Al-Zr Alloy Strand for ACCR Conductor Experimental Measurement of Resistance Temperature Coefficient

Similar documents
Temperature Profile for 36 Marker Spheres on 3M 788 ACCR Conductor 3M Company

CTC 460 kcmil ACCC Conductor Stress Strain Tests

Coefficient of Thermal Expansion for 477-T16 ACCR

VEIKI-VNL ELECTRIC LARGE LABORATORIES Ltd. TYPE TEST REPORT

KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 774-KCMIL 3M TM COMPOSITE CONDUCTOR

EA Guidelines on the Calibration of Temperature Indicators and Simulators by Electrical Simulation and Measurement

Kinectrics North America Inc. Report No.: K RC-0001-R00 March 20, C.J. Pon, Z. Peter Transmission and Distribution Technologies Business

Emissivity: Understanding the difference between apparent and actual infrared temperatures

A Model for Calculating ACCC Resistance Based on Fit Method


TRANSMISSION LINES. All aluminum alloy conductor (AAAC) Aluminum conductor alloy reinforced (ACAR)

Lab E3: The Wheatstone Bridge

Physics 3 Summer 1989 Lab 7 - Elasticity

Lecture 11 Temperature Sensing. ECE 5900/6900 Fundamentals of Sensor Design

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z ALPHAGAGE th Avenue Rockford, IL James Hoard Phone:

IB Physics STUDENT GUIDE 13 and Processing (DCP)

The Development of a High-Temperature PRT Calibration Process Based On Dry- Block Calibrators

Using a handheld digital thermometer in an analytical laboratory

Wenzhou Tripod Instrument Manufacturing Co., Ltd.

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005. ADVANCED TECHNOLOGY SERVICES HMA 1800 Honda Drive Lincoln, AL Lasheila Hayes Phone:

MENG 302L Lab 6: Stress Concentration

Feasibility of HTS DC Cables on Board a Ship

Experiment Five (5) Principal of Stress and Strain

Voltage Dividers, Nodal, and Mesh Analysis

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

Uncertainty Analysis of Experimental Data and Dimensional Measurements

Certificate of Accreditation

The Underground Experimental Investigation of Thermocouples

Certificate of Accreditation

Thermocouple Calibrations and Heat Transfer Coefficients

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

Composite Conductor Field Trial Summary Report: Western Area Power Administration FARGO

Microwave Loss Reduction in Cryogenically Cooled Conductors R. Finger and A. R. Kerr

Composite Conductor Field Trial Summary Report: Western Area Power Administration Phoenix

Solder Joint Reliability Lucent X Summary Report

Nusselt Correlations for Select Substation Bus. Presented by: Tony Pribble IEEE JTC Orange County, CA January, 2019

EXPERIMENT ET: ENERGY TRANSFORMATION & SPECIFIC HEAT

Tuesday 23 May 2017 Morning

EXPERIMENT 14 SPECIFIC HEAT OF WATER. q = m s T

Strain Gauge Application and Measurement of Unknown Load

IPC-TM-650 TEST METHODS MANUAL

Thermal Expansion Experiment

Measuring Humidity in the Charters of Freedom Encasements Using a Moisture Condensation Method

Certificate of Accreditation

TEMPERATURE SENSOR. Model TH-T. Roctest Limited, All rights reserved.

Temperature Measurement

Understanding the uncertainties associated with using the 5128A RHapid Cal portable humidity generator

DISTRIBUTION CONDUCTOR STRINGING EQUIPMENT & TECHNIQUES

NOVALYNX CORPORATION MODEL 110-WS-16BP BAROMETRIC PRESSURE SENSOR INSTRUCTION MANUAL

1) Thermo couple sensor

Introduction. Measurement of temperature is generally considered to be one of the simplest and most accurate measurements performed in engineering.

INTRODUCTION TO LABORATORY EXPERIMENT AND MEASUREMENT

Group 1 Group 2. 1 meter = 100 cm 9.88 cm of Copper Wire 1 dollar = 4 quarters Room Temp is 22.7 C

Certificate of Accreditation

Scope of Accreditation For ISOLAB Inc. Calibration

Unit 11 Wire Tables and Conductor Sizes

ME 105 Mechanical Engineering Laboratory Spring Quarter Experiment #2: Temperature Measurements and Transient Conduction and Convection

CLASSix UTP Patch Cords

Physics laboratory safety precautions / rules:

Initial Evaluation of Composite Distribution Pole Technology

Refer to page E-6 for details. Refer to page E-31 for details. Digital Height Master. Refer to page E-35 for details. High Precision Square

T h e rm i s t o r s

D501 and D501-RS. Microscanner D-Series IR Thermometers. no effect. no effect. no effect. no effect no effect

Metrology Experiment for Engineering Students: Platinum Resistance Temperature Detector

DHANALAKSHMI COLLEGE OF ENGINEERING. (Dr.VPR Nagar, Manimangalam, Tambaram) Chennai

Tflex HD700 Thermal Reliability Report

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

Experiment B6 Thermal Properties of Materials Procedure

Resistance Learning Outcomes

Specific resistance of conductors

Measurement. 2. The magnitude of the quantity. Even with the same instrument, every order of magnitude jump will generate one more significant digit.

PHYS320 ilab (O) Experiment 2 Instructions Conservation of Energy: The Electrical Equivalent of Heat

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

Certificate of Accreditation

Understanding uncertainties associated with the 5128A RHapid-Cal Humidity Generator

Resistance Learning Outcomes. Resistance Learning Outcomes. Resistance

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

Chapter 1. Blackbody Radiation. Theory

Engineering Metrology and Instrumentation

Reading analog scales

Resistance : R = ρ( ) units are Ohms ( 14 ) Resistor 100 ohms

3B SCIENTIFIC PHYSICS

Certificate of Accreditation

Certificate of Accreditation

16 Input AC Block I/O Module

Semiconductor thermogenerator

Measurement and Uncertainty. To determine the uncertainty associated with various measuring devices.

Model 791 Calibration Plate for Tiltmeters and Inclinometers

Exercise 1: Thermistor Characteristics

Height Master Page 343. Check Master Page 347. Calibration Tools Page 352

National 5 Physics. Electricity and Energy. Notes

Field Instrumentation and Monitoring of Eyebars within the Southeast Anchorage of the Walt Whitman Bridge

Experiment 2: THE DENSITY OF A SOLID UNKNOWN AND CALIBRATION WITH DATASTUDIO SOFTWARE

MECHANICAL ENGINEERING TECHNOLOGY ESSENTIALS FOR LABORATORY REPORTS

Cambridge International Examinations Cambridge International General Certificate of Secondary Education

Standard Test Method for Thermal Conductivity of Refractories 1

Certificate of Accreditation

Power transfer capacity improvements of existing overhead line systems

High Temperature Strain Measurements Using Fiber Optic Sensors

MET 301 EXPERIMENT # 2 APPLICATION OF BONDED STRAIN GAGES

Transcription:

Al-Zr Alloy Strand for ACCR Conductor Experimental Measurement of Resistance Temperature Coefficient NEETRAC Project Number: 04-235b 3M Purchase Order #0001562911 May 2006 A Research Center of the Georgia Institute of Technology Requested by: Mr. Colin McCullough 3M Principal Investigator: Paul Springer, PE Reviewed by: Dale Callaway

SUMMARY Al-Zr Alloy Strand for ACCR Conductor Experimental Measurement of Resistance Temperature Coefficient NEETRAC Project Number: 04-235b 3M Purchase Order #0001562911 May 2006 Strands of Al-Zr alloy used in 3M s ACCR conductors were tested to determine the volume resistivity and the temperature coefficient of resistance from room-temperature to 250 C. The purpose is to collect data to better predict the temperature and sag-tension behavior of of ACCR conductor in transmission lines operated at elevated temperature. KEY FINDINGS 1) The resistance temperature coefficient is linear with respect to temperature up to 250 C. A value of 0.361%/ C was measured. For reference, the Southwire Conductor Manual value for EC alloy 1350-H19 aluminum used in ACSR conductors is 0.404%/ C. 2) Resistivity of Al-Zr alloy at 20 C measured 2.833 µω-cm. For reference, the Southwire Conductor Manual resistivity value for EC alloy 1350-H19 aluminum is 2.817 µω-cm. SAMPLES 1) Three (3) strands of Al-Zr aluminum received from Nexans received in January 2005. PROCEDURE DC resistance measurements are typically quoted for 20 C conductor temperature. Elevated temperature resistance must be known for ampacity calculations. The 1994 Southwire Conductor Manual provides the following expression for resistance change with changing temperature: R T2 = R Tref [1+α ref (T 2 T ref )] where: α ref = temperature coefficient of resistance R Tref = dc resistance at reference temperature (typically 20 C) T 2 = temperature at which new resistance is desired R T2 = dc resistance at temperature T 2 A test was designed to measure the change in resistance from room temperature to 250 C. Nexans Cables provided Al-Zr strands that had not been stranded into conductor. The strands were relatively straight as-received, but straightening was needed to get close to an ideal test sample. Strand diameter and gage length were measured to provide data for volume resistivity 774 T53 ACCR, resistance temperature coefficient, NEETRAC Project 04-235b Page 2 of 6

calculations. Taper and ovalness of the test sample were accounted for by measuring diameter at 5 locations along the sample, and in 3 directions at each location (15 total measurements). A jeweler s file was used to make gage marks at two locations on the sample. A caliper micrometer was used to measure distance between the gage marks. A measurement error of +/- 0.020 inches is estimated for a gage section that is nominally 14 inches. This estimate includes an allowance for any residual curvature in the sample. System error due to gage length measurement is, therefore, 0.14%. Two electrical clip leads used to connect the votage leads of the 4-wire resistance instrument to the sample. The clip leads were modified with a die grinder to provide a line contact against the gage marks, and thereby define the active section in the resistance measurement. The two current leads of the 4-wire instrument were connected to the sample ends using standard electrical clip leads. The test was run in a Blue-M laboratory oven. The oven has forced-air circulation to ensure uniform temperature. Temperature control is on/off only, but it is possible to wait for stable periods where the temperature change was on the order of 0.2 C per minute. To ensure that accurate temperature data was obtained, a set of reference standard thermometers with accuracy certified +/- 0.1 C were placed in the oven as near as practical to the test sample. The thermometers were read visually through the oven window with satisfactory results. A second Al-Zr strand identical to the test sample was prepared. A hole was drilled to the center, and a Type T thermocouple was placed in the center of the sample. The purpose for the second sample was to have a temperature reference with identical thermal properties to the test sample. The test sample could not be directly instrumented for temperature for fear that the local resistance value would be affected by the thermocouple hole. The dummy sample was used to monitor temperature stability, and ensure that data was recorded only when the test sample and the more massive glass thermometer were in thermal equilibrium. The samples were placed on heatresistant fabric gloves to provide electrical isolation from the metal oven parts. Photograph 1 shows the sample arranged in the oven prior to testing. Photograph 1, test sample (top), dummy with thermocouple (middle), and glass thermometer (bottom) 774 T53 ACCR, resistance temperature coefficient, NEETRAC Project 04-235b Page 3 of 6

RESULTS I) Resistance Temperature Coefficient: Fifteen evenly-space measurements of the strand diameter showed the minimum and maximum diameters are 0.1520 inches and 0.1525 inches, respectively. This shows the sample is reasonably round and free of taper. The average diameter measures 0.1523 inches. The nominal gage section was 14 inches. A gage section length of 14.015 inches could be consistently measured using a micrometer. Length and average diameter measurements were used to convert the resistance readings to volume resistivity in µω-cm. The glass thermometer is more accurate than a thermocouple temperature indicator, but has lead/lag effects due to thermal time constant larger than the aluminum strand. Therefore, the temperature needed to be stable to ensure that the thermometer correctly reflected the strand temperature. The thermocouple in the dummy sample was used to verify stable temperature. Once stability was confirmed, the glass thermometer was read to the nearest 0.1 C. A total of seven (7) different thermometers were needed to cover the full temperature range. Because of viewing conditions through the oven window, it was not feasible to interpolate an additional decade of resolution. One reading at 217 C fell outside a reasonable range, and was discarded as an anomalous data point. All other data points are used as-recorded. No attempt was made to adjust the sample dimensions for temperature change (all resistivity values are based on roomtemperature dimensions). Figure 1 shows the heat-up curve, along with the calculated volume resistivity based on the room-temperature dimensions of the test sample. Resistance vs. Temperature Data, Al-Zr Strand 1800 7.0 1700 6.5 1600 y = 3.6081x + 785.89 R 2 = 0.9997 6.0 1500 5.5 Resistance (µω) 1400 1300 1200 1100 Resistance (Y1 Axis) y = 0.0119x + 2.5947 R 2 = 0.9997 Volume Resistivity (Y2 Axis) 5.0 4.5 4.0 3.5 Resistivity (µω-cm) 1000 Linear (Volume Resistivity (Y2 Axis)) 3.0 Linear (Resistance (Y1 Axis)) 900 2.5 800 2.0 0 50 100 150 200 250 300 Temperature (deg C) Figure 1, data and linear fits for resistance vs. temperature data 774 T53 ACCR, resistance temperature coefficient, NEETRAC Project 04-235b Page 4 of 6

Additional data was recorded during the cool-down of the sample from 250 C. In this case, the glass thermometer fell below range at 240 C. Because the door needed to remain closed to minimize thermal gradients, only the dummy-sample thermocouple could be recorded. Figure 2 shows the heat-up and cool-down data for the thermocouple in the dummy sample. This data is considered less reliable than the data based on the reference standard thermometer set. 1800 Resistance vs. Temperature Data, Al-Zr Strand Temperature data based on thermocouple in dummy sample 1700 1600 1500 y = 3.451x + 795.09 R 2 = 0.9996 Resistance (micro-ohm) 1400 1300 1200 1100 1000 900 y = 3.4781x + 784.46 R 2 = 0.9993 Dummy Thermocouple, heat-up Dummy Thermocouple, cool-down Linear (Dummy Thermocouple, heat-up) Linear (Dummy Thermocouple, cooldown) 800 0 50 100 150 200 250 300 Temperature (deg C) Figure 2, resistance temperature coefficient based on thermocouple temperature data (considered less reliable than data from glass thermometer) Summary of resistance temperature coefficient: 1) Reference thermometer data imply α ref = 0.003608 2) Thermocouple data imply α ref = 0.003451 to 0.003478 3) Volume resistivity of the Al-Zr strand is 2.833 µω-cm at 20 C CONCLUSION The temperature coefficient for resistance, α ref, measures 0.00361 based on a linear fit through the test data. Polynomial fits through the test data fail to improve the correlation coefficient. Therefore, the coefficient is linear with respect to temperature. Published values of α ref for 1350-H19 EC grade aluminum range from 0.00403 to 0.00423. According to the Southwire reference, values of α ref depend on the conductivity of the aluminum. 774 T53 ACCR, resistance temperature coefficient, NEETRAC Project 04-235b Page 5 of 6

EQUIPMENT LISTING 1) AVO/Biddle Digital Low Resistance Ohmmeter, Calibration Control #CQ 1092 2) Fluke 77 thermocouple reader, Calibration Control # CQ 0173 3) Starrett digital caliper micrometer, Calibration Control # CQ 3046 (diameter measurements) 4) Starrett vernier caliper micrometer, Calibration Control # CQ 0144 (length measurements) 5) Brooklyn Reference Standard Thermometer Set, Calibration Control # CN 0155 774 T53 ACCR, resistance temperature coefficient, NEETRAC Project 04-235b Page 6 of 6