Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha

Similar documents
The energy performance of an airflow window

STUDY OF A PASSIVE SOLAR WINTER HEATING SYSTEM BASED ON TROMBE WALL

DYNAMIC INSULATION APPLIED TO THE RESIDENTIAL BUILDING (PART 2) Numerical Evaluation of Thermal Insulation Effect on Air Supply Window System

Aalborg Universitet. Publication date: Document Version Publisher's PDF, also known as Version of record

Thermal performance of the new hall of the historical hospital in Florence

Transient Analysis of the Buoyancy Driven Flow in a Passive Solar System for Indoor Heating

AR/IA 241 LN 231 Lecture 4: Fundamental of Energy

Effect of Installing a Curved Venetian Blind to the Glass Window on Heat Transmission

Computer Evaluation of Results by Room Thermal Stability Testing

ADVANCED ROOF COATINGS: MATERIALS AND THEIR APPLICATIONS

Double-Skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of Direct Solar Radiation

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

DEVELOPMENT OF COOLING LOAD TEMPERATURE DIFFERENTIAL VALUES FOR BUILDING ENVELOPES IN THAILAND

Cooling of Electronics Lecture 2

The Electrodynamics of a Pair of PV Modules with Connected Building Resistance

Thermodynamics I Spring 1432/1433H (2011/2012H) Saturday, Wednesday 8:00am - 10:00am & Monday 8:00am - 9:00am MEP 261 Class ZA

STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION

TREES Training for Renovated Energy Efficient Social housing

2-D CFD analysis of passenger compartment for thermal comfort and ventilation

Supply air window PAZIAUD : Comparison of two numerical models for integration in thermal building simulation

CHAPTER 7 NUMERICAL MODELLING OF A SPIRAL HEAT EXCHANGER USING CFD TECHNIQUE

Performance Assessment of PV/T Air Collector by Using CFD

Chapter 1: 20, 23, 35, 41, 68, 71, 76, 77, 80, 85, 90, 101, 103 and 104.

Heat Transfer: Physical Origins and Rate Equations. Chapter One Sections 1.1 and 1.2

Parametric Study on the Effect of a Domestic Wind Catcher-Solar Chimney System for Arid Regions

CAE 331/513 Building Science Fall 2016

Validation of DNS techniques for dynamic combined indoor air and constructions simulations using an experimental scale model

Patrick H. Oosthuizen and J.T. Paul Queen s University Kingston, ON, Canada

Natural Ventilation. CFD modelling of a double-skin facade. Huw Birch. Supervisor: Abigail Hathway

A Numerical Investigation on Active Chilled Beams for Indoor Air Conditioning

Natural Convection Heat Loss from A Partly Open Cubic Enclosure Timothy N Anderson 1,a * and Stuart E Norris 2,b

Building heat system sizing

How to evaluate daylight. Initiated by the VELUX Group

Modelling and Experimental Validation Possibilities of Heat Transfer Room Model

Solar Flat Plate Thermal Collector

HIGHLY INSULATING AEROGEL GLAZING

SIMULATION OF THE CONVECTIVE HEAT T W T TRANSFER AND WORKING TEMPERATURE FIELD OF A PHOTOVOLTAIC MODULE USING COMSOL MULTIPHYSICS

Experimental and numerical investigations of heat transfer and thermal efficiency of an infrared gas stove

Solar Control in Traditional Architecture, Potentials for Passive Design in Hot and Arid Climate

Definitions of U- and g-value in case of double skin facades or vented windows

EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS

Performance of Fixed Horizontal Shading Devices in South Facing Residential Buildings in Dhaka

Occupant Behavior Related to Space Cooling in a High Rise Residential Building Located in a Tropical Region N.F. Mat Hanip 1, S.A. Zaki 1,*, A. Hagish

CONICAL SOLAR COOKER

Design strategy for Low e windows with effective insulation

Study on Reusing Abandoned Chimneys as Solar Chimneys to Induce Breeze in Residential Areas

MICROENCAPSULATED PHASE CHANGE MATERIALS (PCM) FOR BUILDING APPLICATIONS

Energy flows and modelling approaches

Study on Performance of Anisotropic Materials of Thermal Conductivity

Simulation and Modification of a Composite Trombe Wall to Adapt to the Climate in Victoria, Canada

EE-489 Modeling Project: Behavior of the. Temperature Changes in a Room

FUNDAMENTALS OF HVAC

Mathematical Modelling of Ceramic Block Heat Transfer Properties

Simplified Collector Performance Model

Simulation of Free Convection with Conjugate Heat Transfer

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND

Glazing selection for solar design

Thermal Comfort; Operative Temperature in the Sun

Optimization of the Air Gap Spacing In a Solar Water Heater with Double Glass Cover

Project 2. Introduction: 10/23/2016. Josh Rodriguez and Becca Behrens

Solar Radiation 230 BTU s per Hr/SF. Performance Glazing Coatings, Layers & Gases

Heat Transfer and Natural Ventilation Airflow Rates from Single-sided Heated Solar Chimney for Buildings

ARCH 348 BUILDING AND ENVIRONMENTAL SYSTEMS

Drying out capacity and snow melting risk for ventilated wooden roofs - a parameter study

Chapter 5 MATHEMATICAL MODELING OF THE EVACATED SOLAR COLLECTOR. 5.1 Thermal Model of Solar Collector System

Atrium assisted natural ventilation of multi storey buildings

DEFINING THE PERFORMANCE OF THE DOUBLE SKIN FAÇADE WITH THE USE OF THE SIMULATION MODEL

THERMAL PERFORMANCE EVALUATION OF AN INNOVATIVE DOUBLE GLAZING WINDOW

EFFECT OF INTERNAL LONG WAVE RADIATION AND CONVECTION ON FENESTRATION SIMULATION

Experimental investigation

Thermal Field in a NMR Cryostat. Annunziata D Orazio Agostini Chiara Simone Fiacco

Modeling night-time ventilation in Stanford s Y2E2 building

A SIMPLE MODEL FOR THE DYNAMIC COMPUTATION OF BUILDING HEATING AND COOLING DEMAND. Kai Sirén AALTO UNIVERSITY

USEFUL WASTE HEAT OF VENTILATED PV-MODULES: PHYSICAL MODELLING AND VALIDATION RESULTS. Lucerne, Switzerland. to

CFD MODELLING OF CONVECTIVE HEAT TRANSFER FROM A WINDOW WITH ADJACENT VENETIAN BLINDS

MOISTURE TRANSPORT THROUGH

Computational Modelling of the Impact of Solar Irradiance on Chemical Degradation of Painted Wall Hangings in an Historic Interior

AP PHYSICS 2 WHS-CH-14 Heat Show all your work, equations used, and box in your answers! 1 108kg

HEAT TRANSFER CAPABILITY OF A THERMOSYPHON HEAT TRANSPORT DEVICE WITH EXPERIMENTAL AND CFD STUDIES

Increasing Energy Efficiency of HVAC Systems in Buildings Using Phase Change Material

Numerical study of the use of photovoltaic- Trombe wall in residential buildings in Tibet

BRE Client Report. Calculation of summertime solar shading performance for MicroLouvre. Prepared for: Smartlouvre. BRE Watford, Herts WD25 9XX

Simulation and improvement of the ventilation of a welding workshop using a Finite volume scheme code

Introduction HMTTSC Nikolay Smirnov 1,*, Vladimir Tyutikov 1, and Vadim Zakharov 1

Natural Convection from Horizontal Rectangular Fin Arrays within Perforated Chassis

not for commercial-scale installations. Thus, there is a need to study the effects of snow on

Numerical Study of PCM Melting in Evacuated Solar Collector Storage System

CFD-SIMULATIONS OF TRANSPARENT COATED AND GAS-FILLED FACADE PANELS

1 BAKER HOUSE DINING: LIGHTING DIAGNOSTIC

Chapter 22: Uses of Solar Energy

Benefits and Costs of Radiant Barrier and Roof Insulation Used under Tropical Climate

A Numerical Analysis of Indoor Thermal Environment and Human Thermophysiological Responses under Natural Ventilation S. Iizuka 1,*, T. Sakoi 2, T. Sai

announcements 4/17/08

Orientation of Building

Faculty of Technology and Science Department of Physics and Electrical Engineering. Helena Johansson. Nocturnal cooling

Fundamentals of WUFI-Plus WUFI Workshop NTNU / SINTEF 2008

Solar Radiation Protections on Façades: A Case Study in a Hot Semi-Humid Climate

SAMPLE ASSESSMENT TASKS PHYSICS ATAR YEAR 11

Study on Stack Effect of Stairwell by Numerical Model of Leakage Flow through Gap of Door

Baker House Dining Room: Thermal Balance Report. + Q c. + Q v. + Q s. + Q e. + Q heating. + Q appliances. =Q appliances,21h Q appliances, x H

Transcription:

Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha Abstract This paper reports the numerical and experimental performances of Double Glass Wall are investigated. Two configurations were considered namely, the Double Clear Glass Wall (DCGW) and the Double Translucent Glass Wall (DTGW). The coupled governing equations as well as boundary conditions are solved using the finite element method (FEM) via COMSOL TM Multiphysics. Temperature profiles and flow field of the DCGW and DTGW are reported and discussed. Different constant heat fluxes were considered as 400 and 800 W.m -2 the corresponding initial condition temperatures were 30.5 and 38.5ºC respectively. The results show that the simulation results are in agreement with the experimental data. Conclusively, the model considered in this study could reasonable be used simulate the thermal and ventilation performance of the DCGW and DTGW configurations. Keywords Thermal simulation, Double Glass Wall, Velocity field. I. INTRODUCTION OWADAYS the buildings have high energy consumption Nof air conditioning systems because the tropical climate of Thailand. One solution is the reduction of heat transfer into the habitants. An important part of building energy saving comes from mirror material types and its configurations. Thus, many researchers [1]-[4] try to find the new design with well energy saving. In fact, various double pane configurations and theoretical and experimental studies are available [5]-[7] and more details for daylighting effect reported the Double Clear Glass Wall (DCGW) and Double Translucent Glass Wall (DTGW) developed by Faculty of Architecture and Design of King Mongkut s University of Technology North Bangkok (KMUTNB) [8]. Experimental results were showed the average indoor illuminance of DTGW and DCGW was higher than the standard illuminance by about 1,500 lux and 2,000 lux, respectively. The air flow rate and number of air change by about 0.0025-0.004 m 3 /s (9-14.4 m 3 /hr) and 2-14 ACH, respectively. This paper aims to conduct experimental and numerical simulation to study the performance of the Double Clear Glass Wall (DCGW) and Double Translucent Glass Wall (DTGW). II.EXPERIMENT SETUP The small houses for experiment are shown in Fig. 1. The DCGW put to comparison with DTGW. The sizing of the T. A. is with the Department of Architecture, Faculty of Architecture and Design, King Mongkut s University of Technology North Bangkok, 1518 Pracharat 1 Road, Wongsawang, Bangsue, Bangkok 10800, Thailand (phone: +66 2 586 7313; fax: +66 2 587 4350; e-mail: thanaa@kmutnb.ac.th). DCGW is same dimensions with DTGW and sizing was 0.14 x 0.60 x 2.14 m. The DCGW is made of double layers consisted of clear glass pane 0.60 x 2.00 x 0.06 m with an air gap and openings located at the bottom (room side clear glass pane) and at the top (ambient side). The size of openings was 0.14 x 0.60 m² and 0.14 m air gap. The different of DTGW is translucent glass installed outer side. They were integrated into the south facing of two small houses. The sizings of the room were 1.50 x 1.50 x 2.40 m. The wall and ceiling were built by gypsum board. They were located on the top floor of 4th floor commercial building at the Phoem Sin Road, Khlong Thanon, Sai Mai, Bangkok, Thailand. Two types of the wall are considered as follows: 1) Double Clear Glass Wall (DCGW) 2) Double Translucent Glass Wall (DTGW) The different materials used for constructing the models are as follow: 1) Clear glass (w) 10 cm, (L) 200 cm, 6 mm thk. 2) Translucent glass (w) 10 cm, (L) 200 cm, 6 mm thk. Fig. 2 showed the measuring positions of the experimental set-up. Fig. 1 The double glass wall models in the experiment (DCGW and DTGW) III. SIMULATION MODEL To simulate the thermal performance of double glass wall we used commercial software, COMSOL TM Multiphysics. The analytical model is shown in Fig. 3 (a). In order to obtain a good approximation, a fine mesh is specified in the sensitive areas as shown in Fig. 3 (b). 1184

Fig. 2 The position of thermocouples of the DCGW and DTGW To reduce complexity of the problem, several assumptions have been made as follows: 1) Heat transfer is considered as steady state condition. 2) Heat transfer occurs in two-dimension along the cavity. 3) Thermal properties and physical properties are constants. 4) Air leakage effect is negligible. 5) Dust and dirt in the cavity are negligible. 6) The other walls, floor and roof are insulated. Fig. 3 Schematic diagram of the DCGW and DTGW A. Heat Transfer Equation The governing equations for the heat transfer of the clear glass pane are given as: (-kt) = Q-C p u T (1) where: k is thermal conductivity of material [W m -1 K -1 ], T is Temperature [K], Q is Heat source, (Q = 0), is Density of material [kg/m 3 ], C p is Specific heat capacity of material [kj kg -1 K -1 ], u is velocity of air [m s -1 ] B. Thermal Boundary Conditions 1) At solid surfaces; the walls, floor and roof are considered insulated; the thermal boundary condition is therefore: n (kt -C p Tu) = 0 (2) At the surface of the clear glass pane in the left side which gets sunlight, the boundary condition at this surface is considered constant surface heat flux. In this study we used various heat fluxes for simulations namely q = 400, 800 W/m 2. 2) Initial condition; furthermore, the temperature of air at the inlet of cavity is assumed to be uniform: (add to nomenclature not included) It varies depending on the 1185

intensity of considered incident heat flux considered; the values considered are T 0 =30.5 C for q =400 W/m 2, T 0 =38.5 C for q =800 W/m 2. In fact the initial temperature considered (27.5 C) is the average ambient temperature throughout the year in Thailand [9]. 3) At openings; the boundaries for heat transfer analysis of inlet and outlet are considered a convective flux boundary condition: n (-kt)=0 (3) C.Flow Field Equation The Navier-Stokes equation used to represent the air flow in the cavity. Using standard symbols, the governing equations describing the flow field of air are given as follows: Continuity equation: Momentum equation: where: u = 0 F y is volume force - y-dir [N/m 3 ], P is pressure [Pa], is dynamic viscosity [Pa s], g is gravitational constant, = 9.81 ms -2, is coefficient of thermal expansion, = 110-4 1/K, T is reference temperature, T = T 0 K D.Boundary Condition for Flow Field The outer surface of walls, floor and roof, a no slip boundary condition is applied for the momentum equations: u = 0 The velocity of air at the inlet of cavity uniform. In the simulation the value used is u u pi u u F y u = 0.2 m s -1 IV. RESULTS AND DISCUSSION Testing performance of DCGW and DTGW was conducted during November to December. The air gap space of DCGW and DTGW were fixed at 0.14 m. The opening air vents at the ambient side and the room sides are of equal size (0.14 m 0.60 m). The total surface area of each was 1..284 m 2. The data analysis required reaching a relative study state. A. Temperature Profiles 1) Experimental Results Temperature profile at different measured positions of the DCGW and DTGW are shown in Figs. 4 and 5 respectively. As expected and due to the effect of external Translucent glass of DTGW, the temperatures of various measured positions of the DTGW are lower than those of the DCGW configuration. g T T T F F y (4) (5) (6) (7) is considered as (8) Obviously, the temperature difference depends on the prevailing conditions. The temperature of the inner surface of clear glass pane outside (T g2 ) and the inner surface of clear glass pane inside (T g4 ) are much higher when compared to those of DTGW. This is due to the contribution of heat associated with the incident solar radiation through the clear glass slats. Consequently, the temperature of room-side gypsum board of the DCGW is 1 to 2 C higher than that of the DTGW. Fig. 4 Hourly variation of measured temperature of DCGW Fig. 5 Hourly variation of measured temperature of and DTGW 2) Simulation Results Temperature contour across the façade wall at various constant heat fluxes is shown in Fig. 6. The temperature within the air gap space increases with the increase of incoming incident heat flux obviously. The region close to the top has a high temperature than elsewhere within the air gap space. Figs. 7 and 8 show different positions of temperature across the air gap. It could be observed that the temperature lowers along the propagation direction due to the skin depth heating effect. The temperature of DCGW is much higher when compared to those of DTGW. This due to the contribution of heat associated with the incident heat flux through the clear glass slats. (See Table I) 1186

Fig. 6 Simulated result of temperature contour of DCGW and DTGW (a) q"=400 W. m -2, T= 30.5 C, u= 0.2 m.s -1 (b) q" "=800 W. m -2, T= 38.5 C, u= 0.2 m.s -1 Fig. 7 Simulated result across the air gap temperature of DCGW and DTGW, q"=400 W. m -2, T= 30.5 C, u= 0.2 m.s -1 Fig. 8 Simulated result across the air gap temperature of DCGW and DTGW, q"=800 W. m -2, T= 38.5 C, u= 0.2 m.s -1 TABLE I PROPERTIES OF CONSTRUCTION MATERIALS Thermal Thermal Thermal Specific Materials Conductivity Absorptivity Emissivity Heat Density W/m K L g -1 cm -1 kj/kg K kg/m³ Clear glass 0.344 0.13 0.89 1.41 2487 B. Air Velocity through the Air Gap 1) Experimental Results The DCGW and DTGW are heated by solar radiation and the stored heat in their cavity is utilized to induce ventilation. The gap heated surface of both DCGW and DTGW generates a natural convection current that withdraws air from the room and extracts it to the ambient at the outlet opening. As a consequence outdoor air enters the room through the room openings making the indoor more comfortable. Accordingly, the higher is the solar intensity, the greater is the temperature difference between air gap and room and hence, the larger is the induced airflow rate. Fig. 9 showed a comparison between induced volume airflow rate of DCGW and DTGW. Obviously, the airflow rate inducedd by the DCGW is much higher than that of DTGW as more heat is admitted into the air gap. 1187

2) Simulation Results Obviously, the temperature gradient across the height air gap and increased constant heat flux. The temperature of heat flux, the different of materials and to protect significantly increased quasi linearly velocity from the inlet up to the outlet air of the air gap. Air temperature within the air gap space also increased following the constant heat flux but mainly the higher rate of air temperature was observed. Fig. 10 showed the velocity vector within the air gap with for the different cases, considered. The simulation results of velocity across the air gap appear good agreement with velocity vector distribution. Also the simulation models of DCGW showed significant gradient of air gap temperature height than that DTGW. It could be observed the buoyancy force increases as a result from direct lighting transmitted through clear glass slats leading to higher air velocity in the air gap as showed in Figs. 11 and 12. Fig. 9 Hourly variations of volume flow rate and DCGW and DTGW solar radiation of C.Comparison between Experimental and Simulations Result Tables II, III showed a comparison of surface temperature of materials across the air gap space between experimental and simulations result. It can be seen that the simulation results are close to the data obtained from the experiments. The difference between the simulated and measured profiles observed varies between 3 to 7%. This is mainly due to the effect of inlet air temperature considered constant during each heat fluxes and velocity in our program. V.CONCLUSION An experimental and numerical study of the thermal performance of Double Clear Glass is presented. Experimental results conducted using a configuration of 2.14 m high and 14 cm air gap are in good agreement with those obtained by using the finite element method (FEM) via COMSOL TM Multiphysics. Therefore the computer program can be used for estimating the performance of the system toward an application design of DTGW with different types of the wall. This study confirmed that DTGW is highly suitable for hot countries: it can reduce heat gain through glass walls into the house by developing air circulation, which can help improve the thermal comfort of residents too. The proposed DTGW was also economical due to low cost of materials used. The use of DTGW can also reduce the usage of fans due to induced ventilation. During daytime when residents are away from their homes, indoor temperature will be much lower which may help reducing demand on electrical energy for air- will be moderate. conditioning as evening indoor conditions TABLE II MEASURED AND SIMULATED THE POSITION OF SURFACE TEMPERATURES OF MATERIALS OF THE DCGW AND DTGW: Q"=400 W. M -2,T=30.5C,U=0.2 M.S -1 DCGW g1 g2 g3 g4 Tout Tf Tin Experimental 33.57 33.55 33.13 33.32 36.5 32.98 32.5 Simulation 31.66 31.66 31.55 31.55 32.58 31.57 30.5 Absolute deviation -1.91-1.89-1.58-1.77-3.92-1.41-2.00 Relative deviation -6% -6% -5% -5% -11% -4% -6% DTGW g1 g2 g3 g4 Tout Tf Tin Experimental (16-Feb-2012) 33.5 33.45 31.9 31.85 33.45 31.95 31.07 Simulation 31.65 31.65 31.54 31.54 32.59 31.56 30.5 Absolute deviation -1.85-1.80-0.36-0.31-0.86-0.39-0.57 Relative deviation -6% -5% -1% -1% -3% -1% -2% TABLE III MEASURED AND SIMULATED THE POSITION OF SURFACE TEMPERATURES OF MATERIALS OF THE DCGW AND DTGW: Q"=800 W. M -2,T=38.5C,U=0.2 M.S -1 DCGW g1 g2 g3 g4 Tout Tf Tin Experimental 41.91 42.15 43.67 43.92 41.78 40.29 39.3 Simulation 40.95 40.95 40.74 40.74 42.79 40.78 38.5 Absolute deviation -0.96-1.20-2.93-3.18 1.01 0.49-0.80 Relative deviation -2% -3% -7% -7% 2% 1% -2% DTGW g1 g2 g3 g4 Tout Tf Tin Experimental (16-Feb-2012) 43.5 43.34 41.94 41.79 40.15 39.5 39.26 Simulation 40.94 40.94 40.72 40.72 42.82 40.76 38.5 Absolute deviation -2.56-2.40-1.22-1.07 2.67 1.26-0.76 Relative deviation -6% -6% -3% -3% 7% 3% -2% 1188

Fig. 10 Simulated result the flow field (arrows) of the velocity in the air gap of DCGW and DTGW (a) q"=400 W. m -2, T= 30.5 C, u= 0.2 m.s -1 (b) q"=800 W. m -2, T= 38.5 C, u= 0.2 m.s -1 Fig. 11 Simulated result of the velocity in the air gap of DCGW and DTGW q"=400 W. m -2, T= 30.5 C, u= 0.2 m.s -1 Fig. 12 Simulated result of the velocity in the air gap of DCGW and DTGW q"=800 W. m -2, T= 38.5 C, u= 0.2 m.s -1 ACKNOWLEDGMENT This Research was supported by the Faculty of Architecture and Design of KMUTNB. (ArchR&C 01/56). The authors are grateful to Center of Excellence in Sustainable Energy and Environment (SEE) of Thaksin University (Phatthalung Campus) for the use of COMSOL TM Multiphysics. REFERENCES [1] J. Khedari, C. Pongsathirat, W. Puangsombut, J. Hirunlabh, Experimental performance of a partially-glazed Modified Trombe Wall, The International Journal of Ambient Energy 2005;26:27-36. [2] P. Chantawong, J. Hirunlabh, B. Zeghmati, J. Khedari, S. Teekasap, M. M Win, Investigation on thermal performance of solar chimney wall, Solar Energy 2006;80:288-97. [3] W. Puangsombut, Experimental performance of solar chimney window on school building Research and Development Journal of The Engineering Institute of Thailand under H.M. The King s Patronage 2009;20:70-5. [4] T. Ananacha, Reduction of Heat Accumulated in attic by PV Ventilation for Energy Consumption Reduction of Air Conditioner for housing", The 19th Sarasart: Architectural Journal the Faculty of Architecture, May 2, 2014, Chulalongkorn University. [5] T. Ananacha, W. Puangsombut, J. Hirunlabh, Shading Effects on the winter of the Thai Modern Façade Wall, Proceedings of 3th International Conference on Sustainable Energy and Green Architect (SEGA), Bangkok, Thailand; 2012. [6] T. Ananacha, W. Puangsombut, J. Hirunlabh and J. Khedari, "Field Investigation of the Thermal Performance of the Thai Modern Façade 1189

Wall", The International Journal of Ventilation, Vol. 12, No 3, December 2013, pp. 223-234. [7] T. Ananacha, W. Puangsombut, J. Hirunlabh and J. Khedari, "Daylighting and Thermal Performance of Thai Modern Façade Wall", Energy Procedia, Vol. 52 (2014), pp. 271-277. [8] T. Ananacha, Daylighting and Thermal Performance of Double Glass Wall International Conference on Advances in Science & Technology (ICAST), Chonburi, Thailand; 2014. [9] W. Maneesarn, Global Solar Radiation and the climate statistics 30 year period of Thai Meteorological Data: No 551.582-02-2538, ISBN:974-7567-25-3; September 1995 1190