Critical Measurement Set with PMU for Hybrid State Estimation

Similar documents
Smart Grid State Estimation by Weighted Least Square Estimation

Fine Tuning Of State Estimator Using Phasor Values From Pmu s

Mixed Integer Linear Programming and Nonlinear Programming for Optimal PMU Placement

OPTIMAL PLACEMENT AND UTILIZATION OF PHASOR MEASUREMENTS FOR STATE ESTIMATION

Optimal PMU Placement

Optimal PMU Placement for Power System State Estimation with Random Communication Packet Losses

Weighted Least Squares Topology Error Detection And Identification

Role of Synchronized Measurements In Operation of Smart Grids

CHAPTER 2 LOAD FLOW ANALYSIS FOR RADIAL DISTRIBUTION SYSTEM

A Term Project report on. State Estimation of Power Systems Using Weighted Least Squares Optimization Technique

CÁTEDRA ENDESA DE LA UNIVERSIDAD DE SEVILLA

Introduction to State Estimation of Power Systems ECG 740

Identifying Critical Measurements in the Power System Network

AS conceived during the 1970 s [1], [2], [3], [4] State

Cyber Attacks, Detection and Protection in Smart Grid State Estimation

Fast Real-Time DC State Estimation in Electric Power Systems Using Belief Propagation

= V I = Bus Admittance Matrix. Chapter 6: Power Flow. Constructing Ybus. Example. Network Solution. Triangular factorization. Let

OPTIMAL CAPACITOR PLACEMENT USING FUZZY LOGIC

State Estimation and Power Flow Analysis of Power Systems

STATE ESTIMATION IN DISTRIBUTION SYSTEMS

Robust State-Estimation Procedure using a Least Trimmed Squares Pre-processor

A Comparison of Local vs. Sensory, Input- Driven, Wide Area Reactive Power Control

On the Use of PMUs in Power System State Estimation

Generalized Injection Shift Factors and Application to Estimation of Power Flow Transients

MEASUREMENTS that are telemetered to the control

A NEW STATE TRANSITION MODEL FOR FORECASTING-AIDED STATE ESTIMATION FOR THE GRID OF THE FUTURE

HIERARCHICAL STATE ESTIMATION FOR WIDE AREA POWER SYSTEMS

Optimal Placement of PMUs in Power Systems Using Mixed Integer Non Linear Programming and Bacterial Foraging Algorithm

STUDY OF THE UTILIZATION AND BENEFITS OF PHASOR MEASUREMENT UNITS FOR LARGE SCALE POWER SYSTEM STATE ESTIMATION. A Thesis YEO JUN YOON

Advanced load modelling techniques for state estimation on distribution networks with multiple distributed generators

An Approach to Achieving Global Optimum of AC Electric Power System State Estimators

A Linear Formulation for Power System State Estimation including RTU and PMU Measurements

668 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 24, NO. 2, MAY 2009

Performance Improvement of the Radial Distribution System by using Switched Capacitor Banks

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

Optimal Capacitor placement in Distribution Systems with Distributed Generators for Voltage Profile improvement by Particle Swarm Optimization

A technique for simultaneous parameter identification and measurement calibration for overhead transmission lines

Simultaneous placement of Distributed Generation and D-Statcom in a radial distribution system using Loss Sensitivity Factor

CAPACITOR PLACEMENT IN UNBALANCED POWER SYSTEMS

False Data Injection Attacks Against Nonlinear State Estimation in Smart Power Grids

AN OPTIMIZED FAST VOLTAGE STABILITY INDICATOR

State estimation in distribution grids

PMU-Based Power System Real-Time Stability Monitoring. Chen-Ching Liu Boeing Distinguished Professor Director, ESI Center

A SYNCHROPHASOR ASSISTED HYBRID STATE ESTIMATOR

Power System Security Analysis. B. Rajanarayan Prusty, Bhagabati Prasad Pattnaik, Prakash Kumar Pandey, A. Sai Santosh

Power Grid Partitioning: Static and Dynamic Approaches

Branch Outage Simulation for Contingency Studies

POWER SYSTEM DYNAMIC STATE ESTIMATION and LOAD MODELING. Cem Bila

Performance analysis and comparison of load flow methods in a practical distribution system

Real Time Voltage Control using Genetic Algorithm

A Scenario-based Transmission Network Expansion Planning in Electricity Markets

COMPARISON OF STATISTICAL ALGORITHMS FOR POWER SYSTEM LINE OUTAGE DETECTION

Advances in Environmental Biology

Power Grid State Estimation after a Cyber-Physical Attack under the AC Power Flow Model

URTDSM Initiative in India and Controlled Islanding using PMU Measurements

Optimal Capacitor Placement in Distribution System with Random Variations in Load

UNCERTAINTY-DRIVEN ADAPTIVE ESTIMATION WITH APPLICATIONS IN ELECTRICAL POWER SYSTEMS

1 Unified Power Flow Controller (UPFC)

Optimal DG allocation and sizing in a Radial Distribution System using Analytical Approach

A Fast Solution for the Lagrange Multiplier-Based Electric Power Network Parameter Error Identification Model

LINE FLOW ANALYSIS OF IEEE BUS SYSTEM WITH THE LOAD SENSITIVITY FACTOR

Effect of Various Holomorphic Embeddings on Convergence Rate and Condition Number as Applied to the Power Flow Problem

Empirical analysis of l 1 -norm for state estimation in power systems

Extended Optimal PMU Placement Problem for Voltage Stability Assessment

An Equivalent Circuit Formulation of the Power Flow Problem with Current and Voltage State Variables

A Framework for Phasor Measurement Placement in Hybrid State Estimation Via Gauss Newton

A DC Power Flow Extension

Modelling and Simulation of TCPAR for Power System Flow Studies

Research on the Effect of Substation Main Wiring on the Power System Reliability Yuxin Zhao 1, a, Tao Liu 2,b and Yanxin Shi 3,c

SINGLE OBJECTIVE RISK- BASED TRANSMISSION EXPANSION

Data-Driven Joint Topology and Line Parameter Estimation for Renewable Integration

Assessment and enhancement of voltage stability based on reactive power management using UPFC

Towards on-line voltage stability assessment using synchrophasors

An Investigation on the Numerical Ill-conditioning of Hybrid State Estimators

Optimal PMU-Based Monitoring Architecture Design for Power Systems 1

Sensitivity-Based Line Outage Angle Factors

OPTIMAL CAPACITORS PLACEMENT IN DISTRIBUTION NETWORKS USING GENETIC ALGORITHM: A DIMENSION REDUCING APPROACH

Adaptive under frequency load shedding using synchrophasor measurement

Fast Decoupled Power Flow for Unbalanced Radial Distribution Systems

Dynamic Decomposition for Monitoring and Decision Making in Electric Power Systems

Understanding Load Flow Studies by using PSAT

ECEN 615 Methods of Electric Power Systems Analysis Lecture 18: Least Squares, State Estimation

CURENT Course Power System Coherency and Model Reduction

A Community-Based Partitioning Approach for PMU Placement in Large Systems

A Decomposition Based Approach for Solving a General Bilevel Linear Programming

Power System Security. S. Chakrabarti

Optimal Locating and Sizing of TCPST for Congestion Management in Deregulated Electricity Markets

Determination of the Minimum-Variance Unbiased Estimator for DC Power-Flow Estimation

Extension of a Probabilistic Load Flow Calculation Based on an Enhanced Convolution Technique

EE 581 Power Systems. Admittance Matrix: Development, Direct and Iterative solutions

On Computing Power System Steady-State Stability Using Synchrophasor Data

POWER flow studies are the cornerstone of power system

ECEN 615 Methods of Electric Power Systems Analysis Lecture 19: State Estimation

Lossy DC Power Flow. John W. Simpson-Porco. Universidad de Chile Santiago, Chile. March 2, 2017

Voltage Stability Monitoring using a Modified Thevenin Impedance

FLEXIBLE ac transmission system (FACTS) devices give

On-line Calibration of Voltage Transformers Using Synchrophasor Measurements

K. Valipour 1 E. Dehghan 2 M.H. Shariatkhah 3

Performance of Flocking-Based Control Schemes in Smart Grid Applications

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

Transcription:

6th NATIONAL POWER SYSTEMS CONFERENCE, 5th-th DECEMBER, 200 25 Critical Measurement Set with for Hybrid State Estimation K.Jamuna and K.S.Swarup Department of Electrical Engineering Indian Institute of Technology, Madras Chennai 60006 Email: jamram k@yahoo.co.in Abstract This paper presents a method for designing minimal measurement set that include both Supervisory Control And Data Acquisition (SCADA) and Synchronized Phasor Measurements Units (S) data for a Hybrid State Estimation (HSE). The optimal location of Phasor Measurement Units () is performed by Binary Integer Linear Programming (BILP). Among these s, the highest priority indexed s are selected for implementation and the remaining unobservable buses are made to be observable using traditional measurements. An augmented bus matrix corresponds to each unobservable node in a network is calculated. Power Injection and Power Flow measurements are to be placed in the unobservable node and branch of the power system network based on the fixed index value. The hybrid measurement jacobian matrix is formed with the critical measurements and system observability has been proved numerically. System states are evaluated using the chosen measurements by applying Hybrid State Estimation and are validated through the simulations carried out on standard IEEE systems and New England systems and the results are compared. Index Terms Hybrid State Estimation, SCADA, Synchro Phasor Measurement Units, Binary Linear Integer Programming, Hybrid Measurement Jacobian Matrix. I. INTRODUCTION State Estimation is the process of assigning a value to an unknown system variables based on the measurements obtained from the system. State estimator has been widely used as an important tool for online monitoring, analysis and control of power systems. It is also exploited to filter redundant data, to eliminate incorrect measurements and to produce reliable state estimates. Entire power system measurements are obtained through RTU (Remote Terminal Unit) of SCADA systems which have both analog and logic measurements. Logic measurements are used in topology processor to determine the system configuration. State estimator uses a set of analog measurements such as bus voltage magnitude, real power injections, reactive power injections, active power flow, reactive power flow and line current flows along with the system configuration. Therefore the measurement placement becomes an important problem in SE requires sufficient measurements. Optimal meter placement of Traditional State Estimation (TSE) for maintaining observability has been proposed by many researchers. In order to reduce the metering cost, meters are to be placed only at the essential location in the system. A topological algorithm proposed by Nucera []. Baran has developed a method for choice of measurements and loss of RTUs [2]. Bei Gou and Ali abur have contributed an algorithm for meter placement for network observability ( [] - []). In addition to the observability bad data measurements have been done in [5]. Optimal meter placement during contingencies are also presented in [6]. Simulated annealing is also used for obtaining optimal location of meters []. Static state estimation is performed based on singular value decomposition [8], which could identify unobservable islands in the system. The synchronized phasor measurements make significant improvements in control and protection functions of the entire power system and also improves the accuracy of state variables. The is a device capable of measuring voltage and current phasor in a power system. Synchronism among phasor measurements is achieved using a common synchronizing signal from Global Positioning Satellite (GPS) [9]. Many researchers have focused on the optimal location of for system to be observable. Tabu search algorithm is proposed to identify the optimal placement of. Bad data detection is done along with optimal placement by Jain Chan and Ali abur [0]. Bei Gou [] is proposed a new integer linear programming approach for optimal placement with and without considering traditional SCADA measurements. In earlier work, loss of measurements are not included, it has been done in [6]. Recently placement of problem has been solved optimally using differential evolution [2]. From early days of Schweppes [], developments of SE were begun. The number of requirements to meet sufficient measurements in a power network poses a problem. Due to the factor of price, technology, communication ability the could not be implemented at all the buses in the system. When few phasor measurements are added to sufficient numbers of traditional measurements, improvements can obtained []. In this paper, a new method has been proposed for the selection of, Power Flow measurements and Power Injection measurements, such that the entire power network is observable. Only the bus - branch model of the network is needed to identify the minimum s, traditional measurements and their locations. Using these measurements, system states have been evaluated using Hybrid State Estimation. A step by step procedure for replacement of SCADA by has been proposed here.

6th NATIONAL POWER SYSTEMS CONFERENCE, 5th-th DECEMBER, 200 255 The organization of the paper is as follows. Section II talks about the selection of a critical measurement set including both and SCADA measurements, which explicated in two stages. The system observability has been verified numerically in the third stage. Hybrid State Estimation and its formulation elucidates in Section III. Section IV shows the chosen measurement sets of test systems and simulation results of state estimation tested on IEEE standard systems. Finally, concluding remarks are given in Section V. II. CRITICAL MEASUREMENT SETS The observability of a power system depends on the number of measurement data. Meter location of SE is very essential in a power system network. The number of measurements have been increased, which improves the observability but cost increased. Therefore enough measurements have been identified to estimate states. In practice, s needed to be installed in the power system network which already monitored by the traditional measurements. Suppose a is installed at a particular location, the identification of essential traditional measurements have to be monitored is performed in this paper. If any one the chosen measurements is removed, then the system become unobservable. Therefore the selected measurements are named as critical measurements. In the first stage, optimal location of is identified by binary linear integer programming [] to make the system to be observable. Priority Index (PI) is defined for each based on number of buses to be observed using that particular. Among these optimally located s, certain s (0. times of network buses) are chosen for implementation according to their PI. The remaining buses are considered to be unobservable or remaining system are named as unobservable island. In the second stage, the unobservable island is made to be observable using power injection and power flow measurements. An augmented matrix (P aug ) of each network buses are evaluated. The elements of (P aug ) corresponds to the unobservable node is more than the Fixed Index (FI) value, Power Injection measurement ( ) is placed at that node. Power Flow measurement ( ) must be positioned in the branch which is connected to the unobservable node having a less fixed index. In the third stage, the network observability checking is performed. It determines whether the selected measurements are able to estimate unique solution of SE. The hybrid jocobian measurement matrix (C h ) is formed using the above selected measurements and the rank of this matrix R Ch is found. The working of the proposed strategy is shown as a flowchart in fig.. A. Selection of measurements The is able to measure the voltage phasor of the installed bus and current phasor of the lines connected to this bus. In the first step, the optimal location of is done using binary integer linear programming. The placement Start Optimal Location of - binary linear integer programming Calculate Priority Index for each optimally selected Highest Priority Indexed chosen and placed at the node No. of unobservable buses ( N uno ) identified Bus augmented matrix is calculated based on unobservable buses P aug If P aug (N uno ) >FI No Yes Place Power Flow meter at branch connected to that node Place Power Injection meter at Fig.. Form C h matrix and find rank, which is equal to ( n -) for DC power flow equation Entire power network is observable Stop Flowchart for Choice of Measurements STAGE - I Selection of STAGE - II & measurements selection N uno (i) STAGE - III Observability Checking problem can be formulated as follows: n min s i () S.T. i= A pmu S B pmu S=[s,s 2,...s n ] T s i 0, B pmu is a unit vector (n X ) and s i is the placement variable. n is number of buses in a system. The elements of A pmu can be written as follows,, if u=v a uv =, if u and v are connected 0, otherwise In the second step, the priority index is estimated for each optimally located using eqn. (2). Here, the number of for implementation is chosen only a 0% of the network buses in the system from optimal set (O pmu ). Buses with high value PI values are preferred to put into practice. The number of unobservable buses or unobservable islands are also identified. In this island, SCADA measurements are going to be placed. The priority index are given below, PI(j) =N obs (j)/r; (2) where PI(j) Priority Index of j th N obs (j) Number of buses to be observed by j th

6th NATIONAL POWER SYSTEMS CONFERENCE, 5th-th DECEMBER, 200 256 r j PF Fig. 2. Max. buses observed by highest PI valued Optimally Located 2 2 8 6 5 Example System illustrate the working of the proposed method A placed at a particular bus measures both voltage phasor of that bus and current phasor of the lines connected to that bus. A linearized measurement jacobian of (C pmu ) is shown below. δ i δ j. δ k.. δ n δ i 0 0 0 0 0 0 I jk 0 0 0 0 0 I ij 0 0 0 0 0........ Consider a bus system as shown in fig. 2. Optimal location of is identified and located in the system. O pmu is optimal set for the example seven bus system O pmu = {2,, }. The PI of O pmu is estimated using the eqn. (2) and shown in Table I. Bus no. has the highest priority index, so is implemented on this bus. The number of observable buses (r) is due to the choice of at bus no. and is shown as a dotted line in fig. 2. Now the unobservable buses of example systems are and. These buses are made to be observable using SCADA measurements such as power injection and power flow. TABLE I LOCATION AND ITS PRIORITY INDEX Optimal Loc Observed Priority No. of unobserve of Bus Index Buses 2,, 0.5 2,5,6, 2,2, 0.5 Suppose the at bus 2 is chosen, the number of unobservable buses are, they are buses numbered, 5 and 6. Now we require traditional measurements to make the system observable. But the former case required only two SCADA measurements. Hence, highest PI valued is chosen for implementation. B. Selection of SCADA measurements In this paper, unobservable island made to be observable by traditional measurements such as both real and reactive power injections and also power flows. Initially, augmented 6 PF 5 bus matrix (P aug ) is evaluated using the eqn. (), where n is the number of buses in a system This matrix is found based on the unobservable bus of the previous stage. The values of unobservable vector X u is for unobservable node and zero for observable node. This vector is producted with the (A pmu ) matrix, the augmented bus (P aug ) matrix is obtained. P aug(nx) = A pmu(nxn) X u(nx) () The elements of (P aug ) corresponds to unobservable bus is more than the Fixed Index (FI) value, then power injection measurements are to be placed in that node. By running more trials, the fixed index is found to be which gives less number of traditional measurements. Power flow measurements are to be positioned in the branches, when the (P aug ) of the unobservable bus will be less than FI value. The algorithm for selection of SCADA measurements is explained in the following steps. ) Input the number of unobservable buses N uno. 2) Calculate the augmented bus matrix P aug based on the unobservable buses. ) If the elements of P aug correspond to unobservable bus is greater than FI value, then Power Injection measurement ( ) is placed at this unobservable bus N uno (i). ) If P aug is less than FI, then Power Flow measurement ( ) is positioned in any one of the branches connected to that unobservable bus N uno (i). 0 0 0 0 0 0 0 0 0 0 0 P aug = 2 = 0 0 0 0 X u 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TABLE II CHOICE OF SCADA MEASUREMENTS Unobservable Bus (N uno) P aug(n uno) Choice of measurements (-2) Power Flow 2 (2-, -5) Power Flow In this case, the is placed at rd bus of the system. The number of unobservable buses in a system is two (, ). P aug matrix for this example is shown above. The vector X u is [ 0 0 0 0 0] T. The elements corresponds to the unobservable node is and 2. Therefore, the number of power injection measurements is selected here. But the power flow measurements are to be placed at st and th branches and is shown in fig. 2. The chosen SCADA measurements for the example system is explained in Table II. C. Observability Checking Observability analysis can be carried out using fully coupled or decoupled measurement equation. Observability of δ based

6th NATIONAL POWER SYSTEMS CONFERENCE, 5th-th DECEMBER, 200 25 only on real power (P) measurements is analyzed using DC power flow equations. The measurement jacobian matrix (C) is formed based on the measurements obtained from SCADA systems. The rank of this matrix should be equal to (n-) for (P-δ equation); n for (Q-V equation) [5]. In this paper, both SCADA and measurements have been used. So the hybrid measurement jacobian matrix (C h ) is formed by joining two sub matrices C and C SCADA. The rank is equal to the network buses. Then the system is fully observable, which is verified numerically. ] C h = [ C C SCADA The at bus measures voltage phasor of bus and line current phasor of the lines (,6, and 8). The measurement jacobian of (C ) is framed for this case as described below. δ δ 2 δ δ δ 5 δ 6 δ δ 0 0 0 0 0 0 I 2 0 0 0 0 0 I 5 0 0 0 0 0 I 6 0 0 0 0 0 I 0 0 0 0 0 The traditional measurements of this example is (P ) and (P 2 ). The measurement jacobian for SCADA measurements (C SCADA ) is shown below. Bus no. is considered to be reference bus. The (P-δ) equation of hybrid systems is obtained by joining both C and C SCADA and then remove the reference bus column, which rank is equal to 6. So the system is fully observable using these selected measurements. For the estimation of voltage, reactive power is required. The reactive power injection and power flow measurement are placed at the same location of real power injection and power flow respectively. Now both voltage and angle of network buses are able to calculate. [ ] 0 0 0 0 0 C SCADA = 0 0 0 0 0 III. HYBRID STATE ESTIMATION (HSE) In hybrid state estimation the S are added to the existing SCADA measurements for estimating system states. The unknown state variables X and the measurement vector are related by the linear Gaussian measurement model, where Z hse H hse ɛ Z hse = H hse X + ɛ () Both SCADA and measurements vector First order derivative of both SCADA and measurements w.r.t state variables Measurement Noise The measurement noise ɛ = N(0, R) is zero mean with standard deviation of 0.02. The measurement matrix H hse is known and deterministic. Initially, flat profile is assumed for the state variables. The optimal state estimate ˆX is given by, ΔX ˆ =(Hhse T R hse H hse) (Hhse T R hse ΔZ hse) (5) ˆX = X 0 + ΔX ˆ (6) Measurement matrices, Jacobian and its sub matrices for traditional measurements, voltage phasor and current phasor measurements of can be written as, ΔP [ ] ΔZhse = ΔZ SCADA ΔZ Vpmu ΔZ Ipmu ΔQ Δθ p = ΔV p M I G I ΔI ij r ΔI ij i M F G N H [ ] Hhse = H V I 0 = 0 I H I A typical transmission line π model of the network is used in the formation of H I matrix is shown in fig., where g pq + jb pq is the series branch of the transmission line and g sp +jb sp is shunt branch of the transmission line. The branch current flowing through the nodes between p and q are given in [6]. The elements of H I matrix are the derivatives of branch currents with respect to state variables. σ 2 I pq,r V p Fig.. F I N I () (8) =( I pq,r I pq ) 2 σ 2 I pq +( I pq,r δ pq ) 2 σ 2 δ pq =(cosδ pq ) 2 σ 2 I pq +(I pq sinδ pq ) 2 σ 2 δ pq (9) σ 2 I pq,i =( I pq,i ) 2 σi 2 I pq +( I pq,i ) 2 σδ 2 pq δ pq pq =(sinδ pq ) 2 σi 2 pq +(I pq cosδ pq ) 2 σδ 2 pq (0) I pq g sp +jb sp g pq b pq V q g sq +jb sq Typical π Model of Transmission Network

6th NATIONAL POWER SYSTEMS CONFERENCE, 5th-th DECEMBER, 200 258 The standard deviation of the errors of voltage and current phasor measurement is set as 0.00rad and 0.002 pu []. Similarly 0.08pu is assumed for the standard deviation of power flows and power injections. Here the real and imaginary values of branch current measurements are used for the formation of measurement set. So that standard deviation of real and imaginary of branch current have been evaluated using eqn.( - 2). σ 2 I pq,r =( I pq,r ) 2 σi 2 I pq +( I pq,r ) 2 σδ 2 pq δ pq pq =(cosδ pq ) 2 σi 2 pq +(I pq sinδ pq ) 2 σδ 2 pq () =( I pq,i ) 2 σi 2 I pq +( I pq,i ) 2 σδ 2 pq δ pq pq =(sinδ pq ) 2 σi 2 pq +(I pq cosδ pq ) 2 σδ 2 pq (2) σ 2 I pq,i The covariance matrix (R hse ) of HSE is formed using conventional covariance matrix R, voltage phasor covariance (R v ) and current phasor covariance (R i ). R hse = R 0 0 0 R v 0 0 0 R i If enormous measurements used for estimating the system states, then it leads to iterative procedure. The chosen measurements are equal to the number of state variables. Therefore,the solution of this algorithm is direct and non-iterative [8]. The chosen measurements are essential one for the system to be observable and give unique state estimates. IV. SIMULATION RESULTS The working of the proposed method is tested for IEEE, New England 9 bus and IEEE 5 bus. The assumption made that there is no zero injection bus in the system. First stage of measurement selection is choice of. Traditional measurements have been selected in the second stage. The selected measurements (both and SCADA) have been used for evaluating state variables in Hybrid State Estimation. System data was obtained from [9]. The true values of state vectors are taken from Fast Decoupled Load Flow (FDLF). Bus and Bus are chosen as reference bus for IEEE ans NE 9 systems respectively. The voltage phasor and current phasor measurements of s are acquired from FDLF in addition with measurement errors. Initially optimal location of is obtained by BILP and is shown in Table III. Optimal set for IEEE bus system is O pmu = [2,6,,9]. is elected based on priority index. PI value for buses 2,6, and 9 are and for is 0.5. Highest PI valued s are chosen for implementation. So, Only one at bus 9 and s at bus 2,6,25 and 29 are opted for IEEE and NE 9 bus system respectively. Suppose is placed at bus no.2, the unobservable buses are [6,,8,9,0,,2, and ], totally 9 bus measurements. The N uno is equal for same priority valued buses. Therefore, any one of the is selected among the same priority indexed buses. Test Case IEEE Bus NE 9 Bus IEEE 5 Bus TABLE III SELECTION OF S FOR IEEE TEST SYSTEMS Optimal Location Priority Index Selected s Unobservable buses 2,6,9.000 9,2,,5,6 0.50 8,,2, 2,6.000 2,6,8,9,0,2 0,,, 25,29,,5,6 9,20,22,2 0.50,8,9,20 25,29 2,22,2,2 9,20 0.500 2,2,, 5,6,9.000 0,9,20,2,22 0.8 2,2,25,26,2,6, 0.66,6, 28,29,0,,2 6,2,29,25,22 0.500 6,,8,9, 5,5,,5 5,6,,8,50 9,2,20 0. 5 to 55,5 TABLE IV SELECTION OF SCADA MEASUREMENTS Test Case Nodes of Branches of N uno measurements measurements IEEE Bus 2,5,6,,2,8,9,9 9 NE 9 Bus 6,2,22,9,, 2,26,2,2,0,6,9 2,0,8, 5,,2,,0,9,8 8,2,8,2,29,25 6,0,69,68,6,6,6 IEEE 5 Bus 22,0 60,59,58,5,5,6, 2,9,8,,,,0 29,5 Only few buses are observable using the selected s, remaining buses are considered to be unobservable. These are made to be observable by proper choice of traditional measurements. In the second stage, selections of power flow ( ) and power injection measurements ( ) have been done and listed in Table IV. This table explains the location of traditional measurements and also the number of unobservable buses (N uno ). IEEE bus system have power injections and 5 power flow measurements. Power injection measurements are located, if the elements of that augmented bus matrix is more than FI value else power flow measurements are positioned at the branches connected to that bus. The location of measurements for IEEE bus system is shown in fig.. The performance of the HSE is estimated though Mean Square Error (MSE). By increasing s, MSE error of state vectors should be reduced []. So the simulation has been done for different number of s and according to this, SCADA measurements have been selected. The results of HSE are shown in Table V. Two set of s have been considered. First Case and s (0. times of network bus) and second case and 8 s (0.2 times of network bus) are decided for IEEE and NE 9 bus system respectively. The location of for second case is highest PI valued buses 2, 6, and 9 for IEEE bus test case. Table V also shows that MSE of state vectors are reduced by increasing s. Errors lie within the tolerable limits. If the s are increased, the required traditional measurements will be decreased, so calculation time for H matrix is reduced.

6th NATIONAL POWER SYSTEMS CONFERENCE, 5th-th DECEMBER, 200 259 6 2 9 5 8 Fig.. 0 2 5 8 0 8 20 9 5 6 Location of Measuremnts for IEEE bus 6 2 2 Therefore the computation time is very low. It is well suitable for online implementation. TABLE V RESULTS OF HSE WITH CRITICAL MEASUREMENT SETS Test No. of Comp. time MSE of V MSE of δ systems s s pu deg IEEE 0.6 0.00.55e 0.5.022e.e 5 NE 9 0.98.69e.8e 8 0.808.e 5 6.e 5 IEEE 5 bus 6 0.0 0.068 0.005 0.0989 0.0 0.0 Mean Squared Error 0.2 0.5 0. 0.05 Magnitude Error, pu Angle Error, deg 0 0 2 6 8 0 2 6 8 Number of Fig. 5. Effect of increasing number of s to the system on errors for IEEE 5 bus The effect of increase in number of s is done for IEEE 5 bus system and is shown in fig 5. It reveals that the estimated state variables error is drastically decreasing by increase in. Also selected s are chosen from optimal set O, which improves the estimate values. Both angle and magnitude error of bus voltage are reached to zero when all s are located optimally. V. CONCLUSION A Hybrid State Estimation algorithm, using critical measurements including both and SCADA is proposed in this 9 paper. From the simulation study performed on standard IEEE systems, it is observed that this algorithm provides the best state estimates with less computation time. This method gives an idea about where to implement a into the existing SCADA systems, which provokes a much better result. The more accurate values of state variables is obtained when the number of s are increased in the system. An important advantage of this method is non-iterative which reduces the computation time and suitable to implement in the near future. In view of extension in this work, analysis can be done taking into account the loss of measurements, failure of and effectiveness of positions in HSE. REFERENCES [] R. Nucera and M. Gilles, Observability analysis: a new topological algorithm, IEEE Transactions on Power Systems, vol. 6, no. 2, pp. 66 5, 99. [2] M. Baran, J. Zhu, H. Zhu, and K. Garren, A meter placement method for state estimation, IEEE Transactions on Power Systems, vol. 0, no., pp. 0 0, 995. [] B. Gou and A. Abur, A direct numerical method for observability analysis, IEEE Transactions on Power Systems, vol. 5, no. 2, pp. 625 60, 2000. [], An improved measurement placement algorithm for network observability, IEEE Transactions on Power Systems, vol. 6, no., pp. 89 82, 200. [5] F. Wu, W. Liu, and S. Lun, Observability analysis and bad data processing for state estimation with equality constraints, IEEE Transactions on Power Systems, vol., no. 2, pp. 5 58, 988. [6] F. Magnago and A. Abur, A unified approach to robust meter placement against loss of measurements and branch outages, IEEE Transactions on Power Systems, vol. 5, no., pp. 95 99, 2000. [] A. Antonio, J. Torreao, and M. Do Coutto Filho, Meter placement for power system state estimation using simulated annealing, in 200 IEEE Porto Power Tech Proceedings, vol., 200. [8] C. Madtharad, S. Premrudeepreechacharn, and N. Watson, Power system state estimation using singular value decomposition, Electric Power Systems Research, vol. 6, no. 2, pp. 99 0, 200. [9] A. Phadke, Synchronized phasor measurements in power systems, IEEE Computer Applications in Power, vol. 6, no. 2, pp. 0 5, 99. [0] J. Chen and A. Abur, Placement of s to enable bad data detection in state estimation, IEEE Transactions on Power Systems, vol. 2, no., pp. 608 65, 2006. [] B. Gou, Generalized integer linear programming formulation for optimal placement, IEEE Transactions on Power Systems, vol. 2, no., pp. 099 0, 2008. [2] C. Peng, H. Sun, and J. Guo, Multi-objective optimal placement using a non-dominated sorting differential evolution algorithm, International Journal of Electrical Power & Energy Systems, 200. [] F. Schweppe and J. Wildes, Power system static-state estimation, Part I: Exact model, IEEE Transactions on Power Apparatus and Systems, pp. 20 25, 90. [] M. Zhou, V. Centeno, J. Thorp, and A. Phadke, An alternative for including phasor measurements in state estimators, IEEE transactions on power systems, vol. 2, no., pp. 90 9, 2006. [5] A. Abur and A. Exposito, Power system state estimation: theory and implementation. CRC, 200. [6] K. Jamuna and K. Swarup, Two stage state estimator with phasor measurements, International Conference on Power Systems, pp. 5, Date:2-29 2009. [] K. Martin, D. Hamai, M. Adamiak, S. Anderson, M. Begovic, G. Benmouyal, G. Brunello, J. Burger, J. Cai, B. Dickerson et al., Exploring the IEEE Standard C. 8 2005 Synchrophasors for Power Systems, IEEE Transactions on Power Delivery, vol. 2, no., pp. 805 8, 2008. [8] A. Wood and B. Wollenberg, Power generation, operation, and control. Wiley New York et al., 98. [9] R. Zimmerman and D. Gan, MatPower: A Matlab power system simulation package, Manual, Power Systems Engineering Research Center, Ithaca NY, vol., 99.