The Operation of a Generator on Infinite Busbars

Similar documents
Generators. What its all about

MODULE TITLE : ELECTRICAL SUPPLY AND DISTRIBUTION SYSTEMS

Introduction to Synchronous. Machines. Kevin Gaughan

Power System Stability GENERATOR CONTROL AND PROTECTION

ECE 585 Power System Stability

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

POWER SYSTEM STABILITY

EE 451 Power System Stability

The synchronous machine (SM) in the power system (2) (Where does the electricity come from)?

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Synchronous Machines

Chapter 9: Transient Stability

SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS. Transient Stability LECTURE NOTES SPRING SEMESTER, 2008

Dynamics of the synchronous machine

Lesson 17: Synchronous Machines

Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines)

JRE SCHOOL OF Engineering

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

Fault Calculation Methods

Chapter 4. Synchronous Generators. Basic Topology

KINGS COLLEGE OF ENGINEERING Punalkulam

Damping SSR in Power Systems using Double Order SVS Auxiliary Controller with an Induction Machine Damping Unit and Controlled Series Compensation

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

Dynamic simulation of a five-bus system

Transient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

From now, we ignore the superbar - with variables in per unit. ψ ψ. l ad ad ad ψ. ψ ψ ψ

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS

ELG4125: Power Transmission Lines Steady State Operation

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

7. Transient stability

1 Unified Power Flow Controller (UPFC)

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

Symmetrical Components Fall 2007

Predicting, controlling and damping inter-area mode oscillations in Power Systems including Wind Parks

Tutorial 1 (EMD) Rotary field winding

3 d Calculate the product of the motor constant and the pole flux KΦ in this operating point. 2 e Calculate the torque.

DESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

ECE 421/521 Electric Energy Systems Power Systems Analysis I 3 Generators, Transformers and the Per-Unit System. Instructor: Kai Sun Fall 2013

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department

Examples of Applications of Potential Functions in Problem Solving (Web Appendix to the Paper)

Week No. 6 Chapter Six: Power Factor Improvement

The Effects of Machine Components on Bifurcation and Chaos as Applied to Multimachine System

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1).

IGEE 402 Power System Analysis. FINAL EXAMINATION - SAMPLE Fall 2004

CHAPTER 2 DYNAMIC STABILITY MODEL OF THE POWER SYSTEM

UNIT I INTRODUCTION Part A- Two marks questions

Prince Sattam bin Abdulaziz University College of Engineering. Electrical Engineering Department EE 3360 Electrical Machines (II)

Synchronous Machines

CHAPTER 3 MATHEMATICAL MODELING OF HYDEL AND STEAM POWER SYSTEMS CONSIDERING GT DYNAMICS

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

(Refer Slide Time: 00:55) Friends, today we shall continue to study about the modelling of synchronous machine. (Refer Slide Time: 01:09)

Synchronous Machines

CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS

CHAPTER 3 SYSTEM MODELLING

Torques 1.0 Two torques We have written the swing equation where speed is in rad/sec as:

Chapter 8 VOLTAGE STABILITY

6 Chapter 6 Testing and Evaluation

Power system modelling under the phasor approximation

Modeling of Hydraulic Turbine and Governor for Dynamic Studies of HPP

Transmission and Distribution of Electrical Power

EE Branch GATE Paper 2010

EE2351 POWER SYSTEM ANALYSIS

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

An Introduction to Electrical Machines. P. Di Barba, University of Pavia, Italy

Module 6 : Preventive, Emergency and Restorative Control. Lecture 27 : Normal and Alert State in a Power System. Objectives

ELG3311: Assignment 3

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai QUESTION BANK V SEMESTER. EE6501-Power system Analysis

Analyzing the Effect of Ambient Temperature and Loads Power Factor on Electric Generator Power Rating

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines

Electrical Machines-I Prof. D. Kastha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Three Phase Circuits

ECEN 460 Exam 1 Fall 2018

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science

Understanding the Inductances

ELEC Introduction to power and energy systems. The per unit system. Thierry Van Cutsem

Part A: From (14.19) in your text (see notes Stability1 ), we have

The synchronous machine (detailed model)

BASIC PRINCIPLES. Power In Single-Phase AC Circuit

Performance Of Power System Stabilizerusing Fuzzy Logic Controller

ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models

Module 4. Single-phase AC Circuits

Control of Wind Turbine Generators. James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University

A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

Chapter 8: Unsymmetrical Faults

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

Fault Analysis Power System Representation

GATE 2010 Electrical Engineering

SYNCHRONOUS GENERATOR s ROTOR INVESTIGATION OF A HYBRID POWER SYSTEM INCLUDING A.G.

Solution of Tutorial 3 Synchronous Motor Drives

CENTRAL TERMOELÉCTRICA ANDINA UNIDAD Nº 1

CHAPTER 3 ANALYSIS OF THREE PHASE AND SINGLE PHASE SELF-EXCITED INDUCTION GENERATORS

Transcription:

The Operation of a Generator on Infinite Busbars In order to simplify the ideas as much as possible the resistance of the generator will be neglected; in practice this assumption is usually reasonable. Figure 1 (a) shows the schematic diagram of a machine connected to an infinite busbar along with the corresponding phasor diagram. Figure 1. If losses are neglected the power output from the turbine is equal to the power output from the generator. The angle δ between the E and V phasors is known as the load angle is dependent on the power input from the turbine shaft. With an isolated machine supplying its own load the latter dictates the power required and hence the load angle; when connected to an infinite-busbar system, however, the load delivered by the machine is no longer directly dependent on the connected load. By changing the turbine output and hence δ the generator can be made to take on any load the operator desires, subject to economic and technical limits. From the phasor diagram in Figure 1 (b), the power delivered to the infinite busbar = VI cos φ per phase but, E IXs = sin( 90 + φ) sinδ (1.1) hence I cosφ = E sinδ X s VE power delivered = sinδ X s

This expression is of extreme importance as it governs to a large extent the operation of a power system. Equation 1.1 is shown plotted in Figure 2. The maximum power is obtained at δ = 90 o. If δ becomes larger than 90 o due to an attempt to obtain more than P max, increase in δ results in less power output and the machine becomes unstable and loses synchronism. Loss of synchronism results in the interchange of current surges between the generator and network as the poles of the machine pull into synchronism and then out again. Figure 2. If the power output of the generator is increased by small increments with the noload voltage kept constant, the limited of stability occurs at δ = 90 o and is known as the steady-state stability limit. There is another limit of stability due to a sudden large change in conditions such as caused by a fault, known as the transient stability limit, and it is possible for the rotor to oscillate beyond 90 o a number of times. If these oscillations diminish, the machine is stable. The load angle δ has a physical significance; it is the angle between like radial marks on the end of the rotor shaft of the machine and on an imaginary rotor representing the system. The marks are in identical physical positions when the machine is on no-load. The synchronizing power coefficient = dp/dδ watts per radian and the synchronizing torque coefficient = (1/ ws )/(dp/dδ).

In figure 3(a) the phasor diagram for the limiting steady-state condition is shown. It should be noted that in this condition current is always leading. The following figures, 3(b), (c) and (d), show the phasor diagrams for various operational conditions. Figure 3.

Another interesting operating condition is variable power and constant excitation. This is shown in Figure 4. In this case as V and E are constant when the power from the turbine is increased δ must increase and the power factor changes. Figure 4. It is convenient to summarize the above types of an operation in a single diagram or chart which will enable an operator to see immediately whether the machine is operating within the limits of stability and rating. The performance chart of a synchronous generator Consider figure 5(a), the phasor diagram for a round-rotor machine ignoring resistance. The locus of constant IX s,i, and hence MVA is a circle and the locus of constant E a circle. Hence, 0s is proportional to VI or MVA ps is proportional to VI sin φ or MVAr sq is proportional to VI cos φ or MW To obtain the scaling factor for MVA, MVAr and MW the fact that at zero excitation, E = 0 and IX s = V, is used, from which I is V/X s at 90 o leading to 00, corresponding to VAr/phase. Figure 5(b) represents the construction of a chart for a 60 MW machine.

Figure 5 Machine data 60 MW, 0.8 pf, 75 MVA 11.8 kv, SCR 0.63, 3000 rev/min Maximum exciter current 500 A 1 X s = pu = 294. Ω / phase 063.

The chart will refer to complete three-phase values of MW and MAVr. When the excitation and hence E are reduced to zero, the current leads V by 90 o and is equal to (V/X s ), ie 11,800/ 3 x 2.94. The leading vars correspond to this = 11,800 2 /2.94 = 47 MVAr. With centre 0 a number of semicircles are drawn of radii equal to various MVA loadings, the most important being the 75 MVA circle. Arcs with 0 as centre are drawn with various multiples of 00 (or V) as radii to give the loci for constant excitation. Lines may also be drawn from 0 corresponding to various power factors, but for clarity only 0.8 pf lagging is shown. The operational limits are fixed as follows. The rated turbine output gives a 60 MW limit which is drawn as shown, ie line efg, which meets the 75 MVA line in g. The MVA arc governs the thermal loading of the machine, ie the stator temperature rise, so that over portion gh the output is decided by the MVA rating. At point h the rotor heating becomes more decisive and the arc hj is decided by the maximum excitation current allowable, in this case assumed to be 2.5 p.u. The remaining limit is that governed by loss of synchronism at leading power factors. The theoretical limit is the line perpendicular to 00' at 0' (ie δ = 90 o ), but in practice a safety margin is introduced to allow a further increase in load of either 10 or 20 per cent before instability. In Figure 5 a 10 per cent margin is used and is represented by ecd: it is constructed in the following manner. Considering point a on the theoretical limit on the E = 1 p.u. arc, the power 0 a is reduced by 10 per cent of the rated power (ie by 6MW) to 0 b; the operating point must, however, still be on the same E arc and b is projected to c which is a point on the new limiting curve. This is repeated for several excitations giving finnaly the curve ecd. The complete operating limit is shown shaded and the operator should normally work within the area bounded by this line. As an example of the use of the chart, the full-load operating point g (60 MW, 0.8 p.f.lagging) will require an excitation E of 2.3 p.u. and the measured load angle δ is 33 o. This can be checked by using, power = VE/X s sin δ, ie 60x10 from which δ = 33.4 o 6 2 11, 800 x2. 3 = sinδ 294. `