Small Signal Stability Analysis of Power System with Increased Penetration of PV Generation

Similar documents
Impact of Photovoltaic Generation On The Power System Stability

Analysis of Field Oriented Control Strategy for Induction Motor

Automated Spur Gear Designing Using MATLAB

Design and Fabrication of Solar Parabolic Collector for Water Distillation

Numerical Investigation on Thermal Conductivity of Vapor Chamber by Using Iterative Approach

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)

Predicting, controlling and damping inter-area mode oscillations in Power Systems including Wind Parks

DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID

ECE 585 Power System Stability

A Novel Wideband Metamaterial Absorber for S, C & X Bandwith Good Absorbption

A STATIC AND DYNAMIC TECHNIQUE CONTINGENCY RANKING ANALYSIS IN VOLTAGE STABILITY ASSESSMENT

Real-Life Observations of Power System Dynamic Phenomena Some Interesting Aspects

1 Unified Power Flow Controller (UPFC)

ANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER

Location-Dependent Impacts of Resource Inertia on Power System Oscillations

Transient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods

Phasor model of full scale converter wind turbine for small-signal stability analysis

QFT Framework for Robust Tuning of Power System Stabilizers

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Self-Tuning Control for Synchronous Machine Stabilization

New criteria for Voltage Stability evaluation in interconnected power system

ECE 522 Power Systems Analysis II 3.3 Voltage Stability

COMPARISON OF DAMPING PERFORMANCE OF CONVENTIONAL AND NEURO FUZZY BASED POWER SYSTEM STABILIZERS APPLIED IN MULTI MACHINE POWER SYSTEMS

Chapter 9: Transient Stability

EVALUATION OF THE IMPACT OF POWER SECTOR REFORM ON THE NIGERIA POWER SYSTEM TRANSIENT STABILITY

A Computer Application for Power System Control Studies

Adaptive under frequency load shedding using synchrophasor measurement

Optimal Placement & sizing of Distributed Generator (DG)

Performance Of Power System Stabilizerusing Fuzzy Logic Controller

DESIGNING POWER SYSTEM STABILIZER WITH PID CONTROLLER

Prediction of Instability Points Using System Identification

ELECTROMECHANICAL oscillations have been observed

Comparative Analysis of an integration of a Wind Energy Conversion System of PMSG and DFIG Models Connected to Power Grid

Generators. What its all about

Research Paper ANALYSIS OF POWER SYSTEM STABILITY FOR MULTIMACHINE SYSTEM D. Sabapathi a and Dr. R. Anita b

Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS

Power System Stability GENERATOR CONTROL AND PROTECTION

ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 4 Active Power and Frequency Control

Generalized Injection Shift Factors and Application to Estimation of Power Flow Transients

IEEE PES Task Force on Benchmark Systems for Stability Controls

Impact of Increased Penetration of Solar PV on Small Signal Stability of Power System

IEEE PES Task Force on Benchmark Systems for Stability Controls

Aug 2015 PES-TR18. Benchmark Systems for Small-Signal Stability Analysis and Control. IEEE Power & Energy Society TECHNICAL REPORT

Application of Virtual Synchronous Generator in Solar Power Generation

Eigenvalue Analysis of Subsynchronous Resonance Study in Series Compensated Wind Farm

ECEN 667 Power System Stability Lecture 20: Oscillations, Small Signal Stability Analysis

Unified Power Flow Controller (UPFC) Based Damping Controllers for Damping Low Frequency Oscillations in a Power System

Micro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

Impact of Large-Scale PV Penetration on Power System Oscillatory Stability

Modeling of Hydraulic Turbine and Governor for Dynamic Studies of HPP

Aldi Mucka Tonin Dodani Marjela Qemali Rajmonda Bualoti Polytechnic University of Tirana, Faculty of Electric Engineering, Republic of Albania

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 8 - Voltage Stability

WECC-WGMG. Model Validation Working Group. Phoenix, AZ November 18-20, 2009

Control Lyapunov Functions for Controllable Series Devices

Impact of Distributed Synchronous Generators on Distribution Feeder Stability

A Power System Dynamic Simulation Program Using MATLAB/ Simulink

Static and Transient Voltage Stability Assessment of Power System by Proper Placement of UPFC with POD Controller

Cooperative & Distributed Control of High-Density PVs in Power Grid

Steady State Performance of Doubly Fed Induction Generator Used in Wind Power Generation

Application of Posicast Controller on Power System Stabilizer and Its Effect on Oscillatory Stability

POWER SYSTEM STABILIZER CONTROL FOR WIND POWER TO ENHANCE POWER SYSTEM STABILITY

The Effects of Machine Components on Bifurcation and Chaos as Applied to Multimachine System

WIND and solar power account for almost half of newly

Transient Stability Analysis with PowerWorld Simulator

Reliability of Bulk Power Systems (cont d)

Cascading Outages in Power Systems. Rui Yao

MITIGATION OF POWER SYSTEM SMALL SIGNAL OSCILLATION USING POSICAST CONTROLLER AND EVOLUTIONARY PROGRAMMING

Centralized Supplementary Controller to Stabilize an Islanded AC Microgrid

SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS. Transient Stability LECTURE NOTES SPRING SEMESTER, 2008

APPLICATIONS OF CONTROLLABLE SERIES CAPACITORS FOR DAMPING OF POWER SWINGS *

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

An improved voltage-collapse protection algorithm based on local phasors

Power System Linear Modeling. Application for Small Signal Stability Analysis

Oscillation energy based sensitivity analysis and control for multi-mode oscillation systems

Short and Long-Term Dynamic Voltage Instability

Spontaneous Speed Reversals in Stepper Motors

FLEXIBLE ac transmission system (FACTS) devices give

Influence of Large-scale PV on Voltage Stability of Sub-transmission System

DESIGN OF GRID CONNECTED PV INVERTER THROUGH FEEDBACK LINEARIZATION

Power Grid Partitioning: Static and Dynamic Approaches

Analytical Study Based Optimal Placement of Energy Storage Devices in Distribution Systems to Support Voltage and Angle Stability

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

HOW TO DEAL WITH ELECTROMAGNETIC DISTURBANCES CAUSED BY NEW INVERTER TECHNOLOGIES CONNECTED TO PUBLIC NETWORK

Chapter 8 VOLTAGE STABILITY

IEEE PES Task Force on Benchmark Systems for Stability Controls

EE 451 Power System Stability

Vector Controlled Power Generation in a Point Absorber Based Wave Energy Conversion System

TCSC-Based Wide Area Damping Controller (WADC) for Inter-area oscillations in Saudi Power Network

Voltage Stability Monitoring using a Modified Thevenin Impedance

CHAPTER 3 SYSTEM MODELLING

Notes on Power System Voltage Stability

Robust Tuning of Power System Stabilizers Using Coefficient Diagram Method

The influence of the self-excited induction machine into the electrical grid under instability situation - Real case measurement

EXCITATION CONTROL OF SYNCHRONOUS GENERATOR USING A FUZZY LOGIC BASED BACKSTEPPING APPROACH

Simulating a Power System

DESIGN OF A HIERARCHICAL FUZZY LOGIC PSS FOR A MULTI-MACHINE POWER SYSTEM

Investigation of Inertia s Locational Impacts on Primary Frequency Response using Large-scale Synthetic Network Models

Effects of STATCOM, TCSC, SSSC and UPFC on static voltage stability

Transcription:

Kalpa Publications in Engineering Volume, 207, Pages 200 207 ICRISET207. International Conference on Research and Innovations in Science, Engineering &Technology. Selected Papers in Engineering Small Signal Stability Analysis of Power System with Increased Penetration of PV Generation David Parmar, Dr.Bhinal Mehta 2 M&V Patel Department of Electrical Engineering, C. S. Patel Institute of Technology, CHARUSAT- Changa, Anand, Gujarat, India davidparmar20@gmail.com, bhinalmehta.ee@charusat.ac.in Abstract With the increase in the penetration of photo-voltaic (PV) generation in the power system it is utmost important to analyze the impact and issues of PV generation on the interconnected power system. As the output of PV is not constant its influence on the power system stability needs to be considered and it is evident from the grid codes of most of the countries. In this paper two different model of solar photovoltaic generation suitable for small signal stability analysis are presented and its behavior is investigated considering the IEEE 4-bus test system. The research review the impact of solar power on the interconnected power system with a high penetration of PV generation by the control of active and reactive power output. Based on constant reactive power and constant voltage magnitude models, the effect of voltage and angle stability of grid connected PV systems are studied and discussed. The eigenvalue analysis is carried out for the test system without any PV penetration and with different PV penetration levels and the results are compared using the power system analysis toolbox on MATLAB platform. The most influencing critical modes are identified and their behavior with increase in PV penetration is demonstrated. Introduction As the effects of global warming are increasing tremendously these days, the amount of renewable energy integration is growing worldwide and among these renewables solar photovoltaic installations are given tremendous boost by the government in developing countries like India. The solar energy is the major option among renewable energy resources to satisfy the energy needs. Government of India has set the ambitious target of deploying 72 GW by 2022 and among these renewables grid-connected solar PV will be given high preference []. With the large-scale integration of the PV generation to the existing power system its impact on power system stability needs to be analyzed more carefully due to its detrimental and beneficial impact as the PV generators have characteristics that are different from the conventional synchronous generators. As the solar power plant mainly consists of the PV modules inverters, they do not possess A. Shukla, J.M. Patel, P.D. Solanki, K.B. Judal, R.K. Shukla, R.A. Thakkar, N.P. Gajjar, N.J. Kothari, S. Saha, S.K. Joshi, S.R. Joshi, P. Darji, S. Dambhare, B.R. Parekh, P.M. George, A.M. Trivedi, T.D. Pawar, M.B. Shah, V.J. Patel, M.S. Holia, R.P. Mehta, J.M. Rathod, B.C. Goradiya and D.K. Patel (eds.), ICRISET207 (Kalpa Publications in Engineering, vol. ), pp. 200 207

inertia which the traditional synchronous generators possess due to the rotating mass. Also, the behavior and interaction of these solar power plants with the power system depends on the dynamics of the inverter. Therefore, it is utmost important to study the impact of the penetration level of PV generation on the dynamic performance of power system. The impact of the PV systems connected to the utility side and rooftop PV generation connected to transmission/sub transmission system are discussed in [2]- [5]. The impact of PV generation on small signal stability considering the probabilistic analysis is discussed in [6], [7]. The voltage stability and sensitivity analysis are depicted. In the present paper, two different models for the large PV generations are connected at the transmission system are put forward for consideration by showing its impact on IEEE 4-bus test system. The proposed models are much simple, generic and can be readily implemented. The objective of the paper is to do the detailed small signal stability analysis and voltage stability analysis of the PV generation with the high penetration level. The structure of the remaining is as follows: Section 2 dealt with modeling of PV models followed by proposed approach in Section 3. The results of different cases are demonstrated in Section 4 along with its discussion. The conclusions of the paper are mentioned in Section 5. 2 Pv Modeling Power system stability is a property of a power system which enables it to remain in a state of operating equilibrium under normal operating conditions and to regain an acceptable state of equilibrium after being subjected to a disturbance [8]. The two different models suitable for small signal stability and voltage stability analysis are given below considering the NERC standards. 2. Modelling of PV systems The PV generation model can be based on thinking approach of the grid side model that is like type 4 wind turbine generator (WTG) that have almost the same characteristics because both solar and wind are usually connected to the grid through a convertor and should perform nearly similar operations. [5]. Fig. shows atypical type 4 WTG WECC generic model. All the generated power from the generator preferably permanent magnet synchronous generator (PMSG) is transferred to the grid through back to back voltage source converter familiarly known as generator side convertor (GSC) and network side convertor (NSC) via DC link. The NSC controls the reactive power output and voltage at point of common coupling (PCC). To do the similar task in these paper two models of PV generation are given below in Fig.2 and Fig.3 as follow: Model : PQ control model Model 2: PV control model Vreg bus Vterm Pref Qref SPVG Id, iq PCC NETWORK Converter Control Model Ip (P) Command Iq (Q) Command PGen, QGen Converter Model PGen, QGen Pref Vref V, θ Figure 2: Model Id PCC SPVG, iq NETWORK Figure : Type 4 wind turbine generator general block diagram V, θ Figure 3: Model 2 20

2.2 Grid-Side Model The Model and Model 2 in single line diagram as per the control modes are shown in both fig. 2 and fig. 3 respectively. The block diagram also depicts the equations for inverter transfer functions, the closed loop controller transfer function with unity value of steady state gain. The block-diagrams of the two SPVG models shown in fig.4 and fig. 5 respectively. In these two models, the reference current i dref and i qref of the d axis and q axis are generated as per the desired reference active power and reactive power, P ref and Q ref respectively. Pref Qref Currents Set point controller idref iqref +stp +stq Converter id, iq NETWORK Vref Voltage Regulator Kv + - Ki s Pref Qref Currents Set point controller idref iqref +stp +stq Converter id, iq NETWORK V, θ V, θ Figure 4: Model block diagram Figure 5: Model 2 block diagram. 3 Proposed Approach 3. Small Signal Stability Small signal stability analysis is carried out by obtaining a linearized model of the nonlinear system and then the state space model is created. The initial conditions are obtained at the operating point. The eigenvalue (λ) of the state matrix A is obtained and the stability of the system is analyzed. The frequency of oscillations and damping ratio is obtained by right eigenvector (ɸ) and left eigenvector (ψ). The most critical influencing modes are identified along with their percentage participation. The basic equations used for the eigenvalue analysis are as follows: [8] Aφ $ = λ $ φ $ () ψ $ A = λ $ ψ $ (2) For the complex pair of eigenvalue related to an oscillatory mode of the system, the frequency (f) and the damping ratio (ζ) are expressed as λ $ = σ $ ± jw $ (3) f $ =, -./ (4) ζ $ = 2 - (5) 2-3 4,- 3 The equation (5) shows that damping ratio, and its relationship with real part of the eigenvalue, this ratio shows the rate at which the amplitude of oscillations decreases. 3.2 Test System All numerical studied load flow analysis, continuation power flow, voltage stability analysis, eigenvalue analysis and time domain simulation were performed in power system simulation toolbox (PSAT) using a MATLAB platform. The IEEE 4-bus test system shown in fig. 6 is used. The base system considered main synchronous generator (SG) whose rating is 65 MVA connected at bus, and one 40 MW smaller synchronous generator connected at bus 2. The generator at bus 2 is replaced with PV generator of the same rating allowing a real modelling effect. The AVRs were connected to SG and the three synchronous condensers are connected at buses 3,6 and 8. The active power and reactive power of base system load is considering 362.6 MW and 3.96 MVAr, respectively. 202

Figure 6: IEEE 4-bus test system The following steps are considered for the proposed approach: The eigenvalue analysis is carried out of the system without any PV penetration and the critical modes of the systems are identified. This is taken as base case. Then the eigenvalue analysis is carried out of the system with the various levels of the utility scale PV penetration in the system. The both models are considered for PV penetration. The obtained results without and with PV generation are compared and the impact of the PV penetration on the stability of the system is observed. The obtained results of the eigenvalue analysis are validated using transient stability analysis by performing time domain analysis of the system by exciting the critical modes of the system. The PV penetration definition used based on available generation in the system base case and PV penetration levels based on system maximum load or by the amount of energy served for one year are defined as follows: Total PV generation MW PV Penetration % = Total generation MW PV EFGFHIJH$KG = PV LFGFHIJH$KG c. f The capacity factor (c.f) of the PV systems is considered as 25%. 4 Results & Discussion The Table shows the summary of the power system considering IEEE 4 bus test system which includes system generation data, system load data and system total losses. The summary of PV penetrations as defined above is presented in table 2. TOTAL GENERATION REAL POWER [MW] 392.0304 REACTIVE POWER [MVAr] 204.2345 TOTAL LOAD REAL POWER [MW] 362.6 REACTIVE POWER [MVAr] 3.96 TOTAL LOSSES REAL POWER [MW] 29.4304 REACTIVE POWER [MVAr] 90.2745 Table : System Description 203

PV Generation (MW) PV Penetration Level (%) PV Penetration Level by energy 80 60 235 34 392 20 40 60 80 00 5 0 5 20 25 Table 2: summary of PV penetration levels Real part Imag. Part Frequency Damping (%) -.895 0.2699.662 8.4565888 -.793 0.794.7298 6.4983846 -.323 8.9507.4398 4.5063399-0.239 2.5332 0.40486 9.7869293 Table 3: Critical Modes: Base case Small signal stability analysis is carried out for base case and two PV models. The most critical modes are identified for all three cases. The critical values of the system are identified from the eigenvalue analysis and are decided that modes having a frequency of 0.0-2Hz as well as damping having less than 20% are observed. A disturbance which excites the most detrimentally impacted critical modes with increased penetration level of PV is simulated. The main aim of this work is to study how the system behave with decreased system inertia and therefore in this study only most critical modes carefully considered. These eigenvalues are shown in Table 3,4 and 5 along with frequency of oscillations and damping percentage. Penetration (%) Real Part Imag. Part Frequency (Hz) Damping (%) 20 -.290 8.875.4274 4.38669 40-0.3 2.250 0.3659 3.7059 60-0.30 2.250 0.3655 3.65553 80-0.308 2.250 0.365 3.602 00-0.307 2.250 0.3647 3.5480 Table 4: Critical Modes: Model Penetration Mode Mode2 Mode3 Mode4 20% -0.57654 -.3563-3.3958 -.2903 40% -.0508-3.9798-2.9597-0.339 60% -.05-3.9798-2.9598-0.302 80% -.05-3.9798-2.9598-0.30896 00% -.052-3.9798-2.9599-0.3077 Table 6: Real part of Eigenvalue: Model Penetration (%) Real Part Imag. Part Frequency (Hz) Damping (%) 20-0.687 9.8605.5732 6.954068 40-0.83 9.885.5682 8.25265 60-0.932 9.7832.564 9.489245 80 -.064 9.752.563 0.8407 00 -.20 9.73.5603 2.25532 Table 5: Critical Modes: Model 2 Penetration Mode Mode2 Mode3 Mode4 20% -3.9853-3.0249-2.2786-0.68737 40% -3.9822-3.005-2.2567-0.8306 60% -3.9794-2.9842-2.239-0.93256 80% -3.9765-2.959-2.2 -.0634 00% -3.9738-2.9297-2.606 -.205 Table 7: Real part of Eigenvalue: Model 2 Table 6 and 7 depict the real part of eigenvalue of the critical modes for model and model 2, respectively with the increased in PV penetration level. Fig. 7 and Fig.8 shows the comparison of all four critical modes for model and model 2 respectively as the PV generation rises. The result reveals that for model the system is more stable as a real part of mode,2 and 4 increases, whereas for model 2 the modes are not much affected. It can be overall concluded that as penetration level increases the stability increases which is beneficial impact. Figure 7: Real Part of eigenvalue as PV Penetration Level Increases: Model Figure 8: Real Part of eigenvalue as PV Penetration Level Increases: Model 2 204

4. Voltage Stability Analysis The load flow and continuation power flow is carried out by increasing the loading level up to certain point after which the voltage collapse for all three cases. The voltage profile of Bus,2,4 and 4 are examined. The results are shown in Fig. 9 -Fig 2 and Table 8. In case of voltage stability analysis Model 2 gives better results compare to base case under normal and contingency conditions, while Model gives best result under normal condition and poor result under contingency conditions. Normal Condition (MW) Contingency Condition (MW) Base Case 602.2376 560.99 Model 59.4 59.4 Model 2 698.52 698.52 Base Case Normal Condition (MW) Contingency Condition (MW) 68.87 56 Model 77.26 543.52 Model 2 628.520 60.62 Table 8: Voltage Stability Margins Table 9: Oscillatory Stability Margins 4.2 Angle stability Due to the continuous operation of AVR the system becomes oscillatory unstable with the increase in the loading level after certain point. The Table 9 shows the result of frequency oscillations which appear for both models and system conditions. A time domain simulation considering the contingency was carried out by taking the line 2-4 trips at 20 seconds. The results for bus frequency and voltage magnitudes are shown in Figs.3-6 for both models. It is observed that at initial condition the system is stable, and after contingency occurs the system shows oscillatory behavior. The table 9, it is shown that the loadability margins are going to increased when an PV generation model replaces the conventional generator particularly in model 2 which is PV-control mode. It can be noticed that voltage regulator which is used in PV-control mode has a same effect on system damping similar as of PSS. Fig 7 and Fig. 8 shows that by tuning the gains of voltage controller properly the system damping can be increased until the oscillations were totally disappear..2 Volltage profiles for mdel 2: contingency conditions.2 voltage profiles for model : Normal conditions. 0.9 0.8 0.8 V Bus 0 V Bus 0 0.7 0.6 0.6 0.5 V Bus 4 0.4 V Bus 4 0.4 0.2 0.3 0.2 0 0.2 0.4 0.6 0.8.2.4.6 Loading Parameter l (p.u.) Figure 9: Voltage profile: Model : normal condition.2. 0.9 Volltage profiles for model 2: normal conditions.2. 0 0 0.2 0.4 0.6 0.8.2.4.6 Loading Parameter l (p.u.) Figure 0: Voltage profile: Model : contingency Volltage profiles for condition mdel 2: contingency conditions 0.9 0.8 V Bus 0 0.8 V Bus 0 0.7 0.7 0.6 V Bus 4 0.6 V Bus 4 0.5 0.5 0.4 0.4 0.3 0.3 0.2 0 0.2 0.4 0.6 0.8.2.4.6.8 Loading Parameter l (p.u.) Figure : Voltage profile: Model 2: normal conditions 0.2 0 0.2 0.4 0.6 0.8.2.4.6 Loading Parameter l (p.u.) Figure 2: Voltage profile: Model 2: contingency conditions 205

.0006 Time domain simulation for a Line 2-4 trip for Model : Bus frequency..0005.0004.0003 w Syn.08.06.0002.000.04.02 V Bus 0 0.9999 0.9998 0.98 V Bus 4 0.9997 0 0 20 30 40 50 Figure 3: Bus frequency: Model 0.96 0 0 20 30 40 50 Figure 4: Voltage magnitudes: Model.0007 Time domain simulation for a Line 2-4 trip for model 2 : bus frequency..0006.0005.0004.0003 w Syn.08.06.04.0002.000 0.9999.02 0.98 V Bus 0 V Bus 4 0.9998 0 0 20 30 40 50 60.0009 Figure 5: Bus frequency: Model 2 0.96 0 0 20 30 40 50. Figure 6: Voltage magnitudes: Model 2.0008.0007.0006 w Syn.08.06.0005.0004.0003.0002.000.04.02 0.98 V Bus 0 V Bus 4 0.9999 0 0 20 30 40 50 Figure 7: Bus frequency with properly tuned gains: Model 2 0.96 0 0 20 30 40 50 Figure 8: Voltage magnitudes with properly tuned gains: Model 2 5 Conclusion The impact of high PV penetration on power system stability considering the small signal stability analysis, voltage stability analysis and angle stability analysis are successfully investigated in this paper. In this work two different types of PV models are put forward and being analyzed deeply. The detrimental and beneficial impact of both the model are shown at various levels of PV penetration are studied for power system. The comparison for with and without PV penetration are performed and shown. Critical modes are identified using the eigenvalue analysis. Time domain simulation confirms the results. It can conclude that the PV generation in PV-control mode does not much affect the voltage stability compare PQ-control mode. The PV generation may improve system stability by increasing the loadability margin at which oscillatory behaviour can be observed. Also, the effect of tuning the gains is demonstrated. 206

References [] www.mnre.gov.in [2] Behnam Tamimi, Claudio Cañizares, Kankar Bhattacharya, Modeling and Performance Analysis of Large Solar Photo- Voltaic Generation on Voltage Stability and Inter-area Oscillations IEEE PES General Meeting, July 20. [3] Madhur A. Jagpat, S. L. Shaikh, The effect of high PV penetration on the small signal stability of the power system using PSAT Proceedings of ITResearch International Conference, 22nd June 205. [4] S. Eftekharnejad, V. Vittal, G. T. Heydt, B. Keel, and J. Loehr, Impact of increased penetration of photovoltaic generation on power systems, IEEE Trans. Power Syst., vol. 28, no. 2, pp. 893 90, May 203. [5] Behnam Tamimi, Claudio Cañizares, and Kankar Bhattacharya, System Stability Impact of Large-Scale and Distributed Solar Photovoltaic Generation: The Case of Ontario, Canada IEEE Transactions on Sustainable Energy, Vol. 4, No. 3, July 203. [6] Sara Eftekharnejad, Vijay Vittal, Gerald Thomas Heydt, Brian Keel, and Jeffrey Loehr, Small Signal Stability Assessment of Power Systems With Increased Penetration of Photovoltaic Generation: A Case Study IEEE Transactions on Sustainable Energy, Vol. 4, No. 4, October 203. [7] S. Bu, "Probabilistic analysis of small-signal stability of large-scale power systems as affected by penetration of wind generation", IEEE Trans. Power Syst., vol. 27, no. 2, pp. 762-770, 202. [8] P. Kundur, Power System Stability and Control, ser. EPRI Power System Engineering Series. New York, NY, USA: McGraw-Hill, 994. 207