INSTRUCTOR: PM DR MAZLAN ABDUL WAHID

Similar documents
INTRODUCTION: Shell and tube heat exchangers are one of the most common equipment found in all plants. How it works?

Chapter 11: Heat Exchangers. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Overall Heat Transfer Coefficient

Introduction to Heat and Mass Transfer

23 1 TYPES OF HEAT EXCHANGERS

c Dr. Md. Zahurul Haq (BUET) Heat Exchangers: Rating & Sizing - I ME 307 (2017) 2 / 32 T666

T718. c Dr. Md. Zahurul Haq (BUET) HX: Energy Balance and LMTD ME 307 (2018) 2/ 21 T793

Multiple pass and cross flow heat exchangers

INSTRUCTOR: PM DR MAZLAN ABDUL WAHID

PROBLEM The heat rate, q, can be evaluated from an energy balance on the cold fluid, 225 kg/h J. 3600s/h

INSTRUCTOR: PM DR MAZLAN ABDUL WAHID

HEAT EXCHANGER. Objectives

Heat Exchanger Design

NUMERICAL ANALYSIS OF PARALLEL FLOW HEAT EXCHANGER

Heat and Mass Transfer Unit-1 Conduction

Examination Heat Transfer

How can we use Fundamental Heat Transfer to understand real devices like heat exchangers?

CHAPTER FOUR HEAT TRANSFER

PLATE & FRAME HEAT EXCHANGER

Numerical Analysis of Plate Heat Exchanger Performance in Co-Current Fluid Flow Configuration

Applied Heat Transfer:

Heat Exchangers: Rating & Performance Parameters. Maximum Heat Transfer Rate, q max

Circle one: School of Mechanical Engineering Purdue University ME315 Heat and Mass Transfer. Exam #2. April 3, 2014

Thermal Analysis of Cross Flow Heat Exchangers

HEAT TRANSFER AND EXCHANGERS

S.E. (Chemical) (Second Semester) EXAMINATION, 2011 HEAT TRANSFER (2008 PATTERN) Time : Three Hours Maximum Marks : 100

Experimental Analysis of Double Pipe Heat Exchanger

Welcome to the course in Heat Transfer (MMV031) L1. Martin Andersson & Zan Wu

Heat processes. Heat exchange

طراحی مبدل های حرارتی مهدي کریمی ترم بهار HEAT TRANSFER CALCULATIONS

ME 331 Homework Assignment #6

Simplified and approximated relations of heat transfer effectiveness for a steam condenser

Chapter 3 NATURAL CONVECTION

Lecture 3 Heat Exchangers

Coolant. Circuits Chip

Estimating number of shells and determining the log mean temperature difference correction factor of shell and tube heat exchangers

ANSI/AHRI Standard (Formerly ARI Standard ) 2006 Standard for Performance Rating of Desuperheater/Water Heaters

Phone: , For Educational Use. SOFTbank E-Book Center, Tehran. Fundamentals of Heat Transfer. René Reyes Mazzoco

DESIGN AND COST ANALYSIS OF HEAT TRANSFER EQUIPMENTS

If there is convective heat transfer from outer surface to fluid maintained at T W.

S.E. (Chemical) (Second Semester) EXAMINATION, 2012 HEAT TRANSFER (2008 PATTERN) Time : Three Hours Maximum Marks : 100

first law of ThermodyNamics

Heat and Mass Transfer Prof. S.P. Sukhatme Department of Mechanical Engineering Indian Institute of Technology, Bombay

Numerical Investigation on Effect of Operating Parameters on Plate Fin Heat Exchanger

Analyzing Mass and Heat Transfer Equipment

Experiment 1. Measurement of Thermal Conductivity of a Metal (Brass) Bar

Chapter 7: External Forced Convection. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Chapter 9 NATURAL CONVECTION

Principles of Food and Bioprocess Engineering (FS 231) Problems on Heat Transfer

Transfer processes: direct contact or indirect contact. Geometry of construction: tubes, plates, and extended surfaces

Comparative Analysis of Different Fluids in One Shell Pass And Two Tube Heat Exchanger

Numerical Heat and Mass Transfer

HEAT TRANSFER. Mechanisms of Heat Transfer: (1) Conduction

The Effect of Mass Flow Rate on the Effectiveness of Plate Heat Exchanger

Chapter 10: Boiling and Condensation 1. Based on lecture by Yoav Peles, Mech. Aero. Nuc. Eng., RPI.

C ONTENTS CHAPTER TWO HEAT CONDUCTION EQUATION 61 CHAPTER ONE BASICS OF HEAT TRANSFER 1 CHAPTER THREE STEADY HEAT CONDUCTION 127

Designing Steps for a Heat Exchanger ABSTRACT

In order to optimize the shell and coil heat exchanger design using the model presented in Chapter

Chapter 3: Steady Heat Conduction. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

1. Nusselt number and Biot number are computed in a similar manner (=hd/k). What are the differences between them? When and why are each of them used?

PROBLEM and from Eq. 3.28, The convection coefficients can be estimated from appropriate correlations. Continued...

Level 7 Post Graduate Diploma in Engineering Heat and mass transfer

Heat Transfer Coefficient Solver for a Triple Concentric-tube Heat Exchanger in Transition Regime

Effect of External Recycle on the Performance in Parallel-Flow Rectangular Heat-Exchangers

: HEAT TRANSFER & EVAPORATION COURSE CODE : 4072 COURSE CATEGORY : B PERIODS/ WEEK : 5 PERIODS/ SEMESTER : 70 CREDIT : 5 TIME SCHEDULE

CHAPTER 3 SHELL AND TUBE HEAT EXCHANGER

ME-662 CONVECTIVE HEAT AND MASS TRANSFER

Ministry of Higher Education And Scientific Research. University Of Technology Chemical Engineering Department. Heat Transfer

Analytical Study on Thermal and Mechanical Design of Printed Circuit Heat Exchanger

HEAT TRANSFER FROM FINNED SURFACES

Thermal Analysis of Shell and Tube Heat Ex-Changer Using C and Ansys

PHYSICAL MECHANISM OF NATURAL CONVECTION

Transport processes. 7. Semester Chemical Engineering Civil Engineering

Heat Transfer Performance in Double-Pass Flat-Plate Heat Exchangers with External Recycle

THERMAL PERFORMANCE OF SHELL AND TUBE HEAT EXCHANGER USING NANOFLUIDS 1

ENERGY PERFORMANCE IMPROVEMENT, FLOW BEHAVIOR AND HEAT TRANSFER INVESTIGATION IN A CIRCULAR TUBE WITH V-DOWNSTREAM DISCRETE BAFFLES

PROBLEM 8.3 ( ) p = kg m 1m s m 1000 m = kg s m = bar < P = N m 0.25 m 4 1m s = 1418 N m s = 1.

Biological Process Engineering An Analogical Approach to Fluid Flow, Heat Transfer, and Mass Transfer Applied to Biological Systems

Thermal Unit Operation (ChEg3113)

PERFORMANCE ANALYSIS OF CORRUGATED PLATE HEAT EXCHANGER WITH WATER AS WORKING FLUID

Key words: heat exchanger, longitudinal conduction, heat in-leak, helium liquefier, helium refrigerator

1/54 Circulation pump, safety valve, expansion vessel

Heat exchangers: Heat exchanger types:

a. Fourier s law pertains to conductive heat transfer. A one-dimensional form of this law is below. Units are given in brackets.

arxiv: v1 [physics.app-ph] 25 Mar 2018

Analysis of Shell & Tube Type Heat Exchangers

Heat Transfer Convection

4.1 Derivation and Boundary Conditions for Non-Nipped Interfaces

HEAT AND MASS TRANSFER. List of Experiments:

Thermal Unit Operation (ChEg3113)

Convection. forced convection when the flow is caused by external means, such as by a fan, a pump, or atmospheric winds.

HEAT TRANSFER. PHI Learning PfcO too1. Principles and Applications BINAY K. DUTTA. Delhi Kolkata. West Bengal Pollution Control Board

Heat Transfer with Phase Change

Chemical and Biomolecular Engineering 150A Transport Processes Spring Semester 2017

ME2251 HEAT AND MASS TRANSFER L T P C

EFFECT OF AMBIENT HEAT-IN-LEAK AND LONGITUDINAL WALL CONDUCTION ON A THREE-FLUID PARALLEL FLOW CRYOGENIC HEAT EXCHANGER

International Journal of Scientific & Engineering Research, Volume 5, Issue 11, November ISSN

4.1. Physics Module Form 4 Chapter 4 - Heat GCKL UNDERSTANDING THERMAL EQUILIBRIUM. What is thermal equilibrium?

4.1. Physics Module Form 4 Chapter 4 - Heat GCKL UNDERSTANDING THERMAL EQUILIBRIUM. What is thermal equilibrium?

University School of Chemical Technology

Transcription:

SMJ 4463: HEAT TRANSFER INSTRUCTOR: PM DR MAZLAN ABDUL WAHID http://www.fkm.utm.my/~mazlan TEXT: Introduction to Heat Transfer by Incropera, DeWitt, Bergman, Lavine 5 th Edition, John Wiley and Sons DR MAZLAN Chapter 11 Heat Exchangers Assoc Prof. Dr Mazlan Abdul Wahid Faculty of Mechanical Engineering Universiti Teknologi Malaysia www.fkm.utm.my/~mazlan DR MAZLAN 1

Objectives Recognize numerous types of heat exchangers, and classify them. Develop an awareness of fouling on surfaces, and determine the overall heat transfer coefficient for a heat exchanger. Perform a general energy analysis on heat exchangers. Obtain a relation for the logarithmic mean temperature difference for use in the LMTD method, and modify it for different types of heat exchangers using the correction factor. Develop relations for effectiveness, and analyze heat exchangers when outlet temperatures are not known using the effectiveness-ntu method. Know the primary considerations in the selection of heat exchangers. 3 Types Heat Exchanger Types Heat exchangers are ubiquitous in energy conversion and utilization. They involve heat exchange between two fluids separated by a solid and encompass a wide range of flow configurations. Concentric-Tube Heat Exchangers Parallel Flow Counterflow Simplest configuration. Superior performance associated with counter flow. 2

5 Types (cont.) Cross-flow Heat Exchangers Finned-Both Fluids Unmixed Unfinned-One Fluid Mixed the Other Unmixed For cross-flow over the tubes, fluid motion, and hence mixing, in the transverse direction (y) is prevented for the finned tubes, but occurs for the unfinned condition. Heat exchanger performance is influenced by mixing. 3

Compact heat exchanger: It has a large heat transfer surface area per unit volume (e.g., car radiator, human lung). A heat exchanger with the area density β > 700 m 2 /m 3 is classified as being compact. Cross-flow: In compact heat exchangers, the two fluids usually move perpendicular to each other. The crossflow is further classified as unmixed and mixed flow. 7 Types (cont.) Compact Heat Exchangers Widely used to achieve large heat rates per unit volume, particularly when one or both fluids is a gas. Characterized by large heat transfer surface areas per unit volume, small flow passages, and laminar flow. (a) Fin-tube (flat tubes, continuous plate fins) (b) Fin-tube (circular tubes, continuous plate fins) (c) Fin-tube (circular tubes, circular fins) (d) Plate-fin (single pass) (e) Plate-fin (multipass) 4

Shell-and-tube heat exchanger: The most common type of heat exchanger in industrial applications. They contain a large number of tubes (sometimes several hundred) packed in a shell with their axes parallel to that of the shell. Heat transfer takes place as one fluid flows inside the tubes while the other fluid flows outside the tubes through the shell. Shell-and-tube heat exchangers are further classified according to the number of shell and tube passes involved. 9 Types (cont.) Shell-and-Tube Heat Exchangers One Shell Pass and One Tube Pass Baffles are used to establish a cross-flow and to induce turbulent mixing of the shell-side fluid, both of which enhance convection. The number of tube and shell passes may be varied, e.g.: One Shell Pass, Two Tube Passes Two Shell Passes, Four Tube Passes 5

Regenerative heat exchanger: Involves the alternate passage of the hot and cold fluid streams through the same flow area. Dynamic-type regenerator: Involves a rotating drum and continuous flow of the hot and cold fluid through different portions of the drum so that any portion of the drum passes periodically through the hot stream, storing heat, and then through the cold stream, rejecting this stored heat. Condenser: One of the fluids is cooled and condenses as it flows through the heat exchanger. Boiler: One of the fluids absorbs heat and vaporizes. 11 Plate and frame (or just plate) heat exchanger: Consists of a series of plates with corrugated flat flow passages. The hot and cold fluids flow in alternate passages, and thus each cold fluid stream is surrounded by two hot fluid streams, resulting in very effective heat transfer. Plate heat exchangers are well suited for liquid-to-liquid applications. A plate-and-frame liquid-to-liquid heat exchanger. 12 6

Overall Coefficient Overall Heat Transfer Coefficient An essential requirement for heat exchanger design or performance calculations. Contributing factors include convection and conduction associated with the two fluids and the intermediate solid, as well as the potential use of fins on both sides and the effects of time-dependent surface fouling. With subscripts c and h used to designate the cold and hot fluids, respectively, the most general expression for the overall coefficient is: 1 = 1 = 1 UA UA UA ( ) ( ) c h R R = + + R + + 1 f, c f, h 1 w ( η ha) ( η A) ( η A) ( η ha) o c o c o h o h Overall Coefficient (cont.) R f Rw η o η o, c or h Overall surface efficiency of fin array (Section 3.6.5) Af = 1 ( 1 η f ) A c or h A = At total surface area (fins and exposed base) A surface area of fins only f Assuming an adiabatic tip, the fin efficiency is η f, cor h ( ml) tanh = ml ( 2 / ) m = U k t U Fouling fa for a unit surface area ( Table 11.1 c or h c or h p w c or h p, c or h 2 ctor m K/W) Wall conduction resistance (K/W) h = partial overall coefficient 1+ hr f c or h 7

THE OVERALL HEAT TRANSFER COEFFICIENT A heat exchanger typically involves two flowing fluids separated by a solid wall. Heat is first transferred from the hot fluid to the wall by convection, through the wall by conduction, and from the wall to the cold fluid again by convection. Any radiation effects are usually included in the convection heat transfer coefficients. Thermal resistance network associated with heat transfer in a double-pipe heat exchanger. 15 U is the overall heat transfer coefficient, W/m 2 C. When The overall heat transfer coefficient U is dominated by the smaller convection coefficient. When one of the convection coefficients is much smaller than the other (say, h i << h o ), we have 1/h i >> 1/h o, and thus U h i. This situation arises frequently when one of the fluids is a gas and the other is a liquid. In such cases, fins are commonly used on the gas side to enhance the product UA and thus the heat transfer on that side. 16 8

The overall heat transfer coefficient ranges from about 10 W/m 2 C for gas-to-gas heat exchangers to about 10,000 W/m 2 C for heat exchangers that involve phase changes. When the tube is finned on one side to enhance heat transfer, the total heat transfer surface area on the finned side is For short fins of high thermal conductivity, we can use this total area in the convection resistance relation R conv = 1/hA s, or to account for fin efficiency. 17 Fouling Factor The performance of heat exchangers usually deteriorates with time as a result of accumulation of deposits on heat transfer surfaces. The layer of deposits represents additional resistance to heat transfer. This is represented by a fouling factor R f. The fouling factor increases with the operating temperature and the length of service and decreases with the velocity of the fluids. 18 9

ANALYSIS OF HEAT EXCHANGERS An engineer often finds himself or herself in a position 1. to select a heat exchanger that will achieve a specified temperature change in a fluid stream of known mass flow rate the log mean temperature difference (or LMTD) method. 2. to predict the outlet temperatures of the hot and cold fluid streams in a specified heat exchanger the effectiveness-ntu method. The rate of heat transfer in heat exchanger (HE is insulated): Two fluid streams that have the same capacity rates experience the same temperature change in a wellinsulated heat exchanger. Heat capacity rate 19 is the rate of evaporation or condensation of the fluid,. h fg is the enthalpy of vaporization of the fluid at the specified temperature or pressure. The heat capacity rate of a fluid during a phase-change process must approach infinity since the temperature change is practically zero. Variation of fluid temperatures in a heat exchanger when one of the fluids condenses or boils. T m is an appropriate mean (average) temperature difference between the two fluids. 20 10

THE LOG MEAN TEMPERATURE DIFFERENCE (LMTD) METHOD log mean temperature difference Variation of the fluid temperatures in a parallel-flow doublepipe heat 21 exchanger. Arithmetic mean temperature difference: The logarithmic mean temperature difference T lm is an exact representation of the average temperature difference between the hot and cold fluids. Note that T lm is always less than T am. Therefore, using T am in calculations instead of T lm will overestimate the rate of heat transfer in a heat exchanger between the two fluids. When T 1 differs from T 2 by no more than 40 percent, the error in using the arithmetic mean temperature difference is less than 1 percent. But the error increases to undesirable levels when T 1 differs from T 2 by greater amounts. 22 11

Counter-Flow Heat Exchangers In the limiting case, the cold fluid will be heated to the inlet temperature of the hot fluid. However, the outlet temperature of the cold fluid can never exceed the inlet temperature of the hot fluid. For specified inlet and outlet temperatures, the T lm for a counter-flow heat exchanger is always greater than that for a parallelflow heat exchanger. That is, T lm, CF > T lm, PF, and thus a smaller surface area (and thus a smaller heat exchanger) is needed to achieve a specified heat transfer rate in a counterflow heat exchanger. When the heat capacity rates of the two fluids are equal 23 LMTD Method A form of Newton s law of cooling may be applied to heat exchangers by using a log-mean value of the temperature difference between the two fluids: q = U A T lm Evaluation of T and T 1 2 depends on the heat exchanger type. T T Tlm = 1n / 1 2 ( T T ) 1 2 Counter-Flow Heat Exchanger: T T T = T T 1 h,1 c,1 h, i c, o T T T = T T 2 h,2 c,2 h, o c, i 12

LMTD Method (cont.) Parallel-Flow Heat Exchanger: T T T = T T 1 h,1 c,1 h, i c, i T T T = T T 2 h,2 c,2 h, o c, o Note that T c,o cannot exceed T h,o for a PF HX, but can do so for a CF HX. For equivalent values of UA and inlet temperatures, T lm,cf > T lm,pf Shell-and-Tube and Cross-Flow Heat Exchangers: T = F T lm lm,cf F Figures 11S.1-11S.4 Energy Balance Overall Energy Balance Application to the hot (h) and cold (c) fluids: Assume negligible heat transfer between the exchanger and its surroundings and negligible potential and kinetic energy changes for each fluid. q = m i i ( h, i h, o ) (,, ) h c c o c i q = m i i i fluid enthalpy Assuming no l/v phase change and constant specific heats, = h p, h ( h, i h, o ) = Ch ( Th, i Th, o ) = c p, c ( c, o c, i ) = Cc ( Tc, o Tc, i ) q m c T T q m c T T C, C Heat capacity rates h c 13

Special Conditions Special Operating Conditions Case (a): C h >>C c or h is a condensing vapor ( C ). Negligible or no change in Th ( Th o = Th i ),,. Case (b): C c >>C h or c is an evaporating liquid ( C ). Negligible or no change in Tc ( Tc o = Tc i ) Case (c): C h =C c. T1 = T2 = T l m,,. h c Multipass and Cross-Flow Heat Exchangers: Use of a Correction Factor The correction factor F depends on the geometry of the heat exchanger and the inlet and outlet temperatures of the hot and cold fluid streams. F for common cross-flow and shell-andtube heat exchanger configurations is given in Fig. 11-18 versus two temperature ratios P and R defined as 1 and 2: inlet and outlet T and t: shell- and tube-side temperatures F = 1 for a condenser or boiler 28 14

FIGURE 11-18 Correction factor F charts for common shelland-tube heat exchangers. 29 FIGURE 11-18 Correction factor F charts for common shelland-tube heat exchangers. 30 15

General Considerations The LMTD method is very suitable for determining the size of a heat exchanger to realize prescribed outlet temperatures when the mass flow rates and the inlet and outlet temperatures of the hot and cold fluids are specified. With the LMTD method, the task is to select a heat exchanger that will meet the prescribed heat transfer requirements. The procedure to be followed by the selection process is: 1.Select the type of heat exchanger suitable for the application. 2.Determine any unknown inlet or outlet temperature and the heat transfer rate using an energy balance. 3.Calculate the log mean temperature difference T lm and the correction factor F, if necessary. 4.Obtain (select or calculate) the value of the overall heat transfer coefficient U. 5.Calculate the heat transfer surface area A s. The task is completed by selecting a heat exchanger that has a heat transfer surface area equal to or larger than A s. 31 General Considerations Computational Features/Limitations of the LMTD Method: The LMTD method may be applied to design problems for which the fluid flow rates and inlet temperatures, as well as a desired outlet temperature, are prescribed. For a specified HX type, the required size (surface area), as well as the other outlet temperature, are readily determined. If the LMTD method is used in performance calculations for which both outlet temperatures must be determined from knowledge of the inlet temperatures, the solution procedure is iterative. For both design and performance calculations, the effectiveness-ntu method may be used without iteration. 16

THE EFFECTIVENESS NTU METHOD A second kind of problem encountered in heat exchanger analysis is the determination of the heat transfer rate and the outlet temperatures of the hot and cold fluids for prescribed fluid mass flow rates and inlet temperatures when the type and size of the heat exchanger are specified. Heat transfer effectiveness The maximum possible heat transfer rate C min is the smaller of C h and C c. 33 Definitions Heat exchanger effectiveness, ε : q ε = q max Definitions 0 ε 1 Maximum possible heat rate: ( h i c i ) q = C T T C max min,, min C if C < C = C if C < C or h h c c c h Will the fluid characterized by C min or C max experience the largest possible temperature change in transit through the HX? Why is C min and not C max used in the definition of q max? 17

Definitions (cont.) Number of Transfer Units, NTU NTU UA C min A dimensionless parameter whose magnitude influences HX performance: q with NTU HX Relations ( h, i h, o ) q = mh i i or q = C T T (,, ) h h i h o q = mc ( ic, o ic, i ) or q = Cc Tc, o Tc, i ( ) q = ε Cmin ( Th, i Tc, i ) Heat Exchanger Relations Performance Calculations: ε = f ( NTU, C / C ) min max C r Relations Table 11.3 or Figs. 11.10-11.15 18

HX Relations (cont.) Design Calculations: NTU = f ( ε, C / C ) min max Relations Table 11.4 or Figs. 11.10-11.15 For all heat exchangers, ε with Cr For C r = 0, a single ε NTU relation applies to all HX types. ( ) ε = 1 exp NTU or ( ) NTU = 1n 1 ε Actual heat transfer rate 38 19

The effectiveness of a heat exchanger depends on the geometry of the heat exchanger as well as the flow arrangement. Therefore, different types of heat exchangers have different effectiveness relations. Here, we illustrate the development of the effectiveness ε relation for the double-pipe parallel-flow heat exchanger. 39 Effectiveness relations of the heat exchangers typically involve the dimensionless group UA s /C min. This quantity is called the number of transfer units NTU. Capacity ratio For specified values of U and C min, the value of NTU is a measure of the surface area A s. Thus, the larger the NTU, the larger the heat exchanger. The effectiveness of a heat exchanger is a function of the number of transfer units NTU and the capacity ratio c. 40 20

Table 11.3 41 Effectiveness for heat exchangers. 42 21

43 Table 11.4 When all the inlet and outlet temperatures are specified, the size of the heat exchanger can easily be determined using the LMTD method. Alternatively, it can be determined from the effectiveness NTU method by first evaluating the effectiveness ε from its definition and then the NTU from the appropriate NTU relation. 44 22

(e.g., boiler, condenser) 45 Observations from the effectiveness relations and charts The value of the effectiveness ranges from 0 to 1. It increases rapidly with NTU for small values (up to about NTU = 1.5) but rather slowly for larger values. Therefore, the use of a heat exchanger with a large NTU (usually larger than 3) and thus a large size cannot be justified economically, since a large increase in NTU in this case corresponds to a small increase in effectiveness. For a given NTU and capacity ratio c = C min /C max, the counterflow heat exchanger has the highest effectiveness, followed closely by the cross-flow heat exchangers with both fluids unmixed. The lowest effectiveness values are encountered in parallel-flow heat exchangers. The effectiveness of a heat exchanger is independent of the capacity ratio c for NTU values of less than about 0.3. The value of the capacity ratio c ranges between 0 and 1. For a given NTU, the effectiveness becomes a maximum for c = 0 (e.g., boiler, condenser) and a minimum for c = 1 (when the heat capacity rates of the two fluids are equal). 46 23

SELECTION OF HEAT EXCHANGERS The uncertainty in the predicted value of U can exceed 30 percent. Thus, it is natural to tend to overdesign the heat exchangers. Heat transfer enhancement in heat exchangers is usually accompanied by increased pressure drop, and thus higher pumping power. Therefore, any gain from the enhancement in heat transfer should be weighed against the cost of the accompanying pressure drop. Usually, the more viscous fluid is more suitable for the shell side (larger passage area and thus lower pressure drop) and the fluid with the higher pressure for the tube side. The proper selection of a heat exchanger depends on several factors: Heat transfer rate Cost Pumping power Size and weight Type Materials The rate of heat transfer in the prospective heat exchanger is Annual cost of electricity associated with the operation of the pumps and fans: 47 Summary Types of Heat Exchangers The Overall Heat Transfer Coefficient Fouling Factor Analysis of Heat Exchangers The Log Mean Temperature Difference Method Counter-Flow Heat Exchangers Multipass and Cross-Flow Heat Exchangers: Use of a Correction Factor The Effectiveness-NTU Method Selection of Heat Exchangers 48 24