OPTIMAL CAPACITOR PLACEMENT USING FUZZY LOGIC

Similar documents
CAPACITOR PLACEMENT USING FUZZY AND PARTICLE SWARM OPTIMIZATION METHOD FOR MAXIMUM ANNUAL SAVINGS

Optimal Capacitor Placement and Sizing on Radial Distribution System by using Fuzzy Expert System

OPTIMAL DG UNIT PLACEMENT FOR LOSS REDUCTION IN RADIAL DISTRIBUTION SYSTEM-A CASE STUDY

Optimal Performance Enhancement of Capacitor in Radial Distribution System Using Fuzzy and HSA

A PROPOSED STRATEGY FOR CAPACITOR ALLOCATION IN RADIAL DISTRIBUTION FEEDERS

J. Electrical Systems x-x (2010): x-xx. Regular paper

PROPOSED STRATEGY FOR CAPACITOR ALLOCATION IN RADIAL DISTRIBUTION FEEDERS

THE loss minimization in distribution systems has assumed

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

CHAPTER 2 LOAD FLOW ANALYSIS FOR RADIAL DISTRIBUTION SYSTEM

Optimal Placement of Multi DG Unit in Distribution Systems Using Evolutionary Algorithms

Optimal capacitor placement and sizing using combined fuzzy-hpso method

Optimal Capacitor Placement in Radial Distribution System to minimize the loss using Fuzzy Logic Control and Hybrid Particle Swarm Optimization

OPTIMAL CAPACITORS PLACEMENT IN DISTRIBUTION NETWORKS USING GENETIC ALGORITHM: A DIMENSION REDUCING APPROACH

ENERGY LOSS MINIMIZATION AND RELIABILITY ENHANCEMENT IN RADIAL DISTRIBUTION SYSTEMS DURING LINE OUTAGES

Performance Improvement of the Radial Distribution System by using Switched Capacitor Banks

Optimal Placement & sizing of Distributed Generator (DG)

Fuzzy Control for Shunt Capacitors Applied in Distribution Feeders

Real Time Voltage Control using Genetic Algorithm

Optimal Capacitor Placement in Distribution System with Random Variations in Load

K. Valipour 1 E. Dehghan 2 M.H. Shariatkhah 3

Energy Conversion and Management

Simultaneous placement of Distributed Generation and D-Statcom in a radial distribution system using Loss Sensitivity Factor

Optimal Sizing And Placement Of Capacitor In A Radial Distribution System Using Loss Sensitivity Factor And Firefly Algorithm.

Meta Heuristic Harmony Search Algorithm for Network Reconfiguration and Distributed Generation Allocation

Optimal placement of capacitor in distribution networks according to the proposed method based on gradient search

Reduced Size Rule Set Based Fuzzy Logic Dual Input Power System Stabilizer

Chapter-2 Literature Review

Fast Power Loss Computation and Shunt Capacitor Insertion Using Fuzzy Logic Technique

Farzaneh Ostovar, Mahdi Mozaffari Legha

Multi-objective Placement of Capacitor Banks in Distribution System using Bee Colony Optimization Algorithm

Classification of Capacitor Allocation Techniques

Transmission Line Compensation using Neuro-Fuzzy Approach for Reactive Power

AN IMMUNE BASED MULTI-OBJECTIVE APPROACH TO ENHANCE THE PERFORMANCE OF ELECTRICAL DISTRIBUTION SYSTEM

A Comparative Study Of Optimization Techniques For Capacitor Location In Electrical Distribution Systems

Optimal Capacitor placement in Distribution Systems with Distributed Generators for Voltage Profile improvement by Particle Swarm Optimization

Analytical approaches for Optimal Placement and sizing of Distributed generation in Power System

Optimal capacitor placement and sizing via artificial bee colony

is implemented by a fuzzy relation R i and is defined as

Multiple Distribution Generation Location in Reconfigured Radial Distribution System Distributed generation in Distribution System

Voltage Profile Improvement by Capacitor Placement and Control in Unbalanced Distribution Systems Using Differential Evolution Algorithm

EEE 8005 Student Directed Learning (SDL) Industrial Automation Fuzzy Logic

A Novel Analytical Technique for Optimal Allocation of Capacitors in Radial Distribution Systems

PARTICLE SWARM OPTIMIZATION BASED APPROACH FOR LOSS REDUCTION IN UNBALANCED RADIAL DISTRIBUTION SYSTEM

Comparison of Loss Sensitivity Factor & Index Vector methods in Determining Optimal Capacitor Locations in Agricultural Distribution

Optimal Compensation of Reactive Power in Transmission Networks using PSO, Cultural and Firefly Algorithms

International Journal of Mechatronics, Electrical and Computer Technology

Fast Energy Loss Computation and Fuzzy-Based Shunt Capacitor Insertion

2008 IEEE. Personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes

CAPACITOR PLACEMENT IN UNBALANCED POWER SYSTEMS

Maximum Cost Saving Approach for Optimal Capacitor Placement in Radial Distribution Systems using Modified ABC Algorithm

OPTIMAL DG AND CAPACITOR ALLOCATION IN DISTRIBUTION SYSTEMS USING DICA

Congestion Alleviation using Reactive Power Compensation in Radial Distribution Systems

Optimal Unified Power Quality Conditioner Allocation in Distribution Systems for Loss Minimization using Grey Wolf Optimization

Fuzzy Logic Approach for Short Term Electrical Load Forecasting

A Study of the Factors Influencing the Optimal Size and Site of Distributed Generations

CHAPTER 5 FUZZY LOGIC FOR ATTITUDE CONTROL

EE5250 TERM PROJECT. Report by: Akarsh Sheilendranath

K. MAHESH 2 Asst Prof & HOD, Sri kottam tulasi reddy memorial college of engineering, AP-INDIA

Nowadays computer technology makes possible the study of. both the actual and proposed electrical systems under any operating

Optimal capacitor placement in radial distribution networks with artificial honey bee colony algorithm

Analyzing the Effect of Loadability in the

Week No. 6 Chapter Six: Power Factor Improvement

Solving Distribution System Overload Contingency Using Fuzzy Multi-Objective Approach Considering Customer Load Pattern

Secondary Frequency Control of Microgrids In Islanded Operation Mode and Its Optimum Regulation Based on the Particle Swarm Optimization Algorithm

A PARTICLE SWARM OPTIMIZATION TO OPTIMAL SHUNT-CAPACITOR PLACEMENT IN RADIAL DISTRIBUTION SYSTEMS

The AR OPF: an Exact Convex Formulation for the Optimal Power Flow in Radial Distribution Networks

CHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS

J. Electrical Systems 10-1 (2014): Regular paper. Optimal Power Flow and Reactive Compensation Using a Particle Swarm Optimization Algorithm

Transient Stability Assessment and Enhancement Using TCSC with Fuzzy Logic Controller

1 Unified Power Flow Controller (UPFC)

Capacitor Placement for Economical Electrical Systems using Ant Colony Search Algorithm

Application of Monte Carlo Simulation to Multi-Area Reliability Calculations. The NARP Model

NEW EVOLUTIONARY TECHNIQUE FOR OPTIMIZATION SHUNT CAPACITORS IN DISTRIBUTION NETWORKS

Journal of Artificial Intelligence in Electrical Engineering, Vol. 1, No. 2, September 2012

Handling Uncertainty using FUZZY LOGIC

Energy saving in electromechanical equipment with power coefficient correction. Dimitris Al. Katsaprakakis Aeolian Land S.A.

OPTIMAL CAPACITOR PLACEMENT AND SIZING IN A RADIAL DISTRIBUTION SYSTEM USING CLONAL SELECTION ALGORITHM

KINGS COLLEGE OF ENGINEERING Punalkulam

Lecture 06. (Fuzzy Inference System)

A Particle Swarm Optimization for Reactive Power Optimization

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

DG-Embedded Radial Distribution System Planning Using Binary-Selective PSO

FEEDER RECONFIGURATION AND CAPACITOR SETTINGS ON DISTRIBUTION SYSTEMS : AN APPROACH FOR SIMULTANEOUS SOLUTION USING A GENETIC ALGORITHM

CHAPTER 7 MODELING AND CONTROL OF SPHERICAL TANK LEVEL PROCESS 7.1 INTRODUCTION

A LOOP BASED LOAD FLOW METHOD FOR WEAKLY MESHED DISTRIBUTION NETWORK

Optimal Placement of Capacitor Banks in order to Improvement of Voltage Profile and Loss Reduction based on PSO

Hamidreza Rashidy Kanan. Electrical Engineering Department, Bu-Ali Sina University

Models for Inexact Reasoning. Fuzzy Logic Lesson 8 Fuzzy Controllers. Master in Computational Logic Department of Artificial Intelligence

EXCITATION CONTROL OF SYNCHRONOUS GENERATOR USING A FUZZY LOGIC BASED BACKSTEPPING APPROACH

Network reconfiguration and capacitor placement for power loss reduction using a combination of Salp Swarm Algorithm and Genetic Algorithm

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

CHAPTER 3 ANALYSIS OF THREE PHASE AND SINGLE PHASE SELF-EXCITED INDUCTION GENERATORS

Application of Teaching Learning Based Optimization for Size and Location Determination of Distributed Generation in Radial Distribution System.

An Evolutionary Algorithm for Reactive Power Compensation in Radial Distribution Networks

USE OF FUZZY LOGIC TO INVESTIGATE WEATHER PARAMETER IMPACT ON ELECTRICAL LOAD BASED ON SHORT TERM FORECASTING

Optimal Locating and Sizing of TCPST for Congestion Management in Deregulated Electricity Markets

Power Distribution in Electrical Grids

Brief Steady of Power Factor Improvement

Genetic Algorithm for Optimal Capacitor Allocation in Radial Distribution Systems

Transcription:

CHAPTER - 5 OPTIMAL CAPACITOR PLACEMENT USING FUZZY LOGIC 5.1 INTRODUCTION The power supplied from electrical distribution system is composed of both active and reactive components. Overhead lines, transformers and loads consume the reactive power. So voltage/var control is an essential measure to reduce the power losses through the switching operations of capacitors and load tap changing transformers. Reactive power compensation plays an important role in the planning of an electrical system. A proper control of the reactive power will improve the voltage profile, reduces the system losses and improves the system efficiency. Proper generation and control of reactive power is important for maintaining the network voltages under normal and abnormal conditions and to reduce system losses. The system voltage collapse due to lack of global control of reactive power flow during crucial contingencies is emerging as a serious problem. The aim is principally to provide an appropriate placement and sizing of the compensation devices to ensure a satisfactory voltage profile while minimizing the cost of compensation. Mainly capacitors are used to develop reactive power near the point of consumption. Series and shunt capacitors in a power system generate reactive power to improve power factor and voltage, thereby enhancing the system capacity and reducing the losses. Due to various limitations in the use of series capacitors, shunt capacitors are widely used in distribution systems. The general capacitor placement problem is formulated as an optimization problem to determine the location of capacitors, the types and size of capacitors to be installed and the control scheme for the capacitors at the buses of radial distribution networks. Several methods of loss reduction by placing capacitors in distribution systems have been reported over the years. The early approaches to this problem include those using

analytical methods, heuristic methods, artificial intelligence methods and those using dynamic programming technique to include the discrete nature of the capacitor size. Baran and Wu [18] have proposed an analytical method based on mixed integer programming to find the optimal size of capacitor to reduce the losses of a radial distribution system. Haque [51] has proposed a method of minimizing the loss associated with the reactive component of branch currents by placing capacitors at proper locations. The method first finds the location of the capacitor in a sequential manner. Once the capacitor locations are determined, the optimal capacitor size at each selected location is determined by optimizing the loss saving equation. More recently, the use of various non-deterministic methods like tabu search, genetic algorithms, fuzzy expert system and simulated annealing to determine the location and size of capacitor to improve the voltage profile of the system have been reported. Mekhamer et al. [73] have proposed a method to select an optimal location of capacitors using fuzzy logic and its allocation by analytical method. Ng et al. [40] presents a methodology to convert the analytical method stated in Salama and Chikani [28] from crisp solution into fuzzy solution by modeling the parameters using possibility distribution function, thus accounting for the uncertainties in these parameters. Prasad et al. [102] have presented a genetic approach to determine optimal size of capacitor. The optimal location to install capacitor is determined by taking values of Power Loss Indices randomly. Power loss indices are calculated by compensating the self-reactive power at each bus and run the load flows to determine the total active power losses in each case. Most of the previous studies [30, 31, 45, 57, 64, 124] have presented a method to find the location and size of capacitors using heuristic, genetic, simulated annealing techniques. In this chapter, a method is proposed to determine the optimal location of capacitors using fuzzy expert system by considering power loss indices and voltage at each bus

simultaneously and size of the capacitor by an index based method to obtain good results without violating the voltage constraints. This method has the versatility of being applied to the large distribution systems and having any uncertain data. The proposed method is tested with different radial distribution systems. The mathematical formulation of the proposed method is explained in Section 5.2. In this Section, the objective function and its constraints are defined. The identification of sensitive bus for capacitor placement using fuzzy logic is described in Section 5.3. Also this Section explains the calculation of Power Loss Index and implementation aspects of Fuzzy Expert System (FES) to identify sensitive bus to place capacitor. The effectiveness of the proposed FES is tested with one example and the results are presented in Section 5.4. The size of the capacitor using Index based method is explained in Section 5.5. In Section 5.6, algorithm to be followed to obtain optimal location and size of capacitor are presented. The effectiveness of the proposed method is tested with different examples of distribution system and the results obtained are compared with the results of existing methods. In Section 5.7, conclusions of the proposed method are presented. 5.2 MATHEMATICAL FORMULATION The objective function is to maximize the net savings function (F) by placing the proper size of capacitors at suitable locations is formulated as: Max. F e lr K P 8760 k N K Q (5.1) I c c c where F P lr = net savings (`.) = Reduction in power losses due to installation of capacitor = (Power loss before installation of capacitor - Power loss after installation of capacitor)

K e = Cost of energy in `./kwh = Installation cost in `. = Total number of capacitor buses Q C K C λ = total size of capacitor = Capital cost of each capacitor = rate of annual depreciation and interest charges of capacitor 5.2.1 Constraints The objective function is subjected to the following constraints The voltage at each bus should lie within the voltage limits. V min. V i V max. i=1,2,..no. of buses The size of the capacitor to be installed at suitable bus is less than the total reactive load of the system. Q nbus c Q i i 1 where nbus= total number of buses 5.3 IDENTIFICATION OF SENSITIVE BUS FOR CAPACITOR PLACEMENT USING FUZZY LOGIC The fuzzy logic is used to identify the optimal location to place the capacitor in a radial distribution system so as to minimize the losses while keeping the voltage at buses within the limit and also by taking the cost of the capacitors in to account. The Fuzzy Expert System (FES) contains a set of rules, which are developed from qualitative descriptions. In a FES, rules may be fired with some degree using fuzzy inference, where as in a conventional Expert System, a rule is either fired or not fired. For the capacitor placement problem, rules are defined to determine the suitability of a bus for capacitor placement. Such rules are expressed in the following general form: If premise (antecedent), THEN conclusion (Consequent)

For determining the suitability of a particular bus for capacitor placement at a particular bus, sets of multiple-antecedent fuzzy rules have been established. The inputs to the rules are the bus voltages in p.u., power loss indices, and the output consequent is the suitability of a bus for capacitor placement. 5.3.1 Procedure to calculate power loss index The Power Loss Index at i th bus, PLI (i) is the variable which is given to fuzzy expert system to identify suitable location for the capacitor. Step 1 : Read radial distribution system data Step 2 : Perform the load flows and calculate the base case active power loss Step 3 : By compensating the reactive power injections (Q c ) at each bus (except source bus)and run the load flows, and calculate the active power loss in each case. Step 4 : Calculate the power loss reduction and power loss indices using the following equation where PLI i X i Y (5.2) Z Y X(i) Y Z = loss reduction at i th bus = minimum loss reduction = maximum loss reduction nbus = number of buses Step 5 : Stop 5.3.2 Implementation aspects of Fuzzy expert system to identify the sensitive bus The power loss indices and bus voltages are used as the inputs to the fuzzy expert system, which determines the buses which are more suitable for capacitor installation. The

Degree of Membership Low High Degree of membership Low Lo-Norm Hi-Norm Norm High Degree of Membership Low High power loss indices range varies from 0 to 1, the voltage range varies from 0.9 to 1.1 and the output [Capacitor Suitability Index (CSI)] range varies from 0 to 1. These variables are described by five membership functions of high, high-medium/normal, medium/normal, lowmedium/normal and low. The membership functions of power loss indices and CSI are triangular in shape, the voltage is combination of triangular and trapezoidal membership functions. These are graphically shown in Figs. 5.1 to 5.3. 1.0 0.8 0.6 0.4 0.2 0 Low-Med Med Hi-Med 0 0.2 0.4 0.6 0.8 1.0 Power Loss Index Fig. 5.1 Power loss index membership function 1.0 0.8 0.4 0.2 0.0 0.0 0.92 0.94 1.0 1.04 1.06 1.1 Voltage (p.u.) Fig. 5.2 Voltage membership function 1.0 0.8 0.6 0.4 0.2 0 Low-Med Med Hi-Med 0 0.2 0.4 0.6 0.8 1.0 Capacitor Suitability Index

Fig. 5.3 Capacitor suitability index membership function For the capacitor placement problem, rules are defined to determine the suitability of a bus for capacitor installation. For determining the suitability for capacitor placement at a particular bus, a set of multiple antecedent fuzzy rules have been established. The rules are summarized in the fuzzy decision matrix in Table 5.1. The consequent of the rules are in the shaded part of the matrix. Table 5.1 Decision matrix for determining suitable capacitor locations Power Loss Index (PLI) Low- Med. Med. Low-Med. Low-Med. Low Low Med. High- Med. Med. Low-Med. Low Low And Voltage Low- High- Low Normal High Normal Normal Low Low-Med. Low-Med. Low Low Low High- Med. High-Med. High-Med. Med. Low-Med. Low High High High-Med. Med. Low-Med. Low-Med. After the FES receives inputs from the load flow program, several rules may fire with some degree of membership. The fuzzy inference methods such as Mamdani max-min and max-prod implication methods [34] are used to determine the aggregated output from a set of triggered rules. A final aggregated membership function is achieved by taking the union of all the truncated consequent membership functions of the fired rules. For the capacitor placement problem, resulting capacitor suitability index membership function, s, of bus i for m fired rules is s i max min i, i (5.3) m PLI v Where PLI and v are the membership functions of the power loss index and p.u. voltage level respectively.

Once the suitability membership function of a bus is calculated, it must be defuzzified in order to determine the buses suitability ranking. The centroid method of defuzzification is used; this finds the center of area of the membership function. Thus, the capacitor suitability index is determined by: s CSI z z s.zdz dz (5.4) 5.3.3 Illustration of FES for a sample system The proposed method is explained with a sample system. Consider a 15 bus system whose single line diagram is shown in Fig. 2.3. The line and load data of this system is given in Appendix A (Table A.1). After performing the load flows for base case, the total active power loss and minimum voltage is given as 61.7993 kw and 0.9445 p.u. Considering one bus at a time, every bus is compensated with reactive power injection equivalent to that of self reactive load. Now perform the load flows to determine the active power loss, power loss index and the voltage in each case. These are given in Table 5.2. Table 5.2 Power Loss Index and voltage Bus No. Voltage Voltage PLI Bus No. (p.u.) (p.u.) PLI 1 1.0000 0 9 0.9697 0.3231 2 0.9730 0.1874 10 0.9686 0.2128 3 0.9599 0.4478 11 0.9532 0.9891 4 0.9551 0.9676 12 0.9491 0.5621 5 0.9542 0.3289 13 0.9478 0.3706 6 0.9600 0.8375 14 0.9529 0.5221 7 0.9578 0.8661 15 0.9537 1.0000 8 0.9587 0.4528

The Capacitor Suitability Indices (CSI) of 15 bus system from FES is given in Table 5.3. The most suitable buses for capacitor placement are selected based on the maximum value of CSI of the system and they are 3, 4, 6, 11 and 15. Table 5.3 Capacitor suitability indices of 15 bus system Bus No. CSI Bus No. CSI 1 0.0800 9 0.2574 2 0.2407 10 0.2451 3 0.7500 11 0.7500 4 0.7500 12 0.5719 5 0.3371 13 0.3715 6 0.7500 14 0.5301 7 0.4246 15 0.7500 8 0.4336 5.4 PROCEDURE TO CALCULATE CAPACITOR SIZE USING INDEX BASED METHOD After knowing the optimal locations to place the capacitor, the size of the capacitor can be calculated by using index based method. Where Index i 1 V V k k total q effectiveload,i (5.5) i i I I p Q Q V i Ip[k], Iq[k] Q effectiveload,i Q total = Voltage at i th bus. = real and reactive component of current in k th branch. = total reactive load beyond i th bus (including Qload at i th bus) = total reactive load of the given distribution system capacitors ize i index i Qload i (5.6) where Qload[i] = local reactive load at i th bus 5.5 ALGORITHM FOR CAPACITOR PLACEMENT AND SIZING USING FES AND INDEX BASED METHOD

Step 1: Read the system input data a) Number of buses, number of branches, resistance and reactance of each branch, from bus and to bus of each branch, active and reactive power of each bus. b) Base kv, base kva, tolerance, etc. Step 2: Run load flow program and calculate the voltage at each bus and calculate the active power loss before compensation. Step 3: Run the load flow program by compensating the reactive load at each bus, considering one bus at a time, and calculate the loss reduction at each bus. Step 4: The power-loss reduction indices and the bus voltages are the inputs to the fuzzy expert system. Step 5: The outputs of FES, the capacitor suitability index, CSI are obtained from which the optimal location for the capacitor placement is selected by considering the maximum value of it. Step 6: The index vector is determined at selected buses using Eqn.(5.5). Step 7: Calculate the size of capacitor at selected buses by multiplying the reactive load at that bus with index vector at that bus (Eqn. (5.6)). Step 8: Then placing the calculated size of capacitors at best locations conduct a load flow study. Step 9: Print the results. Step 10: Stop

5.6 FLOW CHART FOR OPTIMAL CAPACITOR PLACEMENT USING FES Start Read Distribution System line and load data, base kv and kva, iteration count (IC) =1and tolerance (ε) = 0.0001 Perform load flows and calculate voltage at each bus, real and reactive power losses Calculate the loss reduction by running load flow by compensating the reactive load at each bus, considering one bus at a time Calculate power loss reduction indices, PLI using Eqn. (5.2) Obtain Capacitor Suitability Index (CSI) from the FES by

Fig. 5.4 Flow chart for optimal capacitor placement using FES 5.7 ILLUSTRATIVE EXAMPLES The proposed method is tested with four different radial distribution systems having of 15, 33, 34 and 69 buses. 5.7.1 Example 1 Consider a 15 bus system whose single line diagram is shown in Fig. 2.3. The line and load data of this system is given in Appendix A (Table A.1). The total real power loss and minimum bus voltage before compensation are 61.7993 kw and 0.9445 p.u.

The optimal locations and the size of the capacitors obtained by the proposed method are given in Table 5.4. In addition, voltage at these buses before and after compensation, loss reduction and net savings due to compensation are also given in the same table. The effect of using the nearest standard size capacitors instead of actual size of the capacitors is presented in Table 5.5 and it is observed that the changes in loss reduction and net savings are marginal. The active power loss reduction due to compensation is from 61.7933 kw to 32.1437 kw i.e., a reduction of 47.98% of the original active power loss. The voltage profile of the system before and after compensation is given in Table 5.6. The minimum voltage is improved from 0.9445 p.u. to 0.9667 p.u. The voltage regulation is improved from 5.55% to 3. 33%. The line flows of the system is given in Table 5.7. Table 5.4 Capacitor allocation and loss reduction of 15 bus RDS for calculated size of capacitor Without capacitor With capacitor Bus No. Q-Cap Voltage (p.u.) Voltage (p.u.) 3 0.9567 0.9734 189.7 4 0.9509 0.9739 349.54 6 0.9582 0.9747 292. 65 11 0.9500 0.9761 284.19 15 0.9484 0.9752 278.95 Total size of capacitor 1,395.03 Without capacitor With capacitor Improvement P loss (kw) Q loss P loss (kw) Q loss P loss (kw) Q loss 61.7933 57.2967 31.8981 24.5325 29.8952 32.7642 Net Saving (`.) Without Capacitor With Capacitor ----- 6, 79, 844/-

Table 5.5 Capacitor allocation and loss reduction of 15 bus system for standard size of capacitor Without capacitor With capacitor Bus No. Q-Cap Voltage (p.u.) Voltage (p.u.) 3 0.9567 0.9765 200 4 0.9509 0.9740 350 6 0.9582 0.9751 300 11 0.9500 0.9742 275 15 0.9484 0.9748 275 Total size of capacitor 1,400 Without capacitor With capacitor Improvement P loss (kw) Q loss P loss (kw) Q loss P loss (kw) Q loss 61.7933 57.2967 32.1437 24.9865 29.6496 32.3102 Net Saving (`.) Without Capacitor With Capacitor ----- 6,74, 695/- Table 5.6 Voltage profile before and after compensation of 15 bus RDS Before compensation After compensation Bus Voltage magnitude Voltage magnitude No. Angle (deg.) Angle (deg.) (p.u.) (p.u.) 1 1.0000 0.0000 1.0000 0.0000 2 0.9713 0.0320 0.9835-0.6516 3 0.9567 0.0493 0.9765-1.0673 4 0.9509 0.0565 0.9740-1.2488 5 0.9499 0.0687 0.9730-1.2372 6 0.9582 0.1894 0.9751-0.8776 7 0.9560 0.2166 0.9738-0.9327 8 0.9570 0.2050 0.9738-0.8625 9 0.9680 0.0720 0.9802-0.6126 10 0.9669 0.0850 0.9792-0.5999 11 0.9500 0.1315 0.9742-1.2571 12 0.9458 0.1824 0.9690-1.2086 13 0.9445 0.1987 0.9677-1.1931 14 0.9486 0.0848 0.9717-1.2218

Real Power Loss (kw) 15 0.9484 0.0869 0.9748-1.3096 Bus No. Table 5.7 Line flows of 15 bus system Before compensation Active power loss (kw) Reactive power loss After compensation Active power loss (kw) Reactive power loss 1 37.7019 36.8772 18.2521 17.8528 2 11.2895 11.0426 5.2822 5.1667 3 2.4439 2.3904 1.1573 1.1320 4 0.0554 0.0374 0.0528 0.0356 5 0.4722 0.3185 0.4604 0.3106 6 0.0592 0.0399 0.0577 0.0389 7 5.7680 3.8906 2.8006 1.8890 8 0.3936 0.2655 0.1864 0.1257 9 0.1129 0.0762 0.1091 0.0736 10 2.1763 1.4679 1.0427 0.7033 11 0.6016 0.4058 0.5732 0.3866 12 0.0740 0.0499 0.0705 0.0476 13 0.2049 0.1382 0.1952 0.1317 14 0.4399 0.2967 0.2055 0.1386 The variations of real power loss at each branch and voltage magnitude at each bus with and without compensation are shown in Figs. 5.5 and 5.6 respectively. 60 50 Losses after capacitor placement Losses before capacitor placement 40 30 20 10 0 0 2 4 6 8 10 12 14 Branch number Fig. 5.5 Real power loss at each branch of 15 bus RDS with and without

Voltages (p.u.) capacitor 1 0.99 Voltages after capacitor placement Voltages before capacitor placement 0.98 0.97 0.96 0.95 0.94 0 5 10 15 Bus number Fig. 5.6 Voltages at each bus of 15 bus RDS with and without capacitor 5.7.2 Example 2 Consider a 34 bus system whose single line diagram is shown in Fig. 5.7. The line and load data of this system is given in Appendix A (Table A.4).The total real power loss and minimum bus voltage before compensation are 221.7210 kw and 0.9417p.u. The capacitor Suitability Index and capacitor sizes (nearest standard size of capacitors to the actual value) at the best suitable buses are given in Table 5.8. Fig. 5.7 Single line diagram of 34 bus radial distribution system Table 5.8 CSI and size of capacitor of 34 bus RDS Bus No. CSI Capacitor size 20 0.7500 450

21 0.7500 150 23 0.7500 300 24 0.7500 300 25 0.7500 300 Total size of capacitor 1,500 The summary of results before and after compensation is given in Table 5.9. The comparison of results with existing methods is given in Table 5.10. Table 5.9 Capacitor allocation and loss reduction for 34 bus system Without capacitor With capacitor Bus No. Q-Cap Voltage (p.u.) Voltage (p.u.) 20 0.9549 0.9684 450 21 0.9520 0.9659 150 23 0.9460 0.9587 300 24 0.9435 0.9555 300 25 0.9423 0.9539 300 Total size of capacitor required 1,500 Without capacitor With capacitor Improvement P loss (kw) Q loss P loss (kw) Q loss P loss (kw) Q loss 221.7210 65.1093 156.4270 39.8758 65.293 25.2335 Description Real power losses (kw) Net saving (`.) Total size of capacitor required Net Saving (`.) Without Capacitor With Capacitor ---- 16, 05, 926/- Min. Voltage (p.u.) 0.9417 0.9509 Table 5.10 Comparison of results of 34 bus system with existing methods Existing method [45] Existing method [36] Proposed method Before compensation After compensation Before compensation After compensation Before compensation After compensation 221.72 168.35 221.72 181.72 221.7210 156.4270 ---- 12,40,563/- --- 9,65,200/- ---- 16,05,926/- 1550 --- 1650 ---- 1500 --- From Table 5.9 it is observed that, the minimum voltage is improved from 0.9417 p.u. to 0.9509 p.u., total real power loss reduced from 221.7210 kw to 156.4270 kw (i.e., 29.45%) and total reactive power loss reduced from 65.1093 kvar to 39.8758 kvar (i.e., 38.76%) due to reactive power compensation. Thus, voltage regulation is improved from

Voltages (p.u.) Real Power Loss (kw) 5.83% to 4.91%. From Table 5.10, the size of the capacitor required is 1500 kvar and the net saving is `.16, 05, 926/- which is comparable with the existing methods. The variations of real power loss at each branch and voltages at each bus for with and without compensation are shown in Figs. 5.8 and 5.9 respectively. 40 35 Losses after capacitor placement Losses before capacitor placement 30 25 20 15 10 5 0 0 5 10 15 20 25 30 35 branch number Fig. 5.8 Real power loss at each branch of 34 bus RDS with and without capacitor 1 0.99 Voltages after capacitor placement Voltages before capacitor placement 0.98 0.97 0.96 0.95 0.94 0 5 10 15 20 25 30 35 Bus number Fig. 5.9 Voltages at each bus of 34 bus RDS with and without capacitor 5.7.3 Example 3 Consider a 33 bus system whose single line diagram is shown in Fig. 2.5. The line and load data of this system is given in Appendix - A (Table A.2). The CSI and size of capacitor

is given in Table 5.11. The summary of results before and after compensation is given in Table 5.12. From results it is observed that, the minimum voltage is improved from 0.9131 p.u. to 0.9237 p.u. The improvement in voltage regulation is 1.06%. Also, the total real power loss reduces from 202.5022 kw to 145.0658 kw (i.e., 28.36%) and reactive power loss reduces from 135.1286 kvar to 96.956 kvar (i.e., 28.25%) after capacitor placement. The net saving is `.14,57,428/-. The variation of real power loss at each branch and voltages at each bus with and without capacitor are shown in Figs. 5.10 and 5.11 respectively. Table 5.11 CSI and size of capacitor for 33 bus system Bus No. CSI Capacitor size 30 0.9180 1050 Table 5.12 Capacitor allocation and loss reduction for 33 bus system Description Without capacitor With capacitor Min. Voltage 0.9131 0.9237 Voltage regulation (%) 8.69 7.63 Total real power loss(kw) 202.5022 145.0658 Total reactive power loss 135.1286 96.956 Improvement in real power loss (kw) 157.4364 Improvement in reactive power loss 38.1726 Total capacitor size at bus 30 1050 Net saving (`.) ----- 14,57,428/-

Voltages (p.u.) Real Power Losses (kw) 60 50 Losses after capacitor placement Losses before capacitor placement 40 30 20 10 0 0 5 10 15 20 25 30 35 Branch number Fig. 5.10 Real power loss at each branch of 33 bus RDS with and without capacitor 1 0.99 0.98 0.97 Voltages after capacitor placement Voltages before capacitor placement 0.96 0.95 0.94 0.93 0.92 0.91 0 5 10 15 20 25 30 35 Bus number Fig. 5.11 Voltages at each bus of 33 bus RDS with and without capacitor 5.7.4 Example 4 Consider a 69 bus system whose single line diagram is shown in Fig. 2.6. The line and load data of this system is given in Appendix - A (Table A.3). The CSI and size of capacitor (nearest standard size of capacitor to the actual value) is given in Table 5.13. The summary of results before and after compensation is given in Table 5.14. From results it is observed that, the minimum voltage is improved from 0.9123 p.u. to 0.9341 p.u. The improvement in voltage regulation is 2.18%. Also, the total real power loss reduces from 224.9457 kw to

Real Power Loss (kw) 152.0469 kw (i.e., 32.40%) and reactive power loss reduces from 102.1397 kvar to 70.485 kvar (i.e., 30.99%) after capacitor placement. The net saving is `. 20, 65, 298/-.The variation of real power loss at each branch and voltages at each bus with and without capacitor are shown in Figs. 5.12 and 5.13 respectively. Table 5.13 CSI and size of capacitor for 69 bus system Bus No. CSI Capacitor size 61 0.9200 1350 Table 5.14 Capacitor allocation and loss reduction for 69 bus system Description Without capacitor With capacitor Min. Voltage 0.9123 0.9341 Voltage regulation (%) 8.77 6.59 Total real power loss(kw) 224.9457 152.0469 Total reactive power loss 102.1397 70.485 Improvement in real power loss (kw) 72.8988 Improvement in reactive power loss 31.6547 Total capacitor size at bus 61 1350 Net saving (`.) ----- 20,65,298/- 60 50 Losses after capacitor placement Losses before capacitor placement 40 30 20 10 0 0 10 20 30 40 50 60 70 Branch number Fig. 5.12 Real power loss at each branch of 69 bus RDS with and without capacitor

Voltages (p.u.) 1 0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 Voltages after capacitor placement Voltages before capacitor placement 0.9 0 10 20 30 40 50 60 70 Bus number Fig. 5.13 Voltages at each bus of 69 bus RDS with and without capacitor 5.8 CONCLUSIONS A method has been proposed to determine most sensitive buses to place capacitors using fuzzy logic and its size is calculated using index based method in radial distribution systems. The FES considers loss reduction and voltage profile improvement simultaneously while deciding which buses are the most ideal for placement of capacitor. Hence, a good compromise of loss reduction, voltage profile improvement and net saving is achieved when compared to existing methods. The proposed method has been tested on four distribution systems consisting of 15, 33, 34 and 69 buses. It has been noticed that losses are reduced and voltage profile is improved.