Draft for comment (613) Public Works Canada Design & Construction Technology DRAn' 1 July, Computer-Aided Design Centre (CAD) TSS COPY

Similar documents
Appendix 5.A11: Derivation of solar gain factors

WC Engineering Corp Touchton Rd., Bldg. 100, Suite 150 Jacksonville, FL Attn: Michael Jones May 25, 2017

MDSRC Proceedings, December, 2017 Wah/Pakistan. Cooling load analysis by CLTD and RLF. Sher ali nawaz 1 Muzammil shahbaz 2

Chapter Seven. Solar Energy

A SIMPLE MODEL FOR THE DYNAMIC COMPUTATION OF BUILDING HEATING AND COOLING DEMAND. Kai Sirén AALTO UNIVERSITY

(Refer Slide Time: 00:01:19 min)

Greenhouse Steady State Energy Balance Model

Chapter 2 Available Solar Radiation

The Numerical Psychrometric Analysis

CZECH TECHNICAL UNIVERSITY IN PRAGUE FACULTY OF MECHANICAL ENGINEERING DEPARTMENT OF ENVIRONMENTAL ENGINEERING

CAE 331/513 Building Science Fall 2016

ESTIMATION OF AUTOMOBILE COOLING LOADS FOR AIR CONDITIONING SYSTEM DESIGN

SENSITIVITY OF THE SOLAR HEAT GAIN COEFFICIENT OF COMPLEX FENESTRATION SYSTEMS TO THE INDOOR CONVECTION COEFFICIENT

Fundamentals of light

Fundamentals of light

Taking the garbage out of energy modeling through calibration

''* Although numerous references are available for these traditional methods, the most convenient one

Thermal Comfort; Operative Temperature in the Sun

Validation of IDA Indoor Climate and Energy

Glazing selection for solar design

An Analytical Verification Test Suite for Building Fabric Models in Whole Building Energy Simulation Programs

COMMERCIAL HEAT GAIN - HEAT LOSS CALCULATION LOAD FORM

ApacheLoads Calculation Methodology as used in Revit MEP 2008 <Virtual Environment> 5.7

Ttioning cooling load for sizing cooling equipment and a general

AR/IA 241 LN 231 Lecture 4: Fundamental of Energy

Aalborg Universitet. Comparative Test Case Specification Larsen, Olena Kalyanova; Heiselberg, Per Kvols. Publication date: 2007

The Choice of Supply Design Conditions

Double-Skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of Direct Solar Radiation

DEVELOPMENT OF COOLING LOAD TEMPERATURE DIFFERENTIAL VALUES FOR BUILDING ENVELOPES IN THAILAND

5. Thermal Design. Objective: Control heat flow to: Maintain comfortable indoor conditions

Energy flows and modelling approaches

TREES Training for Renovated Energy Efficient Social housing

Nigusse, B.A., and J.D. Spitler Refinements and Improvements to the Radiant Time Series Method. ASHRAE Transactions 116(1):

BACK TO BASICS: PIPE INSULATION

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND

Effect of Installing a Curved Venetian Blind to the Glass Window on Heat Transmission

Cooling of Electronics Lecture 2

WALL D*TA PRINT-OUT. 3 nmth ZONE

1. Base your answer to the following question on the weather map below, which shows a weather system that is affecting part of the United States.

Calculation Method For Summer Cooling With Radiant Panels

IDA ICE CIBSE-Validation Test of IDA Indoor Climate and Energy version 4.0 according to CIBSE TM33, issue 3

Simplified Collector Performance Model

*%2V. M2\d. c, a National Research Council of Canada. w2e*c- 1 I. Conseil national de recherches du Canada

PASSIVE SOLAR HEATING

EFFECT OF INTERNAL LONG WAVE RADIATION AND CONVECTION ON FENESTRATION SIMULATION

Solar Radiation 230 BTU s per Hr/SF. Performance Glazing Coatings, Layers & Gases

ABSTRACT INTRODUCTION OPTICAL CALCULATIONS

Model 3024 Albedometer. User s Manual 1165 NATIONAL DRIVE SACRAMENTO, CALIFORNIA WWW. ALLWEATHERINC. COM

BRE Client Report. Calculation of summertime solar shading performance for MicroLouvre. Prepared for: Smartlouvre. BRE Watford, Herts WD25 9XX

Principles of Energy Conversion Part 11A. Solar Energy Insolation

Winter Night. Thermos 6mm Outdoors # #

PROPOSAL OF SEVEN-DAY DESIGN WEATHER DATA FOR HVAC PEAK LOAD CALCULATION

Aalborg Universitet. Empirical Test Case Specification Larsen, Olena Kalyanova; Heiselberg, Per Kvols. Publication date: 2006

Thermal Properties, Moisture Diffusivity Chpt 8

Humidification requirements in economizer-type HVAC systems

CHAPTER 3. The sun and the seasons. Locating the position of the sun

Orientation of Building

Heat Transfer through Building Envelope

ARCHITECTURE IN THE DAYLIGHT

Load Calculations Heat Balance Method - Theory. Prof. Jeffrey D. Spitler School of Mechanical and Aerospace Engineering, Oklahoma State University

Solar Heated Greenhouse

Project 2. Introduction: 10/23/2016. Josh Rodriguez and Becca Behrens

Institut national des sciences appliquées de Strasbourg GENIE CLIMATIQUE ET ENERGETIQUE APPENDICES

Prentice Hall EARTH SCIENCE. Tarbuck Lutgens

Aalborg Universitet. Final Empirical Test Case Specification Larsen, Olena Kalyanova; Heiselberg, Per Kvols. Publication date: 2008

Baker House Dining Room: Thermal Balance Report. + Q c. + Q v. + Q s. + Q e. + Q heating. + Q appliances. =Q appliances,21h Q appliances, x H

UNIT TEST PRACTICE TEST

Interaction between building services and environment.

The Electrodynamics of a Pair of PV Modules with Connected Building Resistance

ABOUT UNCERTAINTIES IN SIMULATION MODELS FOR BUILDING SYSTEMS CONTROL

OPTICAL PROPERTIES OF THE COOKIT SOLAR COOKER

Radiant Heating Panel Thermal Analysis. Prepared by Tim Fleury Harvard Thermal, Inc. October 7, 2003

1D-HAM. Coupled Heat, Air and Moisture Transport in Multi-layered Wall Structures. Manual with brief theory and an example. Version 2.

Time Series Model of Photovoltaic Generation for Distribution Planning Analysis. Jorge Valenzuela

A Simulation Tool for Radiative Heat Exchangers

FUNDAMENTALS OF HVAC

Working of a SUNLUX SUNSCREEN

EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS

ASSESSING THE ERROR FROM FAILURE TO ACCOUNT FOR URBAN MICROCLIMATE IN COMPUTER SIMULATION OF BUILDING ENERGY PERFORMANCE

Enerpool v Swimming Pool Simulation Simulation File: C:\ENERPOOL\SANDA.EPL Run on: Fri Feb 07 19:27:

PNEUMATIC ENTHALPY COMPARATOR

Fundamentals of WUFI-Plus WUFI Workshop NTNU / SINTEF 2008

Solar irradiance measurement up to 2500nm with the Arcoptix FT-NIR

THERMAL COMFORT IN HIGHLY GLAZED BUILDINGS DETERMINED FOR WEATHER YEARS ON ACCOUNT OF SOLAR RADIATION. Dominika Knera 1 and Dariusz Heim 1

Chapter 1 Solar Radiation

CAE 331/513 Building Science Fall 2013

SEASONAL AND DAILY TEMPERATURES

How does the surface type and moisture content affect the surfaceʼs temperature?

Response function method

Heat Transfer: A Practical Approach - Yunus A Cengel Assignment 11 Fall 2003 Tuesday, November 18, 2003 Chapter 11, Problem 49

Heat Flow Calculations Made Using the Models 8386 and 8386A VELOCICALC Plus Air Velocity Meters Application Note ITI-124

INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS

Solar Radiation Protections on Façades: A Case Study in a Hot Semi-Humid Climate

BinMaker PRO. User Manual. InterEnergy Software for the Energy Industry. Version 4.0. Gas Technology Institute

Solar Control in Traditional Architecture, Potentials for Passive Design in Hot and Arid Climate

Why the Earth has seasons. Why the Earth has seasons 1/20/11

Radiation, Sensible Heat Flux and Evapotranspiration

Global Climate Change

Measured versus Calculated Roof Peak Sol-air Temperature in Hot-arid Regions

STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION

Transcription:

~------------ 6. (c) Public Works Canada Design & Construction Technology DRAn' 1 July, 1980 Draft for comment Computer-Aided Design Centre (CAD) TSS COPY DO NOT REMOVE User enquiries and requests for this or other CAD documentation: CAD Centre Public Works Canada 7E Sir Charles Tupper Building Riverside Drive Ottawa K1A OM2 (613) 998-9513 Not a publication. Do not cite as a reference or catalogue in library.

.......

The EAS program (Draft 1) computes the following hourly heating/cooling loads based on a constant room temperature of 75 F: sensible load to return air sensible load to spaoe latent load to space (CLr).. (CL 8 ) ( CLro) These loads are saved on a loads file for subsequent use in system simulation; the report of peak heating/cooling and heating/cooling consumptions refers to only the space sensible load. Hourly load calculations are performed for the following components: People Lights nfiltration Transmission through walls, roofs, and windows Solar radiation through windows 1

2.1 People 2.2 Lights These calculations are performed in imperial units (i.e., S input is converted before calculation) and on a unitized basis (per square foot of floor area). the load due to people is assumed to b~ _instantaneous; each person contributes 250 btu/hr of 0.1885 lb/hr of moisture. CLs = 250 (person per sq. ft.) CLm = 0.1885 * (person per sq. ft.).. sensible heat and The return air load due to lights is assumed to be instantaneous. CLr = W * 3.413 (fraction to RA) where W =input to lights (watts/sq. ft.) The remainder of heat from lights is considered in two parts. The convection portion is assumed to be instantaneous. CLs = W * 3.413 (1-fraction to RA) (1-fraction radiant) The calculation for the radiant portion uses the transfer function method to account for heat storage in the building mass. where CLs(t) - cooling load at time t CLs<t-1) - cooling load at time ( t-1) Q(t-1> - Q(t-2> heat gain at time (t-2) heat gain at time ( t-1) v 1,v 2,w 1 - transfer function Table ) coefficients (see 2

The heat gain is: Q(t) = W * 3.413 * (1-fraction to RA) * (fraction radiant) TABLE Transfer Function Coefficients for Radiant Portion of Lights Note: X 1 0 0 L 0.224 -.044 -.082 0.197 -.067 -.087 H 0.187 -.097-0.91 v 0.180 -.130-0.95 The transfer function for radiant portion of lights is essentially the same as for solar radiation except for a delay of 1 hour; this delay makes it consistent with the equations developed by Mitalas. 2.3 nfiltration Th~ load due to infiltration is considered instantaneous. The sensible load is: The latent load is: - specific heat of air (btu/lb F) - infiltration rate (lb/hr) - outdoor air temperature room air temperature - humidity ratio of outdoor air (lb/hr) - humidity ratio of room air 2.4 Transwtssions Through Walls, Roofs and Windows n order to simplify the input and decrease execution time, the EAS program does not use transfer functions for ca!culating the heat gain through walls and roofs. More significantly, outdoor dry bulb temperature is used rather than air temperature. This may result in a significant error when transmission through the roof is a major component of load; however, in most cases the error will be relatively small. 3

The C9Qling load ror transmission through walls, roofs and windows is computed using the transfer function: The heat gain is computed by: Q = u-value area (6 0 - Qi) cooling load at ~ime (t) cooling load at time (t-1) heat gain at time (t) heat gain at time (t-1) transfer function coefficients (see Table ) TABLE Transfer Function Coefficients for Transmission X L M H v Yo 1 703.681.676.670 v1 0 -.!)23 -.551 -.586 -.620 w1 0-0.82-0.87-0.91-0.95 2.5 Solar JladiatiOG TbJ:oougb Windows The cooling load due to solar radiation is calculated using the transfer fu~otion method: where cooling load :at time t cooling load at time (t-1) heat gain at time t heat gain at time (t-1) transfer function coefficients (see Table ) The heat gain is calculated by: where Ag SCg H = area of glass = shading coefficient of glass =.solar radiation through standard glass (1/8" DS) for the given orientation. (The effect of cloud cover is included in H.}

TABLE Transfer Function Coefficients for Solar Radiation X L M H v Vo 1 0.224 0.197 0.187 0.180 v1 0 -.044-0.067-0.097-0.130 w1 0-0.82-0.87-0.91-0.95 l J. 5

6 The EAS program uses values of solar radiation (direct normal and sky diffuse) read directly from the weather file for each hour. These values are treated as if they are measured data even though they may, in fact, have been created from calculated solar,and cloud cover modifier. (The Montreal and Vancouver data presently available are created using R.F. Meriwether and Associa.tes cloud cover modifiers). The value of solar radiation through standard glass, H, is calculated each hour: = sky dit'fu>'~e radiation = direct normal radiation = modifier, for particular azimuth and tilt, to be applied to sky diffuse = modifier, for particular azimuth and tilt, to be applied to direct normal The factors a and B are functions of the geometry; they are calculated for only 1 day, the 21st of the month. Note that the effect of shading devices, if any, is also included in B The derivation of a and B factors is given in Appendix.

. ttl The EAS program performs hourly calculations for seven days to represent each month. Monthly consumptions are obtained by multiplying by the ratio (no. of days in month/7). The seven days representing each montb.are chosen to give approximately the same values for peaks and comsumptions as the full year analysis. ndications are that this results in errors of less than 5%. The advantages are that computation time is reduced by a factor of 4, and the size of weather and loads files is also reduced by a factor of 4. This makes floppy disk storage practical for these files. i ~ 7

8 5. The purpose of the reference system model is to provide some indication of the cooling which would be required when outdoor air is used for "free-cooling". ~he system chosen is basically an ideal variable air volume system which maintains room conditions without using "reheat". This system is one which provides the necessary cooling by adjusting the flow of supply air, fs, which is assumed to be at a constant condition of Ss (60 F) and h 8 (25 btu/lb). = {?* Cp t 60 ll (Sr - 6 8 ) The amount of mechanical cooling required by this system, R, depends upon the outdoor air conditions: - f outdoor air temperature Goa is less than or equal to 6 8 then the supply air condition can be maintained by mixing without any refrigeration; R = e. f outdoor air temperature, Goa is greater than Ss then mechanical cooling is required. f outdoor air dewpoint is less than or equal to the supply air dewpoint then only sensible cooling is required. The amount of sensible cooling is: R = E?* cp * 60 * f 8 11 ( G 0 a - Gs) where e = density of air Cp = specific heat of air R = < 8 oa - 8 s> * CL 5 (Sr - Ss) - f ou'tdoor air dewpoint is greater than supply air dewpoint, and outdoor enthalpy, hoa is less than or equal to room enthalpy, hr, then outdoor air must be cooled to the supply condition. The cooling required in this case is: R = f 11 60 fa (hoa - hs) combining equations R " (hoa - hs) * CLs cp <er - 9s) - f outdoor air enthalpy, hoa is greater than room enthalpy, hr then room air is recirculated and cooled rather than cooling outside air (except for outdoor air which is included as ventilation/ infiltration air). n this case the mechanical cooling required is equal to the space load, or 1 f l! i ' r : i R = CLs

Derivation of Sollll' Modifiers a and B The solar heat gain through glass is the sum of transmitted radiation plus the inward flowing fraction of radiation absorbed in the glass; both direct and diffuse components must be consigered: H = (direct transmitted + direct absorbed) * SHRAT + (diffuse transmitted + diffuse absorbed) where SHRAT is ratio of unshaded area/total area for windows with shading devices (1. for unshaded window). Direct transmitted = Direct absorbed = Diffuse transmitted = Diffuse absorbed = direct * transmittance of glass for direct absorptance. direct absorptance of glass for direct * inward flowing fraction. diffuse * transmittance for diffuse. diffuse * absorptance for diffuse * inward flowing fraction. For standard glass ( 1/8 11 DS): inward flowing fraction = 0.2673796 transmittance for diffuse (Td) = 0.7990111 absorptance for diffuse (Ad) = 0.0543594 n u ' '.'',, J ~. n. Transmittance and absorbance of glass for direct solar are functions of the cosine of the incident angle, ~: 5 Act = Y. aj cosj (~) j = 0 5 Tct = l. tj cosj (') j = 0 The values of aj and tj for standard glass are given in Table V. 9

TABLE V Values of aj and tj for Standard Glass 0 1 2 3 4 5 a 0.01154 0.77674-3.94657 8.57881-8.38135 3.01188 t -0.00885 2.71235-0.62062-7.07329 9.75995-3.89922 The direct solar component is: direct = n cos ($) The diffuse solar component is: diffuse = Y * s + Z ground brightness where y y z = Sky brightness = 0.45 if cos (n) < -.2 = = otherwise.55 +.437 + cos ~ +.313 cos2 ~ 1 +cos (180 - tilt angle) 2 ground brightness = ROG (s + n * sin (altitude angle)) where ROG - ground reflectivity. Substituting into equation 1 and regrouping terms: H = a. s + Bn where a. = 0.8135456 * (Y + Q * ROG) ~ = (0.8135456 * Z * ROG * sin (altitude.angle) + FUNCT (cos(~)) * SHRAT where FUNCT = '(Ad +.267396 Tct) * cos ($) SHRAT is calculated using the subroutine SHADOW from ASHRAE Energy Calculations 1. 10