Chapter 8: Unsymmetrical Faults

Similar documents
CHAPTER 8 UNSYMMETRICAL FAULTS

Module 3 : Sequence Components and Fault Analysis

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

BEE701 POWER SYSTEM ANALYSIS

KINGS COLLEGE OF ENGINEERING Punalkulam

Fault Analysis Power System Representation

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

Module 3 : Sequence Components and Fault Analysis

Last Comments on Short-Circuit Analysis

SECTION 7: FAULT ANALYSIS. ESE 470 Energy Distribution Systems

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

In the previous chapter, attention was confined

4.10 Unbalanced fault analysis using Z BUS matrix:

Fault Calculation Methods

Fault Location in Distribution Feeders with Distributed Generation using Positive Sequence Apparent Impedance

Chapter 3 AUTOMATIC VOLTAGE CONTROL

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai QUESTION BANK V SEMESTER. EE6501-Power system Analysis

EE 451 Power System Stability

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

ECE 585 Power System Stability

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

Power system model. Olof Samuelsson. EIEN15 Electric Power Systems L2 1

AC Circuits Homework Set

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

+ ( )= with initial condition

Power Flow Analysis. The voltage at a typical bus i of the system is given in polar coordinates by

EE Branch GATE Paper 2010

ELG4125: Power Transmission Lines Steady State Operation

Power system model. Olof Samuelsson. EIEN15 Electric Power Systems L2

Dynamic simulation of a five-bus system

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

POWER SYSTEM STABILITY

Introduction to Synchronous. Machines. Kevin Gaughan

EE 3120 Electric Energy Systems Study Guide for Prerequisite Test Wednesday, Jan 18, pm, Room TBA

Chapter 9 Balanced Faults, Part II. 9.4 Systematic Fault Analysis Using Bus Impedance Matrix

NETWORK CALCULATIONS updated 11/5/13 1:02 PM

Harmonic Modeling of Networks

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department

Z n. 100 kv. 15 kv. pu := 1. MVA := 1000.kW. Transformer nameplate data: X T_pu := 0.1pu S T := 10MVA. V L := 15kV. V H := 100kV

JRE SCHOOL OF Engineering

Chapter 9: Transient Stability

Dynamics of the synchronous machine

Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations

ECEN 460 Exam 1 Fall 2018

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

Three Phase Circuits

Generators. What its all about

EE2351 POWER SYSTEM ANALYSIS

SESSION 3. Short Circuit Calculations, Unsymmetrical Faults. Leonard Bohmann, Michigan State University Elham Makram, Clemson University

Chapter 6. Induction Motors. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

EG2040 Wind Power Systems Assignment 2 - Grid Integration of Wind Power Systems

AC Source and RLC Circuits

CHAPTER 22 ELECTROMAGNETIC INDUCTION

Chapter 5 Steady-State Sinusoidal Analysis

Symmetrical Fault Current Calculations Unlv

Electrical Circuits Lab Series RC Circuit Phasor Diagram

4 Fault Calculations. Introduction 4.1. Three phase fault calculations 4.2. Symmetrical component analysis 4.3 of a three-phase network

The equivalent model of a certain op amp is shown in the figure given below, where R 1 = 2.8 MΩ, R 2 = 39 Ω, and A =

Faults on Electrical System. A Research

GATE 2010 Electrical Engineering

1 Unified Power Flow Controller (UPFC)

Transients on Integrated Power System

Apparatus Models: Transformers

IMPEDANCE and NETWORKS. Transformers. Networks. A method of analysing complex networks. Y-parameters and S-parameters

CHAPTER 2 LOAD FLOW ANALYSIS FOR RADIAL DISTRIBUTION SYSTEM

ANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER

Figure 1-44: 4-Wire Wye PT Configurations

Lecture 3: Three-phase power circuits

ELEC Introduction to power and energy systems. The per unit system. Thierry Van Cutsem

BASIC PRINCIPLES. Power In Single-Phase AC Circuit

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

Unit 21 Capacitance in AC Circuits

Chapter 8 VOLTAGE STABILITY

Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

ELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines

THREE PHASE SYSTEMS Part 1

Electromagnetic Oscillations and Alternating Current. 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3.

Transformer Fundamentals

Chapter 1W Basic Electromagnetic Concepts

Electric Circuit Theory

Transformer. Transformer comprises two or more windings coupled by a common magnetic circuit (M.C.).

7. Transient stability

Synchronous Machines

Sinusoidal Steady State Analysis (AC Analysis) Part I

LO 1: Three Phase Circuits

Improving Transient Stability of Multi-Machine AC/DC Systems via Energy-Function Method

2/7/2013. Topics. 15-System Model Text: One-Line Diagram. One-Line Diagram

Examples of Applications of Potential Functions in Problem Solving (Web Appendix to the Paper)

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

PHASOR DIAGRAM OF TRANSFORMER. Prepared By ELECTRICALBABA.COM

ELECTRICAL ENGINEERING

Two-Port Networks Admittance Parameters CHAPTER16 THE LEARNING GOALS FOR THIS CHAPTER ARE THAT STUDENTS SHOULD BE ABLE TO:

Lesson 17: Synchronous Machines

Transcription:

Chapter 8: Unsymmetrical Faults Introduction The sequence circuits and the sequence networks developed in the previous chapter will now be used for finding out fault current during unsymmetrical faults. Three Types of Faults Calculation of fault currents Let us make the following assumptions: The power system is balanced before the fault occurs such that of the three sequence networks only the positive sequence network is active. Also as the fault occurs, the sequence networks are connected only through the fault location. The fault current is negligible such that the pre-fault positive sequence voltages are same at all nodes and at the fault location. All the network resistances and line charging capacitances are negligible. All loads are passive except the rotating loads which are represented by synchronous machines. Based on the assumptions stated above, the faulted network will be as shown in Fig. 8.1 where the voltage at the faulted point will be denoted by V f and current in the three faulted phases are I fa, I fb and I fc. We shall now discuss how the three sequence networks are connected when the three types of faults discussed above occur. Fig. 8.1 Representation of a faulted segment. 145

Single-Line-to-Ground Fault Let a 1LG fault has occurred at node k of a network. The faulted segment is then as shown in Fig. 8.2 where it is assumed that phase-a has touched the ground through an impedance Z f. Since the system is unloaded before the occurrence of the fault we have (8.1) Fig. 8.2 Representation of 1LG fault. Also the phase-a voltage at the fault point is given by From (8.1) we can write (8.2) (8.3) Solving (8.3) we get This implies that the three sequence currents are in series for the 1LG fault. Let us denote the zero, positive and negative sequence Thevenin impedance at the faulted point as Z kk0, Z kk1 and Z kk2 respectively. Also since the Thevenin voltage at the faulted phase is V f we get three sequence circuits that are similar to the ones shown in Fig. 7.7. We can then write (8.4) (8.5) Then from (8.4) and (8.5) we can write Again since (8.6) We get from (8.6) 146

The Thevenin equivalent of the sequence network is shown in Fig. 8.3. (8.7) Fig. 8.3 Thevenin equivalent of a 1LG fault. Example 8.1 A three-phase Y-connected synchronous generator is running unloaded with rated voltage when a 1LG fault occurs at its terminals. The generator is rated 20 kv, 220 MVA, with subsynchronous reactance of 0.2. Assume that the subtransient mutual reactance between the windings is 0.025. The neutral of the generator is grounded through a 0.05 reactance. The equivalent circuit of the generator is shown in Fig. 8.4. We have to find out the negative and zero sequence reactances. Fig. 8.4 Unloaded generator of Example 8.1. Since the generator is unloaded the internal emfs are Since no current flows in phases b and c, once the fault occurs, we have from Fig. 8.4 147

Then we also have From Fig. 8.4 and (7.34) we get Therefore From (7.38) we can write Z1 = j ω ( L s + M s ) = j 0.225. Then from Fig. 7.7 we have Also note from (8.4) that Therefore from Fig. 7.7 we get Comparing the above two values with (7.37) and (7.39) we find that Z 0 indeed is equal to j ω ( L s - 2 M s ) and Z2 is equal to j ω ( L s + M s ). Note that we can also calculate the fault current from (8.7) as 148

Line-to-Line Fault The faulted segment for an L-L fault is shown in Fig. 8.5 where it is assumed that the fault has occurred at node k of the network. In this the phases b and c got shorted through the impedance Z f. Since the system is unloaded before the occurrence of the fault we have (8.8) Fig. 8.5 Representation of L-L fault. Also since phases b and c are shorted we have (8.9) (8.10) Therefore from (8.8) and (8.9) we have We can then summarize from (8.10) (8.11) Therefore no zero sequence current is injected into the network at bus k and hence the zero sequence remains a dead network for an L-L fault. The positive and negative sequence currents are negative of each other. Now from Fig. 8.5 we get the following expression for the voltage at the faulted point Again (8.12) 149

(8.13) (8.14) (8.15) Moreover since I fa0 = I fb0 = 0 and I fa1 = - I fb2, we can write Therefore combining (8.12) - (8.14) we get (8.16) Equations (8.12) and (8.15) indicate that the positive and negative sequence networks are in parallel. The sequence network is then as shown in Fig. 8.6. From this network we get Example 8.2 Fig. 8.6 Thevenin equivalent of an LL fault. Let us consider the same generator as given in Example 8.1. Assume that the generator is unloaded when a bolted ( Z f = 0) short circuit occurs between phases b and c. Then we get from (8.9) I fb = - I fc. Also since the generator is unloaded, we have I fa = 0. Therefore from (7.34) we get Also since V bn = V cn, we can combine the above two equations to get 150

Then We can also obtain the above equation from (8.16) as Also since the neutral current I n is zero, we can write V a = 1.0 and Hence the sequence components of the line voltages are Also note that which are the same as obtained before. 151

Double- Line -to Ground Fault The faulted segment for a 2LG fault is shown in Fig. 8.7 where it is assumed that the fault has occurred at node k of the network. In this the phases b and c got shorted through the impedance Z f to the ground. Since the system is unloaded before the occurrence of the fault we have the same condition as (8.8) for the phase-a current. Therefore (8.17) Also voltages of phases b and c are given by Fig. 8.7 Representation of 2LG fault. Therefore (8.18) (8.19) We thus get the following two equations from (8.19) (8.20) Substituting (8.18) and (8.20) in (8.21) and rearranging we get (8.21) Also since I fa = 0 we have (8.22) The Thevenin equivalent circuit for 2LG fault is shown in Fig. 8.8. From this figure we get (8.23) 152

(8.24) The zero and negative sequence currents can be obtained using the current divider principle as (8.25) (8.26) Fig. 8.8 Thevenin equivalent of a 2LG fault. Example 8.3 Let us consider the same generator as given in Examples 8.1 and 8.2. Let us assume that the generator is operating without any load when a bolted 2LG fault occurs in phases b and c. The equivalent circuit for this fault is shown in Fig. 8.9. From this figure we can write Fig. 8.9 Equivalent circuit of the generator in Fig. 8.4 for a 2LG fault in phases b and c. 153

Combining the above three equations we can write the following vector-matrix form Solving the above equation we get Hence We can also obtain the above values using (8.24)-(8.26). Note from Example 8.1 that Then Now the sequence components of the voltages are Also note from Fig. 8.9 that and V b = V c = 0. Therefore 154

which are the same as obtained before. FAULT CURRENT COMPUTATION USING SEQUENCE NETWORKS In this section we shall demonstrate the use of sequence networks in the calculation of fault currents using sequence network through some examples. Example 8.4 Consider the network shown in Fig. 8.10. The system parameters are given below Generator G : 50 MVA, 20 kv, X" = X1 = X2 = 20%, X0 = 7.5% Motor M : 40 MVA, 20 kv, X" = X1 = X2 = 20%, X0 = 10%, X n = 5% Transformer T1 : 50 MVA, 20 kv Δ /110 kvy, X = 10% Transformer T2 : 50 MVA, 20 kv Δ /110 kvy, X = 10% Transmission line: X1 = X2 = 24.2 Ω, X0 = 60.5 Ω We shall find the fault current for when a (a) 1LG, (b) LL and (c) 2LG fault occurs at bus-2. Fig. 8.10 Radial power system of Example 8.4. Let us choose a base in the circuit of the generator. Then the impedances of the generator are: The impedances of the two transformers are The MVA base of the motor is 40, while the base MVA of the total circuit is 50. Therefore the impedances of the motor are 155

For the transmission line Therefore Let us neglect the phase shift associated with the Y/ Δ transformers. Then the positive, negative and zero sequence networks are as shown in Figs. 8.11-8.13. Fig. 8.11 Positive sequence network of the power system of Fig. 8.10. Fig. 8.12 Negative sequence network of the power system of Fig. 8.10. Fig. 8.13 Zero sequence network of the power system of Fig. 8.10. From Figs. 8.11 and 8.12 we get the following Y bus matrix for both positive and negative sequences 156

Inverting the above matrix we get the following Z bus matrix Again from Fig. 8.13 we get the following Y bus matrix for the zero sequence Inverting the above matrix we get Hence for a fault in bus-2, we have the following Thevenin impedances Alternatively we find from Figs. 8.11 and 8.12 that (a) Single-Line-to-Ground Fault : Let a bolted 1LG fault occurs at bus-2 when the system is unloaded with bus voltages being 1.0. Then from (8.7) we get Also from (8.4) we get Also I fb = I fc = 0. From (8.5) we get the sequence components of the voltages as 157

Therefore the voltages at the faulted bus are (b) Line-to-Line Fault : For a bolted LL fault, we can write from (8.16) Then the fault currents are Finally the sequence components of bus-2 voltages are Hence faulted bus voltages are (c) Double-Line-to-Ground Fault : Let us assumes that a bolted 2LG fault occurs at bus-2. Then Hence from (8.24) we get the positive sequence current as The zero and negative sequence currents are then computed from (8.25) and (8.26) as 158

Therefore the fault currents flowing in the line are Furthermore the sequence components of bus-2 voltages are Therefore voltages at the faulted bus are Example 8.5 Let us now assume that a 2LG fault has occurred in bus-4 instead of the one in bus-2. Therefore Also we have Hence Also 159

Therefore the fault currents flowing in the line are We shall now compute the currents contributed by the generator and the motor to the fault. Let us denote the current flowing to the fault from the generator side by I g, while that flowing from the motor by I m. Then from Fig. 8.11 using the current divider principle, the positive sequence currents contributed by the two buses are Similarly from Fig. 8.12, the negative sequence currents are given as Finally notice from Fig. 8.13 that the zero sequence current flowing from the generator to the fault is 0. Then we have Therefore the fault currents flowing from the generator side are and those flowing from the motor are 160

It can be easily verified that adding I g and I m we get I f given above. In the above two examples we have neglected the phase shifts of the Y/ Δ transformers. However according to the American standard, the positive sequence components of the high tension side lead those of the low tension side by 30, while the negative sequence behavior is reverse of the positive sequence behavior. Usually the high tension side of a Y/ Δ transformer is Y-connected. Therefore as we have seen in Fig. 7.16, the positive sequence component of Y side leads the positive sequence component of the Δ side by 30 while the negative sequence component of Y side lags that of the Δ side by 30. We shall now use this principle to compute the fault current for an unsymmetrical fault. Let us do some more examples Example 8.6 Let us consider the same system as given in Example 8.5. Since the phase shift does not alter the zero sequence, the circuit of Fig. 8.13 remains unchanged. The positive and the negative sequence circuits must however include the respective phase shifts. These circuits are redrawn as shown in Figs. 8.14 and 8.15. Note from Figs. 8.14 and 8.15 that we have dropped the 3 α vis-à-vis that of Fig. 7.16. This is because the impedances remain unchanged when referred to the either high tension or low tension side of an ideal transformer. Therefore the impedances will also not be altered. Fig. 8.14 Positive sequence network of the power system of Fig. 8.10 including transformer phase shift. Fig. 8.15 Negative sequence network of the power system of Fig. 8.10 including transformer phase shift. Since the zero sequence remains unaltered, these currents will not change from those computed in Example 8.6. Thus 161

and Now the positive sequence fault current from the generator I ga1, being on the Y-side of the Y/ Δ transformer will lead I ma1 by 30. Therefore Finally the negative sequence current I ga2 will lag I ma2 by 30. Hence we have Therefore Also the fault currents flowing from the motor remain unaltered. Also note that the currents flowing into the fault remain unchanged. This implies that the phase shift of the Y/ Δ transformers does not affect the fault currents. Example 8.7 Let us consider the same power system as given in Example 1.2, the sequence diagrams of which are given in Figs. 7.18 to 7.20. With respect to Fig. 7.17, let us define the system parameters as: Generator G1 : 200 MVA, 20 kv, X" = 20%, X0 = 10% Generator G 2 : 300 MVA, 18 kv, X" = 20%, X0 = 10% Generator G3 : 300 MVA, 20 kv, X " = 25%, X0 = 15% Transformer T1 : 300 MVA, 220Y/22 kv, X = 10% Transformer T2 : Three single-phase units each rated 100 MVA, 130Y/25 kv, X = 10% Transformer T3 : 300 MVA, 220/22 kv, X = 10% Line B-C : X1 = X2 = 75 Ω, X0 = 100 Ω Line C-D : X1 = X2 = 75 Ω, X0 = 100 Ω Line C-F : X1 = X2 = 50 Ω, X0 = 75 Ω 162

Let us choose the circuit of Generator 3 as the base, the base MVA for the circuit is 300. The base voltages are then same as those shown in Fig. 1.23. Per unit reactances are then computed as shown below. Generator G1 : Generator G2 :, X0 = 0.15, X0 = 0.0656 Generator G3 :, X0 = 0.15 Transformer T 1 : Transformer T2 : Transformer T3 : Line B-C : Line C-D :,, Line C-F :, Neglecting the phase shifts of Y/ Δ connected transformers and assuming that the system is unloaded, we shall find the fault current for a 1LG fault at bus-1 (point C of Fig. 7.17). From Figs. 7.18 and 7.19, we can obtain the positive and negative sequence Thevenin impedance at point C as (verify) X1 = X2 = j 0.2723 Similarly from Fig. 7.20, the Thevenin equivalent of the zero sequence impedance is X0 = j 0.4369 Therefore from (8.7) we get Then the fault current is I fa = 3 I fa0 = 3.0565. 163