 1 T (3 mm)(8 K) 24 mm K

More information

NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06

NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06 ALL SEASONS DOOR & WINDOW, INC. Report No: NCTL-110-8058-5S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06 Test Specimen NFRC Code Manufacturer : All Seasons Door & Window, Inc. Series/Model

More information

Documentation of the Solutions to the SFPE Heat Transfer Verification Cases

Documentation of the Solutions to the SFPE Heat Transfer Verification Cases Documentation of the Solutions to the SFPE Heat Transfer Verification Cases Prepared by a Task Group of the SFPE Standards Making Committee on Predicting the Thermal Performance of Fire Resistive Assemblies

More information

NFRC THERMAL TEST SUMMARY REPORT January 27, 1999 Test Specimen

NFRC THERMAL TEST SUMMARY REPORT January 27, 1999 Test Specimen * This is not the original copy of the test report if you would like an original copy, please contact our East Brunswick office or the NCTL to request a copy. ALL SEASONS DOOR & WINDOW, INC. REPORT NO:

More information

Overall Heat Transfer Coefficient

Overall Heat Transfer Coefficient Overall Heat Transfer Coefficient A heat exchanger typically involves two flowing fluids separated by a solid wall. Heat is first transferred from the hot fluid to the wall by convection, through the wall

More information

KEYWORDS Glazing; Window; Low E; Teflon; U-value; Shading Coefficient INTRODUCTION

KEYWORDS Glazing; Window; Low E; Teflon; U-value; Shading Coefficient INTRODUCTION / : - '\. SIMULATION AND MEASUREMENT OF WINDOWS WITH LOW EMISSIVITY COATINGS USED IN CONJUNCTION WITH TEFLON * INNER GLAZINGS John L. Wright, Prof. H.F. Sullivan Advanced Glazing System Laboratory Department

More information

ERT 460 CONTROLLED ENVIRONMENT DESIGN II HEAT TRANSFER. En Mohd Khairul Rabani Bin Hashim

ERT 460 CONTROLLED ENVIRONMENT DESIGN II HEAT TRANSFER. En Mohd Khairul Rabani Bin Hashim ERT 460 CONTROLLED ENVIRONMENT DESIGN II HEAT TRANSFER En Mohd Khairul Rabani Bin Hashim 1 Heat Transfer Steady and transient heat conduction, natural and forced convection, and radiation of controlled

More information

1.0 BACKGROUND 1.1 Surface Radiation

1.0 BACKGROUND 1.1 Surface Radiation 1.0 BACKGROUND 1.1 Surface Radiation Meteorologists have utilized recent advances in computer speeds and atmospheric models to create increasingly accurate models of the environment. The computational

More information

Model 3024 Albedometer. User s Manual 1165 NATIONAL DRIVE SACRAMENTO, CALIFORNIA WWW. ALLWEATHERINC. COM

Model 3024 Albedometer. User s Manual 1165 NATIONAL DRIVE SACRAMENTO, CALIFORNIA WWW. ALLWEATHERINC. COM Model 3024 Albedometer User s Manual 1165 NATIONAL DRIVE SACRAMENTO, CALIFORNIA 95834 WWW. ALLWEATHERINC. COM TABLE OF CONTENTS INTRODUCTION... 1 THEORY OF OPERATION... 2 General Description... 2 Accuracy...

More information

OPTIMIZATION of the GEOMETRY & MATERIAL of SOLAR WATER HEATERS.

OPTIMIZATION of the GEOMETRY & MATERIAL of SOLAR WATER HEATERS. OPTIMIZATION of the GEOMETRY & MATERIAL of SOLAR WATER HEATERS. FLAT PLATE COLLECTORS ABSORBER PLATES OPTIMIZATION OF GEOMETRY SELECTIVE SURFACES METHODS OF TESTING TO DETERMINE THE THERMAL PERFORMANCE

More information

AIR-INS inc. 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) Fax : (450)

AIR-INS inc. 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) Fax : (450) 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) 652-0838 Fax : (450) 652-7588 info@air-ins.com THERMAL PERFORMANCE VALIDATION TEST CONDUCTED ON YOUR 300 / 301 FIXED WINDOW IN ACCORDANCE

More information

THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS. Agnieszka A. Lechowska 1, Jacek A. Schnotale 1

THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS. Agnieszka A. Lechowska 1, Jacek A. Schnotale 1 THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS Agnieszka A. Lechowska 1, Jacek A. Schnotale 1 1 Cracow University of Technology, Department of Environmental Engineering,

More information

Definitions of U- and g-value in case of double skin facades or vented windows

Definitions of U- and g-value in case of double skin facades or vented windows Windows as Renewable Energy Sources for Europe Window Energy Data Network www.windat.org Project supported by DG for Energy and Transport of the European Commission contract NNE5-2000-122 Definitions of

More information

Arctice Engineering Module 3a Page 1 of 32

Arctice Engineering Module 3a Page 1 of 32 Welcome back to the second part of the second learning module for Fundamentals of Arctic Engineering online. We re going to review in this module the fundamental principles of heat transfer. Exchange of

More information

LECTURE NOTES. Heat Transfer. III B. Tech II Semester (JNTUA-R15) CHADALAWADA RAMANAMMA ENGINEERING COLLEGE (AUTONOMOUS)

LECTURE NOTES. Heat Transfer. III B. Tech II Semester (JNTUA-R15) CHADALAWADA RAMANAMMA ENGINEERING COLLEGE (AUTONOMOUS) LECTURE NOTES on Heat Transfer III B. Tech II Semester (JNTUA-R15) Mr. K.SURESH, Assistant Professor CHADALAWADA RAMANAMMA ENGINEERING COLLEGE (AUTONOMOUS) Chadalawada Nagar, Renigunta Road, Tirupati 517

More information

Report No: NCTL NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15

Report No: NCTL NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15 MGM INDUSTRIES, INC. Report No: NCTL-110-14571-1 NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15 Test Specimen NFRC Code Manufacturer: MGM Industries, Inc. Series/Model: Series 4600 Window Type:

More information

EVALUATION OF AN APPROXIMATE METHOD FOR PREDICITING THE U-VALUE OF A WINDOW WITH A BETWEEN-PANES LOUVERED SHADE. D. Naylor *, M.

EVALUATION OF AN APPROXIMATE METHOD FOR PREDICITING THE U-VALUE OF A WINDOW WITH A BETWEEN-PANES LOUVERED SHADE. D. Naylor *, M. Proceedings of CHT-04 ICHMT International Symposium on Advances in Computational Heat Transfer April 19-24, 2004, Norway CHT-04-110 EVALUATION OF AN APPROXIMATE METHOD FOR PREDICITING THE U-VALUE OF A

More information

Chapter Seven. Solar Energy

Chapter Seven. Solar Energy Chapter Seven Solar Energy Why Studying Solar energy To know the heat gain or heat loss in a building In making energy studies In the design of solar passive homes. Thermal Radiation Solar spectrum is

More information

Test Results: Results of the test period on 06/19/16 using the Equivalent CTS Method: Thermal transmittance at test conditions (U s ):

Test Results: Results of the test period on 06/19/16 using the Equivalent CTS Method: Thermal transmittance at test conditions (U s ): NORTH EAST WINDOWS USA, INC. NFRC THERMAL TEST SUMMARY REPORT Report No: NCTL-110-17842-3S Test Specimen NFRC Code Manufacturer: North East Windows USA, Inc. Series/Model: Series CW 300 Window Type: Casement-

More information

Double-Skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of Direct Solar Radiation

Double-Skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of Direct Solar Radiation ouble-skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of irect Solar Radiation G-LO 011 Rosady Mulyadi epartment of Architecture Faculty of Engineering Hasanuddin

More information

Report No: NCTL S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15. Test Specimen

Report No: NCTL S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15. Test Specimen MGM INDUSTRIES, INC. Report No: NCTL-110-13834-1S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15 Test Specimen NFRC Code Manufacturer: MGM Industries, Inc. Series/Model: 8017 Window Type: Double

More information

THERMAL DYNAMIC BEHAVIOR OF SINGLE COMPONENT: EXPERIMENTAL ANALYSIS AND NUMERICAL MODELING

THERMAL DYNAMIC BEHAVIOR OF SINGLE COMPONENT: EXPERIMENTAL ANALYSIS AND NUMERICAL MODELING U.P.B. Sci. Bull., Series C, Vol. 74, Iss. 1, 2012 ISSN 1454-234x THERMAL DYNAMIC BEHAVIOR OF SINGLE COMPONENT: EXPERIMENTAL ANALYSIS AND NUMERICAL MODELING Paolo BAGGIO 1, Alessandro PRADA 2 In the present

More information

ANALYSIS OF FLAT PLATE PHOTOVOLTAIC-THERMAL (PVT) MODELS

ANALYSIS OF FLAT PLATE PHOTOVOLTAIC-THERMAL (PVT) MODELS ANALYSIS OF FLAT PLATE PHOTOVOLTAIC-THERMAL (PVT) MODELS J. Bilbao and A. B. Sproul School of Photovoltaic and Renewable Energy Engineering University of New South Wales Kensington, NSW 52, Australia j.bilbao@unsw.edu.au

More information

Heriot-Watt University

Heriot-Watt University Heriot-Watt University Distinctly Global www.hw.ac.uk Thermodynamics By Peter Cumber Prerequisites Interest in thermodynamics Some ability in calculus (multiple integrals) Good understanding of conduction

More information

Building heat system sizing

Building heat system sizing May 6th, 203 MVK60 Heat and Mass Transfer Project report Building heat system sizing Arnaud BELTOISE Dept. of Energy Sciences, Faculty of Engineering, Lund University, Box 8, 2200 Lund, Sweden . Introduction

More information

MCS 7 Chia Laguna, Cagliari, Sardinia, Italy, September 11-15, 2011

MCS 7 Chia Laguna, Cagliari, Sardinia, Italy, September 11-15, 2011 MCS 7 Chia Laguna, Cagliari, Sardinia, Italy, September 11-15, 2011 CONVECTIVE HEAT TRANSFER COEFFICIENT IN COMPARTMENT FIRES J. G. Qunitiere* and P. S. Veloo** jimq@umd.edu *University of Maryland, College

More information

CAE 463/524 Building Enclosure Design Fall 2012

CAE 463/524 Building Enclosure Design Fall 2012 CAE 463/524 Building Enclosure Design Fall 2012 Lecture 8: Fenestration (+ exam review) Dr. Brent Stephens, Ph.D. Department of Civil, Architectural and Environmental Engineering Illinois Institute of

More information

INFLUENCE OF SURFACE EMISSIVITY AND OF LOW EMISSIVITY SHIELDS ON THE THERMAL PROPERTIES OF LOW DENSITY INSULATING MATERIALS

INFLUENCE OF SURFACE EMISSIVITY AND OF LOW EMISSIVITY SHIELDS ON THE THERMAL PROPERTIES OF LOW DENSITY INSULATING MATERIALS 8th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics HEFAT2011 8 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 11 13 July 2011 Pointe Aux

More information

Construction and performance analysis of a three dimensional compound parabolic concentrator for a spherical absorber

Construction and performance analysis of a three dimensional compound parabolic concentrator for a spherical absorber 558 Journal of Scientific & Industrial Research J SCI IND RES VOL 66 JULY 2007 Vol. 66, July 2007, pp. 558-564 Construction and performance analysis of a three dimensional compound parabolic concentrator

More information

Thermal Resistance of a Window with an Enclosed Venetian Blind: Guarded Heater Plate Measurements

Thermal Resistance of a Window with an Enclosed Venetian Blind: Guarded Heater Plate Measurements 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 112, Part 2. For personal use only. Additional reproduction,

More information

3.0 FINITE ELEMENT MODEL

3.0 FINITE ELEMENT MODEL 3.0 FINITE ELEMENT MODEL In Chapter 2, the development of the analytical model established the need to quantify the effect of the thermal exchange with the dome in terms of a single parameter, T d. In

More information

Physics 111. Lecture 36 (Walker: ) Heat Capacity & Specific Heat Heat Transfer. May 1, Quiz (Chaps. 14 & 16) on Wed.

Physics 111. Lecture 36 (Walker: ) Heat Capacity & Specific Heat Heat Transfer. May 1, Quiz (Chaps. 14 & 16) on Wed. Physics 111 Lecture 36 (Walker: 16.4-6) Heat Capacity & Specific Heat Heat Transfer May 1, 2009 Quiz (Chaps. 14 & 16) on Wed. May 6 Lecture 36 1/26 Heat Capacity (C) The heat capacity C of an object is

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed NFRC 102-201 THERMAL PERFORMANCE TEST REPORT Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed Summary of Results Standardized Thermal Transmittance (U-Factor) 0.39 Unit Size: 7" x

More information

NUMERICAL SIMULATION OF THE AIR FLOW AROUND THE ARRAYS OF SOLAR COLLECTORS

NUMERICAL SIMULATION OF THE AIR FLOW AROUND THE ARRAYS OF SOLAR COLLECTORS THERMAL SCIENCE, Year 2011, Vol. 15, No. 2, pp. 457-465 457 NUMERICAL SIMULATION OF THE AIR FLOW AROUND THE ARRAYS OF SOLAR COLLECTORS by Vukman V. BAKI] *, Goran S. @IVKOVI], and Milada L. PEZO Laboratory

More information

Collector test according to EN ,2:2002

Collector test according to EN ,2:2002 Test Report: KTB Nr. 2003-18-b-en Collector test according to EN 12975-1,2:2002 for: RM Solar Ltd Brand Name: S-Class Responsible for Testing: Dipl.-Ing. (FH) A. Schäfer Date: 17th July 2006 Address: Fraunhofer-Institute

More information

The Electrodynamics of a Pair of PV Modules with Connected Building Resistance

The Electrodynamics of a Pair of PV Modules with Connected Building Resistance Proc. of the 3rd IASME/WSEAS Int. Conf. on Energy, Environment, Ecosystems and Sustainable Development, Agios Nikolaos, Greece, July 24-26, 2007 563 he Electrodynamics of a Pair of s with Connected Building

More information

THERMAL PERFORMANCE TEST REPORT

THERMAL PERFORMANCE TEST REPORT THERMAL PERFORMANCE TEST REPORT Manufacture: Address: Coral Architectural Products 7704B Industrial Lane Tampa, Florida 33637 Specifications: ANSI/NFRC 102-2014: Test Procedure for Measuring the Steady-State

More information

NUMERICAL ANALYSIS OF HEAT STORAGE AND HEAT CONDUCTIVITY IN THE CONCRETE HOLLOW CORE DECK ELEMENT

NUMERICAL ANALYSIS OF HEAT STORAGE AND HEAT CONDUCTIVITY IN THE CONCRETE HOLLOW CORE DECK ELEMENT NUMERICAL ANALYSIS OF HEAT STORAGE AND HEAT CONDUCTIVITY IN THE CONCRETE HOLLOW CORE DECK ELEMENT Michal Pomianowski 1, Per Heiselberg 1, Rasmus Lund Jensen 1, and Hicham Johra 1 1 Aalborg University,

More information

Heat Transfer: Physical Origins and Rate Equations. Chapter One Sections 1.1 and 1.2

Heat Transfer: Physical Origins and Rate Equations. Chapter One Sections 1.1 and 1.2 Heat Transfer: Physical Origins and Rate Equations Chapter One Sections 1.1 and 1. Heat Transfer and Thermal Energy What is heat transfer? Heat transfer is thermal energy in transit due to a temperature

More information

Thermal Systems. What and How? Physical Mechanisms and Rate Equations Conservation of Energy Requirement Control Volume Surface Energy Balance

Thermal Systems. What and How? Physical Mechanisms and Rate Equations Conservation of Energy Requirement Control Volume Surface Energy Balance Introduction to Heat Transfer What and How? Physical Mechanisms and Rate Equations Conservation of Energy Requirement Control Volume Surface Energy Balance Thermal Resistance Thermal Capacitance Thermal

More information

This file contains the author's copy of:

This file contains the author's copy of: This file contains the author's copy of: Collins, M.R., Harrison, S.J., Oosthuizen, P.H., and Naylor, D., "Heat Transfer from an Isothermal Vertical Surface with Adjacent Heated Horizontal Louvers: Validation",

More information

Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha

Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha Abstract This paper reports the numerical and experimental performances of Double Glass Wall are investigated. Two

More information

Applied Thermodynamics HEAT TRANSFER. Introduction What and How?

Applied Thermodynamics HEAT TRANSFER. Introduction What and How? LANDMARK UNIVERSITY, OMU-ARAN LECTURE NOTE: 3 COLLEGE: COLLEGE OF SCIENCE AND ENGINEERING DEPARTMENT: MECHANICAL ENGINEERING PROGRAMME: ENGR. ALIYU, S.J Course code: MCE 311 Course title: Applied Thermodynamics

More information

Thermal Analysis of a Flat-Plate Solar Collectors in Parallel and Series Connections Huseyin Gunerhan

Thermal Analysis of a Flat-Plate Solar Collectors in Parallel and Series Connections Huseyin Gunerhan Thermal Analysis of a Flat-Plate Solar Collectors in Parallel and Series Connections Huseyin Gunerhan Department of Mechanical Engineering, Faculty of Engineering Ege University, 35100 Bornova, Izmir,

More information

HEAT TRANSFER 1 INTRODUCTION AND BASIC CONCEPTS 5 2 CONDUCTION

HEAT TRANSFER 1 INTRODUCTION AND BASIC CONCEPTS 5 2 CONDUCTION HEAT TRANSFER 1 INTRODUCTION AND BASIC CONCEPTS 5 2 CONDUCTION 11 Fourier s Law of Heat Conduction, General Conduction Equation Based on Cartesian Coordinates, Heat Transfer Through a Wall, Composite Wall

More information

Greenhouse Steady State Energy Balance Model

Greenhouse Steady State Energy Balance Model Greenhouse Steady State Energy Balance Model The energy balance for the greenhouse was obtained by applying energy conservation to the greenhouse system as a control volume and identifying the energy terms.

More information

CFD MODELLING OF CONVECTIVE HEAT TRANSFER FROM A WINDOW WITH ADJACENT VENETIAN BLINDS

CFD MODELLING OF CONVECTIVE HEAT TRANSFER FROM A WINDOW WITH ADJACENT VENETIAN BLINDS Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 CFD MODELLING OF CONVECTIVE HEAT TRANSFER FROM A WINDOW WITH ADJACENT VENETIAN BLINDS Ljiljana Marjanovic 1,2, Malcom Cook 2, Vic

More information

Assessing Convective Heat Transfer Coefficients Associated with Indoor Shading Attachments Using a New Technique Based on Computational Fluid Dynamics

Assessing Convective Heat Transfer Coefficients Associated with Indoor Shading Attachments Using a New Technique Based on Computational Fluid Dynamics 2015 ASHRAE www.ashrae.org). Published in ASHRAE Conference Papers, Winter Conference, Chicago, IL. For personal use only. Additional reproduction, distribution, or transmission in either print or digital

More information

DEFINING THE PERFORMANCE OF THE DOUBLE SKIN FAÇADE WITH THE USE OF THE SIMULATION MODEL

DEFINING THE PERFORMANCE OF THE DOUBLE SKIN FAÇADE WITH THE USE OF THE SIMULATION MODEL Eighth International IBPSA Conference Eindhoven, Netherlands August -4, 003 DEFINING THE PERFORMANCE OF THE DOUBLE SKIN FAÇADE WITH THE USE OF THE SIMULATION MODEL Wojtek Stec & Dolf van Paassen Energy

More information

SOLAR GEOMETRY (AND RADIATION)

SOLAR GEOMETRY (AND RADIATION) SOLAR GEOMETRY (AND RADIATION) Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 Solar Radiation Components glass will reflect some incoming radiation; absorb some; and transmit some SHGF (above)

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NORTH EAST WINDOWS USA, INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NORTH EAST WINDOWS USA, INC. NFRC 102-2014 THERMAL PERFORMANCE TEST REPORT Rendered to: NORTH EAST WINDOWS USA, INC. SERIES/MODEL: 100 Double Hung TYPE: Vertical Slider (Double Hung) Summary of Results Standardized Thermal Transmittance

More information

Chapter 1 INTRODUCTION AND BASIC CONCEPTS

Chapter 1 INTRODUCTION AND BASIC CONCEPTS Heat and Mass Transfer: Fundamentals & Applications 5th Edition in SI Units Yunus A. Çengel, Afshin J. Ghajar McGraw-Hill, 2015 Chapter 1 INTRODUCTION AND BASIC CONCEPTS Mehmet Kanoglu University of Gaziantep

More information

ABSTRACT INTRODUCTION OPTICAL CALCULATIONS

ABSTRACT INTRODUCTION OPTICAL CALCULATIONS Seventh International IBPSA Conference Rio de Janeiro, Brazil August 3-5, 2 MODELING WINDOWS IN ENERGYPLUS F. C. Winkelmann Simulation Research Group Building Technologies Department Environmental Energy

More information

Baker House Dining Room: Thermal Balance Report. + Q c. + Q v. + Q s. + Q e. + Q heating. + Q appliances. =Q appliances,21h Q appliances, x H

Baker House Dining Room: Thermal Balance Report. + Q c. + Q v. + Q s. + Q e. + Q heating. + Q appliances. =Q appliances,21h Q appliances, x H Shauna Jin + Caitlin Mueller 4.401 15 March 2006 Baker House Dining Room: Thermal Balance Report For this project, we chose to analyze the thermal balance of Alvar Aalto's Baker House Dining Room. In order

More information

Development and Validation of Flat-Plate Collector Testing Procedures

Development and Validation of Flat-Plate Collector Testing Procedures Development and Validation of Flat-Plate Collector Testing Procedures Report for February, 2007 Focus on Energy (FOE) supports solar thermal systems that displace conventional fuels by offering cash-back

More information

PROBLEM L. (3) Noting that since the aperture emits diffusely, I e = E/π (see Eq ), and hence

PROBLEM L. (3) Noting that since the aperture emits diffusely, I e = E/π (see Eq ), and hence PROBLEM 1.004 KNOWN: Furnace with prescribed aperture and emissive power. FIND: (a) Position of gauge such that irradiation is G = 1000 W/m, (b) Irradiation when gauge is tilted θ d = 0 o, and (c) Compute

More information

METHOD OF IN-SITU MEASUREMENT OF THERMAL INSULATION PERFORMANCE OF BUILDING ELEMENTS USING INFRARED CAMERA

METHOD OF IN-SITU MEASUREMENT OF THERMAL INSULATION PERFORMANCE OF BUILDING ELEMENTS USING INFRARED CAMERA METHOD OF IN-SITU MEASUREMENT OF THERMAL INSULATION PERFORMANCE OF BUILDING ELEMENTS USING INFRARED CAMERA Shinsuke Kato 1, Katsuichi Kuroki 2, and Shinji Hagihara 2 1 Institute of Industrial Science,

More information

Predicting Natural Light in Atria and Adjacent Spaces using Physical Models

Predicting Natural Light in Atria and Adjacent Spaces using Physical Models Predicting Natural Light in Atria and Adjacent Spaces using Physical Models Ibrahim Al-Turki P.O.Box 59035, Riyadh 11525 Saudi Arabia and Marc Schiler, Assoc. Prof. School of Architecture University of

More information

Thermal Analysis. with SolidWorks Simulation 2013 SDC. Paul M. Kurowski. Better Textbooks. Lower Prices.

Thermal Analysis. with SolidWorks Simulation 2013 SDC. Paul M. Kurowski. Better Textbooks. Lower Prices. Thermal Analysis with SolidWorks Simulation 2013 Paul M. Kurowski SDC PUBLICATIONS Schroff Development Corporation Better Textbooks. Lower Prices. www.sdcpublications.com Visit the following websites to

More information

Thermal Unit Operation (ChEg3113)

Thermal Unit Operation (ChEg3113) Thermal Unit Operation (ChEg3113) Lecture 3- Examples on problems having different heat transfer modes Instructor: Mr. Tedla Yeshitila (M.Sc.) Today Review Examples Multimode heat transfer Heat exchanger

More information

A. Solar Walls. B. Prototype I

A. Solar Walls. B. Prototype I A Introduction There are many different technologies that are emerging to help develop the future power infrastructure. The importance of these technologies is increasing the sustainability of how our

More information

Div. 1 Div. 2 Div. 3 Div.4 8:30 am 9:30 pm 12:30 pm 3:30 pm Han Xu Ruan Pan

Div. 1 Div. 2 Div. 3 Div.4 8:30 am 9:30 pm 12:30 pm 3:30 pm Han Xu Ruan Pan Write Down Your NAME, Last First Circle Your DIVISION Div. 1 Div. 2 Div. 3 Div.4 8:30 am 9:30 pm 12:30 pm 3:30 pm Han Xu Ruan Pan ME315 - Heat and Mass Transfer School of Mechanical Engineering Purdue

More information

Chapter 3: Steady Heat Conduction. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Chapter 3: Steady Heat Conduction. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University Chapter 3: Steady Heat Conduction Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University Objectives When you finish studying this chapter, you should be able to: Understand the concept

More information

PROBLEM Node 5: ( ) ( ) ( ) ( )

PROBLEM Node 5: ( ) ( ) ( ) ( ) PROBLEM 4.78 KNOWN: Nodal network and boundary conditions for a water-cooled cold plate. FIND: (a) Steady-state temperature distribution for prescribed conditions, (b) Means by which operation may be extended

More information

Institut national des sciences appliquées de Strasbourg GENIE CLIMATIQUE ET ENERGETIQUE APPENDICES

Institut national des sciences appliquées de Strasbourg GENIE CLIMATIQUE ET ENERGETIQUE APPENDICES Institut national des sciences appliquées de Strasbourg GENIE CLIMATIQUE ET ENERGETIQUE APPENDICES DEVELOPMENT OF A TOOL, BASED ON THE THERMAL DYNAMIC SIMULATION SOFTWARE TRNSYS, WHICH RUNS PARAMETRIC

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. NFRC 102-2014 THERMAL PERFORMANCE TEST REPORT Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: 45X - High Performance Dual Thermally Broken Storefront TYPE: Glazed Wall Systems (Site-built) Summary of

More information

The Characterization of Thermal Interface Materials using Thermal Conductivity for Within Sample and Batch to Batch Variation Analysis

The Characterization of Thermal Interface Materials using Thermal Conductivity for Within Sample and Batch to Batch Variation Analysis The Characterization of Thermal Interface s using Thermal Conductivity for Within Sample and Batch to Batch Variation Analysis Raymond Qiu, Karina Schmidt, Adam Harris and Gareth Chaplin* *Manager, Application

More information

Chapter 11. Energy in Thermal Processes

Chapter 11. Energy in Thermal Processes Chapter 11 Energy in Thermal Processes Energy Transfer When two objects of different temperatures are placed in thermal contact, the temperature of the warmer decreases and the temperature of the cooler

More information

Fig 1. Power Tower during Operation

Fig 1. Power Tower during Operation Accurate Flux Calculations Using Thermographic IR cameras in Concentrated Solar Power Fields A. Eitan*, G. Naor*, R. Hayut*, I. Segev*, J. Golbert**, S. Pekarsky*, A. Zisken*, G. Medan*, A. Feigelstock*,

More information

Heat and Mass Transfer Unit-1 Conduction

Heat and Mass Transfer Unit-1 Conduction 1. State Fourier s Law of conduction. Heat and Mass Transfer Unit-1 Conduction Part-A The rate of heat conduction is proportional to the area measured normal to the direction of heat flow and to the temperature

More information

Emissivity: Understanding the difference between apparent and actual infrared temperatures

Emissivity: Understanding the difference between apparent and actual infrared temperatures Emissivity: Understanding the difference between apparent and actual infrared temperatures By L. Terry Clausing, P.E. ASNT Certified NDT Level III T/IR, for Fluke Corporation Application Note Taking infrared

More information

Chapter 11. Energy in Thermal Processes

Chapter 11. Energy in Thermal Processes Chapter 11 Energy in Thermal Processes Energy Transfer When two objects of different temperatures are placed in thermal contact, the temperature of the warmer decreases and the temperature of the cooler

More information

Department of Energy Science & Engineering, IIT Bombay, Mumbai, India. *Corresponding author: Tel: ,

Department of Energy Science & Engineering, IIT Bombay, Mumbai, India. *Corresponding author: Tel: , ICAER 2011 AN EXPERIMENTAL AND COMPUTATIONAL INVESTIGATION OF HEAT LOSSES FROM THE CAVITY RECEIVER USED IN LINEAR FRESNEL REFLECTOR SOLAR THERMAL SYSTEM Sudhansu S. Sahoo* a, Shinu M. Varghese b, Ashwin

More information