THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

Similar documents
C60N circuit breakers0 B, C and D curves IEC 60898: 6000 A, IEC : 10 ka

90 MCB range Modular circuit breakers for circuit protection

UL 1077 DIN Rail Supplementary Protectors

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION

5SJ4...-.HG Circuit Breakers to IEC and UL 489

MCB NB1-63H Miniature Circuit Breaker

C120N circuit-breakers B, C and D curves EN 60898/EN 61009: IEC : 10 ka

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity

MR medium rating busbar

SIRCOVER Manual transfer switches from 125 to 3200 A

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

3VT4 Molded Case Circuit Breakers up to 1000 A

ATyS Automatic and remotely operated transfer switches from 125 to 3200 A

Single Core XLPE/LSF/AWA/LSF Power Cable

Thermal-Magnetic Circuit Breaker 2210-T2...

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

TeSys circuit-breakers

Thermal-Magnetic Circuit Breaker 2210-S2..

Three Core XLPE/LSF/SWA/LSF Power Cable

1SDC007004D0201. Discrimination tables

Thermal-Magnetic Circuit Breaker 2210-S2...

Thermal-Magnetic Circuit Breaker 2210-S2...

Thermal-Magnetic Circuit Breaker 2210-S2..

Table of Contents Pin-Configuration Selection Guide for HDE, HDS, & EFP

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

Overload Relays. SIRIUS 3RU1 Thermal Overload Relays. 3RU11 for standard applications. 5/46 Siemens LV 1 AO 2011

SWITCHGEAR: design concepts, testing, standards and safety of persons and installations

Thermal-Magnetic Circuit Breaker 2210-S2..

Issued August DATA SHEET. 3VT3 MCCB up to 630 A

I, THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

TECHNICAL INFORMATION

Film Capacitors. EMI suppression capacitors. Date: June 2018

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

File E28476 Vol. 7 Sec. 44 Page 1 Issued: Vol. 23 Sec. 18 Revised: Vol. 67 Sec. 4 and Report D E S C R I P T I O N

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

08/072 PKZ2 Motor-Protective Circuit-Breakers Tripping Characteristics

S R O T C U D IN & MYRRA

Siemens AG Miniature Circuit Breakers. Totally Integrated Power SENTRON. Configuration. Edition 10/2014. Manual. siemens.

M I N I S T R Y O F C O M M U N I C A T I O N S T E L E C O M M U N I C A T I O N S S E C T O R T E C H N I C A L S T A N D A R D F O R

FAZ tripping characteristics at 30 C: B, C, D to IEC/EN FAZ tripping characteristics at 30 C: R to IEC/EN

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS

Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000,

Digital Current Transducer HO-SW series I P N = A. Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW

5SP and 5SY Supplementary Protection UL 1077

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018

Semiconductor (AC) fuses

Electrical installation solutions for buildings Technical details Arc Fault Detection Devices

Fire Resistant Armoured Power Cable


Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T...

Redline Unibis : the solution Circuit protection

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals.

DC/DC regulator Input V Output up to 16 A

H07RN-F. Flexible Cables and Cords 60 C 450/750 V. Application. Specifications

An Innovative Simple Test Circuit for Single-Phase Short Circuit Making Test of High-Voltage Switching Devices

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM

Electrical installation solutions for buildings Technical details RCDs

TeSys enclosed starters 2

LD-LP-LL-LC Rope Safety Switches with reset for emergency stop

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD.

Report No 247/ This Report consists of 41 pages

Masterpact. Installation recommendations

Semiconductor (AC) fuses

2.12. Ex-Linear light fittings for fluorescent lamps - max. ambient temperature + 60 C - nllk W - 58 W for Zone 2 and 22

440V 500V V / / /2 12.

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS. Type PVA10 / PV10 PV14 PV22 Rated current I n up to 32 A up to 63 A up to 125 A Rated voltage U n

PHOENIX CONTACT - 04/2016. Features

GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN Mitglied der Short-Circuit-Testing Liaison (STL) Test Report

LEDlight 30 W Universal dimmable series

Current protection I 2 t long-time protection

Impedance relay and protection assemblies

BETA Protecting Miniature Circuit Breakers

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM

Ex-Floodlight PXLED. (Ex-Zone 1, 2, 21 and 22)

40 CD RANGE FLUSH-MOUNTING DISTRIBUTION BOARDS AND ENCLOSURES

Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation

Sealing possibility Electrical endurance (ops) Mechanical endurance (ops) Overvoltage category Standards

Blocks and Holders POWR-BLOKS. Connectors. Ampere Ratings. Ordering Information. Applications. Specifications. Distribution/Splicer Blocks and Covers

DATA SHEET POSITIVE TEMPERATURE COEFFICIENT AC/DC POWER SUPPLY SMD0603 series

Internal Components Forms of Separation

DATA RACK BUSBAR. Data Rack Busbar Systems A.

INFORMATION TECHNOLOGY SYSTEMS SPDs FOR 19 TECHNOLOGY. NET Protector Surge Arrester. Protects switches, HUBs and telecommunication

NH fuse-links gg 500VAC double indicator/live tags size 000, 00, 0, 1, 2, 3

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

16 Appendix 16 Electrical Research Association Report

LEDlight 20 W Universal dimmable series

TEST REPORT IEC/EN Circuit-breakers for over current protection for household and similar installations

Single Phase Motors Technical Datasheets

Switches in conformity with ATEX directive

1SDC007004D0205. Coordination tables

8 Installation Equipment

2.12. Ex-Linear light fittings for fluorescent lamps. nllk W - 58 W (Zone 2, 21, 22)

VK2 volume flow controller Overview

General characteristics, Products

C60 UL489 차단기. Standard features

Transcription:

July 04 THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE In this third part. we want to speak about how important is the correct sizing of the electrical conductors to be used as "wiring" inside the distribution panels which will be installed in explosion proof areas. So as the electrical conductors are properly sized, you need to analyze also the sizes and the characteristics of the organs responsible for their protection, as well as the protection of the underlying loads. Beyond the capacity of current conductors and the operating temperature, it s essential that they are also sized according to pass-through specific energy, in order to avoid that the overheating, generated during the working or during the event of overcurrent due to a malfunction caused by short circuits, may be the cause of the increasing of enclosure surface temperature and, consequently, the automatic triggering of explosion of the outer atmosphere which, at that time, may be saturated with gas. This dimensioning will be according to the pass-through specific energy in evry electrical conductors (I t) in extreme short-circuit situation (value detectable in the manufacturer's technical documentation). This value must be taken as the basis for calculating according to the temperature class and the ambient temperature of the project. Let s see a brief overview of what the reference Electrical Standard states of. Extract from CEI EN 64-8/4 Standard (paragraph 434.3.) (see also Community standard DS/HD 60364-4 and international IEC 60364-4). All currents caused by a short circuit observed in any point of the circuit, must be interrupted in a time not greater than that which brings the wires to the allowable temperature limit. For short-circuit of duration of not more than 5 s, the time "t" required so that a given short-circuit current leads wires from the maximum allowable temperature in ordinary service to the temperature limit can be calculated by the formula: S t = K x I where: t = duration in seconds S= conductor section, expressed in sqmm I = effective short-circuit current in amperes, K = 5 for copper conductors with PVC insulation 43 for copper conductors insulated with ethylene propylene rubber and polypropylene 74 for aluminium conductors with PVC insulation 87 for aluminium conductors insulated with ethylene propylene rubber and polypropylene 5 corresponding to a temperature of 60 C, for soft-

soldered joints between copper conductors. The above formula assumes that the heating of the conductors, during the passage of the shortcircuit current, is adiabatic. The formula is better represented in the following way: ( I t ) K S where (I t) ) is the integral Joule for the duration of the short circuit (in A s), "A" is equal to the current and "s" to the time. For short-circuit lasting more than a few times, you can get the value of (I t) assuming "I " the true RMS in amperes of the short- circuit current and "t" the duration, in seconds, of the same shortcircuit. For short durations (<0. s), when the asymmetry of the short-circuit current is relevant and for protective limiting devices of pass-through energy, the value (I t) must be specified by the manufacturer of the protective device. The formula should be checked for a short circuit that occurs at any point of the protected conductors. The values of the constant "K" were determined on the basis of the values of the maximum temperatures allowed during ordinary service and during short circuit for the isolation of wires. These parameters, in this analysis referred to conductors with PVC insulation, operating at an operating temperature of 70 C and at a short circuit temperature of 60 C, will be recalculated according to the temperature class required (temperature class must be provided by customer at the time of size request) and considering that the maximum temperature reached by the conductors must not exceed the maximum surface temperature for the design specific class temperature. Therefore, according to what described above, a correct dimensioning of the electrical conductors is of primary importance, in order to avoid the occurrence of systematic critical temperatures that may be the cause of ignition of explosion just because of exceeding the safety threshold determined by the class temperature, by which the enclosure will have to be installed and operate in continuous service. Considering that these enclosures must be suitable for installation in explosion proof areas ( Ex d with directly entry or Ex de with indirect entry), hence subject to certification by qualified internationally recognized body, therefore the dimensioning must be responsive to all the parameters set by the reference standards, such as: IEC 60079-0 o EN 60079-0 o CEI EN 60079-0: Explosive atmospheres Part 0: Equipment General requirements. IEC 60079- o EN 60079- o CEI EN 60079-: Explosive atmospheres Part : Equipment protection by flameproof enclosures d. IEC 60079-7 o EN 60079-7 o CEI EN 60079-7: Explosive atmospheres - Part 7: Equipment protection by increate safety e. IEC 60079-4 o EN 60079-4 o CEI EN 60079-4: Explosive atmospheres Part 4: Electrical installations design, selection and erection.

With equal importance, but for the use of the equipment intended to be included within and / or above the lid of the enclosures, must also be considered the specific electrical regulations such as: IEC 60439- o EN 60439- o CEI EN 60439-: Low-voltage switch gear and control gear assemblies - Part : General requirements. (currently in force until the end of 04, after this date will be replaced with the new IEC 6439- or EN 6439- or IEC 6439-). IEC 60439-3 o EN 60439-3 o CEI EN 60439-3: Low-voltage switch gear and control gear assemblies Part 3: Distribution boards (currently in force until the end of 04, after this date will be replaced with the new IEC 6439- or EN 6439-3 or IEC 6439-3). Should be considered, of course, all applicable specific reference rules for equipment that will be included in the enclosures with the function of "switch gear or control gear assemblies", such as circuit breakers, terminal blocks, etc The basic parameters to be considered for this dimensioning are: - The current-limiting of thermo-magnetic circuit breaker; - The acceptable thermal stress of conductors and/or cables. The current-limiting of thermo-magnetic circuit breaker, is usually defined by limitation curves that can be summarized as follows: (A s) Graphic 000000 0 ms - Short Circuit presumed current (ka rms) - Limited pass-through specific energy (A s) ( specific limited energy passing ) 00000 0000 000 50 63 3 40 0 5 6 8 0 6 4 3 00 0,0 0, 0 00 (ka rms) (Short Circuit presumed current ) Graphic shows, for an ease interpretation, the characteristic curves of thermo-magnetic circuit breakers of Acti9 series Schneider Electric, specifically, the circuit breakers ic60n series. As can be seen, the straight line indicated in red represents the energy "A s" of a short-circuit current of a half period (0 ms), which indicates the energy that would be dissipated in the absence of limitation of the protection device. The acceptable thermal stress of conductors and/or cables, according to their isolation, their composition (copper or aluminum) and their section expressed in sqmm, is a factor that must be

collected from the manufacturer's technical documentation of the conductors and / or cables (cable is defined as a formation of multiple conductors enclosed in a further insulator). For the purposes of this example, let's take a table type below (extracted from the Guide to the low voltage of Schneider Electric), of the various conductors and/or cables in copper and aluminum with PVC insulation (polyvinyl chloride), with pass-through specific energy in A s: Material sect ion (sqmm),5 Specific let-through energy, in A s,5 4 6 0 6 5 35 50 PVC Cu Al 9700 8600 000 476000 30000 3400000 860000 600000 300000 54000 390000 3380000 6640000 3500000 We can proceed now with the sizing of conductors that will be used to support the current demands, assuming the input data that the customer must notify us at the time of size request. So, for this dimensional hypothesis, we will assume that the client has provided us with the following input data: - Ambient temperature: 45 C - Temperature Class: T5 - Breaking capacity: 0 ka at 400VAC - Total installed and working power: 0 kw at 400VAC - Rated current for incoming line three pole plus neutral: 3A at 400VAC - Rated power for each outgoing lighting feeders: kw at 30VAC - Rated current for each outgoing lighting feeders one phase plus neutral: ~ 9A at 30VAC (n 0 outgoing feeders) - Rated voltage: 400/30VAC ± 0% - Rated frequency: 50 Hz ± 5% - Electric system: TN-S, three phase plus neutral - Protection system: PE, separate from neutral - Tripping curve: C (standard loads) - Degree of mechanical protection: IP66 - Coefficient of contemporaneity: (all outgoing feeders operate in parallel and at nominal load of kw, for a total of 0 kw) Based on these input data, we proceed to the first stage of sizing, selecting the circuit breakers suitable for the application, that is: - Main incoming circuit breaker, three pole plus neutral, suitable for a total load of 0 kw at 400 VAC, with characteristic curve C for standard loads. According to the typical formula: I = P 3 x V x cos

Where: I = rated current, in Ampere P = total power, in kw (0 kw) V = rated voltage, in kv (0,4kV) Cosphì = assumed value 0,9 you will then have that I= 0/(,73. 0,4kV. 0,9) = 3A. - Two pole distribution circuit breakers, suitable for a unit load each of kw at 30VAC, with characteristic curve C for standard loads according to the formula for single-phase systems: where: I = rated current, in Ampere P = rated power, in kw ( kw) V = rated voltage, in kv (0,3V) Will be: I= /0,3 = 8,7A. I = P V According to the derating temperature table (see catalog Acti9 Scheider Electric) and in accordance with CEI EN 60898- standard, for a circuit breaker of 400VAC,responsive to the specifications required by the customer, we will adopt the type ic60n that has a breaking capacity (Icu) of 0kA at 400VAC. On the basis of this first dimensioning, we ll proceed to its temperature derating, up to find the electrical quantity responsive to our needs, (the rated current of this range of circuit breakers is referred to 30 C). - 3A at 30 C, downgraded to 45 C, gives 30. A which downgraded by a further 0% for installation in an ambient with prevented ventilation, gives 4.6 A, and then not responding to our needs. - 40A at 30 C, downgraded to 45 C, gives 37,74A which downgraded by a further 0% for installation in an ambient with prevented ventilation, gives 30,9A, and then not responding to our needs. - 50A at 30 C, downgraded to 45 C, gives 46,93A which downgraded by a further 0% for for installation in an ambient with prevented ventilation, gives 37,54A, and then responding to our needs. It should be noted that the ambient temperature, it s NOT the one inside the enclosure, but rather the outside, so the above mentioned derating is the result of the experience of our tests laboratory in Villesse. Given the complexity of these inspections, for convenience of calculation, we assume

in this analysis that further downgrade is equal to 0% (in reality it is an internal parameter variable depending on the layout of the equipment and then determined only by our tests laboratory). So, according to the above, we will select a circuit breaker of 50A at 30 C, but working at 45 C with a corresponding current of ~ 38 A, redundant with respect to the nominal current request. Obviously this means that, according to this downgrade, will be installed a 50A nominal main incoming circuit breaker with four pole but with maximum capacity of 38A, utilized at the intended temperature inside the enclosure. Let's take an indicative example of the size criteria, assuming to define what will be the limited energy by a circuit breaker of this series, with a rated current of 50A for a short-circuit current of 0kA rms. Graphic 000000 (A s) 0 ms ( specific limited energy passing ) 00000 50 63 60000 3 40 50 63 0 5 6 8 0 4 0000 6 3 000 00 0,0 0, 0 00 (ka rms) (Short Circuit presumed current ) As can be seen from the Graphic, the short-circuit current of 0kA rms may dissipate up to 000000A (K s), but using a 50A switch, type ic60n, as evidenced by the characteristic curve in the graphic, the thermal stress would significantly reduce, leading to 60000A (A s). Reducing it up to 6 times lower, will be a considerable advantage in terms of overheating of conductors. Considering now that it has already carried out the verification of the "Filiation" upstream/ downstream (technique of filiation which will be the subject of another discussion), we can proceed to the sizing of the outgoing lighting circuit breakers at 30VAC: - 0 outgoing feeders for light circuits, with two pole circuit breakers of kw each - 6 ka, ic60a model suitable for a unit load of kw at 30VAC, with characteristic "C" for standard loads. These circuit breakers, according to the filiation technique, although having a breaking capacity of 6 ka at 30 VAC, will be coordinated by a reinforced Icu of 0kA and, then, adapted to the customer's request (please refer to the section "Filiation" on the Guide at low-voltage System of Schneider Electric). On the basis of this first dimensioning, we can proceed to its temperature derating, up to find the electrical quantity responsive to our needs. The rated current of this range of circuit breakers is referred to 30 C. - 0 A at 30 C, downgraded to 45 C, gives 9,4 A which downgraded by a further 0% for installation in an ambient with prevented ventilation, gives 7,5 A, and then not responding to our needs.

- 6 A at 30 C, downgraded to 45 C, gives 5,09 A which downgraded by a further 0% for installation in an ambient with prevented ventilation, gives,07 A, and then responding to our needs. So, according to the above, we will select a circuit breaker of 6A at 30 C, but working at 45 C with a corresponding current of ~ 3 A. Obviously this means that, according to this downgrade, will be installed 6A nominal main incoming circuit breakers with four pole but with maximum capacity of 3A, utilized at the intended temperature inside the enclosure. Similarly, we make an indicative example of the size criterion, assuming that we want to define what will be the energy limited by a circuit breaker of this series, with a rated current of 6A for a short-circuit current of 0kA rms. (A s) Graphic 3 ( Energia specifica passante limit at a) 000000 00000 50 63 3 40 0 5 4500 6 6 8 0 4 0000 6 3 000 0 ms 00 0,0 0, 0 00 (ka rms) (corrente di Corto Circuito presunta) As can be seen in the Graphic 3, referring to pole main circuit breakers - 6A, ic60a series, with breaking capacity of 6kA, (with filiation 0kA), the value of the specific energy is 4500A s, for a time of 0 ms. Conductors must be sized to withstand this specific energy, without distortion and without generating overheating not conform to temperature class requested by the customer. We can now speak about the dimensioning of the electrical conductors to be installed within the "Panel Board". Comparing the current capacity of conductors and/or cables according to IEC 6033- or IEC 6033-3C Standards, designed for an ambient temperature in free air of 30 C, for single core copper conductors with PVC insulation and voltage Uo/U of 0.45/0.75 kv, type H07Z- K (extract from Prismian Group catalog for cables and accessories 03 edition), we have: section (sqmm) rated current at 30 C(A),5,5 4 6 0 6 5 35 50 5,5 8 36 50 68 89 0 34 So, on the basis of these values, we will do a further alignment according to the temperature, the laying side by side (conductors under load, with coefficient of contemporaneity ) and according to the correction factor for installation in an ambient with prevented ventilation:

- for laying side by side of 0 systems under load on two levels = K 0,73 - for ambient temperature (inside of the panel) of 45 C = K 0,7 - coefficient of installation in ambient with prevented ventilation = K 0,8 bringing the sum of these downgrades to the total value of Kt = ~ 0,45 Assumed a nominal current of 38 A, for the incoming conductors and the distribution system (an alternative to the distribution system with conductors is the bus-bar system), the optimal section results to be of 5 sqmm, with current capacity of 89 A at 30 C, but downgraded with the value of Kt 0,45, brings its value to 36.94 A, lower than the nominal value of 38A. We will select the sections immediately above of 35 sqmm, with a range of current of 0A at 30 C, which will give a flow of current, always with the same derating, of 45,65A, suitable for section and also for passthrough energy which is the result of to the formula I t K S. In which for the "K" value we assume 5, referring to copper conductors with PVC insulation, and "S" will be the section of the conductors selected of 35 sqmm. So, I t (60000 A s) must be less than K S (5 x 35 = 60065 ) and, as it turns, the I t value is below the value of 60000 A s. We proceed similarly to the verification of the downstream conductor cross section of the kw two pole circuit breakers: - for laying side by side of 0 systems under load on two levels = K 0,73 - for ambient temperature (inside of the enclosure) of 45 C = K 0,7 - coefficient of installation in an ambient with prevented ventilation = K 0,8 bringing the sum of these downgrades to the total value of Kt = ~ 0,45. Assumed a nominal current of 3A, the optimal section results of.5 sqmm, with current capacity of 5.5A at 30 C, but downgraded with the value of Kt 0,45, brings the value to 6.43A, not able to meet the subtended load. Other suitable size will be selected such as that of 6 sqmm, with nominal current of 36A at 30 C, which will give a flow of current of 4.94A, always with the same derating, suitable for the section and also for the pass-through energy that is responsive to the formula I t K S. In which the value of "K" assumes 5, referring to copper conductors with PVC insulation and "S" will be the section of the conductors selected 6 sqmm. So, I t (4500 A s) must be less than K S (5 x 6 = 47600 ) and, as it turns, the I t value is below the value of 4500 A s. We conclude this second part saying that all activities of electro-mechanical sizing are the prerogative of the manufacturer of the Panel Boards in explosion-proof execution: analysis, calculations and the resulting executive project are of its responsibility, putting the plate certifying the compliance with the relevant Standards.