Fuzzy Logic Control and Fault Detection in Centralized Chilled Water System

Similar documents
Implementation of Recurrent Neural Network to Control Rotational Inverted Pendulum using IMC Scheme

Development of Economic Impact Models for RTU Economizer Faults

A Hybrid Approach For Air Conditioning Control System With Fuzzy Logic Controller

DEVELOPMENT OF FAULT DETECTION AND DIAGNOSIS METHOD FOR WATER CHILLER

Adaptive Fuzzy PID For The Control Of Ball And Beam System

Dynamic Response Analysis of Start-up Transient in Air Conditioning System

On-Line Models for Use in Automated Fault Detection and Diagnosis for HVAC&R Equipment

MODEL BASED FAILURE MODE EFFECT ANALYSIS ON WHOLE BUILDING ENERGY PERFORMANCE

Jurnal Teknologi IMPLEMENTATION OF ROBUST COMPOSITE NONLINEAR FEEDBACK FOR ACTIVE FRONT STEERING BASED VEHICLE YAW STABILITY.

FUZZY LOGIC CONTROL Vs. CONVENTIONAL PID CONTROL OF AN INVERTED PENDULUM ROBOT

Development an Adaptive Incremental Fuzzy PI Controller for a HVAC System

Fuzzy Control Systems Process of Fuzzy Control

Fuzzy Compensation for Nonlinear Friction in a Hard Drive

Research Article Force Control for a Pneumatic Cylinder Using Generalized Predictive Controller Approach

A Model-Based Fault Detection and Diagnostic Methodology for Secondary HVAC Systems

Department of Mechanical Engineering, The Hague University, Delft, The Netherlands PhD candidate Eindhoven University of Technology

Sensor fault detection in building energy management systems

A Comparison Between Polynomial and Locally Weighted Regression for Fault Detection and Diagnosis of HVAC Equipment

Modeling of Hysteresis Effect of SMA using Neuro Fuzzy Inference System

The Electrodynamics of a Pair of PV Modules with Connected Building Resistance

Design On-Line Tunable Gain Artificial Nonlinear Controller

FUZZY CONTROL CONVENTIONAL CONTROL CONVENTIONAL CONTROL CONVENTIONAL CONTROL CONVENTIONAL CONTROL CONVENTIONAL CONTROL

Fuzzy Control of a Multivariable Nonlinear Process

Uncertain System Control: An Engineering Approach

CHAPTER 5 FREQUENCY STABILIZATION USING SUPERVISORY EXPERT FUZZY CONTROLLER

FUZZY CONTROL. Main bibliography

Type-2 Fuzzy Logic Control of Continuous Stirred Tank Reactor

PROCESS CONTROL FOR THERMAL COMFORT MAINTENANCE USING FUZZY LOGIC

Performance Of Power System Stabilizerusing Fuzzy Logic Controller

LONG TERM LOAD FORECASTING OF POWER SYSTEMS USING ARTIFICIAL NEURAL NETWORK AND ANFIS

Occupant Behavior Related to Space Cooling in a High Rise Residential Building Located in a Tropical Region N.F. Mat Hanip 1, S.A. Zaki 1,*, A. Hagish

Some considerations on noise monitoring for air handling equipments

AFAULT diagnosis procedure is typically divided into three

Available online at ScienceDirect. The Malaysian International Tribology Conference 2013, MITC2013

QNET Experiment #05: HVAC System Identification. Heating, Ventilation, and Air Conditioning Trainer (HVACT) Student Manual

Case Study of Chilled Water Loop Low DT Fault Diagnosis

Design and Stability Analysis of Single-Input Fuzzy Logic Controller

THE ENERGY 68,SAVING TDVI. exible Combine Modular 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP 60, 62, 64, 66 HP

Model Based Fault Detection and Diagnosis Using Structured Residual Approach in a Multi-Input Multi-Output System

Approximate active fault detection and control

Developing component models for automated functional testing

Cooling of Electronics Lecture 2

Advanced Adaptive Control for Unintended System Behavior

Stabilization fuzzy control of inverted pendulum systems

H-infinity Model Reference Controller Design for Magnetic Levitation System

Index Terms Magnetic Levitation System, Interval type-2 fuzzy logic controller, Self tuning type-2 fuzzy controller.

1 Nik Mohamad Sharif & Normah Mohd Ghazali / Jurnal Teknologi (Sciences & Engineering) 78: 10 2 (2016) 61 68

AN INTELLIGENT HYBRID FUZZY PID CONTROLLER

International Conference on Mechanics, Materials and Structural Engineering (ICMMSE 2016)

VRF Technical Data Book

Available online at ScienceDirect. Procedia Technology 25 (2016 )

World Academy of Science, Engineering and Technology

Enhanced Fuzzy Model Reference Learning Control for Conical tank process

Experimental Load Emulation for Multi-Evaporator Air Conditioning and Refrigeration Systems ABSTRACT 1. INTRODUCTION

Fuzzy Applications 10/2/2001. Feedback Control Systems FLC. Engine-Boiler FLC. Engine-Boiler FLC. Engine-Boiler FLC. Page 1

A dissertation submitted in partial fulfillment of the requirement for the degree of

COMPARISON OF DAMPING PERFORMANCE OF CONVENTIONAL AND NEURO FUZZY BASED POWER SYSTEM STABILIZERS APPLIED IN MULTI MACHINE POWER SYSTEMS

Multilevel Fault Detection and Diagnosis on Office Building HVAC Systems

DESIGN OF AN ADAPTIVE FUZZY-BASED CONTROL SYSTEM USING GENETIC ALGORITHM OVER A ph TITRATION PROCESS

Fault Detection and Isolation of the Wind Turbine Benchmark: an Estimation-based Approach

Multi-layer Flight Control Synthesis and Analysis of a Small-scale UAV Helicopter

1410. Fuzzy-PID controller on ANFIS, NN-NARX and NN-NAR system identification models for cylinder vortex induced vibration

RamchandraBhosale, Bindu R (Electrical Department, Fr.CRIT,Navi Mumbai,India)

Reduced Size Rule Set Based Fuzzy Logic Dual Input Power System Stabilizer

A BAYESIAN APPROACH FOR PREDICTING BUILDING COOLING AND HEATING CONSUMPTION

2.0 KEY EQUATIONS. Evaporator Net Refrigeration Effect. Compressor Work. Net Condenser Effect

Parameter Estimation for Dynamic HVAC Models with Limited Sensor Information Natarajkumar Hariharan 1 and Bryan P. Rasmussen 2

Water terminal control solutions

Professional Portfolio Selection Techniques: From Markowitz to Innovative Engineering

Evaluation of SIPIC01 and SIPIC02 on Motor Speed Control

Thermal Analysis of an HVAC System with TRV Controlled Hydronic Radiator

EXPERIMENTAL INVESTIGATION OF NOISE PARAMETERS IN HVAC SYSTEMS

MICHELL TECHNOLOGIES FOR MOISTURE. Calibration. General Principles & Theory, Equipment Considerations

Investigation of Model Parameter Variation for Tension Control of A Multi Motor Wire Winding System

Fuzzy-PID Methods for Controlling Evaporator Superheat

A Boiler-Turbine System Control Using A Fuzzy Auto-Regressive Moving Average (FARMA) Model


MODELLING AND SIMULATION OF AN INVERTED PENDULUM SYSTEM: COMPARISON BETWEEN EXPERIMENT AND CAD PHYSICAL MODEL

Intelligent Systems and Control Prof. Laxmidhar Behera Indian Institute of Technology, Kanpur

Novel Modeling and Control Strategies for a HVAC System Including Carbon Dioxide Control

Evaluation of Maximum Power Point Controllers in Photovoltaic System

Design and Comparative Analysis of Controller for Non Linear Tank System

-MASTER THESIS- ADVANCED ACTIVE POWER AND FREQUENCY CONTROL OF WIND POWER PLANTS

A Study on Performance of Fuzzy And Fuzyy Model Reference Learning Pss In Presence of Interaction Between Lfc and avr Loops

FAULT diagnosis is crucial for ensuring the safe operation

Fault Diagnosis of Interconnected Cyber-Physical Systems

CHAPTER 7 MODELING AND CONTROL OF SPHERICAL TANK LEVEL PROCESS 7.1 INTRODUCTION

A New Approach to Control of Robot

Control Of Heat Exchanger Using Internal Model Controller

Robust Actuator Fault Detection and Isolation in a Multi-Area Interconnected Power System

DYNAMIC DAYLIGHT AND SOLAR CONTROL IN TROPICAL CLIMATE

Unifying Behavior-Based Control Design and Hybrid Stability Theory

FAST DEFUZZIFICATION METHOD BASED ON CENTROID ESTIMATION

ScienceDirect. Gnielinski Method in Calculating the Heat Transfer Coefficient for Metallic Solar Tower Absorber

CZECH TECHNICAL UNIVERSITY IN PRAGUE FACULTY OF MECHANICAL ENGINEERING DEPARTMENT OF ENVIRONMENTAL ENGINEERING

Comparison of LQR and PD controller for stabilizing Double Inverted Pendulum System

T ai Temp Air In Duct Temp Set Point f a Mass Flow Air T wo Temp H 2O Out PI Controller T ao Temp Air Out T wi Temp H 2O In f w Mass Flow Rate H 2O Fi

FUZZY SWING-UP AND STABILIZATION OF REAL INVERTED PENDULUM USING SINGLE RULEBASE

Inter-Ing 2005 INTERDISCIPLINARITY IN ENGINEERING SCIENTIFIC CONFERENCE WITH INTERNATIONAL PARTICIPATION, TG. MUREŞ ROMÂNIA, NOVEMBER 2005.

Reinforcement Learning, Neural Networks and PI Control Applied to a Heating Coil

Transcription:

201 IEEE Symposium Series on Computational Intelligence Fuzzy Logic Control and Fault Detection in Centralized Chilled Water System Noor Asyikin Sulaiman 1, 2 Faculty of Electrical Engineering Universiti Teknologi Malaysia Skudai, Johor, Malaysia Faculty of Electronic and Computer Engineering 2 Universiti Teknikal Malaysia Melaka Melaka, Malaysia. noor_asyikin@utem.edu.my Mohd Fauzi Othman Electronic System Engineering Department Malaysia-Japan International Institute of Technology Universiti Teknologi Malaysia Kuala Lumpur, Malaysia Hayati Abdullah Centre of Electrical Energy System (CEES) Universiti Teknologi Malaysia Skudai, Johor, Malaysia Abstract The objective of this work is to develop and implement a fuzzy controller and fuzzy fault detection for centralized chilled water system. Both controller and fault detector are implemented in air supply dampers of air handling unit (AHU). A few cases are tested in this paper to investigate the effectiveness of the developed systems. All simulation is carried out using MATLAB/SIMULINK. Results illustrate that the fuzzy controller is able to maintain room temperature according to that desired whereas the fault detection can detect unusual behavior in supply air flowrate. I. INTRODUCTION Fuzzy systems can be used to estimate any real function on a compact fuzzy subset [1]. Fuzzy system is a rule-based method where the rule set learns from an expert s experience or prior knowledge of the system. Because of its simpler implementation and reduced design costs, fuzzy system is widely used and successfully implemented in the area of control, forecasting, plant monitoring and diagnosing [2]. However, reviews from [1, 3] show that not many fuzzy system are used in the application of HVAC control and fault detection as compared to other area. Eftekhari, Marjanovic and Angelov [4] designed a fuzzy controller for naturally ventilated buildings and validated it at a real building test room. Results show that fuzzy controller can provide better thermal comfort in the test room by adjusting the opening of the air ventilation according to the outdoor weather conditions. A self-tuning fuzzy control algorithm was developed by Wu, Xingxi and Chen [] in multi-evaporator air conditioners such as variable refrigerant volume technology. Controllability test shows that the proposed algorithm is sufficient to achieve the required result. On the other hand, the Research supported by Universiti Teknologi Malaysia (UTM)and Ministry of Education (MOE), Malaysia. Noor Asyikin Sulaiaman is a graduate student in UTM, sponsored by Universiti Teknikal Malaysia Melaka (UTeM) performance of three and five membership functions of fuzzy logic controller for centralized chilled water system has been investigated by Sulaiman, Othman and Abdullah [6]. Results have shown that both types of controller are almost equal in performance. The application of fuzzy logic controller is not limited to building air conditioning system but in car air conditioning as well. For instance, Othman and Othman [7] compared the application of fuzzy logic control and state flow controller in the perspective of car air conditioning. Fuzzy logic control shows encouraging and better performance than the latter controller. Meanwhile, fuzzy system is also successfully employed in fault detection as in [8-11]. Safarinejadian, Ghane and Monirvaghefi [8] proposed a new method for fault detection based on interval type-2 fuzzy sets for two-tank system. The result shows that beside of the ability of the proposed method to detect faults, its computation time to find interval bound is faster than adaptive-network-based fuzzy inference systems (ANFIS) method. Whilst in the HVAC area, a few researchers have proposed fuzzy system as a fault detection and diagnosis method as in [10-11]. Lo, Chan, Wong, Rad and Cheung [11] proposed an intelligent technique based on fuzzy-genetic algorithm (FGA) for automatically detecting faults in the HVAC system. In this paper, performances of fuzzy logic controller and fault detection are analyzed in the context of centralized chilled water system. One fuzzy logic controller and two fuzzy fault detection systems were developed for air supply damper in air handling unit (AHU). The overall system has two zones with the same properties and dimension. The performances of both controller and fault detection at both zones are investigated in different cases. Results show that both developed systems can respond well to the given input. A detail of system description used in this paper is explained in Section II. It includes hardware and modelling 978-1-4799-760-0/1 $31.00 201 IEEE DOI 10.1109/SSCI.201.26 8

parts of the system. Then, the following section, Section III, describes the methodology of this work. In Section IV, results are discussed and analyzed, whereas Section IV concludes the overall findings of this paper. II. SYSTEM DESCRIPT In this work, lab scale chilled water system and modeling of the system were constructed and developed A. Lab Scale Chilled Water System A lab scale of chilled water system was developed which consists of water cooled chiller, cooling tower, air handling unit (AHU) and two test rooms. The water cooled chiller system has a chilled water tank in between its chiller and AHU. The cooling tower is designed as a counter flow type. In AHU system, it has cooling coil, two sets of damper; one for each supply duct, supply and return ducts for each test room and a fan. The test rooms were constructed using insulated board and poly-carbonate and each of it sizes was 2.4m 1.2m 1.6m. The supplied air flow rate is controlled by varying the damper position. Moreover, the supplied air flow rate and returned room temperature are used as the input to fault detection. Nomenclature M C v C p Q T U A h fg w heat mass capacitance specific heat at constant volume air density specific heat at constant pressure volumetric flow rate temperature overall heat transfer coefficient Area latent heat of water humidity ratio subscripts; cc cooling coil a air tr test room s supply air amb ambient air w water chws chilled water supply t chilled water tank B. Modelling of the system The mathematical modelling of each component in the system was derived based on the lumped capacitance method as described in [12]. It is assumed that air velocity and room temperature are uniform in each test room. Furthermore, humidity and indoor air quality are not controlled. The temperature of the test room is derived based on the supplied air, returned air, heat from the ambient and internal heat as follows. where i = 1, 2. The heat between chilled water and air is exchanged in the cooling coil of AHU. The modelling of the cooling coil is expressed as; dt M C s cc v dt C Q ( T T ) a pa m m s U A ( T ( T T )) cc cc amb s m Q C ( T T ) w w pw chws t ( h C ) Q ( w w ) fg p a m tr s The temperature of chilled water tank is modelled as follows. dt M C t U A ( T T ) t pw t t amb t dt Q C ( T T ) (3) w w p chws t III. METHODOLOGY A fuzzy logic controller was designed to settle room temperature and two fuzzy logic fault detection to identify any fault in this simulation work. Each room has its own damper to simulate multi-fault condition. A. Temperature Controller Test room temperature control loop was designed in this study. By comparing the values of room temperature with their set point value, the controller adjusted the amount of supply air flow rate that entered the test rooms. In that way, both rooms temperature can be set to their desired temperature values. From (1), it shows that room temperature is related to the quantity of supply air flow rate that enters the test room. From experimental setup, the relation between supply air flow rate, Q a and the position of the supply air damper, u, was obtained as follow; Q a dt M C tri tr v dt m C a p U T T θ s tri int T T. amb tri 0.08u 0.00814, For u 17% 0, For u 17% a A tr tr a w (1) (2) (4) 9

The quantity of supply air flow rate can be controlled by varying the position of the damper up to 90. Therefore, the control inputs of the controller were temperature errors of both test rooms, T 1 and T 2. The outputs of the controller were the damper position, u 1 and u 2. Fuzzy logic controllers from [6] were improved and used in the simulation. Details of the quantization level and rules for this controller are tabulated in Tables I, II and III. B. Fault Detection In this paper, faults related to supply air dampers were considered and analyzed. These types of faults are categorized as degradation fault and it may affect the control process and performance of the system. Two fault detection systems were developed using fuzzy logic for both test rooms. These systems were to detect any unusual process that may occur during the operation of the system. It compared between its process and normal behavior. Three indicators were used which were no fault, almost fault and fault. No fault represents the process behavior as being similar to that of its normal behavior. In addition, almost fault corresponds to process behavior that was in between 30% to 0% different from its normal behavior. Whereas fault indicates that the system was having a problem. The shapes of the input and output membership functions used in this work were a combination of trapezium and triangle. Details regarding the quantization level of its membership function and fuzzy rules are listed in Tables IV and V. C. Simulations Simulations were done using MATLAB/SIMULINK on for t = 400s. Some parameters were set constant throughout the simulations as in [6, 13]. The reference set point temperature was set as 24C which follows the Malaysian Standard (MS 12:2007) requirement. Different faults have different effects on the system operation. It consists of one fault-free and two different faults cases as described in Table VI. Case 1 represents normal operation of both dampers. In a normal operation, dampers are free to swing from fully closed, 0 to fully opened, 90. Case 2 means that damper 1 has restriction to swing to fully open position at 90 but damper 2 operates normally. Damper 1 can only swing from 0 to 30. Lastly, Case 3 represents one damper working fine but the other is stuck at about 4. The analysis and discussion for all cases are presented in Section IV TABLE I. Type Input 1: Temperature difference of room 1 Input 2: Temperature difference of room 2 Output 1: Position of damper 1 Output 2: Position of damper 2 QUANTIZATION LEVEL FOR ROOM TEMPERATURE CONTROLLER No. of member ship function Quantization level Negative Big (NB) Negative Small (NS) Zero (ZE) Positive Small (PS) Positive Big (PB) Negative Big (NB) Negative Small (NS) Zero (ZE) Positive Small (PS) Positive Big (PB) Very Big (VB) Big (B) Medium (M) Small (S) Very Small (VS) Very Big (VB) Big (B) Medium (M) Small (S) Very Small (VS) TABLE II. RULES FOR DAMPER 1, U 1 T 1 T 2 NB NS ZE PS PB NB VB B M S S NS VB B S S VS ZE B M S VS VS PS B M VS VS VS PB M M VS VS VS TABLE III. RULES FOR DAMPER 2, U 2 T 1 T 2 NB NS ZE PS PB NB VB VB B B M NS B B M M S ZE M S S VS VS PS S S VS VS VS PB S VS VS VS VS 10

TABLE IV. Type Input 1: Temperature difference Input 2: Position of damper Output: Fault detection u TABLE V. T QUANTIZATION LEVEL FOR FAULT DETECTION No. of member ship function 3 Quantization level Negative Big (NB) Negative Small (NS) Zero (ZE) Positive Small (PS) Positive Big (PB) Very Big (VB) Big (B) Medium (M) Small (S) Very Small (VS) No fault (0) Almost fault (0.) Fault (1) RULES FOR FAULT DETECTION NB NS ZE PS PB VS 1 1 0. 0. 0 S 1 0. 0 0 0. M 0 0 0 0. 1 B 0 0 0. 1 1 VB 0 0. 1 1 1 TABLE VI. Cases Case 1 Case 2 Case 3 LIST OF CASES CONSIDERED IN THIS PAPER Operating cases Normal operation without fault Damper 1 can only swing up to 30 of opening position, while damper 2 is normal Damper 1 is normal while damper 2 stuck at 4 of opening position IV. RESULTS AND DISCUSSION certain position. In this case, it was assumed that damper 1 can only swing up to 30 of its opening position, while damper 2 functioned as normal. Despite of damper 1 having a problem, both test rooms were able to settle at 24C. From Fig. 3, it shows that test room 1 was able to be cooled down from 30C to 24C around six minutes and forty seconds as compared to three minutes in test room 2. The limited opening of damper 1 caused test room 1 to receive lesser amount of supply air whilst test room 2 received more than usual in the beginning. As a result, the cooling down time for test room 1 required longer time and test room 2 was slightly faster than those in case 1. As room 1 received unusual amount of air flow rate in the beginning, thus, fault was detected in damper 1. However, since damper 1 can still swing even up to only 30, both rooms eventually can be cooled down to its set point temperature. This explained the reason why the fault subsided later in time. The details of fault detection in both dampers were portrayed in Fig. 4. C. Case 3 Case 3 was simulated with the assumption that damper 1 worked normally while damper 2 was stuck at 4 of the opening position. It was expected that the damper was stuck throughout the simulation. Fig. illustrates the temperature variation in both rooms during the simulation. The temperature in test room 1 behaved similarly as the one in Case 1. However, the temperature in test room 2 was not able to be settled at the required value because the room still received constant amount of cold supply air even when it has cooled down. Fig. 6 displays fault detection for both dampers in this case. Since the temperature in test room 1 behaved normally, no fault was detected in damper 1. Initially, no error was detected in damper 2 as it still complied with rules in Table III. However, since the room continually received a constant amount of cold supply air, the difference between actual and normal supply air flowrate was getting bigger from time to time. Therefore, the system finally detected that the damper was faulty after around two minutes and thirty seconds. A. Case 1 In this case, all components in the system were operated normally. It was assumed that both dampers 1 and 2, operated in normal condition where they were free to swing up to the full opening which was 90. However, the opening was controlled by its controller according to the test rooms' temperature throughout the simulation. Fig. 1 represents the temperature variation for test rooms 1 and 2. The simulation results showed that both test rooms were cooled down from 30C to 24C for about three minutes and thirty seconds. Apparently, there were no steady state errors as compared to [6]. As a result, there was no fault detected in both dampers as shown in Fig. 2. Temperature (Celcius) 31 30 29 28 27 26 2 24 23 22 Test room 1 Test room 2 B. Case 2 The second case simulated was that one of the dampers cannot fully function which means it can only swing up to a 21 0 0 100 10 200 20 300 30 400 Fig. 1. Temperature variation in test room 1 and test room 2. 11

1. damper 1 damper 2 30 Test room 1 Test room 2 1 28 26 Error 0. 0 Temperature (Celcius) 24 22 20 18-0. 0 0 100 10 200 20 300 30 400 Fig. 2. Fault detection for damper 1 and damper 2. 16 0 0 100 10 200 20 300 30 400 Fig.. Temperature variation in test room 1 and test room 2. 31 30 Test room 1 Test room 2 1. damper 1 damper 2 Temperature (Celcius) 29 28 27 26 2 24 23 Error 1 0. 0 22 21 0 0 100 10 200 20 300 30 400 40 Fig. 3. Temperature variation in test room 1 and test room 2. -0. 0 0 100 10 200 20 300 30 400 Fig. 6. Fault detection for damper 1 and damper 2. Error 1. 1 0. 0 damper 1 damper 2 D. Detection Time Detection time of faults simulated in this paper was summarized in Table VII. Case I is a fault-free case, hence no fault detected during simulation. For Case 2, the system detected almost fault condition immediately when simulation ran. However, the fault subsided later on when the system performance recovered as normal. As for Case 3, the first detection time was around 1.3 minutes. At first it detected as almost fault which means the system detected an error but the performance of the system was still acceptable. Later, when the error got bigger and the performance was unacceptable, a fault alarm was triggered. All faults were introduced to the system from the beginning of the simulation. -0. 0 0 100 10 200 20 300 30 400 40 Fig. 4. Fault detection for damper 1 and damper 2. TABLE I. Cases Case 1 Case 2 Case 3 DETECTION TIME Detection time Not applicable 0 min 1.3 min 12

V. CONCLUSION This paper presents the results of fuzzy logic controller and fuzzy fault detection in the context of centralized chilled water system. Three operating cases were examined through two test rooms with some parameters were set constant throughout the simulations. Results show that the controller was able to cool the test rooms to the desired temperature values. Moreover, the fault detection system corresponded well to faults induced to the damper. ACKNOWLEDGMENT The authors would like to thank the Ministry of Education, Malaysia and Universiti Teknologi Malaysia for financially supporting this research project under the MJIIT-Takasago Grant. The authors would also like to thank Universiti Teknikal Malaysia Melaka for the support. REFERENCES [1] J. Singh, N. Singh and J. K. Sharma, Fuzzy modeling and control of HVAC systems A review, Journal of Scientific & Industrial Research, 6, 2006, pp.470-476. [2] A. M. A. Kadir, Autonomous contour tracking industrial robot by using type-2 fuzzy logic, Master Thesis, Faculty of Electrical Engineering, Universiti Teknologi Malaysia, Skudai, 2013. [3] S. Katipamula and M. R. Brambley, Methods for fault detection, diagnostics, and prognostics for building systems-a review, HVAC&R Research, 11:2, 200, pp.169-187. [4] M. Eftekhari, L. Marjanovic. and P. P. Angelov, Design and performance of a rule-based controller in a naturally ventilated room, Computers in Industry, 1,2003, pp. 299-326. [] C. Wu, Z. Xingxi and D. Shimming, Development of control method and dynamic model for multi-evaporator air-conditioners (MEAC), Energy Conversion and Management, 46, 200, pp.41 46. [6] N. A. Sulaiman, M. F. Othman and H. Abdullah, Fuzzy logic control of centralized chilled water system, Jurnal Teknologi, 72:2, 201, pp.7 62. [7] M. F. Othman, and S. M. Othman, Fuzzy logic control for non linear car air conditioning, Elektrika, 8:2, 2006, pp. 38-4. [8] B. Safarinejadian, P. Ghane, and H. Monirvaghefi, Fault detection in non linear systems based on type-2 fuzzy logic, International Journal of Systems Science, 46:3, 2013, pp. 394-404. [9] V. E. Andrade, C. H. Fontes and M. Embirucu, An interval type-2 fuzzy logic approach for instrument fault detection and diagnosis, in Proceedings of the World Congress on Engineering 2011 Vol II, London, U.K, 2011. [10] A. L. Dexter and D. Ngo, Fault diagnosis in air-conditioning systems: a multi-step fuzzy model-based approach, HVAC&R Research, 7:1, 2001, pp. 83-102. [11] C. H. Lo, P. T. Chan, Y. K. Wong, A. B. Rad and K.L. Cheung, Fuzzygenetic algorithm for automatic fault detection in HVAC systems, Applied Soft Computing, 7:2, 2007, pp. 4 60. [12] A. Thosar, A. Patra, and S. Bhattacharyya, Feedback linearization based control of a variable air volume air conditioning system for cooling applications, ISA Transactions, 47, 2008, pp. 339-349. [13] V. Reppa, P. Papadopoulos, M. M. Polycarpou and C. G. Panayioyou, Distributed detection and isolation of sensor faults in hvac systems, in 21st Mediterranean Conference on Control & Automation, Crete, Greece, 2013, pp.401-406. 13