CAPACITOR PLACEMENT IN UNBALANCED POWER SYSTEMS

Similar documents
J. Electrical Systems x-x (2010): x-xx. Regular paper

K. Valipour 1 E. Dehghan 2 M.H. Shariatkhah 3

Optimal Capacitor placement in Distribution Systems with Distributed Generators for Voltage Profile improvement by Particle Swarm Optimization

A PROPOSED STRATEGY FOR CAPACITOR ALLOCATION IN RADIAL DISTRIBUTION FEEDERS

Optimal Capacitor Placement in Distribution System with Random Variations in Load

PROPOSED STRATEGY FOR CAPACITOR ALLOCATION IN RADIAL DISTRIBUTION FEEDERS

Comparison of Loss Sensitivity Factor & Index Vector methods in Determining Optimal Capacitor Locations in Agricultural Distribution

Optimal Capacitor Placement in Radial Distribution System to minimize the loss using Fuzzy Logic Control and Hybrid Particle Swarm Optimization

2008 IEEE. Personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes

THE loss minimization in distribution systems has assumed

A Comparative Study Of Optimization Techniques For Capacitor Location In Electrical Distribution Systems

A Novel Analytical Technique for Optimal Allocation of Capacitors in Radial Distribution Systems

Optimal Performance Enhancement of Capacitor in Radial Distribution System Using Fuzzy and HSA

Simultaneous placement of Distributed Generation and D-Statcom in a radial distribution system using Loss Sensitivity Factor

CHAPTER 2 LOAD FLOW ANALYSIS FOR RADIAL DISTRIBUTION SYSTEM

Elevated Neutral to Earth Voltages Due to Harmonics A T&D Update

Performance Improvement of the Radial Distribution System by using Switched Capacitor Banks

OPTIMAL CAPACITORS PLACEMENT IN DISTRIBUTION NETWORKS USING GENETIC ALGORITHM: A DIMENSION REDUCING APPROACH

CAPACITOR PLACEMENT USING FUZZY AND PARTICLE SWARM OPTIMIZATION METHOD FOR MAXIMUM ANNUAL SAVINGS

A LOOP BASED LOAD FLOW METHOD FOR WEAKLY MESHED DISTRIBUTION NETWORK

Optimal capacitor placement in radial distribution networks with artificial honey bee colony algorithm

OPTIMAL CAPACITOR PLACEMENT USING FUZZY LOGIC

Optimal Placement & sizing of Distributed Generator (DG)

Journal of Artificial Intelligence in Electrical Engineering, Vol. 1, No. 2, September 2012

Optimal Compensation of Reactive Power in Transmission Networks using PSO, Cultural and Firefly Algorithms

Optimal Capacitor Placement and Sizing on Radial Distribution System by using Fuzzy Expert System

Farzaneh Ostovar, Mahdi Mozaffari Legha

The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of Unbalanced Three Phases Electrical Distribution System

K. MAHESH 2 Asst Prof & HOD, Sri kottam tulasi reddy memorial college of engineering, AP-INDIA

Harmonic Modeling of Networks

Real Time Voltage Control using Genetic Algorithm

Classification of Capacitor Allocation Techniques

Distribution System Power Loss Reduction by Optical Location and Size of Capacitor

OPTIMAL LOCATION AND SIZING OF DISTRIBUTED GENERATOR IN RADIAL DISTRIBUTION SYSTEM USING OPTIMIZATION TECHNIQUE FOR MINIMIZATION OF LOSSES

Meta Heuristic Harmony Search Algorithm for Network Reconfiguration and Distributed Generation Allocation

Optimal capacitor placement and sizing via artificial bee colony

Optimal placement of capacitor in distribution networks according to the proposed method based on gradient search

International Journal of Mechatronics, Electrical and Computer Technology

Capacitor Placement for Economical Electrical Systems using Ant Colony Search Algorithm

Power Flow Analysis of Radial Distribution System using Backward/Forward Sweep Method

EE5250 TERM PROJECT. Report by: Akarsh Sheilendranath

LOAD FLOW SOLUTION FOR UNBALANCED RADIAL DISTRIBUTION SYSTEMS

Optimal Placement of Multi DG Unit in Distribution Systems Using Evolutionary Algorithms

Congestion Alleviation using Reactive Power Compensation in Radial Distribution Systems

Voltage Profile Improvement by Capacitor Placement and Control in Unbalanced Distribution Systems Using Differential Evolution Algorithm

Optimal Placement of Capacitor Banks in order to Improvement of Voltage Profile and Loss Reduction based on PSO

Energy Conversion and Management

Application of Monte Carlo Simulation to Multi-Area Reliability Calculations. The NARP Model

OPTIMAL PLACEMENT AND UTILIZATION OF PHASOR MEASUREMENTS FOR STATE ESTIMATION

NEW EVOLUTIONARY TECHNIQUE FOR OPTIMIZATION SHUNT CAPACITORS IN DISTRIBUTION NETWORKS

Multiple Distribution Generation Location in Reconfigured Radial Distribution System Distributed generation in Distribution System

A Study of the Factors Influencing the Optimal Size and Site of Distributed Generations

Simulation of Random Variation of Three-phase Voltage Unbalance Resulting from Load Fluctuation Using Correlated Gaussian Random Variables

DISTURBANCE LOAD MODELLING WITH EQUIVALENT VOLTAGE SOURCE METHOD IN GRID HARMONIC ASSESSMENT

Analytical approaches for Optimal Placement and sizing of Distributed generation in Power System

LINE FLOW ANALYSIS OF IEEE BUS SYSTEM WITH THE LOAD SENSITIVITY FACTOR

ELEC4612 Power System Analysis Power Flow Analysis

PARTICLE SWARM OPTIMIZATION BASED APPROACH FOR LOSS REDUCTION IN UNBALANCED RADIAL DISTRIBUTION SYSTEM

Optimal PMU Placement for Power System State Estimation with Random Communication Packet Losses

J. Electrical Systems 10-1 (2014): Regular paper. Optimal Power Flow and Reactive Compensation Using a Particle Swarm Optimization Algorithm

An Improved Method for Determining Voltage Collapse Proximity of Radial Distribution Networks

KINGS COLLEGE OF ENGINEERING Punalkulam

Fast Decoupled Power Flow for Unbalanced Radial Distribution Systems

Distributed vs Bulk Power in Distribution Systems Considering Distributed Generation

Nowadays computer technology makes possible the study of. both the actual and proposed electrical systems under any operating

ABSTRACT I. INTRODUCTION

The AR OPF: an Exact Convex Formulation for the Optimal Power Flow in Radial Distribution Networks

DISTRIBUTION SYSTEM OPTIMISATION

Chapter-2 Literature Review

A Data-driven Voltage Control Framework for Power Distribution Systems

ENERGY LOSS MINIMIZATION AND RELIABILITY ENHANCEMENT IN RADIAL DISTRIBUTION SYSTEMS DURING LINE OUTAGES

Optimal DG allocation and sizing in a Radial Distribution System using Analytical Approach

Loadability Enhancement by Optimal Load Dispatch in Subtransmission Substations: A Genetic Algorithm

Fast Energy Loss Computation and Fuzzy-Based Shunt Capacitor Insertion

OPTIMAL CAPACITOR PLACEMENT AND SIZING IN A RADIAL DISTRIBUTION SYSTEM USING CLONAL SELECTION ALGORITHM

Network reconfiguration and capacitor placement for power loss reduction using a combination of Salp Swarm Algorithm and Genetic Algorithm

Optimal capacitor placement and sizing using combined fuzzy-hpso method

CHAPTER 5 STEADY-STATE ANALYSIS OF THREE-PHASE SELF-EXCITED INDUCTION GENERATORS

OVER CURRENT RELAYS PROTECTIVE COORDINATION IN DISTRIBUTION SYSTEMS IN PRESENCE OF DISTRIBUTED GENERATION

Power Loss Reduction in Radial Distribution System by Using. Plant Growth Simulation Algorithm

OPTIMAL DG AND CAPACITOR ALLOCATION IN DISTRIBUTION SYSTEMS USING DICA

Power Distribution in Electrical Grids

OPTIMAL POWER FLOW BASED ON PARTICLE SWARM OPTIMIZATION

A PARTICLE SWARM OPTIMIZATION TO OPTIMAL SHUNT-CAPACITOR PLACEMENT IN RADIAL DISTRIBUTION SYSTEMS

The Existence of Multiple Power Flow Solutions in Unbalanced Three-Phase Circuits

FEEDER RECONFIGURATION AND CAPACITOR SETTINGS ON DISTRIBUTION SYSTEMS : AN APPROACH FOR SIMULTANEOUS SOLUTION USING A GENETIC ALGORITHM

AN IMMUNE BASED MULTI-OBJECTIVE APPROACH TO ENHANCE THE PERFORMANCE OF ELECTRICAL DISTRIBUTION SYSTEM

Failure Rate Modification For Evaluating Reliability Indices A Case Study of IEEE 30 Bus System For Optimal Capacitor Placement

Study on Identification of Harmonic Contributions Between Utility and Customer

Study on Fault Location in the T-Connection Transmission Lines Based on Wavelet Transform

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

Two-Layer Network Equivalent for Electromagnetic Transients

An Evolutionary Algorithm for Reactive Power Compensation in Radial Distribution Networks

EFFECT OF TEMPERATURE CHANGE ON THE RESISTANCE OF TRANSMISSION LINE LOSSES IN ELECTRICAL POWER NETWORK

A Comparison of Local vs. Sensory, Input- Driven, Wide Area Reactive Power Control

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

Performance analysis and comparison of load flow methods in a practical distribution system

Fast Power Loss Computation and Shunt Capacitor Insertion Using Fuzzy Logic Technique

AN OPTIMIZED FAST VOLTAGE STABILITY INDICATOR

Smart Grid State Estimation by Weighted Least Square Estimation

Transcription:

CAPACITOR PLACEMET I UBALACED POWER SSTEMS P. Varilone and G. Carpinelli A. Abur Dipartimento di Ingegneria Industriale Department of Electrical Engineering Universita degli Studi di Cassino Texas A&M University 03043 Cassino, Italy College Station, Texas, U.S.A varilone@unicas.it, carpinelli@ing.unicas.it abur@ee.tamu.edu Abstract This paper presents a capacitor placement method for three phase unbalanced power systems. The method aims to minimize not only the power losses and capacitor costs, but also the distortions due to harmonics present in the power system. The proposed method is capable of accomplishing this objective for both balanced and unbalanced operating conditions. One of the objectives of this paper is to demonstrate the significant differences in the results of capacitor placement studies when unbalanced systems are approximated by their positive sequence single phase equivalents. Furthermore, the effects of taking harmonic distortions into account during the capacitor placement procedure are also demonstrated. umerical examples on a distribution test power system are provided to illustrate the method. Keywords: Optimization, capacitor placement, loss minimization, harmonic distortion, unbalanced operation, distribution systems. 1 ITRODUCTIO Power distribution systems contain shunt capacitors at various strategic locations in order to maintain a desired voltage profile, correct power factor and reduce power losses along feeders. When dealing with a large scale distribution system containing several feeders and their laterals, deciding on the best locations and sizes of these capacitors becomes a complicated optimization problem. In addition to the scale of the problem, there are other issues such as the discrete nature of capacitor sizes, operational limits on voltages and feeder loadings, that need to be addressed. Effective solution algorithms for balanced distribution feeders have been developed [1,2]. These solutions mainly utilize the positive sequence network model and the associated power flows in formulating the problem. Hence, the results do not directly apply for systems containing feeders with missing phases, unevenly loaded feeders or shunt capacitors on single or double phase feeders. Three phase unbalanced distribution systems are later studied in [3,4] where simulated annealing and genetic algorithms are respectively used to solve this more complicated problem. A simplified formulation and the MIOS optimization package are used to solve the same problem in [5]. Recently, distribution systems are populated with nonlinear loads or control devices that generate unwanted harmonics in the systems. Harmonics are known to cause overvoltages under certain network configurations involving shunt capacitors. This issue is raised and a solution is proposed for minimizing harmonic overvoltages in [6]. A practical method that avoids convergence problems and incorporates discrete nature of capacitor banks along with the voltage distortions due to the installed capacitors, is developed and presented in [7]. This method is based on the balanced three phase operation and therefore analyzes the positive sequence network only. In this paper, the work reported in [7] will be extended to the more general case of the three phase unbalanced operation. Several distribution feeders are known to have line sections carrying a mixture of single, double or three phase loads. Such systems as well as those having full three phase but unbalanced loads can be studied using the presented method in this paper. In addition to the cost of losses and capacitor installations, it is possible to associate a cost with the harmonic distortions as discussed in [8-9]. Hence, the problem is formulated in such a way that both network losses and harmonics are minimized along with the cost of capacitors placed for this purpose. The paper is organized such that the problem description is presented first. This is followed by the sections describing the details of the three phase power flow and linear harmonic analysis modules, which make up the main computational engines of the overall algorithm. Simulation results obtained using the developed program and a test system will be presented next. Conclusions and suggestions on future work will be presented in the final section. 2 DESCRIPTIO OF THE PROBLEM The objective of the presented method is to determine the best locations and sizes of shunt capacitors for each phase, so that the total cost of the capacitors, of the total power losses of the network and the harmonic distortion of the network are minimized. This objective should be met subject to the network three-phase power flow equations as well as the limits on the bus voltage and current magnitudes, harmonic indices (HI) and the total number of capacitor units to be installed. Hence, it

can be formulated as the following optimization problem: 2.1.1 Cost of Capacitors, J C = CC U C c : is the cost vector for capacitor units at each bus. U : is the vector of capacitor units placed at each bus. 2.1.2 Cost of Losses, J L = CL (PG PD )T C L : is the cost of a per unit energy loss P G : is the total generation at (X,U) P D : is the total load T : is the loss duration (X,U): is the power flow solution corresponding to the installed capacitor vector of U. The cost of demand lost can be also incorporated without difficulty. 2.1.3 Cost of Distortions, J IH The evaluation of the cost of the distortions is studied first by the authors in [8, 9]. These costs are assumed to be the sum of the operating costs and the aging costs. The operating costs refer to the costs of the incremental losses caused by the harmonics and the aging costs refer to the incremental costs due to the premature aging of the components caused by the harmonics. Details can be found in [8, 9]. 2.2 The Constraints Each solution should satisfy the three-phase power balance equations at the fundamental frequency. Thus, a full three-phase power flow solution is to be run to verify this constraint. This solution will also be used to check the limit violations at fundamental on bus voltages and line currents. The effect of each capacitor unit on the distortions of the bus voltages will have to be also checked. This is accomplished by solving a linear three-phase harmonic analysis problem where all nonlinear loads are represented by their harmonic current injections. Details of this computation are discussed in a later section. Minimize J(X,U) = J C + J L + J IH 3 SOLUTIO METHOD Subject to Three-phase PF Eq.s at fundamental and harmonics V, I limits HI limits Limits on number of cap.s where the terms of the objective function and constraint list are defined below. 2.1 The Objective function, J The objective function assumes a given loading level for the system. While it is possible to extend this function to a sum of similar functions, so that a number of loading levels can be accounted for, this will not be done here. All simulation results and the discussion of the proposed algorithm will be based on single loading assumption. Such an extension can however be incorporated into the presented algorithm without much difficulty. The three terms that make up the objective function are described below: T The above described optimization problem is solved by using a simple yet effective procedure, which is developed and successfully employed in solving the single phase problem in [7]. The main idea behind the proposed procedure is based on sequential placement of discrete capacitor units of incremental size. It is assumed that each phase of any bus can be placed an incremental discrete capacitor at each optimization step (three-phase bank in case of three-phase bus, singlephase bank otherwise). If capacitor installations are prohibited for any of the buses, then this condition can easily be enforced by leaving out that bus from the bus list. Furthermore, if different buses have different sizes of unit capacitors, then placement of unit capacitors can be accordingly modified to suit each bus. Therefore, the physical constraints that relate to the discrete nature of capacitor installations as well as the nonhomogeneity of the discrete units available for installations at different buses, are naturally accounted for without any complex logic. At each step of the optimization procedure, the three phase power flow solution as well as the harmonics of the bus voltages corresponding to the incremental addition of unit capacitors at each possible bus, will have to be computed. ote that, the purpose of these computations is to obtain and compare the values of the objective function for all possible incremental installations and choose the one that reduces the objective function the most. It is also noted that for purposes of comparing effects of unit capacitor installations at different buses on the objective function, approximate threephase power flow solutions can be used. Once a candidate is selected, then an accurate solution can be obtained for the selected configuration only. A fast but approximate three phase power flow solution is implemented for the first part. A three phase linear harmonic analysis is carried out for the calculation of distortions. These are discussed in more detail below. 3.1 Fast Three-phase Power Flow Update The three-phase power flow solution is affected incrementally each time a unit capacitor is added at a system bus. This incremental change can be captured by expressing the power flow solution by its first order approximation. Consider the three phase power flow equations given by: f(x,u) = 0 (1) The first order Taylor approximation will be: [F x (X 0,U 0 ) ] [ dx ] = - [ F u (X 0, U 0 ) ] du i (2)

ote that du i is the unit capacitor added at node i, one phase of a bus and the functions F x and F u represent the gradient of f(x,u) evaluated with respect to X and U respectively. At each optimization step, the most recent operating point will be denoted by (X 0,U 0 ) which will depend upon the way the optimization proceeded up till that point. The updated power flow solution will then be obtained as: X = X 0 + dx (3) This procedure will be repeated as many times as the number of nodes excluding those where no capacitors are allowed to be placed. Upon computing the objective function J(X,U) for all cases, the solution which yields the smallest objective function will be selected. A full three phase AC power flow solution will be obtained and all operating constraints will be checked for this case. In case the solution violates any one of the limits, the same procedure will be repeated for the second best solution. This procedure will continue until a feasible solution is obtained. If no solution can be found satisfying all the constraints, then the optimization procedure will be terminated. Otherwise, it will proceed to the next optimization iteration. 3.2 Calculation of distortions In parallel with the fundamental frequency power flow solution, a solution for each dominant harmonic present in the network will have to be obtained so that the corresponding effects of the power system harmonics can be evaluated. This is accomplished by solving the network s linear harmonic equations given by: [ n ] [V n ] = [I n ] (4) where [ n ], [V n ] and [I n ] are the three phase network admittance matrix, bus voltage vector and independent current source vector evaluated at the n-th harmonic frequency. The admittance matrix is modified each time a unit capacitor is added at a bus. Also note that, the harmonic injections of nonlinear devices are modeled according to the recommendations of the IEEE PES Working Group on Harmonics Modeling and Simulation [10-11] where it is suggested that the phase angles of the injected harmonic current sources be adjusted according to the phase angle of the fundamental with respect to reference. A Matlab-based program is developed in order to evaluate the above described procedure for general three phase unbalanced system operation. At this time, the program is implemented for a single loading level and therefore the capacitor placement can be tested only for fixed capacitor types. However, it can be easily modified to account for seasonal or daily load variations of the bus loads. A flow chart of the procedure implemented by this program is shown in Figure 1. ext section will present several representative cases which are simulated using the developed program. stop stop Select the capacitor that yields the minimal J K > bus Capacitor exists? AC Three Phase Power Flow Is J reduced? Check the constraints start AC Three Phase Power Flow set k=1 Approximate operating point when a cap. unit is added at bus k Compute the objective function J Satisfied? Maximal # of capacitor reached? stop k=k+1 Select the next qualifying bus Figure 1: Flowchart of the proposed procedure 4 SIMULATIO RESULTS The simulations are run using the three phase unbalanced IEEE 13-bus test system shown in Figure 2 [11]. This system contains a mixture of single, double and three phase lines and loads, making it quite suitable for evaluating the proposed method. ote that the system lines 684-653 and 684-611 are single phase; lines 671-684, 632-645, 645-646 are two phase and the remaining lines are three phase. The complete network data and parameters can be found in [11]. The system contains loads that are linear, non linear, and/or unbalanced. The harmonic producing loads include fluorescent lighting, adjustable speed drives for

heat pumps and non-specific sources such as PCs, TVs, etc. The load data reported in [11] are reduced by 50%, since the voltage distortions are found to exceed the IEEE-519 recommended limits [12] before the placement of any capacitors. Unit capacitors available at any bus are assumed to come in discrete sizes of 50 kvar. The unit cost of capacitors are reported in [13] while the unit cost of energy are reported in [14]. The constraint limits are assumed as 105% for the voltages at fundamental, 3% for the single voltage harmonics and 5% for the total harmonic distortion. Several cases are simulated. The following results will be presented as representative cases. 4.1 Case 1 In this case the sensitivity of capacitor placement to the objective function structure is investigated. The objective function is first considered as the sum of the losses and the capacitor costs only. The harmonic costs are then introduced into the objective function, to observe the significance of this consideration in the outcome of the optimization process. In order to simplify the analysis, the harmonic index is assumed to be simply the total harmonic distortion and its associated cost is evaluated so as to have the same cost of losses and 646 645 632 633 634 611 684 671 650 692 675 function of capacitor bank additions. The objective functions are normalized to make the comparison easy. It should be noted that in the case without THD term the placement procedure is terminated at the fifth step due to a constraint violation. The violated constraint is the value of the fundamental voltage at bus #675, which exceeds the specified limit of 1.05 p.u., when an additional unit capacitor is attempted to be placed after the fourth step. ote that, in Fig.3, the solid lines represent the variation of the objective function J until the optimal solution is reached. The dashed lines indicate how J would have varied, had the optimization procedure not been terminated. In the top curve, the procedure terminates because the minimum is reached. In the bottom curve, it is terminated by the constraint violation after step 4 and no other solution yielding a lower J within the constraints can be found at the fifth step. 4.2 Case 2 In this case the sensitivity of the capacitor placement procedure to the specified constraints is considered. Initially, constraints identical to those used in Case 1, are considered. These limits are subsequently relaxed (110% for the voltages at fundamental, 5% for the single voltage harmonics and 8% for the total harmonic distortion), in order to observe their significance on the Table 1:Capacitor Placement Results of Case 1 Bus code 675 611 Phase code 1 2 3 1 2 3 Without THD cost 2x50 2x50 2x50 2x50 With THD cost 2x50 2x50 2x50 J [p.u.] 652 680 Figure 2: etwork Diagram for the 13-bus test system 1.05 1 harmonics in the system without capacitors. The locations and sizes of the capacitors that yield the minimum objective function in both cases are listed in Table 1. As evident from the table, two unit capacitor banks are located at the most distant three phase load bus (note that bus #680 is unloaded) and two other unit banks are located at a single phase bus. On the other hand, the capacitor banks at the single phase bus are no longer allocated when the objective function takes into account the THD cost. Fig. 3 shows the variation of the two objective functions one with and one without the THD cost term, as 0.95 0.9 0.85 + J includes THD term o J excludes THD term 0 1 2 3 4 5 6 7 umber of capacitors bank Figure 3: Variation of objective functions versus number of capacitors bank

Table 2: Capacitor Placement Results of Case 2 Bus code 675 611 645 646 Phase code 1 2 3 1 2 3 1 2 3 1 2 3 Without THD cost With THD cost 2x50 2x50 2x50 2x50 1x50 1x50 2x50 2x50 2x50 Table 3: Capacitor Placement Results of Case 3 Bus code 675 611 692 671 652 645 646 Without THD cost With THD cost 2x150 1x150 2x150 1x150 1x150 1x150 1x150 2x150 1x150 2x150 1x150 1x150 1x150 1x150 outcome of the optimization process. The locations and sizes of the capacitors that yield the minimum objective function in case of relaxed limits are listed in Table 2. It follows from the analysis of the results in Tables 1 and 2 without THD cost that the same capacitor banks are located in the three phase bus #675; two more banks are located at the single phase busses #645 and #646. When the objective function takes into account the THD cost, none of the capacitor banks in single phase busses are allocated. 4.3 Case 3 In the absence of a three phase capacitor placement program such as the one described here, an approximate solution may be attempted by using a single phase program that works for balanced systems. This means that all unbalanced loads and structurally non-symmetric lines will be replaced by balanced components and hence the solution will be different. This case investigates the errors involved in such an approximation. The case compares the capacitor placement results of Case 1 with that of a fully balanced version of the same system. Thus, the procedure of Section 3 is applied to a balanced system which is created by approximating the unbalanced system of Case 1 by a balanced version. This is accomplished by balancing all the lines (all lines are assumed three phase and structurally symmetric) and loads (all loads are assumed three phase balanced loads) of the unbalanced system. Moreover, harmonics of order 5, 7, 11 and 13 only have been taken into account with consequent reduction of harmonic distortion levels. The locations and sizes of the capacitors (all 150 kvar three phase banks) that yield the minimum objective function for this fully balanced case are listed in Table 3. Results shown in the table indicate that in both cases capacitor banks are located in the same three phase buses #675, #611, #692, #671, #652, #645, #646. A comparison of the results shown in Tables 1 and 3 implies that in the case of the balanced system a much larger number of capacitors are required to achieve the minimum J. This is due to both the reduced level of voltage harmonics and the larger amount of total reactive load in the balanced system. 5 COCLUSIOS This paper presents a capacitor placement procedure for three phase unbalanced power systems. The proposed procedure not only accounts for system losses and capacitor costs, but also for harmonic distortion of bus voltages and the effects of unbalanced operation. The recent proliferation of nonlinear loads in distribution systems makes the issue of harmonic pollution an important one to be considered in any of the distribution automation functions such as capacitor sizing and location. This paper presents a simple yet effective solution to the problem. umerical examples demonstrating the effectiveness of the procedure under both balanced and unbalanced operating conditions are provided. Future work will involve more realistic representation of the harmonic cost in the objective function. REFERECES [1] M. Baran, F.F. Wu, Optimal Capacitor Placement on Radial Distribution systems, IEEE Trans. on Power Delivery, Vol.4, o.1, Jan. 1989, pp.725-734. [2] J. J. Grainger, and S. H. Lee, Optimum Size and Location of Shunt Capacitors for Reduction of Losses on Distribution Feeders, IEEE Trans. on PAS, Vol.100, Mar.1981, pp.1105-1118. [3] H-D. Chiang, J-C. Wang, J. Tong and G. Darling, Optimal Capacitor Placement, Replacement and Control in Large-Scale Unbalanced Distribution

Systems: System Modeling and A ew Formulation, IEEE Trans. on Power Systems, Vol.10, o.1, February 1995, pp.356-362. [4] C.S. Chen, C.T. Hsu and.h. an, Optimal Distribution Feeder Capacitor Placement Considering Mutual Coupling Effect of Conductors, IEEE Trans. on Power Delivery, Vol.10, o.2, April 1995, pp.987-994. [5] K.. Miu, H-D. Chiang and G. Darling, Capacitor Placement, Replacement and Control in Large- Scale Distribution Systems by a GA-Based Two- Stage Algorithm, IEEE Trans. on Power Systems, Vol.12, o.3, August 1997, pp.1160-1166. [6]. Baghzouz, S. Ertem, Shunt Capacitor Sizing for Radial Distribution Feeders with Distorted Substation Voltages, IEEE Trans. on Power Delivery, Vol.5, April 1990, pp.650-657. [7] Bei Gou and A. Abur, Optimal Capacitor Placement for Improving Power Quality, Paper SM 011. Proceedings of IEEE/PES Summer Meeting, July 18-22, 1999, Edmonton, Canada. [8] P. Caramia, G. Carpinelli, E. Di Vito, A. Losi and P. Verde, Probabilistic Evaluation of the Economical Damage due to the Harmonic Losses in Industrial Energy Systems, IEEE Trans. on Power Delivery, Vol.11, o.2, 1996, pp.1021-1031. [9] P. Caramia, G. Carpinelli, A. Russo, P. Varilone, P. Verde: An Integrated Probabilistic Harmonic Index, IEEE PES 2002 Winter Meeting, ew ork (USA), 27-31 January 2002 [10] IEEE Task Force on Harmonics Modeling and Simulation, Modeling and Simulation of the Propagation of Harmonics in Electric Power etworks Part I: Concepts, Models and Simulation Techniques, IEEE Trans. on Power Delivery, Vol. 11, o. 1, 1996, pp. 452-465 [11] IEEE Task Force on Harmonics Modeling and Simulation, Modeling and Simulation of the Propagation of Harmonics in Electric Power etworks Part II: Sample Systems and Examples, IEEE Trans. on Power Delivery, Vol. 11, o. 1, 1996, pp. 466-474 [12] IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Std 519-1992, IEEE, ew ork,, April 1993. [13] A.E. Emanuel, C. Kawann, Passive Shunt Harmonic Filters for Low and Medium Voltage: A Cost Comparison Study, IEEE Trans. on Power Systems, Vol. 11, o. 4, 1996, pp. 1825-1831 [14] T.T. Chang, H. Chang, Application of Differential Evolution to Passive Shunt Harmonic Filter Planning, 8 th IEEE ICHQP, Athens (Greece), 1998, pp. 149-153