Method for Monitoring the Electromagnetic Impacts due to High Voltage Overheads Lines in Aosta Valley

Similar documents
Power-frequency magnetic field calculation around an indoor transformer substation

Exposure of Workers to Electromagnetic Fields (EMF) Inside the Olive Mills: Preliminary Evaluations During the Oil Production 1

THE EFFECT OF UNBALANCED LOADS IN DISTRIBUTION TRANSFORMERS AND GROUND NETWORK ON ELECTROMAGNETIC FIELDS

CALCULATION OF POWER FREQUENCY FIELDS FROM HIGH VOLTAGE OVERHEAD LINES IN RESIDENTIAL AREAS

MEASUREMENTS AND CALCULATIONS OF NON-IONIZING RADIATION LEVELS IN VICINITY OF 35 KV OVERHEAD POWER LINES

The Influence of Phase Transposing on Double Circuit Overhead Power Line Magnetic Field

HIGH PERFORMANCE MAGNETIC SHIELDING SOLUTION FOR ELF SOURCES

Levels of electric and magnetic fields inside 110/X kv substations

Magnetic Field in an Apartment Located above 10/0.4 kv Substation: Levels and Mitigation Techniques

H ATMOSPHERIC DISPERSION OF ASBESTOS PARTICLES FROM RURAL BUILDING ROOFS. G. Pession 1, T. Magri 1, G. Tinarelli 2

The Milan agglomeration Strategic Noise Map

ELECTRICAL AND THERMAL DESIGN OF UMBILICAL CABLE

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

Magnetic field shielding of underground power cables in urban areas: a real-life example

S.S. Şeker, F. Can Boğaziçi University, Dept. of Electrical- Electronics Engg Bebek, İstanbul, Turkey

Precision Ag Services

Measurements of electric and magnetic fields, in heavy vehicles parking space, in the vicinity of a power station with 150kv to 20kv transformers

Modern techniques of ice-load assessment and icing maps creation for the design of overhead transmission lines used in the Russian Federation

ANALYSIS OF ELECTROMAGNETIC FIELDS IN INTERCONNECTING SUBSTATIONS BETWEEN WTG AND NATIONAL POWER SYSTEM

1 P a g e h t t p s : / / w w w. c i e n o t e s. c o m / Physics (A-level)

APPLICATION OF GIS IN ELECTRICAL DISTRIBUTION NETWORK SYSTEM

ELECTRIC AND MAGNETIC FIELD GUIDELINE EVALUATION AND MAGNETIC FIELD EXPOSURES FOR LIVE-LINE WORKERS

ADMISSION TEST INDUSTRIAL AUTOMATION ENGINEERING

UNIT I ELECTROSTATIC FIELDS

YMCA UNIVERSITY OF SCIENCE AND TECHNOLOGY, FARIDABAD SCHEME OF STUDIES & EXAMINATIONS B.TECH 2 nd YEAR (SEMESTER IV) ELECTRICAL ENGINEERING ( )

Applications of GIS in Electrical Power System

Proximity effect on bare buried conductors connecting together MV/LV substations earth electrodes

ON THE USE OF HIERARCHICAL MODELS

Lectures of ENVIRONMENTAL ELECTRICAL SCIENCE

Environmental & Socio-economic impacts of mass rapid transit using GIS

Magnetic and Thermal Analysis of Current Transformer in Normal and Abnormal Conditions

The Distortion Influence Simulation and Experimental Study of Human Body to High Voltage Power Frequency Electric Field

Overhead lines. 110 kv wood tower with guy wires

A SEARCH FOR ASTROPHYSICAL POINT SOURCES OF 100 TEV GAMMA RAYS BY THE UMC COLLABORATION

Cosmo model validation through precipitation data coming from radar-based estimation and rain gauges measures

Gis for Land Management: An Overview on Italy

Electric field and exposure time in a EHV substation near a bay-equipment: concerning ICNIRP guidelines

Sang Lee Tel: Subject: AC ELF EMF EMC Magnetic Field Testing for True Infra Sauna Heaters

ELECTROMAGNETIC ENVIRONMENT GENERATED IN A TEM CELL FOR BIOLOGICAL DOSIMETRY APPLICATIONS

Calculation of Electric and Magnetic Field under AC Transmission and Distribution Lines in Guwahati City

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

THREE-PHASE CIRCUITS

Module 5 : Plane Waves at Media Interface. Lecture 39 : Electro Magnetic Waves at Conducting Boundaries. Objectives

Risk indexes for studying interconnected earthing systems inside MV networks

Territorial vulnerability analysis: the case studies

Module 2 : Transmission Lines. Lecture 1 : Transmission Lines in Practice. Objectives. In this course you will learn the following

Afghanistan Resource Data and Geospatial Toolkit (GsT)

Calculation of Electric and Magnetic Field Safety Limits Under UHV AC Transmission Lines

This Unit may form part of an National Qualification Group Award or may be offered on a freestanding

Physics 1502: Lecture 25 Today s Agenda

Computation of Electric Field and Human Body Induced Current under Overhead Transmission Lines

This Unit may form part of a National Qualifications Group Award or may be offered on a freestanding

THERMAL BEHAVIOR OF DISTRIBUTION TRANSFORMERS IN SUMMERTIME AND SEVERE LOADING CONDITIONS

TSU Spring 2010 Physics 2020 Final Exam Name. MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.

H07RN-F. Flexible Cables and Cords 60 C 450/750 V. Application. Specifications

Physics 9 Wednesday, April 2, 2014

COLLEGE PHYSICS Chapter 23 ELECTROMAGNETIC INDUCTION, AC CIRCUITS, AND ELECTRICAL TECHNOLOGIES

Proceedings, International Snow Science Workshop, Breckenridge, Colorado, 2016

Italian Map of Design Earthquakes from Multimodal Disaggregation Distributions: Preliminary Results.

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation

EMC Standards. Samuel Burri 2013, EPFL

GIS AND REMOTE SENSING FOR WATER RESOURCE MANAGEMENT

NEW AIRPORT NOISE MANAGEMENT TECHNIQUES

Extensions to the Finite Element Technique for the Magneto-Thermal Analysis of Aged Oil Cooled-Insulated Power Transformers

STUDYING THE EFFECT OF DISTORTION IN BASIC MAP ELEMENTS FOR THE DEGREE OF SPATIAL ACCURACY OF GAZA STRIP MAPS

Chapter 2 Direct Current Circuits

Comparison of Finite Element Analysis to IEC for Predicting Underground Cable Ampacity

T E M P U S P R O J E C T

Quality Assurance of Automated Measuring Systems: practical implementation of pren 14181:2001. Results of field experience at two Italian plants.

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

International Journal on Technical and Physical Problems of Engineering (IJTPE) Published by International Organization of IOTPE

EDDY CURRENT TESTING

Computation of Electromagnetic Energy Absorption in the Human Body Tissues by High Frequency Structure Simulator

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9

LO 1: Three Phase Circuits

SWITCHGEAR: design concepts, testing, standards and safety of persons and installations

Physics 1308 Exam 2 Summer 2015

Probabilistic assessment of danger zones using a surrogate model of CFD simulations

CBSE PHYSICS QUESTION PAPER (2005)

Standard Practices for Air Speed Calibration Testing

Experimental Study on the Cyclic Ampacity and Its Factor of 10 kv XLPE Cable

The WOLF system: forecasting wet-snow loads on power lines in Italy

elgian energ imports are managed using forecasting software to increase overall network e 칁 cienc.

Modeling of Power System Components During Electromagnetic Transients

11 SEPTEMBER This document consists of printed pages.

Electrostatic measurements around a cryo-jet

PATENT FOR INVENTION

Review of Anemometer Calibration Standards

Calculus Relationships in AP Physics C: Electricity and Magnetism

Use of Satellite Data in ATLAEOLICO AND TRITONE WEBGIS TOOLS

Verification of LAMI (Local Area Model Italy) using non-gts Data over Mountainous Regions

A Study of Electromagnetic Field Generated by High Voltage Lines Using Comsol Multiphysics

Electromagnetic Induction

Physics 3204 Electrical Fields

MARKING SCHEME SET 55/1/RU Q. No. Expected Answer / Value Points Marks Total Marks

Modeling of Transmission Line and Substation for Insulation Coordination Studies

TRANSMISSION LINES. All aluminum alloy conductor (AAAC) Aluminum conductor alloy reinforced (ACAR)

ECOPEDOLOGICAL SOIL MAP OF THE ALPS PROTOTYPE VERSION 1.0

Evaluation of the concrete characteristics by measurements of sonic wave velocity

Two point charges, A and B, lie along a line separated by a distance L. The point x is the midpoint of their separation.

Transcription:

Method for Monitoring the Electromagnetic Impacts due to High Voltage Overheads Lines in Aosta Valley Claudia Desandré, Marzia Mathiou, Valeria Bottura, Marco Cappio Borlino, Leo Cerise, Erik Imperial ARPA Valle d Aosta Saint Christophe (AO), Italy Abstract The aim of this paper is to show the methodology used by the Environment Protection Agency (ARPA) of the Aosta Valley for evaluating the electromagnetic impact due to high voltage overhead lines which cross the region, with regards to public exposure. Simulation and inspections have been used to identify the buildings which can be characterized by electromagnetic pollution, due to their proximity to the lines. After the measurements it is definitely possible verify if limits are exceeded, evaluate the exposure level of population living near the lines and identify actions to reduce it. So far, two important branches were examined with the purpose to extend the controls to all lines in Aosta Valley. Keywords-power line; electromagnetic impact; public exposure; simulation; measurement. I. INTRODUCTION Aosta Valley is an Italian alpine region crossed by many high overhead voltage lines ( kv or 38 kv) which transport electric power from France and Switzerland to Italy. Moreover, due to orography and water supplies of the region, many local hydroelectric power plants produce and introduce energy into the national transmission network. The constant increase of the request for electricity and the introduction of economic incentives for renewable energies is incrementing both energy importation and local production. Therefore, the capacity of power lines crossing the Aosta Valley will be enhanced: this will cause an increase of human and environmental exposure to electric and magnetic fields (EMF) generated by high voltage AC lines (ELF). To check this constant evolution of the exposure, the regional Environmental Protection Agency (ARPA) has been carrying out for some years a systematic monitoring campaign of EMF generated in the environment along the main overhead high voltage lines. Legend: Line -15 kv EGENDA Line kv NEA -15 kv NEA kv NEA 38kV Line 38 kv ABINA PRIMARIA Figure 1. High voltage overhead lines crossing the Aosta Valley region.

METHODOLOGY A. Inspections and Measurements Two different strategic branches of kv lines in the Aosta Valley have been controlled. The first one is an important line in the national network: in this work we examined the section connecting Villeneuve to Chatillon, named T9. Due to his relevance this line, now operated at kv, will be enhanced to work at 38 kv. The second one, instead, represents the preferential way of transport for the energy both incoming from Switzerland and produced in local hydroelectric power plants. This branch is composed by two lines which run parallel: the first one, the principal, is named T1 Valpelline-Leinì and the second one consists in three lines in series, T7 Valpelline-Chatillon, T11 ChatillonMontjovet and T15 Montjovet-Leinì that connected three major power stations (Fig. ). was projected to the ground and transferred in a geo-referenced map. So a buffer on both sides of the line was drawn: the buildings standing in this area were taken into account in the following considerations (red lines in Fig 3 and Fig ). Max ground projection Conductors Isoline 1 µt 55 5 5 35 Height (m) II. 3 5 15 1 5 Valpelline - -1-5 5 1 15 Line T7 Distance to center line (m) Figure 3. Simulation of volume that encloses the value of magnetic field equal to 1 µt. Line T11 Châtillon Line T1-15 Line T15 Montjovet After this first theoretical step, inspections were accomplished to identify the buildings that actually require detailed measurements, with the evaluation of both their 3D distance from the conductors and some preventive measures near the buildings. As shown in the Fig., just two buildings, on the total of those falling within the buffer zone, required deeper measurements. Leinì Figure. Line layout The first step to evaluate people exposure to EMF is to make a preliminary simulation of the magnetic field produced along the selected high voltage lines, with the aim to identify restricted areas where carry out inspections and control measurements. The data provided by the power line operator are: shape and coordinates of the pylons, geometry of conductors and current rating in normal service of the conductors (pcsn, as defined by Italian technical standards [1]). The pcsn and the shape of the wider pylons are the data input for the simulation. The simulation is carried out in a spreadsheet. The result is a volume in the space around the conductors that encloses a predetermined value of magnetic field. The magnetic field value used in the simulation for this study is 1 µt, which represents an important reference level, the attention value, introduced by Italian laws for human electromagnetic fields protection [6]. The maximum extension of this volume Figure. Buffer around center line that represents the projection of the volume of 1 µt. Photos of the two buildings, between all the buildings located in the buffer for their characteristics, where measurements were carried out. The interventions in the selected buildings consist in both instantaneous measurements of electric and magnetic fields and long-term magnetic measures. The instruments used are the EMDEX II for instantaneous and the EMDEX LITE for longterm surveys. In latter case the instrument acquires data every 3 seconds for periods of about one week.

The EMDEX II has a frequency response range of to 8 Hz and a measuring range of the magnetic induction of.1 µt to 3 µt, and, combined with an electric field probe, a measuring range of electric field of 1 V/m to kv/m. The EMDEX LITE has a frequency response range of to 8 Hz and a measuring range of the magnetic induction of.1 µt to 7 µt. As electric field for overhead lines depends on the conductors voltage, which is almost constant, instantaneous measurements are representative of the electric field generated. Electric field values are detected outside the buildings along a section perpendicular to the conductor where they are closer to the ground. On the contrary, since the magnetic induction depends on the intensity current flowing in the lines, it follows the temporal trend of the current and it is highly variable in time. So the instantaneous magnetic fields measurements are only representative of the specific time investigated. In order to gather information about the average or maximum exposition of the population it is necessary to make some theoretical considerations about the patterns of load of the lines. B. Indirect assessment The power line operator give to ARPA the trend of the current in the same days when the magnetic long-term measurements were performed. It is so possible to identify the correlation between magnetic field and current, in case of a single line. In the figure below (Fig. 5) the correlation between the two set of data is.996. If the correlation is greater then.9 it is possible to get an index (the average of the ratio between measure and current in the same time). This index will be used to indirectly derive the value of the magnetic field, whenever the current value is available. Magnetic field (µt) 1,8 1,6 1, 1, 1,,8,6,,, Magnetic field Current Time Figure 5. comparison between trend of current flowing in the power lines and the magnetic field measured in the same time with long-term measurements. When the magnetic induction is generated by more lines and the phases are known, different numerical simulation are carried out with two different softwares: WinELF and MOE. WinELF is a module of the software WinEDT (by Vector), for calculate magnetic field generated by power lines working at 5 Hz. It can store lots of information, related to operators, 35 3 5 15 1 5 Current (A) geometrical and electrical characteristics of the power lines and spatial data (Fig. 6). With the tools in the Elf analysis section, the magnetic field can be simulated both in an area near the power lines and in a single point. The principal data needed are the current, the geometry of the line and the position of the point where magnetic field is going to be calculated. The exact representation of the measurements point was found in WinELF model with subsequent comparison between the value measured and simulated, at the same time with the real current flowing in the lines. This is possible if the correlation between magnetic field and current is greater than.9. This step is necessary, since it is not possible to know the correct position of long-term measurement point with Global Positioning System (GPS) because of both the interference with EMF and the intrinsic resolution error. Once the correctly spatial position of the long-term measurement point is found, this is used, together with the geometry of the transmission lines, in the program MoE. MoE is a specific application program powered by Italian Experimental Electrotechnical Centre (CESI). It allows to monitor the magnetic field generated by transmission line in a specific point, starting from the current data only. Such a system has the advantage, with respect to an instrument system, of not having to create, manage and maintain a monitoring network. The comparison between the magnetic field measured and simulated is shown in Figure 7. As we can see the trend is very similar. Magnetic field (µt) 5,5 3,5 3,5 1,5 1,5 Figure 6. Example of 3D WinELF image. Magnetic field MoE Time hourly average of the measures Figure 7. Comparison between measures done in field and simulation of magnetic field with MoE.

After the first year when some measures were done, ARPA implemented, in the same points, the simulation, with the current data throughout time for which operators provided current data. So it was possible to calculate and verify the magnetic field in the average or maximum load conditions and identify any overrun. If field is generated by two lines and the lines phases are not know it isn t possible to apply any simulation program. In this case it is necessary to repeat the measurements over time. III. RESULTS Eight buildings were monitored along the path of the first power line and twenty along the second one. A. Inspections and Measurements The electric field values measured outdoor are shown in the Figure 8 while Figure 9 shows the magnetic field values measured both instantaneously, outdoor and indoor, and longterm, in the buildings identified with the methodology stated above. Afterwards some classes of exposure to electric and magnetic fields have been identified, based on the data collected, to assess the statistic distribution of the sample. The results are shown in Figure 1 and Figure 11 Frequency (%) 35% 3% 5% % 15% 1% 5% % Max value outdoor -..-.5.5-1. 1.-..-3. 3.-..-5. 5.-6. Classes (kv/m) Figure 1. Statistic distribution of electric field values, outdoor measurements. Electric Field (V/m) 8 7 6 5 3 1 Max value outdoor a b c d e f g h i j k l m n o p q r s t u v w x y z aa bb Sites As shown in Figure 8, only in one point measurements exceeds the exposure limit provided by the Italian law for the electric field. Instead any point with magnetic field values over the threshold limit is identified (Fig. 9). Limit Figure 8. Outdoor electric field values. Frequency (%) % 35% 3% 5% % 15% 1% 5% %.-.5.5-1. 1.-1.5 1.5-..-.5.5-3. 3.-..-5. 5.-6. B. Indirect assessment Max value outdoor Max value indoor Max median indoor Classes (µt) Figure 11. Statistic distribution of magnetic field values, outdoor, indoor and long-term measurements. 1 1 Max value outdoor Max value indoor Max median indoor Italian limit ARPA has collected the current data for all power lines since. So, for those cases that respect boundary conditions described above, it has been possible to perform theoretical elaborations since. Magnetic Field ( µt) 8 6 a b c d e f g h i j k l m n o p q r s t u v w x y z aa bb Along the single line path, eight buildings were monitored. In six cases the correlation coefficient between magnetic field and current, flowing during measurements, is more than.9. Thus the index could be calculated as described in the previous section. Finally, both the maximum median (Fig. 1) and the annual average values of magnetic field (Fig. 13) throughout all years could be calculated. For the other two buildings no elaborations could be done. Sites Figure 9. Outdoor, indoor and long-term magnetic field values.

The elaborations have not provided values exceeding the limit. 1 7, 1 8 6 6 7 8 1 6, 5,, 3,, 6 7 8 1 G1 G G3 G A1 A 6 1 8 7 1,, A B C D E F G 7 Figure 1. Maximum daily median of magnetic field in the six buildings monitored throughout all years. As shown in Figure 1, in building A1in 8 the Italian limit was exceeded. However, this overrun never occurred again in the following years. In addition, further studies have shown that the overrun occurred in one single day. The magnetic field annual average represents an important indicator of the average exposure (Fig. 13). The values of the annual average are all less than the Italian limits. 3.5 3.5 1.5 1.5 G1 G G3 G A1 Figure 13. Annual average in the six buildings monitored throughout all years. The second case studied is characterized by two lines which run parallel sharing the same pylons. Twenty buildings were individuated in the buffer of interest. Just for seven buildings, it was possible to carry out the simulations both with WinEDT and MoE. For the other cases, in fact, the current phases between the two lines weren t known. In this case too, both the maximum median (Fig. 1) and the annual average of magnetic field (Fig. 15) throughout all years were calculated. A 6 1 8 7 6 7 8 1 Figure 1. Maximum daily magnetic field median in the seven buildings monitored throughout all years. 3,5 3,,5, 1,5 1,,5, A B C D E F G 7 Figure 15. Annual magnetic field average in the seven buildings monitored throughout all years. IV. CONCLUSIONS In this paper an investigation method to assess, with subsequent steps, the exposure to electric and magnetic field generated by power lines was described, based both on measurements and simulations. 1) Knowing pylons position and shape and line electrical characteristics, a D buffer can be drawn on the map to distinguish buildings to be investigated, due to possible high field exposure. ) By intervention on the spot, a second screening, considering the height of the buildings with respect to line height, further reduces the number of cases in which measurements are needed. 6 7 8 1

3) Electric and magnetic field measurements are carried out: the first don t vary in time so the exposure can be immediately evaluated, the latter, depending on current flow, is not comprehensive and some more analysis has to be accomplished. ) If values of current flowing in the lines during the field measurements and line phases are known, and correlation between current and field data is higher than.9, mathematical methods can be used, both for single or double lines, to evaluate magnetic field values from current data series on any time lapse. 5) If steps from 1 to are verified, the method can be used to investigate exposure limit overrun and evaluate mean exposure on a long period or field values on a specified time, provided that the current data are available. REFERENCES [1] CEI 11-6 Portata al limite termico delle line elettriche aeree esterne con tensione maggiore di 1 kv -6 [] CEI 11-6 Guida per la misura e la valutazione dei campi elettrici e magnetici nell intervallo di frequenza Hz 1 khz, con riferimento all esposizione umana 1-1 [3] CIGRE Technical guide for measurement of Low Frequency Electric and Magnetic Fields near Overhead Power Lines, WG C.3 April [] EN 513 Basic standard on measurement and calculation procedures for human exposure to electric, magnetic and electromagnetic fields ( Hz 3 GHz) 8-1 [5] EN 611 Electric and magnetic fields level generated by AC power systems Measurement procedures with regards to public exposure -11 [6] DPCM 8/7/3 Fissazione dei limiti di esposizione, dei valori di attenzione e degli obiettivi di qualità per la protezione della popolazione dalle esposizioni ai campi elettrici e magnetici alla frequenza di rete (5 Hz) generati dagli elettrodotti., Gazzetta Ufficiale n. del 9 agosto 3 [7] Decreto del Ministero dell Ambiente e della Tutela del Territorio e del Mare Approvazione delle procedure di misura e valutazione dell induzione magnetica, Gazzetta Ufficiale. n. 153 del luglio 8