HEAT CONTENT DECREASES U D R HEAT CONTENT INCREASESO. Btu/lb

Similar documents
PowerPoint Presentation by: Associated Technical Authors. Publisher The Goodheart-Willcox Company, Inc. Tinley Park, Illinois

2.0 KEY EQUATIONS. Evaporator Net Refrigeration Effect. Compressor Work. Net Condenser Effect

NEBB Fundamental Formulas

ENH4X. Product Specifications HORIZONTAL EVAPORATOR COILS ALL CASED N COIL MODELS WARRANTY*

Section 1: Theory of Heat Unit 2: Matter and Energy

level of heat heat intensity

TOLERANCES AND UNCERTAINTIES IN PERFORMANCE DATA OF REFRIGERANT COMPRESSORS JANUARY 2017

END4X, ENW4X, ENA4X. Product Specifications VERTICAL EVAPORATOR COILS ALL N COIL MODELS CASED N COILS UNCASED N COILS ENA4X WARRANTY*

INDUSTRIAL RESOURCES, INC. Power Plant Fundamentals Training

TRADE MATH. accurate means to be without error. The word precise means to be exact.

Properties of Vapors

Glide Effect on Performance

Product Data. CNPVP, CNRVP, CNPVT, CNRVT, CNPVU, CNRVU Evaporator Coil N Coil Cased and Uncased Upflow, Downflow

ANSI/AHRI Standard (Formerly ARI Standard ) 2006 Standard for Performance Rating of Desuperheater/Water Heaters

R- 410A R-22 Size (tons) Shipping Weight (lbs) WLAU184AA 1-1/ WLAU182AA 1-1/ WLAU244AA. Model /2

ENVIRONMENTALLY SOUND R 410A REFRIGERANT

EFFICIENT 13 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

Common Terms, Definitions and Conversion Factors

Product Data. CAPVU Evaporator Coil A Coil --- Uncased Upflow, Downflow CAPVU

Refrigeration. 05/04/2011 T.Al-Shemmeri 1

Chimney Sizing. Project Name: Location: Type Appliance: Hot Water Heater Incinerator. LP Gas #2 Oil #6 Oil Wood/Coal Waste (Type ) Appliance Input:

TOTAL HEAD, N.P.S.H. AND OTHER CALCULATION EXAMPLES Jacques Chaurette p. eng., June 2003

FINAL EXAM. ME 200 Thermodynamics I, Spring 2013 CIRCLE YOUR LECTURE BELOW:

Today s A/C systems include:

PNEUMATIC ENTHALPY COMPARATOR

Basic Thermodynamics Prof. S K Som Department of Mechanical Engineering Indian Institute of Technology, Kharagpur. Lecture - 21 Vapors Power Cycle-II

Density of Air & Water Part 2

Product Data. CNPHP, CNRHP Evaporator Coil N Coil --- Cased Horizontal CNPHP / CNRHP

ME 2322 Thermodynamics I PRE-LECTURE Lesson 23 Complete the items below Name:

Pyschrometric Sample Problem Pharmaceutical Engineering Graduate Program New Jersey Institute of Technology

MODEL: WB009GMFI19HLD (120V) Wall Mount DC Inverter Fan Coil Unit 9,000 BTUH

4HP13 PRODUCT SPECIFICATIONS 13 SEER SPLIT SYSTEM HEAT PUMP WARRANTY

Ductless Split Systems Floating Air

RETA Book 1 Chapter 1 Fundamental Items

MAE 11. Homework 8: Solutions 11/30/2018

3 Port, 2-Ton Outdoor Heat Pump

Purpose of Today s Presentation

THE ENERGY 68,SAVING TDVI. exible Combine Modular 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP 60, 62, 64, 66 HP

(Refer Slide Time: 00:00:43 min) Welcome back in the last few lectures we discussed compression refrigeration systems.

MOTOR WIRING DATA From National Electrical Code 3 PHASE SQUIRREL CAGE INDUCTION MOTORS 230 Volt 460 Volt Min. # Max. Rating

Thermodynamics Introduction and Basic Concepts

Submittals. Advanced Series 1U09ES2VHA / AW09ES2VH* 1U12ES2VHA / AW12ES2VH* 1U18ES2VHA / AW18ES2VH* 1U24ES2VHA / AW24ES2VH* Rev.

Parts Manual R410A Models

Chapter 3 Basic Physical Principles Applications to Fluid Power Sy S stems

GB5BM Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Air Handler WARRANTY

Chemical Engineering Thermodynamics Spring 2002

Lecture 44: Review Thermodynamics I

Accumulators Virginia KMP Suction Line Accumulators

AIR COOLED CONDENSING UNIT

ANSI/AHRI Standard 1250 (I-P) 2014 Standard for Performance Rating of Walk-in Coolers and Freezers

Two mark questions and answers UNIT I BASIC CONCEPT AND FIRST LAW SVCET

BV SERIES. VERTICAL BLOWER COIL UNITS Nominal Sizes 2 thru 10 Ton

Solenoid valves Type EVUL

Brushless DC Variable Speed Compressor Technical Data Sheet

Figure 1.1. Relation between Celsius and Fahrenheit scales. From Figure 1.1. (1.1)

ME 354 THERMODYNAMICS 2 MIDTERM EXAMINATION. Instructor: R. Culham. Name: Student ID Number: Instructions

B6VMAX Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

Brushless DC Variable Speed Compressor Technical Data Sheet

SEM-2017(03HI MECHANICAL ENGINEERING. Paper II. Please read each of the following instructions carefully before attempting questions.

SHORTCUT CALCULATIONS AND GRAPHICAL COMPRESSOR SELECTION PROCEDURES

Northern Lesson 2 Gear Pump Terminology. Gear Pump 101. Lesson 2: Gear Pump Terminology. When your reputation depends on it!

HVAC Electrical Wiring Diagrams / Ohm s Law / Sequence of Operation RV

The following article was authored by Jacques Chaurette, President Fluide Design, Inc. ( All rights reserved.

1. INTRODUCTION TO REFRIGERATION AND AIR CONDITION

Solenoid valve Types CSV 2 - CSV 22 (NC) and solenoid coil

EXPLODED DIAGRAM - PARTS VIEW

1. DEFINITIONS. B. BTUH Hourly Rate of change in Mass Heat BTUH = * CFM * ΔT (Air Heat Transfer) BTUH = 500 * GPM * ΔT (Water Heat Transfer)

SUBMITTAL DATA: 4U36MS2VHB BTU/HR INVERTER DRIVEN MULTI ZONE HEAT PUMP SYSTEM

SECOND ENGINEER REG. III/2 APPLIED HEAT

Readings for this homework assignment and upcoming lectures

Applied Fluid Mechanics

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

Mathematical Modelling for Refrigerant Flow in Diabatic Capillary Tube

R13 SET - 1 '' ''' '' ' '''' Code No RT21033

GAS. Outline. Experiments. Device for in-class thought experiments to prove 1 st law. First law of thermodynamics Closed systems (no mass flow)

Department of Energy Fundamentals Handbook. THERMODYNAMICS, HEAT TRANSFER, AND FLUID FLOW, Module 3 Fluid Flow

ME 200 Thermodynamics I, Spring 2015, Exam 3, 8 p.m. to 9 p.m. on April 14, 2015

Solenoid valve Types EVR 2 - EVR 40

On-Line Models for Use in Automated Fault Detection and Diagnosis for HVAC&R Equipment

Chapter 5. Mass and Energy Analysis of Control Volumes

MAHALAKSHMI ENGINEERING COLLEGE

The exergy of asystemis the maximum useful work possible during a process that brings the system into equilibrium with aheat reservoir. (4.

Section A 01. (12 M) (s 2 s 3 ) = 313 s 2 = s 1, h 3 = h 4 (s 1 s 3 ) = kj/kgk. = kj/kgk. 313 (s 3 s 4f ) = ln

Vapor Pressure Deficit and HVAC System Design

Eliminator Liquid line filter driers, Type DCL and DML

5.2. The Rankine Cycle

Solenoid valves Type EVR 2 g 40 NC/ NO New EVR 6 with Steel cover design

Welcome. HVAC Change Out Regulations and Rater Verification California Track

PUMP PERFORMANCE MEASUREMENTS Jacques Chaurette p. eng. April 2003

PTAC: Applied Physics COURSE OUTLINE & OBJECTIVES ESC Approved October 8, 2004

ASPT Series. Multi-Position, Internal TXV. Air Handler 1½ to 5 Tons

Chapter 5. Mass and Energy Analysis of Control Volumes. by Asst. Prof. Dr.Woranee Paengjuntuek and Asst. Prof. Dr.Worarattana Pattaraprakorn

Thermal Process Control Lap 4 Thermal Energy. Notes:

Non-Dimensional Parameter Development For Transcritical Cycles

Samos SI E1/E2

An introduction to thermodynamics applied to Organic Rankine Cycles

P U M P S. The quality standard for hydraulic efficiency and suction lift. PERIPHERAL PUMPS TEP/ TSP - SERIES 50Hz

ME 201 Thermodynamics

IMPROVING THE PERFORMANCE OF AN AC UNIT USING CFD

SUBMITTAL DATA: MXZ-3C30NA MULTI-INDOOR INVERTER HEAT-PUMP SYSTEM

Transcription:

Pressure (psia) LINES OF CONSTANT ENTHALPY PRESSURE P R E S S U R E R I S E S P R E S S HEAT CONTENT DECREASES U R E D R HEAT CONTENT INCREASESO P S Btu/lb Heat Content

Pressure (psia) SATURATION CURVE Btu/lb Heat Content

THE SATURATION CURVE Under the curve, the refrigerant follows the pressure-temperature relationship The left side of the saturation curve represents 100% liquid The right side of the saturation curve represents 100% vapor For non-blended refrigerants, one pressure corresponds to one temperature

Pressure (psia) LINES OF CONSTANT TEMPERATURE Btu/lb Heat Content

Pressure (psia) LINES OF CONSTANT VOLUME (ft 3 /lb) Btu/lb Heat Content

Pressure (psia) LINES OF CONSTANT ENTROPY Btu/lb Heat Content

Pressure (psia) LINES OF CONSTANT QUALITY Btu/lb Heat Content

Pressure (psia) PUT IT ALL TOGETHER Btu/lb Heat Content

CONDENSER Liquid Vapor High Pressure High Temperature High Pressure High Temperature METERING DEVICE COMPRESSOR Low Pressure Low Temperature Low Pressure Low Temperature Liquid Vapor EVAPORATOR

Subcooled Liquid Saturated Refrigerant Superheated Vapor CONDENSER METERING DEVICE COMPRESSOR EVAPORATOR

Pressure Subcooled Region Superheated Region Saturated Region Heat Content

Pressure Heat Content

Pressure (psia) Btu/lb Heat Content

Pressure (psia) Btu/lb Heat Content

Pressure (psia) PUT IT ALL TOGETHER A E B C D Btu/lb Heat Content

E to PUT IT ALL TOGETHER Pressure A: CONDENSER (psia) (Including discharge and liquid line) A to B: METERING DEVICE B to C: EVAPORATOR C to D: SUCTION LINE D to E: COMPRESSOR A E B C D Btu/lb Heat Content

NET REFRIGERATION EFFECT The portion of the system that provides the desired cooling or conditioning of the space or products being treated. A E B C D

NET REFRIGERATION EFFECT The larger the NRE, the greater the heat transfer rate per pound of refrigerant circulated NRE is in the units of btu/lb Cooling effect can be increased by increasing the NRE or by increasing the mass flow rate The cooling effect can be decreased by decreasing the NRE or by decreasing the rate of refrigerant circulation through the system

NRE Example Heat Content at point B = 35 btu/lb Heat Content at point C = 85 btu/lb NRE = C B = 85 btu/lb 35 btu/lb NRE = 50 btu/lb Each pound of refrigerant can therefore hold 50 btu of heat energy How many btu does it take to make 1 ton?

How Many btu = 1 Ton? 12,000 btu/hour = 1 Ton = 200 btu/min From the previous example, how many lb/min do we have to move through the system to get 1 ton? 200 btu/min/ton 50 btu/lb = 4 lb/min We must circulate 4 pounds of refrigerant through the system every minute to obtain one ton of refrigeration Mass Flow Rate Per Ton

NRE and MFR/ton The NRE determines the number of btu that a pound of refrigerant can hold The larger the NRE the more btu can be held by the pound of refrigerant As the NRE increases, the MFR/ton decreases As the NRE decreases, the MFR/ton increases NRE = Heat content at C Heat content at B MFR/ton = 200 NRE Cool, huh?

THE SUCTION LINE The line that connects the outlet of the evaporator to the inlet of the compressor. This line is field installed on split-type air conditioning systems. A E B C D

SUCTION LINE The suction line should be as short as possible The amount of heat introduced to the system through the suction line should be minimized Damaged suction line insulation increases the amount of heat added to the system and decreases the system s operating efficiency Never remove suction line insulation without replacing Seal the point where insulation sections meet

A E E B C D D

HEAT OF COMPRESSION The quantity, in btu/lb that represents the amount of heat that is added to the refrigerant during the compression process. A E B C D

HEAT OF COMPRESSION (HOC) The HOC indicates the amount of heat added to a pound of refrigerant during compression As the pressure of the refrigerant increases, the heat content of the refrigerant increases as well Heat gets concentrated in the compressor As HOC increases, efficiency decreases As HOC decreases, efficiency increases HOC = Heat content at E Heat content at D

TOTAL HEAT OF REJECTION The quantity, in btu/lb that represents the amount of heat that is removed from the system. THOR includes the discharge line, condenser and liquid line. A E B C D

TOTAL HEAT OF REJECTION (THOR) THOR indicates the total amount of heat rejected from a system Refrigerant (hot gas) desuperheats when it leaves the compressor (sensible heat transfer) Once the refrigerant has cooled down to the condensing temperature, a change of state begins to occur (latent heat transfer) After condensing, refrigerant subcools THOR = Heat content at E Heat content at A THOR = NRE + HOC

SUBCOOLING & FLASH GAS Subcooling is a good thing, right? Flash gas is a good thing, right? Are flash gas and subcooling related? How can we tell? Stay tuned...

HIGH SUBCOOLING... (Only a slight Exaggeration) A E B C D What happened to the amount of flash gas?

LARGE AMOUNT OF FLASH GAS... (Only a slight Exaggeration) A E B C D What happened to the subcooling?

SUBCOOLING & FLASH GAS Subcooling and flash gas are inversely related to each other As the amount of subcooling increases, the percentage of flash gas decreases As the percentage of flash gas increases, the amount of subcooling decreases

COMPRESSION RATIO Determined by dividing the high side pressure (psia) by the low side pressure (psia) High-side pressure A E Low-side pressure B C D

COMPRESSION RATIO Represents the ratio of the high side pressure to the low side pressure Directly related to the amount of work done by the compressor to accomplish the compression process The larger the compression ratio, the larger the HOC and the lower the system MFR The larger the HOC, the lower the efficiency Absolute pressures must be used

ABSOLUTE PRESSURE Absolute pressure = Gauge pressure + 14.7 Round off to 15, for ease of calculation Example 1 High side pressure (psig) = 225 psig High side pressure (psia) = 225 + 15 = 240 psia Low side pressure (psig) = 65 psig Low side pressure (psia) = 65 + 15 = 80 psia Compression ratio = 240 psia 80 psia = 3:1

Low Side Pressure in a Vacuum? First, convert the low side vacuum pressure in inches of mercury to psia Use the following formula (30 Hg vacuum reading) 2 Example High side pressure = 245 psig High side pressure (psia) = 245 + 15 = 260 psia Low side pressure = 4 Hg Low side (psia) = (30 hg 4 Hg) 2 = 13 psia Compression ratio = 260 13 = 20:1

COMPRESSION RATIO Lower compression ratios higher system efficiency Higher compression ratios lower system efficiency The closer the head pressure is to the suction pressure, the higher the system efficiency, all other things being equal and operational

Causes of High Compression Ratio (High Side Issues) Dirty or blocked condenser coil Recirculating air through the condenser coil Defective condenser fan motor Defective condenser fan motor blade Defective wiring at the condenser fan motor Defective motor starting components (capacitor) at the condenser fan motor

Causes of High Compression Ratio (Low Side Issues) Dirty or blocked evaporator coil Dirty air filter Defective evaporator fan motor Dirty blower wheel (squirrel cage) Defective wiring at the evaporator fan motor Closed supply registers Blocked return grill Loose duct liner Belt/pulley issues

THEORETICAL HORSEPOWER PER TON Determines how much compressor horsepower is required to obtain 1 ton of cooling The ft-lb is a unit of work The ft-lb/min is a unit of power 33,000 ft-lb/min = 1 Horsepower The conversion factor between work and heat is 778 ft-lb/btu 33,000 ft-lb/min/hp 778 ft-lb/btu = 42.42 btu/min/hp

THEORETICAL HORSEPOWER PER TON THp/ton = (MFR/ton x HOC) 42.42 For example, if we had a system that had an NRE of 50 and a HOC of 10, the THp/ton would be: THp/ton = (200/NRE) x HOC 42.42 THp/ton = (200/50) x 10 42.42 THp/ton = 4 x 10 42.42 THp/ton = 40 42.42 THp/ton = 0.94

THp/ton Example If we had a 20-Hp reciprocating compressor and the THp/ton calculation yielded a result of 2 hp/ton, what would the expected cooling capability of the system be?

What Affects the THp/ton Number? The Net Refrigeration Effect (NRE) The Heat of Compression (HOC) What Affects the NRE and HOC? Suction pressure Discharge pressure Compression Ratio Airflow through the coils Blowers and fans And so on, and so on, and so on, and so on.

MASS FLOW RATE OF THE SYSTEM The amount of refrigerant that flows past any given point in the system every minute Not to be confused with MFR/ton MFR/system is the actual refrigerant flow, while MFR/ton is the flow per ton MFR/system can be found by multiplying the MFR/ton by the number of tons of system capacity, or MFR/system = (42.42 x Compressor HP) HOC

COOL STUFF As the HOC increases, the MFR/system decreases, and vice versa As the Compression Ratio increases, the HOC increases As head pressure increases, or as suction pressure decreases, the Compression Ratio increases As the MFR/system decreases, the capacity of the evaporator, condenser and compressor all decrease Let s take a closer look

EVAPORATOR CAPACITY A function of the MFR/system and the NRE The MFR/system is in lb/min, the NRE is in btu/lb and the capacity of the evaporator is in btu/hour Evaporator Capacity = MFR/system x NRE x 60 Btu Lb Btu 60 Min Hour Min Lb Hour

EVAPORATOR CAPACITY If the NRE or the MFR/system decreases, the evaporator capacity also decreases The 60 is a conversion factor from btu/min to btu/hour, given that there are 60 minutes in an hour Divide the evaporator capacity in btu/hour by 12,000 to obtain the evaporator capacity in tons

CONDENSER CAPACITY A function of the MFR/system and the THOR The MFR/system is in lb/min, the THOR is in btu/lb and the capacity of the condenser is in btu/hour Condenser Capacity = MFR/system x THOR x 60 Btu Lb Btu 60 Min Hour Min Lb Hour

COMPRESSOR CAPACITY A function of the MFR/system and the Specific volume of the refrigerant at the inlet of the compressor Calculated in cubic feet per minute, ft 3 /min Compresser Capacity = MFR/system x Specific Volume ft 3 Lb ft 3 Min Min Lb

COEFFICIENT OF PERFORMANCE (COP) The ratio of the NRE compared to the HOC, assuming a saturated cycle If the cycle is not saturated, add the suction line heat to the HOC If the HOC remains constant, any increases in NRE will increase the COP If the NRE remains constant, any decrease in HOC will increase the COP The COP is a contributing factor to the EER of an air conditioning system COP is a unitless value

COP EXAMPLE #1 Heat content at point B = 35 btu/lb Heat content at point C = 104 btu/lb Heat content at point D = 104 btu/lb Heat content at point E = 127 btu/lb NRE = 104 btu/lb 35 btu/lb = 69 btu/lb HOC = 127 btu/lb 104 btu/lb = 23 btu/lb COP = 69 btu/lb 23 btu/lb = 3 Notice that the 3 has no units

COP EXAMPLE #2 Heat content at point B = 35 btu/lb Heat content at point C = 105 btu/lb Heat content at point D = 110 btu/lb Heat content at point E = 140 btu/lb NRE = 105 btu/lb 35 btu/lb = 70 btu/lb HOC = 140 btu/lb 110 btu/lb = 30 btu/lb SL superheat = 110 btu/lb 105 btu/lb = 5 btu/lb COP = [70 btu/lb] [30 btu/lb + 5 btu/lb] = 2

ENERGY EFFICIENCY RATIO (EER) A ratio of the amount of btus transferred to the amount of power used In the units of btu/watt The conversion between btus and watts is 3.413 One watt of power generates 3.413 btu For example, if a system required 50,000 btu of heat, 14,650 watts of electric heat (14.65 kw) can be used

ENERGY EFFICIENCY RATIO (EER), Cont d. The efficiency rating of an air conditioning system is the COP For each btu/lb introduced to the system in the suction line and the compressor, a number of btus equal to the NRE are absorbed into the system via the evaporator To convert the COP to energy usage, we multiply the COP by 3.413

EER EXAMPLE The NRE of a system is 70 btu/lb The HOC of the same system is 20 btu/lb The COP is 70 btu/lb 20 btu/lb = 3.5 The EER = COP x 3.413 EER = 3.5 x 3.413 EER = 11.95

SEASONAL EER (SEER) Takes the entire conditioning system into account Varies depending on the geographic location of the equipment Ranges from 10% t0 30% higher than EER So, if the EER is 10, the SEER will range from 11 to 13

From the P-H Chart, We Can Find Compression Ratio NRE HOC HOW THOR COP MFR/ton THp/ton MFR/system Evaporator Capacity Condenser Capacity Compressor Capacity EER of the System SEER Okay, Okay, Okay How do I plot one of these things?

An R-22 A/C System Condenser saturation temperature 120 F Condenser outlet temperature 100 F Evaporator saturation temperature 40 F Evaporator outlet temperature 50 F Compressor inlet temperature 60 F Compressor Horsepower: 4 hp

Pressure-Enthalpy (p-h) Diagram for R-22 (Simplified) Pressure (psia) 160 F 180 F 352 275 211 159 117 84 58 39 25 140 F 120 F 100 F 80 F 60 F 40 F 20 F 0 F -20 F -40 F 0.7 3 4 4 5 1 1 1 1 1 2 0 6 3 1 1 1 2 2 0 2 7 1 5 Enthalpy in btu/lb (Heat Content)

Pressure-Enthalpy (p-h) Diagram for R-22 (Simplified) Pressure (psia) 160 F 180 F 352 275 211 159 117 84 58 39 25 140 F 120 F 100 F 80 F 60 F 40 F 20 F 0 F -20 F -40 F 0.7 3 4 4 5 1 1 1 1 1 2 0 6 3 1 1 1 2 2 0 2 7 1 5 Enthalpy in btu/lb (Heat Content)

Pressure-Enthalpy (p-h) Diagram for R-22 (Simplified) Pressure (psia) 160 F 180 F 352 275 211 159 117 84 58 39 25 A B 140 F 120 F 100 F 80 F 60 F 40 F 20 F 0 F -20 F -40 F C 0.7 3 4 4 5 1 1 1 1 1 2 0 6 3 1 1 1 2 2 0 2 7 1 5 Enthalpy in btu/lb (Heat Content)

Pressure-Enthalpy (p-h) Diagram for R-22 (Simplified) Pressure (psia) 160 F 180 F 352 275 211 159 117 84 58 39 25 A 40 F 140 F 120 F 100 F 80 F 60 F B 20 F C D 0 F -20 F -40 F 0.7 3 4 4 5 1 1 1 1 1 2 0 6 3 1 1 1 2 2 0 2 7 1 5 Enthalpy in btu/lb (Heat Content)

Pressure-Enthalpy (p-h) Diagram for R-22 (Simplified) Pressure (psia) 160 F 180 F 352 275 211 159 117 84 58 39 25 A 40 F 140 F 120 F 100 F 80 F 60 F B 20 F C D 0 F -20 F -40 F 0.7 3 4 4 5 1 1 1 1 1 2 0 6 3 1 1 1 2 2 0 2 7 1 5 Enthalpy in btu/lb (Heat Content)

Pressure-Enthalpy (p-h) Diagram for R-22 (Simplified) Pressure (psia) 160 F 180 F 352 275 211 159 117 84 58 39 25 A 40 F 140 F 120 F 100 F 80 F 60 F B 20 F C D 0 F -20 F -40 F E 0.7 3 4 4 5 1 1 1 1 1 2 0 6 3 1 1 1 2 2 0 2 7 1 5 Enthalpy in btu/lb (Heat Content)

Pressure-Enthalpy (p-h) Diagram for R-22 (Simplified) Pressure (psia) 160 F 180 F 352 275 211 159 117 84 58 39 25 A 40 F 80 F 60 F 120 F 100 F 140 F B 20 F C D 0 F -20 F -40 F 3 4 4 5 1 1 1 1 1 2 0 6 3 1 1 1 2 2 0 2 7 1 5 Enthalpy in btu/lb (Heat Content) E 0.7 High: 275 psia Low: 84 psia A : 40 btu/lb B : 40 btu/lb C : 110 btu/lb D : 112 btu/lb E : 125 btu/lb

High: 275 psia Low: 84 psia A : 40 btu/lb B : 40 btu/lb C : 110 btu/lb D : 112 btu/lb E : 125 btu/lb COMPRESSION RATIO HIGH SIDE PRESSURE (psia) LOW SIDE PRESSURE (psia) COMPRESSION RATIO = 275 psia 84 psia = 3.27:1

High: 275 psia Low: 84 psia A : 40 btu/lb B : 40 btu/lb C : 110 btu/lb D : 112 btu/lb E : 125 btu/lb HEAT OF COMPRESSION HEAT CONTENT AT E HEAT CONTENT AT D HEAT OF COMPRESSION= 125 btu/lb 112 btu/lb = 13 btu/lb

High: 275 psia Low: 84 psia A : 40 btu/lb B : 40 btu/lb C : 110 btu/lb D : 112 btu/lb E : 125 btu/lb NET REFRIGERATION EFFECT HEAT CONTENT AT C HEAT CONTENT AT B NRE = 110 btu/lb 40 btu/lb = 70 btu/lb

High: 275 psia Low: 84 psia A : 40 btu/lb B : 40 btu/lb C : 110 btu/lb D : 112 btu/lb E : 125 btu/lb MASS FLOW RATE PER TON 200 NRE MFR/ton = 200 NRE =200 70 btu/lb = 2.86 lb/min/ton

High: 275 psia Low: 84 psia A : 40 btu/lb B : 40 btu/lb C : 110 btu/lb D : 112 btu/lb E : 125 btu/lb TOTAL HEAT OF REJECTION HEAT CONTENT AT E HEAT CONTENT AT A THOR = 125 btu/lb 40 btu/lb = 85 btu/lb

High: 275 psia Low: 84 psia A : 40 btu/lb B : 40 btu/lb C : 110 btu/lb D : 112 btu/lb E : 125 btu/lb THEORETICAL HORSEPOWER PER TON [MFR/ton x HOC] 42.42 THp/ton = 2.86 lb/min/ton x 13 btu/lb 42.42 = 0.88 Hp/ton

High: 275 psia Low: 84 psia A : 40 btu/lb B : 40 btu/lb C : 110 btu/lb D : 112 btu/lb E : 125 btu/lb COEFFICIENT OF PERFORMANCE NRE [HOC + SL] COP = [70 btu/lb] [15 btu/lb + 2 btu/lb] = 4.12

High: 275 psia Low: 84 psia A : 40 btu/lb B : 40 btu/lb C : 110 btu/lb D : 112 btu/lb E : 125 btu/lb MASS FLOW RATE OF THE SYSTEM [42.42 x Compressor HP] HOC MFR/system = [42.42 x 4] 13 btu/lb = 13.05 lb/min

High: 275 psia Low: 84 psia A : 40 btu/lb B : 40 btu/lb C : 110 btu/lb D : 112 btu/lb E : 125 btu/lb CAPACITY OF THE EVAPORATOR NRE x MFR/system x 60 CAP/evap = 70 btu/lb x 13.05 x 60 = 54,810 btu/hour CAP/evap = 54,810 btu/hour 12,000 btu/hour/ton = 4.57 tons

High: 275 psia Low: 84 psia A : 40 btu/lb B : 40 btu/lb C : 110 btu/lb D : 112 btu/lb E : 125 btu/lb CAPACITY OF THE CONDENSER THOR x MFR/system x 60 CAP/cond = 85 btu/lb x 13.05 x 60 = 66,555 btu/hour CAP/cond = 66,555 btu/hour 12,000 btu/hour/ton = 5.55 tons

High: 275 psia Low: 84 psia A : 40 btu/lb B : 40 btu/lb C : 110 btu/lb D : 112 btu/lb E : 125 btu/lb CAPACITY OF THE COMPRESSOR MFR/system x Specific Volume CAP/comp = 13.05 x 0.7 = 9.13 ft 3 /min

High: 275 psia Low: 84 psia A : 40 btu/lb B : 40 btu/lb C : 110 btu/lb D : 112 btu/lb E : 125 btu/lb ENERGY EFFICIENCY RATIO COP x 3.413 EER = 4.67 x 3.413 = 15.94 SEER (low end) = 1.1 x EER = 1.1 x 15.94 = 17.5 SEER (high end) = 1.3 x EER = 1.3 x 15.94 = 20.7

Properly Operating System Heat Content A = 40 btu/lb Heat Content B = 40 btu/lb Heat Content C = 109 btu/lb Heat Content D = 111 btu/lb Heat Content E = 125 btu/lb High side pressure = 267 psig High side pressure = 282 psia Low side pressure = 70 psig Low side pressure = 85 psia Compressor Hp = 2.5 Hp Specific Volume = 0.7 NRE = 69 btu/lb HOW = 14 btu/lb HOC = 16 btu/lb THOR = 85 btu/lb Comp. Ratio = 3.32 MFR/ton = 2.9 lb/min/ton THp/ton = 0.96 Hp/ton COP = 4.3 MFR/system = 7.58 lb/min CAP/evap = 31,381 btuh CAP/cond = 38,658 btuh CAP/comp = 5.3 ft 3 /min EER = 14.68 SEER = 16.15 19.1 A/B C D E

Clogged Cap Tube System Heat Content A = 39 btu/lb Heat Content B = 39 btu/lb Heat Content C = 112 btu/lb Heat Content D = 118 btu/lb Heat Content E = 134 btu/lb High side pressure = 226 psig High side pressure = 241 psia Low side pressure = 59 psig Low side pressure = 74 psia Compressor Hp = 2.5 Hp Specific Volume = 0.9 NRE = 73 btu/lb HOW = 16 btu/lb HOC = 22 btu/lb THOR = 95 btu/lb Comp. Ratio = 3.26 MFR/ton = 2.74 lb/min/ton THp/ton = 1.03 Hp/ton COP = 3.3 MFR/system = 6.63 lb/min CAP/evap = 29,039 btuh CAP/cond = 37,791 btuh CAP/comp = 5.97 ft 3 /min EER = 11.26 SEER = 12.39 14.64 A/B C D E

System Okay System Clogged Increase/Decrease NRE 69 73 Increase HOW 14 16 Increase HOC 16 22 Increase THOR 85 95 Increase Comp. Ratio 3.32 3.26 Decrease MFR/ton 2.9 2.74 Decrease THp/ton 0.96 1.03 Increase COP 4.3 3.3 Decrease MFR/system 7.58 6.63 Decrease CAP/evap 31,381 (2.62) 29,039 (2.42) Decrease CAP/cond 38,658 (3.22) 37,791 (3.15) Decrease CAP/comp 5.3 5.97 Increase EER 14.68 11.26 Decrease SEER 16.15 19.1 12.39 14.64 Decrease