SHEAR CAPACITY OF REINFORCED CONCRETE COLUMNS RETROFITTED WITH VERY FLEXIBLE FIBER REINFORCED POLYMER WITH VERY LOW YOUNG S MODULUS

Similar documents
POST-PEAK BEHAVIOR OF FRP-JACKETED REINFORCED CONCRETE COLUMNS

A PROPOSAL OF DESIGN PROCEDURE FOR FLEXURAL STRENGTHENING RC BEAMS WITH FRP SHEET

AXIAL COLLAPSE OF REINFORCED CONCRETE COLUMNS

DEFORMATION CAPACITY OF OLDER RC SHEAR WALLS: EXPERIMENTAL ASSESSMENT AND COMPARISON WITH EUROCODE 8 - PART 3 PROVISIONS

EXPERIMENTS ON SHEAR-FLEXURAL BEHAVIORS OF MODEL CAST IN PLACE CONCRETE PILES

SEISMIC PERFORMANCE OF LARGE RC CIRCULAR HOLLOW COLUMNS

Consequently, retrofit of many poor existing structures is a very important issue. for Turkey!

INFLUENCE OF LOADING RATIO ON QUANTIFIED VISIBLE DAMAGES OF R/C STRUCTURAL MEMBERS

Lap splice length and details of column longitudinal reinforcement at plastic hinge region

ME Final Exam. PROBLEM NO. 4 Part A (2 points max.) M (x) y. z (neutral axis) beam cross-sec+on. 20 kip ft. 0.2 ft. 10 ft. 0.1 ft.

Finite Element Analysis of FRP Debonding Failure at the Tip of Flexural/Shear Crack in Concrete Beam

APPLICATION OF INTENSIVE SHEAR REINFORCEMENT TO SPLICING SLEEVE JOINT OF PRE-FABRICATED REINFORCEMENT ASSEMBLY

CHAPTER 6: ULTIMATE LIMIT STATE

Earthquake-resistant design of indeterminate reinforced-concrete slender column elements

Flexure: Behavior and Nominal Strength of Beam Sections

Chapter 4. Test results and discussion. 4.1 Introduction to Experimental Results

CE5510 Advanced Structural Concrete Design - Design & Detailing of Openings in RC Flexural Members-

New model for Shear Failure of R/C Beam-Column Joints. Hitoshi Shiohara

UNIAXIAL COMPRESSION TEST OF STEEL PLATE BONDED VARIOUS FRP SHEETS

EFFECT OF SHEAR REINFORCEMENT ON FAILURE MODE OF RC BRIDGE PIERS SUBJECTED TO STRONG EARTHQUAKE MOTIONS

EARTHQUAKE SIMULATION TESTS OF BRIDGE COLUMN MODELS DAMAGED DURING 1995 KOBE EARTHQUAKE

Eurocode 8 Part 3: Assessment and retrofitting of buildings

Sabah Shawkat Cabinet of Structural Engineering Walls carrying vertical loads should be designed as columns. Basically walls are designed in

Behavior and Modeling of Existing Reinforced Concrete Columns

ULTIMATE SHEAR OF BEAMS STRENGTHENED WITH CFRP SHEETS

D : SOLID MECHANICS. Q. 1 Q. 9 carry one mark each. Q.1 Find the force (in kn) in the member BH of the truss shown.

ME 243. Mechanics of Solids

Simulation of Nonlinear Behavior of Wall-Frame Structure during Earthquakes

NORMAL STRESS. The simplest form of stress is normal stress/direct stress, which is the stress perpendicular to the surface on which it acts.

SHEAR DESIGN EQUATIONS FOR FRP RC BEAMS

Seismic Pushover Analysis Using AASHTO Guide Specifications for LRFD Seismic Bridge Design

Dynamic Analysis of a Reinforced Concrete Structure Using Plasticity and Interface Damage Models

APPENDIX G I-BEAM SUMMARIES 0.6-IN. STRAND G-1

SHOTCRETE OR FRP JACKETING OF CONCRETE COLUMNS FOR SEISMIC RETROFITTING

Lecture-04 Design of RC Members for Shear and Torsion

Special edition paper

ε t increases from the compressioncontrolled Figure 9.15: Adjusted interaction diagram

Chapter 7. Highlights:

Modeling of Interfacial Debonding Induced by IC Crack for Concrete Beam-bonded with CFRP

Chord rotation demand for Effective Catenary Action under Monotonic. Loadings

Non-Linear Modeling of Reinforced Concrete Structures for Seismic Applications

Mechanics of Materials

MECE 3321 MECHANICS OF SOLIDS CHAPTER 3

Strengthening of columns with FRP

Accelerated Testing Methodology for Long Term Durability of CFRP

EQUIVALENT FRACTURE ENERGY CONCEPT FOR DYNAMIC RESPONSE ANALYSIS OF PROTOTYPE RC GIRDERS

Reinforced Concrete Structures

Lecture-08 Gravity Load Analysis of RC Structures

This is a repository copy of Nominal Curvature Design of Circular HSC Columns Confined with Post-tensioned Steel Straps.

FLEXURAL ANALYSIS AND DESIGN METHODS FOR SRC BEAM SECTIONS WITH COMPLETE COMPOSITE ACTION

Name :. Roll No. :... Invigilator s Signature :.. CS/B.TECH (CE-NEW)/SEM-3/CE-301/ SOLID MECHANICS

Behavior of RC beams under impact loading: some new findings

Moment redistribution of continuous composite I-girders with high strength steel

Dynamic analysis of a reinforced concrete shear wall with strain rate effect. Synopsis. Introduction

4.MECHANICAL PROPERTIES OF MATERIALS

BIAXIAL STRENGTH INVESTIGATION OF CFRP COMPOSITE LAMINATES BY USING CRUCIFORM SPECIMENS

PREDICTION OF OPEN HOLE COMPRESSIVE FAILURE FOR QUASI-ISOTROPIC CFRP LAMINATES BY MMF/ATM METHOD

Design of Reinforced Concrete Beam for Shear

HYSTERETIC PERFORMANCE OF SHEAR PANEL DAMPERS OF ULTRA LOW- YIELD-STRENGTH STEEL FOR SEISMIC RESPONSE CONTROL OF BUILDINGS

Strength of Materials (15CV 32)

Seismic Assessment of a RC Building according to FEMA 356 and Eurocode 8

Slenderness Effects for Concrete Columns in Sway Frame - Moment Magnification Method (CSA A )

Discrete Element Modelling of a Reinforced Concrete Structure

CIVIL DEPARTMENT MECHANICS OF STRUCTURES- ASSIGNMENT NO 1. Brach: CE YEAR:

Chapter. Materials. 1.1 Notations Used in This Chapter

Influence of column web stiffening on the seismic behaviour of beam-tocolumn

TABLE OF CONTENTS. Mechanics of Composite Materials, Second Edition Autar K Kaw University of South Florida, Tampa, USA

FCP Short Course. Ductile and Brittle Fracture. Stephen D. Downing. Mechanical Science and Engineering

twenty one concrete construction: shear & deflection ARCHITECTURAL STRUCTURES: FORM, BEHAVIOR, AND DESIGN DR. ANNE NICHOLS SUMMER 2014 lecture

MECHANICS OF MATERIALS

Modeling the bond of GFRP and concrete based on a damage evolution approach

FRACTURE MECHANICS APPROACHES STRENGTHENING USING FRP MATERIALS

Strain-Based Design Model for FRP-Confined Concrete Columns

SEISMIC PERFORMANCE OF CONCRETE COLUMNS WITH INADEQUATE TRANSVERSE REINFORCEMENT. Alistair Boys 1 Des K. Bull 2 Stefano Pampanin 3 ABSTRACT

UNIT I SIMPLE STRESSES AND STRAINS

Non-linear Shear Model for R/C Piers. J. Guedes, A.V. Pinto, P. Pegon

OS MODELER - EXAMPLES OF APPLICATION Version 1.0. (Draft)

Constitutive Modeling of Reinforced Concrete Panel Behavior under Cyclic Loading

MECHANICS OF MATERIALS

Mechanical Properties of Materials

ALGORITHM FOR NON-PROPORTIONAL LOADING IN SEQUENTIALLY LINEAR ANALYSIS

Appendix G Analytical Studies of Columns

AN UNLOADING AND RELOADING STRESS-STRAIN MODEL FOR CONCRETE CONFINED BY TIE REINFORCEMENTS

Introduction to Engineering Materials ENGR2000. Dr. Coates

Cone-shaped socket connections for cylindrical members

Parametric analysis and torsion design charts for axially restrained RC beams

UNIVERSITÀ DEGLI STUDI DI PADOVA DIPARTIMENTO DI INGEGNERIA CIVILE, EDILE ED AMBIENTALE CORSO DI LAUREA MAGISTRALE IN INGEGNERIA CIVILE

Use Hooke s Law (as it applies in the uniaxial direction),

Mesh-sensitivity analysis of seismic damage index for reinforced concrete columns

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 4, July 2013

FRACTURE IN HIGH PERFORMANCE FIBRE REINFORCED CONCRETE PAVEMENT MATERIALS

KINK BAND FORMATION OF FIBER REINFORCED POLYMER (FRP)

SHEAR RESISTANCE BETWEEN CONCRETE-CONCRETE SURFACES

ME 2570 MECHANICS OF MATERIALS

Failure interaction curves for combined loading involving torsion, bending, and axial loading

ANALYSIS: THEORY AND APPLICATION FOR

five Mechanics of Materials 1 ARCHITECTURAL STRUCTURES: FORM, BEHAVIOR, AND DESIGN DR. ANNE NICHOLS SUMMER 2017 lecture

The University of Melbourne Engineering Mechanics

CIVE 2700: Civil Engineering Materials Fall Lab 2: Concrete. Ayebabomo Dambo

Chapter 8. Shear and Diagonal Tension

Transcription:

SHEAR CAPACITY OF REINFORCED CONCRETE COLUMNS RETROFITTED WITH VERY FLEXILE FIER REINFORCED POLYMER WITH VERY LOW YOUNG S MODULUS Hu Shaoqing Supervisor: Susumu KONO ** MEE8165 ASTRACT FRP with low Young s modulus (SoftFRP) was developed in the late 199 s and early 2 s. Polyketone fiber is a kind of new material of FRP with low Young s modulus and made from carbon monoxide and ethylene. And compared with aramid fiber, its material cost is lower. To investigate the improvement of shear strength of column wrapped with this kind of FRP sheets, four specimens among which one was unstrengthened and three specimens were wrapped by different amount of FRP sheets which provided the equivalent shear reinforcement ratio was.4%,.8% and.12% were tested. All specimens were tested under lateral reversal cyclic loading and a constant axial load. It is found that the shear strength of the RC column effectively increased with strengthening FRP sheet. And it prevents the sudden brittle fracture of the column because of the confinement of FRP sheets with large deformation capacity. The shear resistance of the FRP sheet becomes effective after the yield of shear reinforcement, and the strain of FRP sheet becomes large. The shear contribution of the FRP sheets could be explained by truss-arch shear resisting mechanism. Keywords: FRP with low Young s modulus (SoftFRP), shear strength, truss-arch mechanism. 1. INTRODUCTION FRP with low Young s modulus (SoftFRP) was developed in the late 199 s and early 2 s. It was made from relatively economic material like polyacetar [Iihoshi 25] or polyester [Igarashi 2]. Compared to CFRP, FRP with low young s modulus has low cost, easy construction, few dust and noise. So it is applicable to be used as a retrofitting material [Kono 28]. Polyketone fiber is a kind of new material of FRP with low Young s modulus and made from carbon monoxide and ethylene. And compared with aramid fiber, its material cost is relative low. To investigate the improvement of shear strength of column wrapped with polyketone fiber sheets, four specimens of columns, one is un-retrofitted and three other specimens retrofitted, were tested under constant axial load and lateral cyclic load. 2.1. Specimen 2. TEST SETUP The specimen was a vertical column fixed at the top and bottom, as shown in Figure 1. The stubs of top and bottom are strong enough as fixed ends for the column. The column had a rectangular Institute of Engineering Mechanics (IEM), China Earthquake Administration (CEA), China ** Assoc. Prof., Department of Architecture and Architectural Engineering, Kyoto University, Japan 1

cross-section 4mm 4mm and a total length of 12mm. All specimens had the same reinforcement detailing. The steel reinforcement was twelve D16 (SD 295A) for longitudinal reinforcement and D6 (SD 295A) for transverse reinforcement at 1mm spacing. The shear (span/depth) ratio, 1.5 and the axial force ratio,.3 were adopted in the specimen design. For the strengthened test specimens, the unidirectional FRP sheet strips made from polyketone were impregnated with epoxy resin and wrapped around the column with different spaces. And the equivalent reinforcement ratios of specimen D15, D15F8 and D152 provided by FRP were.4%,.8% and.12%, respectively. The width of the FRP strip was mm with the thickness of.333mm. The specimen parameters are listed in the Table 1. For Specimens D15F and D152, the compressive strength is 18.8MPa. And for Specimens D15 and D15F8, the compressive strength is 14.6MPa. The material properties of steel and FRP material are shown in Table 2. 12 (a) D-15-F 15 15 225 3 15 F3 2 15 F3 Strain Gauge 3 15 2 F5 F3 15 1 layer F6 2 3 15 F5 2 layers F7 225 15 15 F8 F6 ( Unit: mm ) (b) D-15- (c) D-15-F8 (d) D-15-2 Figure.1 Four specimens and strain gauges on FRP sheet Specimen Compressive strength of concrete Fc (MPa) Table 1 Details of Specimens Axial force ratio Concrete Young s modulus (MPa) FRP sheets (mm of width) The equivalent reinforcement ratio of FRP D-15-F 18.8.3 22 No % D-15-14.6.3 1942 4 strips 1 layer.4% D-15-F8 14.6.3 1942 8 strips 1 layer.8% D-15-2 18.8.3 22 6 strips 2 layers.12% Table 2 Material properties of steel bar and FRP sheets Materials Type Yield Tensile Young s Yield strain Strength (MPa) Strength (MPa) modulus (GPa) (%) Steel D6 47 52 173.235 D16 366 527 185.198 FRP Polyketon fiber 179-37.6 4.54 2.2. Loading and Measuring System Cyclic reversed horizontal loads were statically applied to the specimens by two 2kN hydraulic jacks in both positive and negative directions. During the cyclic horizontal loading, vertical axial loads were also applied by two 8kN hydraulic jacks. The vertical axial load levels were determined in accordance with the axial force ratio designed to be.3 which was first applied and then maintained constant during the test. Loading was mainly controlled by measured displacement in terms of the member drift angle which was computed by averaging lateral displacements measured at north and south ends of column over the effective length of 12mm. The first cycle of loading was performed up to 5kN with load controlled. Subsequently two cycles of repeated loading were applied for each drift angle: ±.1%, ±.25%, ±.5%, ±.%, ±1.%, ±2.%, ±4.%, ±6.% by using displacement controlled. The test was terminated when the specimen could not sustain the axial force. 2

Two displacement transducers were attached to the central section of the top stub and the bottom stub separately to measure the relative displacement of the specimen. The strains of the longitudinal reinforcement, shear reinforcement and FRP sheets in the test region were measured by strain gauges attached on the surface of the steel bars and FRP sheets, respectively. 3.1. Test Observation 3. EXPERIMENTAL RESULT Figure 2 presented damage of specimens at the drift angle R=4.%. Shear crack occurred at drift angle R=.5%, R=-.3%, R=.25%, R=.25% for Specimen D15F, Specimen D15, Specimen D15F8, Specimen D152, respectively. With the increase of drift angle, more shear cracks formed and the width of shear cracks increased. For the retrofitted specimens, it was observed that the FRP sheets and concrete all dilated. For Specimen D15F, at the first loading cycle at R=4.%, cover spalling in the middle of column was observed and the longitudinal bar buckled, then the specimen could not sustain the axial force. For Specimens D15 at the first loading cycle R=4.%, Specimen D15F8 at second loading cycle R=4.%, Specimen D152 at first loading cycle R=6.%, and FRP sheets fractured, cover spalled off and the longitudinal bar buckled then the axial force could not sustained. (a) D-15-F (b) D-15- (c) D-15-F8 (d) D-15-2 Figure 2 Damage of specimens (at the drift angel R=4.%) The maximum load capacity and drift angle at the positive direction and negative direction and the initial stiffness are presented in Table 3. Compared to Specimen D15F, Specimen D152 increased the ultimate capacity Q max from 352.kN to 413.1kN. And the drift angle corresponding to the maximum lateral load changed from.488% to.8%. Compared to Specimen D15, Specimen D15F8 increased the ultimate capacity Q max by 11.5%. The effect retrofitted by FRP on improving the ultimate capacity is rather obvious The difference of initial stiffness of four specimens is small. So it can be considered that the FRP did not affect the initial stiffness but the shear strength. From the envelope of lateral load-drift angle curves, the degradation of shear strength of Specimens D15F8 and D152 is gentler than that of Specimen D15F. It may be said that the confinement of FRP increased the ductility of column. Specimen Initial stiffness (1 5 kn/rad) Table 3 Summary of test results Maximum lateral load capacity Positive Negative R (%) Q max (kn) R (%) Q max (kn) D15F 1.7.488 352. -.481-359.4 D152 1.82.8 413.1 -.498-361.4 D15 1.74.4 334.3 -.498-311.2 D15F8 1..513 372.9 -.41-33.8 3 Lateral Load (KN) 4 2-2 -4 D15F D15 D15F8 D152-6 -4-2 2 4 6 Figure 3 Envelop of the lateral loaddrift angle relation

3.2. Strain Development in FRP Sheets The shear contribution provided by the wrapped FRP sheet was studied in detail by the strain gauges pasted on it. The strain distributions of the FRP sheet are shown in Figure 4. It was observed that the strain of the FRP sheet was very small before the shear cracks occurred and began to increase very quickly after shear cracking. And the strain of middle FRP strips is larger than that of end FRP strips. For D-15- and D-15-F8 at the drift angle R=.5%, and for D-15-2 at the drift angle R=.%, the strain increased dramatically. It agrees with the yield of shear reinforcement. And the strain of FRP sheet at the maximum lateral load did not attain its fracture strain. 1.6 1.2 F3 1.6 1.2 F3 F5 F6 F7 F8 1.6 1.2 F3 F5 F6 Strain (%).8.4 Strain (%).8.4 Strain (%).8.4-4 -2 2 4 6-4 -2 2 4 6-4 -2 2 4 6 (a) D-15- (b) D-15-F8 (c) D-15-2 Figure 4 Strain developments in FRP Sheets 4. ANALYTICAL SIMULATION 4.1. Shear Strength Calculation ased on FRP Specifications According to the design and construction guideline of continuous fiber reinforced concrete [AIJ 21], the ultimate shear strength of column and beam retrofitted by continuous fiber sheet can be calculated by Eq. (1). Qsu b jt ( pw w )cot tan (1 ) bdv / 2 (1) ( pw w ) pws wys pw E f p ws, wys are the shear reinforcement ratio and the yield strength of shear reinforcement; p wf : the equivalent shear reinforcement ratio of continuous fiber sheet with effective thickness t wf ; pwf 2t wf / b. E : The Young s Modulus of continuous fiber sheet; : Effective strain of continuous fiber sheet. The effective strain of continuous fiber sheet can be calculated by Eq. (2). And the value E can not exceed 2/3 of the tensile strength f of continuous fiber sheet. pwf E.9. 2 (2) If p E wf >2, then =.5; The effective factor of concrete is given in Eq.(3) v.7 / 2 (3) For Specimen D15F, the shear strength calculated by using the effective factor of concrete compressive strength shown in Eq.(3) is lower than the experiment value 352kN. The objective of the experiment is to find the relation between the amount of retrofitting material and the increase of shear 4

capacity. So for Specimen D15F, the effective factor of concrete compressive strength was recalculated according to the calculated shear strength equaling to the experiment data. And the following Eq.(4) was used. The calculated shear strength is consistent with the experiment value according to the modified effective compressive strength of concrete (Table 4). v. / 2 (4) 1 4.2. Shear Resisting Mechanism of Column Retrofitted by FRP Sheets To further understand shear resisting mechanism of column retrofitted by FRP sheets, the shear resistant forces of shear reinforcement and FRP are calculated according to the strain obtained from experiment respectively. Figure 5 presented the total shear force measured during test versus calculated shear force carried by the stirrups. For four specimens, there is no quite difference until the drift angle R=.25%. After.25%, shear force carried by stirrups for Specimen D15F is lower than that of Specimen D152 at the same drift angle. And the shear force carried by stirrups of Specimen D15 is larger than that of Specimen D15F8. Figure 6 showed the calculated shear force carried by FRP sheets for Specimen D15, D15F8 and D152. For three retrofitted specimens the calculated shear force carried by FRP sheets is almost equal to.kn until drift angle R=.25%. After.25%, the shear force carried by FRP sheets increased quickly for Specimen D15 and Specimen D152, but increased quite slowly for Specimen D15F8. Vstirrups(kN) 16 14 12 1 8 6 4 2 D15F D15 D15F8 D152 1 2 3 4 Total shear force (kn) Figure 5 Shear force carried by stirrups VFRP (kn) 3 2 1 D15 D15F8 D152 1 2 3 4 5 Total shear force (kn) Figure 6 Shear force carried by FRP sheets 4.3. Analytical Results Compared to Experimental Results. Table 4 presented the calculated shear strength, calculated flexural strength and test results. The ultimate flexural strength of column can be accurately predicted based on fiber model using the strainor stress-compatibility theories. Shear failures occur when the shear capacity of column exceeds prior to the load level reaching the flexural strength. From this point, it can be said the failure mode of Specimen D15F and D15 is shear failure. Shear strength calculated by design equation using the effective factor Eq.(3) is lower than experimental results. And the ratios of the experimental figures to the calculated figures are 1.28 and 1.18 separately. However, for the design equation using modified effective factor,v the shear strength agreed well on the experiment value. So it maybe said that the design equation underestimate the ultimate shear strength. The load level reached the flexural strength at first for the Specimen D152 and its behavior flexural failure mode. The failure mode of Specimen D15F8 is flexural failure due to the longitudinal bar yield when the lateral load reaches the maximum load. Shear strength calculated by design equation using the effective factor Eq.(3) is underestimated. And the ratios of the experimental figures to the calculated figures are 1.19 and 1.1 separately. So if using the design equation to get the ultimate shear strength, some modification should be 5

considered. Table 4 Calculated results compared to test results Specimens Calculated Results(kN) Flexural Test Result (kn) v Eq.(3) v Eq.(4) Strength(kN) Positive Negative Failure mode D15F 277.4 (1.28) 35.6 (1.) 384.9 (.91) 352. -359.4 Shear D152 352.2 (1.1) 425.5 (.97) 384.9 (1.7) 413.1-361.4 Flexural D15 274. (1.18) 33.9 (1.1) 34.2 (.98) 334.3-311.2 Shear D15F8 298.6 (1.19) 355.5 (1.5) 34.2 (1.9) 372.9-334.8 Flexural 5. CONCLUSIONS Polyketone fiber is a kind of new material of FRP with low Young s modulus and made from carbon monoxide and ethylene. This paper analyzes the test results of four specimens among which three specimens wrapped with FRP strips and calculated the shear force contributed by FRP strips to understand how it worked after the shear reinforcement yield. And the following results were obtained. The strains in FRP sheets were higher than those in shear reinforcement after the yield of shear reinforcement. The shear resistance of the FRP sheet becomes effective after the yield of shear reinforcement. It can be said that the confining action of column distributed moved from the shear reinforcement to the FRP sheets. It prevents the sudden brittle fracture of the column because of the confinement of FRP sheets with large deformation capacity. For Specimens D15F and D15, shear failure occurred before bending yield. Shear strength calculated by design equation using the effective factor Eq.(3) is lower than experiment results. However, the shear strength using modified effective factor, v agreed well on the experiment value. So it maybe said that the design equation underestimate the ultimate shear strength. Specimens D15F8 and D152 are flexural yielding precedence. It is observed that the ultimate shear strength calculation based on FRP specifications is underestimated. It means that the assessment is made in a safe side. So the ultimate shear strength calculation based on FRP specifications is used, some modification should be considered. ACKNOWLEDGEMENT I would like to express my sincere gratitude to Assoc. Prof. S. KONO and the advisor Dr. T. MUKAI for their continuous support, valuable suggestion and guidance during my study. REFERENCE Architectural Institute of Japan (21), Design and Construction Guideline of Continuous Fiber Reinforced Concrete, AIJ, (In Japanese), pp.289 Igarashi, S., 2, Proceedings of the third Japan-Turkey workshop on earthquake engineering, February 22, Istanbul. Iihoshi, C., Fukuyama, H. and Tanaka, H., 25, International Symposium on Earthquake Engineering Commemorating Tenth Anniversary of the 1995 Kobe, Kobe/Awaji, Japan. James G. MacGregor, James K. Wight, 25, Reinforced Concrete Mechanics and Design (Fourth Edition), Prentice Hall Kono, S., Doi, M., Lee, J., Tanaka, H., 28. 14th World Conference on Earthquake Engineering. Michael P.Collins, 1991, Denis Mitchell, Prestressed concrete structure, Prentice-Hall, Inc. Website: http://findarticles.com/p/articles/mi_qa5358/is_253/ai_n2136917/. 6