The Mathematical Model of Power System with Thyristor Controlled Series Capacitor in Long Transmission Line

Similar documents
The Mathematical Model of Power System with Static Var Compensator in Long Transmission Line

Nonlinear Control Design of Series FACTS Devices for Damping Power System Oscillation

KINGS COLLEGE OF ENGINEERING Punalkulam

SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS. Transient Stability LECTURE NOTES SPRING SEMESTER, 2008

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

CHAPTER 2 DYNAMIC STABILITY MODEL OF THE POWER SYSTEM

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

POWER SYSTEM STABILITY

1 Unified Power Flow Controller (UPFC)

Fault Analysis Power System Representation

Chapter 3 AUTOMATIC VOLTAGE CONTROL

ELG4125: Power Transmission Lines Steady State Operation

ECE 585 Power System Stability

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

Module 3 : Sequence Components and Fault Analysis

Improving Power System Transient Stability with Static Synchronous Series Compensator

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

Damping SSR in Power Systems using Double Order SVS Auxiliary Controller with an Induction Machine Damping Unit and Controlled Series Compensation

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

CHAPTER 3 ANALYSIS OF THREE PHASE AND SINGLE PHASE SELF-EXCITED INDUCTION GENERATORS

CHAPTER 5 STEADY-STATE ANALYSIS OF THREE-PHASE SELF-EXCITED INDUCTION GENERATORS

Improvement of Transient Stability of Power System by Thyristor Controlled Phase Shifter Transformer

Static and Dynamic Location of Variable Impedance Devices for Stability Studies

DAMPING OF SUBSYNCHRONOUS MODES OF OSCILLATIONS

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

EE Branch GATE Paper 2010

Examples of Applications of Potential Functions in Problem Solving (Web Appendix to the Paper)

Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS

Design of PSS and SVC Controller Using PSO Algorithm to Enhancing Power System Stability

Chapter 9: Transient Stability

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEM USING UPFC AND FEEDBACK LINEARIZATION CONTROL

Proceedings of the 13th WSEAS International Conference on CIRCUITS

Research Paper ANALYSIS OF POWER SYSTEM STABILITY FOR MULTIMACHINE SYSTEM D. Sabapathi a and Dr. R. Anita b

1. Introduction. Keywords Transient Stability Analysis, Power System, Swing Equation, Three-Phase Fault, Fault Clearing Time

Unified Power Flow Controller (UPFC) Based Damping Controllers for Damping Low Frequency Oscillations in a Power System

Last Comments on Short-Circuit Analysis

CHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS

GATE 2010 Electrical Engineering

Improving Transient Stability of a Multi-Machine Power Network Using FACTS Devices and Nonlinear Controller Tuned by PSO

LabVIEW Based Simulation of Static VAR Compensator for Transient Stability Enhancement in Electric Power Systems

FOR REDUCE SUB-SYNCHRONOUS RESONANCE TORQUE BY USING TCSC

In the previous chapter, attention was confined

SSSC Modeling and Damping Controller Design for Damping Low Frequency Oscillations

STUDY OF SMALL SIGNAL STABILITY WITH STATIC SYNCHRONOUS SERIESCOMPENSATOR FOR AN SMIB SYSTEM

Fault Calculation Methods

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

Harmonic Modeling of Networks

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

A New Scheme for Damping Torsional Modes in a Series Compensated Power System

Study of Transient Stability with Static Synchronous Series Compensator for an SMIB

Transients on Integrated Power System

Transient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods

Transmission and Distribution of Electrical Power

THE RESONANCE ANALYSIS CAUSED BY-HARMONICS IN POWER SYSTEMS INCLUDING THYRISTOR CONTROLLED REACTOR

DESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

IGEE 402 Power System Analysis. FINAL EXAMINATION - SAMPLE Fall 2004

QFT Framework for Robust Tuning of Power System Stabilizers

TRANSIENT ANALYSIS OF SELF-EXCITED INDUCTION GENERATOR UNDER BALANCED AND UNBALANCED OPERATING CONDITIONS

Transient Stability Assessment and Enhancement Using TCSC with Fuzzy Logic Controller

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

DESIGNING POWER SYSTEM STABILIZER WITH PID CONTROLLER

CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS

Detection of Broken Conductor with Ground Contact Faults in Medium Voltage Power Networks

UNIVERSIDAD DE CASTILLA-LA MANCHA

Reactive Power Solutions

Q. 1 Q. 25 carry one mark each.

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai QUESTION BANK V SEMESTER. EE6501-Power system Analysis

EE 451 Power System Stability

Transient Stability Improvement of Multi-machine Power System Using Fuzzy Controlled TCSC

Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Single Phase Parallel AC Circuits

ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling

Optimal Control for the Voltage Regulation of a Power Line Including an Interconnection with a Wind Park and FACTS

Phase-shifting transformers in a structure-preserving energy function

A POWER FLOW CONTROL STRATEGY FOR FACTS DEVICES

ANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER

Power System Stability GENERATOR CONTROL AND PROTECTION

The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of Unbalanced Three Phases Electrical Distribution System

ECEN 460 Exam 1 Fall 2018

Electric Circuit Theory

Conventional Paper-I-2011 PART-A

Dynamic Voltage Stability Enhancement of a Microgrid with Static and Dynamic Loads Using Microgrid Voltage Stabilizer

Chapter 8: Unsymmetrical Faults

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

AN EFFICIENT APPROACH FOR ANALYSIS OF ISOLATED SELF EXCITED INDUCTION GENERATOR

FLEXIBLE ac transmission system (FACTS) devices give

Transient Stability Improvement of a Multi- Machine Power System by Using Superconducting Fault Current Limiters

SESSION 3. Short Circuit Calculations, Unsymmetrical Faults. Leonard Bohmann, Michigan State University Elham Makram, Clemson University

Chapter 8 VOLTAGE STABILITY

Chapter 2 Voltage-, Current-, and Z-source Converters

Modelling and Analysis of Electric Power Systems

Dynamics of the synchronous machine

Critical clearing time evaluation of Nigerian 330kV transmission system

Transcription:

American Journal of Applied Sciences 9 (5): 654-658, 01 ISSN 1546-939 01 Science Publications The Mathematical Model of Power System with Thyristor Controlled Series Capacitor in Long Transmission Line Prechanon Kumkratug Department of Electrical Engineering, Faculty of Engineering at Si Racha, Kasetsart University, 199 M.6, Tungsukhla, Si Racha, Chonburi, 030, Thailand Abstract: Problem statement: It is becoming increasingly important to fully utilize the existing transmission system assets due to environmental legislation, rights-of-way issues and costs of construction and deregulation policies that introduced in recent years. The Thyristor Controlled Series Capacitor () has been proposed for the better control power flow and dynamic performance. The exact long transmission line model consists of the resistance and reactance. Most of previous researches studies transient stability performance of the in SMIB System with neglecting the resistance of the line. Thus the fully capability of the on transient stability improvement of power system may not be applied. The consideration of the resistance causes in the difficulty of deriving the mathematical model. Approach: This study investigates the effect of the on transient stability of the power system with consideration the exact long transmission line mode. The concept of two-port network is applied to simplify the mathematical model of the power system. The proposed method is tested on sample system and compared on various cases. Results: The first swing of rotor angle curve of the faulted system without resistance is obviously higher than that of with resistance whereas the second swing of the faulted system without resistance is slightly less than that of with resistance. The system with a can improve transient stability of power system. Conclusion: It was found from this study that the and resistance of the line can improve first swing of rotor angle. However, the resistance of the line provides the negative effect on second swing of rotor angle. The simulation results indicate that for practical long line, the resistance is very import parameters for evaluating transient stability of power system. Key words: Power system stability, transient stability, critical clearing time, FACTS devices, resistance, capacitance, transmission line, medium transmission line, two ports network INTRODUCTION Nowadays, the demand of electricity has dramatically increased and a modern power system becomes a complex network of transmission lines interconnecting the generating stations to the major loads points in the overall power system in order to support the high demand of consumers. It is becoming increasingly important to fully utilize the existing transmission system assets due to environmental legislation, rights-of-way issues and costs of construction and deregulation policies that introduced in recent years. A number of Flexible AC Transmission System (FACTS) controllers, based on the rapid development of power electronics technology, have been proposed for better utilization of the existing transmission systems (Samikannu, R. and Poonamallie, 011; Nabhan and Abdallah, 010; Padma and Rajaram, 011; Osuwa and Igwiro, 010; Subramani et al., 01; Zarate-Minano et al., 010). The Thyristor Controlled Series Capacitor () is the series FACTS devices. It consists of the capacitor bank reactor bank and thyristor as shown in Fig. 1. The thyristors control the reactance that dictates the power flow through a line. The can be applied for improving transient stability of power system. The evaluation of Critical Clearing Time (CCT) of power system is one of the most important research areas for power engineers because it indicates the robustness of the faulted power system. The rotor angle of the synchronous generator determines the stability of power system. Although the stability of the synchronous machine is used to represent the stability of the power system, all of the power system components such as transmission line and transformer affect the stability of the power system. The transmission line is one of the most important parts in power system components. Most of the fault occurs at the transmission line. It is generally divided into three major categories; short, medium and long model whose distance are about 80 km, above 80-50 km and above 50 km, respectively. 654

(a) Fig. 1: Schematic diagram of Many previous researches used simple transmission line model by neglecting its resistance or capacitance. To fully utilization the existing system, the exact transmission line should be further investigated. This study will investigate the capability of the on transient stability of the SMIB system with the exact long transmission line model. The concept of two-port network is applied to simplify the mathematical model of the power system. The sample system consisting the practical long transmission line is used to investigate in this study. The proposed method is tested on various cases. MATERIALS AND METHODS Mathematical model: The transmission line is considered as long line when its distance is beyond 150 km. The basic model of long transmission line consists of the lump of medium transmission line model with serial models as shown in Fig. a. Its simpler model is represented by a model as shown in Fig. b. The Z and Y are given in Eq. 1- and wriiten by: Z = Z sinh( γ) (1) c Y = / Z tanh( γ) () Here: And: c γ = ZY Z c = Z Y Figure 3a shows the single line diagram of power system consisting of a generator, a transformer, four long transmission lines and. Figure 3b shows the equivalent of Fig. 3a. The generator is represented by a synchronous voltage in quadrature axis (E q ) behind direct transient reactance (X d ). 655 (b) Fig. : Long transmission line model (a) Basic model with the serial π models (b) a π model The V b is the voltage at infinite bus. The exact long transmission line model is represented by the impedance (Z L ) which consists of a resistance (R L ) and reactance (X L ). The can be modeled as the variable series reactance (X ) as shown in Fig. 3b. This study will apply the concept of the two-port network to simplify the equivalent in Fig. 3b. Each component of power system and a can be represented the matrix of two-port networks (A, B, C and D) as shown in Fig. 3c and given by Eq. 3-14: A1 = A = A = 1 (3) A3 = A4 = A5 = A 6 = cosh( γ) (4) B = jx (5) 1 d B = jx (6) t B = B = B = B = Z sinh( γ) (7) 3 4 5 6 c B = -jx (8) C1 = C (9) 1 = = = = sinh( γ) C 3 C 4 C 5 C 6 Zc (10) C (11)

(a) (b) (c) (d) Fig. 3: Single machine infinite bus system with a (a) schematic diagram (b) equivalent circuit (c) two -port networks diagram (d) the net two-port network D1 = D (1) D = D = D = D = cosh( γ) (13) 3 4 5 6 D = 1 (14) It can be seen from the Fig. 3c that some ports are in series and in shunt connection. For example, a port 1 and port are in series connection whereas port 3 and port 4 are in shunt connection. Thus with the series combination of port 1 and port, a new port is given by Eq. 15-18: Bs = A1B + B1D (16) Cs = AC1 + CD 1 (17) Ds = BsCs1 + Ds1D s (18) Similarly, with the shunt combination of port 3 and port 4, a new port is given by Eq. 19-: A = ( A B + A B ) / ( B + B ) (19) sh 3 4 4 3 3 4 B = B B / ( B + B ) (0) sh 3 4 3 4 As = A1A + B1C (15) Csh = C3 + C4 + ( A3 A4)( D4 D3) / ( B3 + B 4) (1) 656

D = ( B D + B D ) / ( B + B ) () sh 4 3 3 4 3 4 With the above concepts, the net two-port network diagram is shown in Fig. 3d. Here A eq, B eq, C eq and D eq are the element in net matrix of net two-port networks. The output electrical power of synchronous machine (P e ) is given by Eq. 3: A (E ) V E P = cos( θ θ ) cos( θ + δ ) (3) eq q b q e Beq Aeq Beq Beq Beq Here: A = A θ B = B θ eq eq Aeq eq eq Beq Fig. 4: Swing curve of the system without FACTS devices for tcl = 170 m sec The dynamic equation for evaluating critical clearing time of the system in Fig. 3a is given by: δ ɺ = ω (4) ω ɺ = 1 [P P ] m e (5) M Here, δ, ω and P m as given in Eq. 4-5 are the rotor angle, speed, mechanical input power and moment of inertia, respectively of synchronous machine. The P e is the output electrical power of synchronous as given in Eq. 3. It can be mentioned here that the variable series reactance of the as given in Eq. 8 is changed during the dynamic state for improve the transient stability. This study uses the linear control given by: X = Kω (6) Here K in Eq. 6 is the constant gain control. RESULTS The proposed method is tested on the sample system Consider the diagram of sample system is shown in Fig. a. The system data are: Generator: H=5, Xt.1 pu, X d.0 pu, E q = 1.<31.64 pu. Fig. 5: Rotor angle of the system with various gains of a for tcl = 190 m sec Table 1: The maximum and minimum rotor angle of the system without for tcl=170 m sec Case R Bc δ max (degree) δ min (degree) 1 0.0000 0.000000 94.6 13.07 0.063 0.000000 93.64 1.68 3 0.0000 0.000594 94.6 13.07 4 0.063 0.000594 93.64 1.68 The percentage of R/X and B c /X of the line are = 5.6% and B c /X.001188%, respectively. With the given reactance of the line (X).5 pu, the per unit of R and B c are 0.063 and 0.00059 pu, respective. It is considered that three phase fault appears at line near bus m and the fault is cleared by opening circuit breakers at the end of the line. Figure 4 shows the rotor angle of the system without a (K ) for the clearing time of fault (t cl ) 170 m sec. Table 1 summarizes the maximum and minimum rotor angles (δ max, δ min ) of Fig. 3. Figure 5 shows the rotor angle of the system with various gains of a and with consideration of the exact long transmission line model. Here the t cl is increased to 198 m sec. Table summarizes the Transmission line data: Voltage level 500 kv, 300 km, f = 50 Hz, R.016 Ω/km, L.97 mh/km, C = 0.0115 µf/km The series Z and the shunt admittance Y of the long line at fundamental frequency are 4.646+j89.9 and 0 + j0.00109, respectively. maximum and minimum rotor angles of Fig. 5. 657

Table : The maximum and minimum rotor angle of the system without for tcl=198 m sec Case K δ max (degree) δ min (degree) 1 0 - - 10 108.5 7.36 3 0 96.8 18.7 4 30 88.8 5.69 DISCUSSION It can be seen from the Fig. 4 and Table 1 that resistance of the long line provides the improvement of the first swing stability but not for the second swing. Without the resistance of the long line, the maximum and the minimum rotor angle are 94.6 and -13.07 degree, respectively whereas with the resistance, the maximum and the minimum rotor angle are 93.64 and 1.68 degree, respectively. In practical long line, the resistance is very import parameters to determine the critical clearing time of the system whereas shunt capacitance doesn t affect on the damping performance because in practical lone line the shunt capacitance is very small. The critical clearing time of the system with exact long transmission line and without FACTS is around 197-198 m sec. As can be seen in Fig. 5 and Table, the system without (K ) is considered as unstable. However, with the the system can be considered as stable and the damping performance is improved as the gain is increased. CONCLUSION This study investigated the effects of The Thyristor Controlled Series Capacitor () on transient stability of the Single Machine Infinite Bus (SMIB) with the consideration of the exact long transmission line model. The concept of two-port network is applied to simplify the mathematical model of the system. The reactance of generator, transformer exact long line model and can be represented by a net two-port network. It was found from the simulation results that the resistance of the line provides the improvement of the first swing but not for the second swing. It was found from this study that for practical long line, the resistance is very import parameters to determine the critical clearing time of the single machine infinite system whereas shunt capacitance would not affect on critical clearing time of single machine infinite bus system. It was also found in this study that the can enhance transient stability of power system. REFERENCES Nabhan, I. and M. Abdallah, 010. A novel low-power cmos operational amplifier with high slew rate and high common-mode rejection ratio. Am. J. Eng. Applied Sci., 3: 189-19. DOI: 10.3844/ajeassp.010.189.19 Osuwa, J.C. and E.C. Igwiro, 010. Uninterruptible power supply using solar rechargeable battery. Phys. Int., 1: 77-8. DOI: 10.3844/pisp.010.77.8. Padma, S. and M. Rajaram, 011. Fuzzy logic controller for static synchronous series compensator with energy storage system for transient stability analysis. J. Comput. Sci., 7: 859-864. DOI: 10.3844/jcssp.011.859.864 Samikannu, R. and B.A. Poonamallie, 011. Design of synthetic optimizing neuro fuzzy temperature controller for dual screw profile plastic extruder using labview. J. Comput. Sci., 7: 671-677. DOI: 10.3844/jcssp.011.671.677 Subramani, C., S.S. Dash, V. Kumar and H. Kiran, 01. Implementation of line stability index for contingency analysis and screening in power systems. J. Comput. Sci., 8: 585-590. DOI: 10.3844/jcssp.01.585.590 Zarate-Minano, R., T. Van Custsem, F. Milano and A.J. Conejo, 010. Sexuring transient stability using time domain simulations within an optimal power flow. IEEE Trans. Power Syst., 5: 43-53, DOI: 10.1109/TPWRS.009.03069. 658