MGM INDUSTRIES, INC. Report No: NCTL-110-14571-1 NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15 Test Specimen NFRC Code Manufacturer: MGM Industries, Inc. Series/Model: Series 4600 Window Type: Double Hung VSDH Frame Composition: Vinyl VY Sash/Vent/Panel Composition: Vinyl w/ Reinforcement-Interlock VI Thermal Break Mat'l: Not Applicable Overall Size: 1200.2 mm (47-1/4 ) wide by 1498.6 mm (59 ) high Glazing Description 0.986 Overall w/low E and Argon No. of Glazing Layers (including films): 2 2 Primary Glazing: Double Glazed DG Spacer Type: Stainless Steel U-Shaped SU-D Gap Fill 1: Argon/ Air (95% Double Probe) ARG Gap Fill 2: Not Applicable Glass/Film Thicknesses (ext to int): 0.086, 0.086 Air Gap 1: 0.814 Air Gap 2: Not Applicable Secondary Glazing: Not Applicable Low Emissivity Coatings: Surface 2: 0.022 Procedure: Standardized Thermal Transmittance (U st ) was determined using the NFRC 102-2010 procedure with a temperature of 69.8 ± 0.5 F on the room side of the specimen and -0.4 ± 0.5 F on the weather side of specimen. The net air leakage across the test specimen was 0.0 cfm. Test Results: Results of the test period 0206-0406 on 12/14/11 using the Equivalent CTS Method: Thermal transmittance at test conditions (U s ): 0.34 BTU/hr/ft 2 / F Standardized thermal transmittance of test specimen (U st ): 0.32 BTU/hr/ft 2 / F Reference should be made to Thermal Performance Test Report Number NCTL-110-14571-1 for complete specimen description and test data. NATIONAL CERTIFIED TESTING LABORATORIES STEVEN H. COBLE Simulator In Responsible Charge
Report Number NCTL-110-14571-1 Report Date 01/06/12 Report To MGM Industries, Inc. 287 Freehill Road Hendersonville, TN 37075 Test End Date 12/14/11 Expiration Date 12/14/15 Specification NFRC 102-2010 Procedure for Measuring the Steady-State Thermal Transmittance of Fenestration Systems (2010 edition)". Description of Sample Tested Note: All dimensions are in the order (Width x Height x Thickness) unless otherwise noted. Model/Type: 4600 Configuration Tilt Double Hung Frame Size 1200.2 mm x 1498.6 mm (47-1/4 x 59 ) Top Sash Size 1117.6 mm x 717.6 mm (44 x 28-1/4 ) Bottom Sash Size 1143 mm x 742 mm (45 x 29-1/4 ) Top Sash Viewing Area 1044.6 mm x 647.7 mm (41-1/8 x 25-1/2 ) Bottom Sash Viewing Area 1047.8 mm x 647.7 mm (41-1/4 x 25-1/2 ) Frame & Sash Type Joint Construction Glazing Components Overall Glass Thickness Coating Extruded vinyl Frame & Sash Mitered, welded 25.0 mm (0.986") nominal Two (2) panes of 2.2 mm (0.086 ) nominal A Cardinal LoE 3 366 sputter-type emissivity coating (e= 0.022 per client) was applied to glazing surface no. 2 Spacer Type/Size Stainless steel U-shaped (SU-D) 20.7 mm (0.814 ) Fill Argon 95% double probe per client Glazing System Exterior glazed with silicone back-bedding and snap-in rigid vinyl glazing bead
MGM Industries, Inc. NCTL-110-14571-1 Weatherstrip Type Size Type Size Sill Extender Type Operating Hardware Latches Type Keeper Type Balance Type Pivot Bar Type Auxiliary Type (2) Strips center fin 6.9 mm (0.270") high Stiles, top rail and exterior meeting rail (1) Strip center fin 6.9 mm (0.270 ) high Bottom rail, interior meeting rail, sill and head Foam-filled bulb-vinyl Bottom rail Cam- type sweep 311.2 mm (12.25 ) from each end of the interior meeting rail Metal Exterior meeting rail at the locked position (1) Dual coil spring Interior and exterior jamb track (1) T-shaped Each end of the bottom rail and exterior meeting rail fastened with (2) screws Weatherstrip holder/ interior vertical leg Head Reinforcement Type Size Contour-shaped aluminum 2.1 mm (0.082") thick Exterior meeting rail Weep Description Size 31.8 mm x 6.4 mm (1.25 x 0.25 ) 76.2 mm (3 ) from each end of the sill face Size 9.5 mm x 3.18 mm (0.375 x 0.125 ) Each end of the exterior meeting rail and bottom rail Size 12.7 mm x 4.76 mm (0.5 x 0.188 ) 22.2 mm (0.874 ) from each end of the screen track Interior/ Exterior Surface Finish Sealant Insect Screen White vinyl (PVC) No apparent sealant applied No screen employed
MGM Industries, Inc. NCTL-110-14571-1 SPECIMEN PREPARATION PRIOR TO TEST The test specimen was pre-conditioned at ambient laboratory conditions prior to the test. The surround panel-tospecimen interfaces were sealed with a non-reflective tape. The specimen was sealed on the interior with a caulk sealant resulting in a measured net air leakage of 0.0 cfm per square foot. TEST PARAMETERS Tests to determine the Standardized Thermal Transmittance (U st ) of the specimen were performed in the guarded hot box apparatus located at the York, PA facility. The most recent calibration of the hot box apparatus was in February 16, 2011. The thermal performance evaluations were completed in accordance with the NFRC 102 procedure using a dynamic wind perpendicular to the specimen on the weather side and simulated natural convection on the room side. A zero static pressure differential (0.00" ± 0.04" H 2 O) was maintained across the specimen during the test by pressurizing the metering box on the room side. Data was collected over two successive 2 hour periods after 4 hours of steady state conditions as defined in section 6.1.2 of the NFRC 102 procedure were achieved. The test was considered completed when the data of the successive 2 hour periods also satisfied the criteria defined in section 6.1.2 of the NFRC 102 procedure. GLASS THICKNESS AND GLAZING DEFLECTION: Glass Thicknesses Glazing Deflection Before Test Glazing Deflection After Test Top Sash 0.086, 0.086 0.04 0.04 Bottom Sash 0.086, 0.086 0.02 0.01 PROJECTED FRAME DIMENSIONS OF MEMBERS: Member: Bottom Jamb Head Meeting Rail Sill Top Jamb Dimension: 3 3. 5 1.875 3.375 3.5 TEST DURATION: The test chamber environmental systems were initiated at 0857 on 12/14/11. The test conditions were considered stable for two consecutive two hour test periods from 0006-0206 and 0206-0406 on 12/15/11. The thermal performance test results were derived from the 0206-0406 test period. Areas: Test Specimen Projected Area (A s ): 19.26 ft² Test Specimen Interior Exposed (Wetted) Surface Area (A int ): 0 ft² Test Specimen Exterior Exposed (Wetted) Surface Area (A ext ): 0 ft² Metering Box Opening Area (A mb ): 54.39 ft² Metering Box Baffle Area (A b1 ): 46.44 ft² Surround Panel Interior Exposed Area (A sp ): 28.48 ft² Exposed Area of Mods to Surround Panel Opening: 6.65 ft² Test Conditions: Average Room Side Air Temperature: 69.8 F Average Weather Side Air Temperature: -0.3 F Average Guard Box Air Temperature: 72.1 F Average Warm Side Surround Panel Temperature: 66.1 F Average Cold Side Surround Panel Temperature: 0.1 F Metering Box Average Relative Humidity: 12 %
MGM Industries, Inc. NCTL-110-14571-1 Test Conditions: (Continued) Measured Weather Side Wind Velocity: 14.3 mph Static Pressure Difference Across Specimen (assumed) : 0.0 H 2 0 Heat Flows: Heat Input Rate to Metering Box (Q total ): 558.9 BTU/hr Surround Panel Heat Flow (Q sp ): 87.5 BTU/hr Surround Panel Thickness: 5.375 Inches Surround Panel Conductance: 0.04659 BTU/hr/ft²/ F Metering Box Heat Flow (Q mb ): -20.5 BTU/hr Flanking Loss Heat Flow (Q fl ): 37.7 BTU/hr Net Test Specimen Heat Flow (Qs): 455.5 BTU/hr EMF vs Heat Flow Equation: y=-8018.4 * EMF + 5.6157 Test Results & Calculated Test Data: Emittance of Glass (e 1 ): 0.84 Warm Side Baffle Emittance (e b1 ): 0.96 Equivalent Room Side Surface Temperature: 53.2 ºF Equivalent Weather Side Surface Temperature: 4.1 ºF Room Side Baffle Surface Temperature: 68.5 ºF Measured Room Side Surface Conductance (h h ): 1.42 BTU/hr/ft²/ F Measured Weather Side Surface Conductance (h c ): 5.29 BTU/hr/ft²/ F Test Specimen Thermal Conductance (C s ): 0.48 BTU/hr/ft²/ F Convection Coefficient (K): 0.346 Radiative Test Specimen Heat Flow (Q r1 ): 231.9 BTU/hr Convective Test Specimen Heat Flow (Q c1 ): 223.6 BTU/hr Radiative Heat Flux of Test Specimen (q r1 ): 12.04 BTU/hr/ft² Convective Heat Flux of Test Specimen (q c1 ): 11.61 BTU/hr/ft² Standardized Room Side Surface Conductance (h STh ): 1.22 BTU/hr/ft²/ F Standardized Weather Side Surface Conductance (h STc ): 5.28 BTU/hr/ft²/ F Test Specimen Thermal Transmittance (U s ): 0.34 BTU/hr/ft²/ F Test Specimen Standardized Thermal Transmittance (U ST ): 0.32 BTU/hr/ft²/ F This test method does not include procedures to determine the heat flow due to either air movement through the specimen or solar radiation effects. As a consequence, the thermal transmittance results obtained do not reflect performances which may be expected from field installations due to not accounting for solar radiation, air leakage effects, and the thermal bridge effects that may occur due to the specific design and construction of the fenestration system opening. Therefore, it should be recognized that the thermal transmittance results obtained from this test method are for ideal laboratory conditions and should only be used for fenestration product comparisons and as input to thermal performance analyses which also include solar, air leakage, and thermal bridge effects. An estimate of the experimental uncertainty for these results is available upon request.
MGM Industries, Inc. NCTL-110-14571-1 Per the client, the test specimen described in this report was a production line unit submitted for initial certification and plant qualification and is described as tested. Detailed drawings were available for laboratory records and compared to the test specimen at the time of this report. A copy of this report along with representative sections of the test specimen will be retained by NCTL for a period of four (4) years. The results obtained apply only to the specimen tested. This report may not be reproduced, except in full, without the written approval of National Certified Testing Laboratories. NCTL is a testing lab accredited by A2LA to ISO/IEC 17025 and assumes that all information provided by the client is accurate and does not guarantee or warranty any product tested or installed. Testing described in this report was conducted in full compliance with NFRC requirements; any deviations are noted. ASTM C1363 and C1199 testing was performed with published NFRC deviations. Ratings included in this report are for submittal to an NFRC licensed IA for certification purposes and are not meant to be used for labeling purposes. Only those values identified on a valid Certification Authorization Report (CAR) are to be used for labeling purposes. National Certified Testing Laboratories STEVEN H. COBLE Simulator In Responsible Charge RAYMOND W. LAMB, P.E. Senior Project Engineer Person-in-Responsible Charge ZM/ hl
ATTACHMENT 1 Section 1: Component Drawings, with Applicable Part Numbers, Manufacturing and Modeling Details, were Reviewed (as submitted) for Product Verification (Reference: NCTL-110-14571-1) See Attached Documentation; any deviations noted. Note: The above referenced component drawings along with representative sections of the test specimen will be retained per procedure by NCTL. This testing facility assumes that all information provided by the client is accurate. Section 2: Identification Date Page & Revision Original Issue 01/06/12 Not Applicable