Product manual Mylos KNX Shutter actuator 2CSY1104C/S
Contents Contents 1 Technical features... 3 1.1 Technical data... 3 1.2 Connection diagram... 4 2 Commissioning... 5 2.1 Parameters... 5 2.1.1 General... 5 2.2 Actuator... 6 2.3 Status... 7 2.4 Scenes... 8 2.5 Position... 9 3 Operation of communication objects... 10 4 Table of 8 bit scene telegram codes... 13 2 Contents MYLOS Building Automation
Technical features 1 Technical features The shutter actuator is a flash-mounted device for the ABB's Mylos Building Automation system, used for the control of a drive for shutters or blinds with the possibility of ascent, descent and louvre adjustment. On the rear side it has connecting terminals for ascent and descent commands of a motor operated shutter. From the parameters it is possible to choose the standby time to be applied to every change of direction. 1.1 Technical data Power supply Operating voltage 21 30 VDC over the bus Absorbed power EIB / KNX < 12 ma Nominal output values Number of Up/DOWN outputs 1 exchange contact UP and DOWN are interlocked Rated voltage U n 230/440 VAC (50/60Hz) Rated current I n (per output) 8A Connections EIB / KNX Connection terminal Bus 0.6-0.8 mm ø, unipole Load circuit 1 screw terminal for phase connection, 2 screw terminals for UP and DOWN Connection cable cross section 0,2.2,5 mm 2 braid 0,2.4 mm 2 unipole Tightening torque Max. 0.5 Nm Control and display elements red LED and EIB / KNX button To set the physical address EIB / KNX EIB / KNX voltage SELV 24 VDC (safety extra low voltage) Ambient temperature Use -5 C + 45 C Storage -25 C + 55 C Transport -25 C + 70 C Design Dimensions (H x W x D) in mm 17 x W x 15 Width W in mm 17 Mounting width in mm 7 Mounting depth in mm 5 Case, colour Plastic container, white or black CE marking acc. to EMC and Low-Voltage Directives Device type Application program Maximum number of communication objects Maximum number of group addresses Maximum number of associations 2CSYK1204 Shutter 1c/1.0 10 255 255 MYLOS Building Automation Technical features 3
Technical features Supplied state The device is supplied with the physical address 1.0.1. The application program is preloaded. It is therefore only necessary to load group addresses and parameters during commissioning. However, the complete application program can be reloaded if required. A longer downtime may result if the application program is changed or after a discharge. Assignment of the physical address The assignment and programming of the physical address is carried out in the ETS. The device features a Programming button for assignment of the physical device address. The red Programming LED lights up, after the button has been pushed. It switches off, as soon as the ETS has assigned the physical address or the Programming button is pressed again. Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive agents or solutions should never be used. Download behaviour Depending on the PC, which is used, the progress bar for the download may take up to one and a half minutes, before it appears, due to the complexity of the device. Maintenance The device is maintenance-free. No repairs should be carried out by unauthorised personnel if damage occurs, e. g. during transport and/or storage. 1.2 Connection diagram N L M DOWN COMMON UP + 4 Technical features MYLOS Building Automation
Commissioning 2 Commissioning The main functions of the shutter actuator are described in this section. The shutter actuator parametrisation is performed via the Engineering Tool ETS Software application program. For the parametrisation you need a pc desktop or a laptop with ETS and connection to the KNX system (obtainable for example by means of RS232, USB or IP Interface). 2.1 Parameters 2.1.1 General Operating mode It is possible to define the device operation mode using this parameter, even if the parameters and communication objects for the two operating modes are very similar. Position for bus voltage interruption The parameter allows you to define the device behaviour upon voltage failure. In particular, for the "No reaction" case the output contacts will remain in their position, whereas in the "Stop" case the shutter/blind will stop immediately. Position upon bus voltage restoration Similarly to the previous parameter, this parameter manages the device output contacts upon voltage restoration. 8 bit scene If it is set on Enable both the Scene communication object and the Scenes parameter window will appear. MYLOS Building Automation Commissioning 5
Commissioning 2.2 Actuator Stroke duration [0 6000] sec Parameter used to set the stroke duration in seconds. Louvre adjustment duration [60 1000] msec (only if the operating mode set by parameters is Blind) The parameter determines louvre adjustment duration. Pause in the change of direction. 300 10000 msec Pause between two changes of direction Maximum number of louvre adjustments [1 60] msec (only if the operating mode set by parameters is Blind) To set the maximum number of louvre adjustment. Start-up delay [0 255] msec To set the delay upon start-up of any device movement. Switch-off delay [0 255] msec To set the delay at the end of any device movement. Switch the voltage-free outputs after This parameter allows the device to actually reach the (upper or lower) limit switch position. At the limit switch duration a further movement command in the same direction will cause: no reaction for "Limit switch reaching, no exceeding"; a stroke equal to 2% of the stroke duration for "Limit switch, 2% exceeding"; a stroke equal to 5% of the stroke duration for "Limit switch, 5% exceeding"; a stroke equal to 10% of the stroke duration for "Limit switch, 10% exceeding"; a stroke equal to 20% of the stroke duration for "Limit switch, 20% exceeding"; a stroke equal to 110% of the stroke duration for "Stroke total time, 10% exceeding"; 6 Commissioning MYLOS Building Automation
Commissioning 2.3 Status Send position [0 255] If Yes the Position status and Louvre status communication objects will appear (the last one only in case of BIlnd operation). Send the position after reaching the limit switch If Yes the Upper limit switch and Lower limit switch will be displayed. MYLOS Building Automation Commissioning 7
Commissioning 2.4 Scenes Association 1 Association 10 The parameters allow you to determine which scene group the device belongs to. It is possible to select up to 10 associations and for each association you can select up to 64 scenes. 8 Commissioning MYLOS Building Automation
Commissioning 2.5 Position Recall position [0 255] If it is set on Enable the Recall position 0 255 communication objects will appear. Objects for "Storing position" If it is set on Enable the Store position 1 or 2 and Store position 3 or 4 communication objects will appear. Objects for "Recalling position" If it is set on Enable the Recall position 1 or 2 and Recall position 3 or 4 communication objects will appear. MYLOS Building Automation Commissioning 9
Operation of communication objects 3 Operation of communication objects For the "Blind" operating mode: No. Function Object name Type of datum Flags 0 Blind up-down Output 1 bit DPT Up Down C, W For the "Shutter" operating mode: 0 Blind up-down Output 1 bit DPT Up Down C, W If a telegram with the value 0 is received at this communication object, the shutter/blind is raised. If a telegram with the value 1 is received, the shutter/blind is lowered. The output contact reverts to the neutral position once the total travel time for UP/DOWN movement has elapsed. UP 1 : DOWN For the "Blind" operating mode: 1 Louvres/Stop up-down Exit 1 bit DPT Up Down C, W For the "Shutter" operating mode: 1 Stop up-down Output 2 bit (EIS 8) DPT 2.001 C, W If the shutter/blind is in motion, the movement is stopped on receipt of a telegram at this communication object, regardless of whether a 0 or a 1 has been received. Blinds operating mode: If the shutter is idle, it is raised ( 0 ) or lowered ( 1 ) for the duration of the louvre adjustment and then stopped on receipt of a telegram at this communication object. Shutter operating mode: If the blind is idle, no action is carried out on receipt of a telegram at this communication object. Stop/louvre adj. UP 1 : Stop/louvre adj. DOWN 2 Recall position 0... 255 Exit 1 Byte DPT Percent U8 C, W 10 Operation of communication objects MYLOS Building Automation
Operation of communication objects If a telegram is received at this communication object, the shutter/blind moves to the corresponding position for the received value. After reaching the target position, the louvres are positioned as before. Only if during the shutter/blind movement a telegram was received on the communication object Move louvres 0 255, the louvres will be positioned accordingly. Top... : Intermediate position 255 : Bottom 3 Scene Output 1 Byte DPT Scene Control Output can be integrated into up to ten scenes with this communication object. A telegram is received which contains the number of the scene that is addressed together with the information about whether the shutter/blind is moved to the last saved position or whether the current position should be stored as the new preset value. The stored scene values are retained in the event of a bus voltage failure and if only the parameters are downloaded during programming. If the complete application is downloaded again during programming, the scene value is reset to the position right at the top. Telegram code: MXNNNNNN NNNNNN: 0...63: Scene number M: Recall scene 1 : Store scene 4 Position status Output 1 Byte DPT Percent U8 C, W C, R, T The Shutter Actuator sends the current position of the shutter/blind to this communication object. The current position is sent approx. 5 seconds after the completion of a movement. If a new movement is started in the meantime, the current position is only sent once the last action has been completed. Top... : Intermediate position 255 : Bottom For the "Shutter" operating mode: 5 Louvres status Exit 1 Byte DPT Percent U8 C, R, T The Shutter Actuator sends the current position of the louvres to this communication object. The current position is sent approx. 5 seconds after the completion of a movement. If a new movement is started in the meantime, the current position is only sent once the last action has been completed. Louvres opened to maximum... : Intermediate position 255 : Louvres closed MYLOS Building Automation Operation of communication objects 11
Operation of communication objects 6 Recall position 1 or 2 Output 1 bit DPT Switch C, W 7 Recall position 3 or 4 Output 1 bit DPT Switch C, W If a telegram is received at this communication object, the shutter/blind is moved to the stored preset position. In the Blinds operating mode, the louvre adjustment is carried out according to the preset position once the position has been reached. If a telegram with the value 0 is received, the shutter/blind moves to position 1 (or position 3). If a telegram with the value 1 is received, the shutter/blind moves to position 2 (or position 4). Move to position 1 or Move to position 3 1 : Move to position 2 or Move to position 4 8 Store position 1 or 2 Output 1 bit DPT Switch C, W 9 Store position 3 or 4 Output 1 bit DPT Switch C, W If a telegram is received at this communication object, the current position of the shutter/blind is adopted as the new preset value. If a telegram with the value 0 is received, the current position is stored as the new preset value for position 1 (or position 3). If a telegram with the value 1 is received, the current position is stored as the new preset value for position 2 (or position 4). If position 1 or 2 is now recalled (position 3 or 4), the shutter/blind moves to the new preset values. The modified preset values are retained on bus voltage failure. After programming the Shutter Actuator, the preset values are reset to the values that were parameterised during the project design stage or the values adapted in operation are stored, depending parameterization. Set position 1 or Set position 3 1 : Set position 2 or Set position 4 10 Upper limit switch Output 1 bit DPT Start C, R, T The Shutter Actuator sends the information to this communication object as to whether the shutter/blind is located in the upper limit position or not. The current position is sent approx. 1 second (plus the switch on duration of the louvre adjustment if applicable) after the upper limit position has been reached or left. If a new movement is started in the meantime, the current position is only sent once the last action has been completed. Shutter/blind not in upper limit position 1 : Shutter/blind in upper limit position 12 Operation of communication objects MYLOS Building Automation
Table of 8 bit scene telegram codes 4 Table of 8 bit scene telegram codes Bit no. 7 6 5 4 3 2 1 0 Bit no. 7 6 5 4 3 2 1 0 8-Bit Values Hexadecimal Recall/Store Not defined Scene number Scene no. Recall (A)/ Store (S) 0 00 0 0 0 0 0 0 0 0 1 A 1 01 0 0 0 0 0 0 0 1 2 A 2 02 0 0 0 0 0 0 1 0 3 A 3 03 0 0 0 0 0 0 1 1 4 A 4 04 0 0 0 0 0 1 0 0 5 A 5 05 0 0 0 0 0 1 0 1 6 A 6 06 0 0 0 0 0 1 1 0 7 A 7 07 0 0 0 0 0 1 1 1 8 A 8 08 0 0 0 0 1 0 0 0 9 A 9 09 0 0 0 0 1 0 0 1 10 A 10 0A 0 0 0 0 1 0 1 0 11 A 11 0B 0 0 0 0 1 0 1 1 12 A 12 0C 0 0 0 0 1 1 0 0 13 A 13 0D 0 0 0 0 1 1 0 1 14 A 14 0E 0 0 0 0 1 1 1 0 15 A 15 0F 0 0 0 0 1 1 1 1 16 A 16 10 0 0 0 1 0 0 0 0 17 A 17 11 0 0 0 1 0 0 0 1 18 A 18 12 0 0 0 1 0 0 1 0 19 A 19 13 0 0 0 1 0 0 1 1 20 A 20 14 0 0 0 1 0 1 0 0 21 A 21 15 0 0 0 1 0 1 0 1 22 A 22 16 0 0 0 1 0 1 1 0 23 A 23 17 0 0 0 1 0 1 1 1 24 A 24 18 0 0 0 1 1 0 0 0 25 A 25 19 0 0 0 1 1 0 0 1 26 A 26 1 A 0 0 0 1 1 0 1 0 27 A 27 1B 0 0 0 1 1 0 1 1 28 A 28 1C 0 0 0 1 1 1 0 0 29 A 29 1D 0 0 0 1 1 1 0 1 30 A 30 1E 0 0 0 1 1 1 1 0 31 A 31 1F 0 0 0 1 1 1 1 1 32 A 32 20 0 0 1 0 0 0 0 0 33 A 33 21 0 0 1 0 0 0 0 1 34 A 34 22 0 0 1 0 0 0 1 0 35 A 35 23 0 0 1 0 0 0 1 1 36 A 36 24 0 0 1 0 0 1 0 0 37 A 37 25 0 0 1 0 0 1 0 1 38 A 38 26 0 0 1 0 0 1 1 0 39 A 39 27 0 0 1 0 0 1 1 1 40 A 40 28 0 0 1 0 1 0 0 0 41 A 41 29 0 0 1 0 1 0 0 1 42 A 42 2 A 0 0 1 0 1 0 1 0 43 A 43 2B 0 0 1 0 1 0 1 1 44 A 44 2C 0 0 1 0 1 1 0 0 45 A 45 2D 0 0 1 0 1 1 0 1 46 A 46 2E 0 0 1 0 1 1 1 0 47 A 47 2F 0 0 1 0 1 1 1 1 48 A 48 30 0 0 1 1 0 0 0 0 49 A 49 31 0 0 1 1 0 0 0 1 50 A 50 32 0 0 1 1 0 0 1 0 51 A 51 33 0 0 1 1 0 0 1 1 52 A 52 34 0 0 1 1 0 1 0 0 53 A 53 35 0 0 1 1 0 1 0 1 54 A 54 36 0 0 1 1 0 1 1 0 55 A 55 37 0 0 1 1 0 1 1 1 56 A 56 38 0 0 1 1 1 0 0 0 57 A 57 39 0 0 1 1 1 0 0 1 58 A 58 3A 0 0 1 1 1 0 1 0 59 A 59 3B 0 0 1 1 1 0 1 1 60 A 60 3C 0 0 1 1 1 1 0 0 61 A 61 3D 0 0 1 1 1 1 0 1 62 A 62 3E 0 0 1 1 1 1 1 0 63 A 127 7F 0 1 1 1 1 1 1 1 0 A 128 80 1 0 0 0 0 0 0 0 1 S 129 81 1 0 0 0 0 0 0 1 2 S 130 82 1 0 0 0 0 0 1 0 3 S 131 83 1 0 0 0 0 0 1 1 4 S 132 84 1 0 0 0 0 1 0 0 5 S 133 85 1 0 0 0 0 1 0 1 6 S 134 86 1 0 0 0 0 1 1 0 7 S 135 87 1 0 0 0 0 1 1 1 8 S 136 88 1 0 0 0 1 0 0 0 9 S 137 89 1 0 0 0 1 0 0 1 10 S 138 8A 1 0 0 0 1 0 1 0 11 S 139 8B 1 0 0 0 1 0 1 1 12 S 140 8C 1 0 0 0 1 1 0 0 13 S 141 8D 1 0 0 0 1 1 0 1 14 S 142 8E 1 0 0 0 1 1 1 0 15 S 143 8F 1 0 0 0 1 1 1 1 16 S 144 90 1 0 0 1 0 0 0 0 17 S 145 91 1 0 0 1 0 0 0 1 18 S 146 92 1 0 0 1 0 0 1 0 19 S 147 93 1 0 0 1 0 0 1 1 20 S 148 94 1 0 0 1 0 1 0 0 21 S 149 95 1 0 0 1 0 1 0 1 22 S 150 96 1 0 0 1 0 1 1 0 23 S 151 97 1 0 0 1 0 1 1 1 24 S 152 98 1 0 0 1 1 0 0 0 25 S 153 99 1 0 0 1 1 0 0 1 26 S 154 9A 1 0 0 1 1 0 1 0 27 S 155 9B 1 0 0 1 1 0 1 1 28 S 8-Bit Values Hexadecimal Recall/Store Not defined Scene number Scene no. Recall (A)/ Store (S) 156 9C 1 0 0 1 1 1 0 0 29 S 157 9D 1 0 0 1 1 1 0 1 30 S 158 9E 1 0 0 1 1 1 1 0 31 S 159 9F 1 0 0 1 1 1 1 1 32 S 160 A0 1 0 1 0 0 0 0 0 33 S 161 A1 1 0 1 0 0 0 0 1 34 S 162 A2 1 0 1 0 0 0 1 0 35 S 163 A3 1 0 1 0 0 0 1 1 36 S 164 A4 1 0 1 0 0 1 0 0 37 S 165 A5 1 0 1 0 0 1 0 1 38 S 166 A6 1 0 1 0 0 1 1 0 39 S 167 A7 1 0 1 0 0 1 1 1 40 S 168 A8 1 0 1 0 1 0 0 0 41 S 169 A9 1 0 1 0 1 0 0 1 42 S 170 AA 1 0 1 0 1 0 1 0 43 S 171 AB 1 0 1 0 1 0 1 1 44 S 172 AC 1 0 1 0 1 1 0 0 45 S 173 AD 1 0 1 0 1 1 0 1 46 S 174 AE 1 0 1 0 1 1 1 0 47 S 175 AF 1 0 1 0 1 1 1 1 48 S 176 B0 1 0 1 1 0 0 0 0 49 S 177 B1 1 0 1 1 0 0 0 1 50 S 178 B2 1 0 1 1 0 0 1 0 51 S 179 B3 1 0 1 1 0 0 1 1 52 S 180 B4 1 0 1 1 0 1 0 0 53 S 181 B5 1 0 1 1 0 1 0 1 54 S 182 B6 1 0 1 1 0 1 1 0 55 S 183 B7 1 0 1 1 0 1 1 1 56 S 184 B8 1 0 1 1 1 0 0 0 57 S 185 B9 1 0 1 1 1 0 0 1 58 S 186 BA 1 0 1 1 1 0 1 0 59 S 187 BB 1 0 1 1 1 0 1 1 60 S 188 BC 1 0 1 1 1 1 0 0 61 S 189 BD 1 0 1 1 1 1 0 1 62 S 190 BE 1 0 1 1 1 1 1 0 63 S MYLOS Building Automation Table of 8 bit scene telegram codes 13
Contact us ABB SACE A division of ABB S.p.A. Wiring accessories, Home & Building automation Viale dell Industria, 18 20010 Vittuone (MI), Italy Tel.: +39 02 9034 1 Fax: +39 02 9034 7609 The data and illustrations are not binding. We reserve the right to modify the contents of this document on the basis of technical development of the products, without prior notice. Copyright 2012 ABB. All rights reserved. 2CSN600008D0901 www.abb.it/mylos www.abb.com from Monday to Saturday from 9.00 to 19.00