Particle Intiated Breakdown Inside Gas Insulated Switchgear for Various Gases Mixtures

Similar documents
EXPERIMENTAL AND THEORETICAL STUDY OF BREAKDOWN VOLTAGE INITIATED BY PARTICLE CONTAMINATION IN GIS

A New Model of Investigating the Electric Field in Dielectric Liquid for Streamer Initiation

PARTICLE TRAJECTORIES IN A THREE PHASE COMMON ENCLOSURE GAS INSULATED BUSDUCT WITH MONTE CARLO TECHNIQUE

EE6701 HIGH VOLTAGE ENGINEERING UNIT II-DIELECTRIC BREAKDOWN PART A

Inception Voltage of Corona Discharge from Suspended, Grounded and Stressed Particles in Uniform-Field Gas-Insulated-Gaps at Varying Pressures

Onset voltage of negative corona on dielectric-coated electrodes in air

Electric Field Stress Calculation for different spacer types in Bus Duct

Comparison of Radial Movement of Metallic Particles in a Single Phase Gas Insulated Busduct

J. Electrical Systems 10-3 (2014): Regular paper

Analysis of Distribution, Pattern, and Vector of Electric Field in the Inter Phases Region of Three-phase Gas Insulated Switchgear

HIGH VOLTAGE INSULATION AND ELECTRICAL DISCHARGE

Adaptive numerical simulation of Streamer. Shailendra Singh

Narapareddy Rama Rao 1, J.Amarnath 2, E.Arunkumar 3, T.Srinivas 4

Flashover Performance of Station Post Insulators under Icing Conditions based on Electric Field Distribution

EFFECT OF DIELECTRIC BARRIERS TO THE ELECTRIC FIELD OF ROD-PLANE AIR GAP

Exponential Expression of Relating Different Positive Point Electrode for Small Air Gap Distance

Solution for High Voltage Engineering

with embedded electrode

Finite Element Method Application in Analyzing Magnetic Fields of High Current Bus Duct

Electric Field Characteristics under Three-phase Voltage in Three-phase Gas Insulated Switchgear

International Journal of Advances in Engineering & Technology, May IJAET ISSN: D. Deepak Chowdary 1, J.Amarnath 2

Electrical Discharge Characteristics of 1-D Plane Micro-electrodes

Recent Improvements in K-Factor Models

Copyright 2014 IEEE. Paper presented at 2014 IEEE conference on electrical insulation and dielectric phenomena, Des Moines, USA, October, 2014.

THE APPROACH TO THE ANALYSIS OF ELECTRICAL FIELD DISTRIBUTION IN THE SETUP OF PAPER INSULATED ELECTRODES IN OIL

CHAPTER 2 ESTIMATION OF BREAKDOWN VOLTAGES IN SMALL INSULATION GAPS AN EMPIRICAL APPROACH

THE grounding resistance decreases as injected current

Analysis of Very Fast Transients in EHV Gas Insulated Substations

IMPULSE BREAKDOWN OF SHORT ROD-PLANE GAPS WITH A ROD COVERED WITH DIFFERENT DIELECTRIC MATERIALS

HUMIDITY INFLUENCES ON THE BREAKDOWN OF ROD-PLANE GAPS UNDER POSITIVE IMPULSES IN ATMOSPHERIC AIR

T of a system during partial-discharge activity are related

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

A Novel Analytical Expressions Model for Corona Currents Based on Curve Fitting Method Using Artificial Neural Network

OR Explain thermal breakdown in solid dielectrics. How this mechanism is

EXPERIMENTAL DEVELOPMENTS ON SOIL IONIZATION: NEW FINDINGS

Hybrid Resistive-Capacitive and Ion Drift Model for Solid Gas Dielectrics

Partial Discharge and Cross Interference Phenomena in a Three-phase Construction

Numerical Calculation and Analysis on the Surface Electric Field Characteristics of Hot-Line Robot

THE EARLY STREAMER EMISSION PRINCIPLE DOES NOT WORK UNDER NATURAL LIGHTNING!!

Electric Filed Simulation and Structure Optimization for 40.5kV GIS Based on Finite Element Method

Performance of SF 6 GIB under the influence of power frequency voltages

EFFICIENCY OF DUAL WIRE-CYLINDER ELECTRODES USED IN ELECTROSTATIC SEPARATORS

On Designing of a High Voltage Standard Capacitor Using a Semi-Analytical Field Computation Method

CHAPTER-I INTRODUCTION. The increasing demand for electricity and the growing energy

Power Engineering Institute Warsaw University of Technology


Finite Element Analysis Method for Detection of the Corona Discharge Inception Voltage in a Wire-Cylinder Arrangement

Electrical Breakdown in Low-Pressure Nitrogen in Parallel Electric and Magnetic Fields

The phenomenon of Ground Effect in contradiction to the Polarity Effect in rod plate air gaps.

The Trials and Tribulations of High Voltage Insulators. David Garton Institute for Environmental Research

ELECTRICAL DISCHARGES AND BREAKDOWN IN COMPRESSED SULPHUR - HEXAFLUORIDE GAS

I n many cold-climate regions of the world, overhead

Modelling Of Mathematical Equation for Determining Breakdown Voltage

Code No: RR Set No. 1

Development of a New Solid Insulation with the use of Phenol Formaldehyde Resin Material for a Liquid-Immersed Transformer

Lecture 6: High Voltage Gas Switches

INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING

A Simulation Model of Fluid Flow and Streamlines Induced by Non-Uniform Electric Field

Influence of Axial Magnetic Field on the Electrical Breakdown and Secondary Electron Emission in Plane-Parallel Plasma Discharge

Progress In Electromagnetics Research, PIER 52, , 2005 FDTD ANALYSIS OF MICROSTRIP PATCH ANTENNA COVERED BY PLASMA SHEATH

Simulation of Prebreakdown Phenomena in Air Gaps of Rod Plane Configuration of Electrodes

Analysis of a Cylinder-Wire-Cylinder Electrode Configuration during Corona Discharge

Field Sensitive Air Terminal (F-SAT) Simply the Best Lightning Rod

Comparison of Partial Discharge Characteristics for Different Defect Types in SF 6 Gas Insulation System

Fatima Michael College of Engineering & Technology

Analysis of Electric Field and Polarization of SF6 Circuit Breaker to Approach a Suitable Structure

UNIT I - INTRODUCTION SYLLABUS

"ELECTRODE SURFACE ROUGHNESS EFFECT ON THE BREAKDOWN CHARACTERISTICS OF COMPRESSED GAS CABLE"

INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING

Numerical Simulation of Corona Discharge in Compressed Gases with the Effect of EHD Flow

Modeling of Degradation Mechanism at the Oil-Pressboard Interface due to Surface Discharge

Modeling of Transmission Line and Substation for Insulation Coordination Studies

Investigation of electrode arrangement on ionic wind velocity for hole-type electrostatic precipitator

Some Aspects of Stress Distribution and Effect of Voids Having Different Gases in MV Power Cables

D DAVID PUBLISHING. Pressure Rise in Electrical Installations due to Internal Arcing in CO 2 as Insulating Gas. 1. Introduction

The Lightning Study of Overhead Transmission Lines

Available online at ScienceDirect. Procedia Computer Science 83 (2016 )

Electrical Discharges Characterization of Planar Sputtering System

Numerical simulation for arc-plasma dynamics during contact opening process in electrical circuitbreakers

Comparative Analysis of Dielectric Properties of Enamel Filled with Various Nanofillers such as ZrO 2, Al 2 O 3, CNT and ZnO

EFFECT OF EARTH DISCONTINUED TO THE ELECTRICAL FIELD DISTRIBUTION IN ROD-PLANE AIR GAPS UNDER LIGHTNING IMPULSE. A. Khechekhouche and D.

Computation of Electric Field for FGM Spacer Using Di-Post Insulator in GIS

Arrangement of conductors in 220 kv double circuit line to reduce E-fields in view of public exposure

MECHANICAL CHARACTERISTICS OF STARCH BASED ELECTRORHEOLOGICAL FLUIDS

Influence of water vapour on acetaldehyde removal efficiency by DBD

Preliminary study on the modeling of negative leader discharges

CONSIDER a simply connected magnetic body of permeability

Electric Field Measurements in Atmospheric Pressure Electric Discharges

Modeling and Simulation of Air Insulated and Gas Insulated Substations

Simulation of Partial Discharge in Solid Dielectric Material

Comparison of Transient Simulations on Overhead Cables by EMTP and FDTD

Measurement of the electric field at the near field radiating by electrostatic discharges

Suppressor film capacitor Highlight and Application in Series with the main

Gas Electronegativity Influence on Electrical Breakdown Mechanisms

Corona Losses Calculation in HVAC Transmission Lines Using FEM and Comparison with HVDC Corona Losses

Extensions to the Finite Element Technique for the Magneto-Thermal Analysis of Aged Oil Cooled-Insulated Power Transformers

Experiment and Modeling of Void Discharges Within Dielectric Insulation Material Under Impulse Voltage

Electric Field Stress Calculation on High Voltage Insulator

Miniature Vacuum Arc Thruster with Controlled Cathode Feeding

Transcription:

International Journal on Electrical Engineering and Informatics Volume 4, Number 2, July 212 Particle Intiated Breakdown Inside Gas Insulated Switchgear for Various Gases Mixtures Sayed A. Ward 1, M. A. Abd Allah 2, and Amr A. Youssef 3 Electrical Engineering Department, Faculty of Engineering at Shoubra, Benha University, Cairo, Egypt 3 eng_power_amr211@yahoo.com Abstract: SF 6 gas insulated switchgear plays an important role in electric power networks all over the world due to its merits as compared to traditional air insulated switchgear.the mixtures composed of a strongly electronegative gases with high dielectric strength such as SF 6 and two ordinary gases such as N 2 and Air or CO 2 and Air with a various fractional concentrations are used in this paper to reduce the gas price and liquefaction temperature. From this point of view, various types of gas mixtures are used inside gas insulated switchgear (GIS) to give a higher dielectric strength. In this paper, the Finite Elements Method (FEM) is used to evaluate the potential and electric field distributions on and around contaminating filamentary wire particle at two positions, first is resting on the earthed plate and second is hovering inside the gap. The effects of particle dimensions such as (length, radius) and gap spacing on the electric field values are also studied. The breakdown voltage calculations under uniform field in case of clean gap and non-uniform field in case of gap with particle contamination are studied. The effects of gas pressure, SF 6 gas concentration in mixture, gap spacing and particle dimensions on the breakdown voltage calculations are also studied. Keywords: Mixtures, GIS, FEM, Electric Field, Breakdown Voltage. 1. Introduction SF 6 has been widely used as insulation media for gas insulated switchgear (GIS) and gas insulated transmission line (GIL), due to its excellent insulation and arc quenching properties. Although the SF 6 gas has superior dielectric properties, SF 6 gas made an issue of environmental influence due to its high global warming potential (GWP=239). Thus the development of an alternative gas or gas mixtures having much lower GWP is strongly required. Mixtures composed of a strongly electronegative gas of high dielectric strength such as SF 6 and two ordinary gases such as N 2 and air or CO 2 and air with a various concentrations are used in this work. The presence of contaminating particles lowered the dielectric strength of the gas sharply. Some studies were carried out both Theoretically [1-6] and experimentally [7-11] to determine the role of single contaminating particles in initiating breakdown in gaseous insulation under pure SF 6 or SF 6 gas with one ordinary gas such as CO 2 or N 2. The determination of the breakdown voltage in the gas requires the knowledge of the potential and field distribution on and around the charged particle surface. So in this paper, the electric potential and field distribution are studied between two parallel plates with a wire-shaped (filamentary) particle when it rested on the earthed plate and hovering in the gap. The finite element method (FEM) has been used throughout the calculations in this paper, for its favorable accuracy, when applied to high voltage problems. 2. Electric Field Calculations The electric field is calculated with using the Finite Element Method (FEM) throughout this work. The Finite Element Method Magnetics (FEMM) Package is used to simulate the Received: May 2 th, 212. Accepted: August 8 th, 212 32

Sayed A. Ward, et al. problems and to calculate the electric field inside the GIS. FEMM is a finite element package for solving 2D planar and axi-symmetric problems in electrostatics and in low frequency magnetic [12]. The FEMM Version 4.2 is used throughout the work in this paper for computation the voltage and the electric field distributions around the contaminating particles. The electric field and voltage distributions on and around filamentary (wire) contaminating particle lies on the earthed electrode of two parallel electrodes will be presented. Also, the electric field distributions around hovering contaminating particles between the two parallel plates will be computed. 3.Electrostatic Modeling of Wire Particle Contamination A. When The Particle is on Earthed Electrode Figure 1 shows two parallel plates configuration with filamentary wire contaminating particles resting on the earthed plate. The gap between the plates is taken as 2mm. Where, L is the particle length, r is hemispherical radius of the particle, G is the gap between two parallel plates and Gu is the upper gap space from upper tip of the particle up to upper plate. Figure 1. Two parallel plates configuration with filamentary wire contaminating particle resting on earthed electrode (a) For wire particle of 2mm length and of.2mm radius The potential distribution along gap between two parallel plates with the wire contaminating particle, resting on earthed plate is shown in Figure 2. It can be observed that the voltage decreases gradually from 1volt at the upper plate through the gap until it reaches zero at the ground plate. Figure 3 shows the electric field distribution along gap between two parallel plates with wire contaminating particle resting on earthed plate. It can be observed that the electric field is maximum value at upper tip of earthed wire particle and minimum value at lower tip of it. Figure 4 shows the electric field distribution around wire contaminating particle resting on earthed electrode. It can be observed that the electric field increases gradually from zero at the lower tip of the wire particle until it reaches to maximum value, about 445.2 V/m, at the upper tip of it. 321

Particle Intiated Breakdown Inside Gas Insulated Switchgear Figure 2. Potential distribution along gap between two parallel plates with wirecontaminating particle resting on earthed electrode Figure 3. Electricc field distribution along gap between two parallel electrodes with wirecontaminating particle resting on earthed electrode Figure 4. Electric field distribution around wire contaminating particle resting onearthed electrode Figure 5 shows the electric potential distribution along gap from upper tip of wire particle up to upper plate. It can be observed that the voltage increases gradually from zero at ground electrode until reach to 1volt at upper plate. Figure 6 shows magnitude, normal and tangential components of electric field distribution along gap from upper tip of wire particle up to upper plate. It can be observed that normal component of electric field is around zero. The tangential component of electric field is maximum value ( 445.21V/m) at upper tip of wire particle and 322

Sayed A. Ward, et al. decreases gradually as far from it and then approximately become constant ( 5.11V/m) along the remainder gap from 4mm from upper tip of wire particle up to upper plate. Figure 7 shows magnitude, normal and tangential components of electric field distribution along surface of wire particle. It can be observed that the tangential component of electric field is around zero and the normal component of it increases gradually from zero until reach to maximum value at upper tip through negative side, so mathematically,the magnitude of electric field is also increases from zero to 445.2 V/m at upper tip of wire particle though positive side. Electric Potential, Volt 1..8.6.4.2. 5 1 15 2 Gu, mm Figure 5. Electric potential distribution along gap from upper tip of wire particle up to upper plate 5 4 Electric Field, V/m 3 2 1 5 1 15 2-1 Gu, mm IEI, V/m Et, V/m En, V/m Figure6. Electric field distribution along gap from upper tip of wire particle up to upper plate Electric Field, V/m 5 4 3 2 1-1..5 1. 1.5 2. -2-3 -4-5 Particle Length, mm IEI, V/m Et, V/m En, V/m Figure 7. Electric field distribution along surface of wire particle 323

Particle Intiated Breakdown Inside Gas Insulated Switchgear (b) Effect of particle length on the electric field values The variation of the electric field value at the upper tip of the wire particle with respect to the particle length is shown in Figure 8. It can be observed that as the particle length increases from 1mm to 5mm, the electric field at upper tip of the wire particle increases from about 445.2V/m to about 1233.8V/m. 14 12 Electric Field, V/m 1 8 6 4 2 1 2 3 4 5 Particle Length (L), mm Figure 8. Electric Field at upper tip of wire particle with respect to Particle length (c) Effect of ratio (L/r) on the electric field values Figure 9 shows the variation of the electric field value at the upper tip of the wire particle with respect to the ratio (L/r). It can be observed that as the ratio of (L/r) increases from 5 to 25, the electric field at upper tip of the wire particle will increase from about 445.2V/m to about 1233.8V/m. Electric Field, V/m 14 12 1 8 6 4 2 5 1 15 2 25 L/r Figure 9. The electric field values at upper tip of wire particle as a function of the ratio (L/r) (d) Effect of wire particle radius on the electric field values The effect of changing the wire particle radius on the electric field values at the upper tip of the wire particle is shown in Figure 1. The wire particle length is taken 2mm. As the wire particle radius increases from.1mm to.5mm, the electric field at the upper tip of the particle decreases from about 139V/m to about 42V/m, i.e as the wire particle radius increases, the electric field decreases. 324

Sayed A. Ward, et al. 12 Electric Field, V/m 1 8 6 4 2.1.2.3.4.5 Hemispherical radius (r), mm Figure 1. The electric field at upper tip of wire particle versus the particle radius (e) Effect of gap spacing between plates on the electric field values The effect of the gap spacing between the two parallel plates on the electric field at upper tip of the wire particle is shown in Figure 11. The wire particle length is taken as 2mm and the wire particle radius as.2mm. It is noticed that as the gap spacing increases from 1mm to 5mm, the electric field at upper tip of the wire particle decreases from about 1312.4V/m to about 261.6V/m. Electric Field, V/m 14 12 1 8 6 4 2 1 2 3 4 5 Gap Spacing (G), mm Figure 11. The electric field at upper tip of wire particle versus the gap spacingbetween two parallel plates B. When The Particle is Hovering Inside the Gap Figure 12 shows a wire particle hovering in the gap between two parallel plates. Figure 13 shows effect of changing of particle height above the ground plate on the electric field. The wire radius (r) is taken as.3mm, the wire length to radius ratio (L/r) as15 and the gap spacing (G) is 2mm. When the height of the wire particle (h) is zero, i.e. the particle is resting on the ground plate, the electric field at the lower tip of the wire particle is equal to zero but its value at the upper tip of wire particle is equal to about 85.8V/m. As the particle height increases from mm to 2mm, the electric field at the lower tip of the wire particle increases from V/m to about 525.V/m, while at the upper tip of the wire particle the field decreases from about 85.8V/m to about 51.2V/m. When the particle height increases from 2mm to 1mm, the electric field at the lower tip of the wire particle is slightly decreased from about 525.V/m to about 54.7V/m, while at the upper tip of the wire particle is slightly increased from about 51.2V/m to about 57.1V/m. 325

Particle Intiated Breakdown Inside Gas Insulated Switchgear Figure 12. Two parallel electrodes configuration with filamentary wire contaminatingparticle hovering in the gap Electric Field, V/m 9 8 7 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 1 Particle height, mm E-Upper Tip, V/m E-Lower Tip, V/m Figure 13. The electric field at the upper tip and the lower tip of the wire particle versusthe particle height above the ground plate 4. Ionization Coefficients for SF 6 -Gas Mixtures In order to compute the breakdown voltages of SF 6 -gas mixtures, a knowledge of the effective ionization coefficient ά= α - η as a function of the electric field intensity (E) in the neighborhood of ά= is a prerequisite. The net ionization coefficients for SF 6 gas mixtures (ά)mix can be calculated from the values of ά in pure gases. For pure Nitrogen the net ionization coefficients ά can be approximated by [13]; 2.15 = 66exp P E / P (1) The measurements of the effective ionization coefficient ά for CO 2 has been summarized by Rein and can be approximated by the following equations[14] : 2.565 = 176.5exp P E / P for.2<=e/p<=.28 (2) 326

Sayed A. Ward, et al. 1.515 = 5.3exp P E / P for.28<e/p<=1 (3) For air, the ionization coefficients can be approximated by [15], = 22 ( E / P.244) 2 P = 15.8114 /.244 P ( E P ) 1.75 for.244<e/p<=.5 (4) for.5<e/p<=1.2 (5) For pure SF 6, /P can be expressed as [16], = 27 /.8775 P ( E P ) In Eqs. (1) through (6), P is the gas pressure in kpa, /P is given in (cm.kpa) -1 and E/P has the units of Kv (cm.kpa) -1. For a given SF 6 -gas mixture, the effective ionization coefficient is assumed to be given by: (ά /P) mix = F(ά /P) SF6 +(1-F) (ά /P) gas (7) Where, F = P(SF 6 ) / P(mix) is the partial pressure ratio of the SF 6 component in a given gas mixture. When added two electronegative gases to SF 6 -gas mixture, the effective ionization coefficient is assumed to be given by : (ά /P) mix = F1(ά /P) SF6 + F2(ά /P) gas1 + F3(ά /P) gas2 (8) where, F 1 = P(SF 6 ) / P(mix) is the partial pressure ratio of the SF 6 component in a given gas mixture, F 2 = P(gas 1 ) / P(mix) is the partial pressure ratio of the first electronegative gas in a given gas mixture and F 3 = P(gas 2 ) / P(mix) is the partial pressure ratio of the second electronegative gas in a given gas mixture. 5. Methodology for Breakdown Voltage Calculations In order to study the breakdown voltages for a fixed particle which is represented by a hemi-spherical tip with diameter (2r) and length (L) which is contaminating a parallel-plane gap with spacing (G) for SF 6 - gas mixture under DC voltage. The electric field around this fixed particle is satisfied in this work by using finite element method. With an applied electric field, discharges in the gas occur as a result of ionization, which lead to streamer formation and ultimately to breakdown of the gas mixture. One way to predict breakdown voltage of the gas mixture is, therefore, by knowing its effective ionization coefficient. In a non-uniform field gap, corona discharges will occur when the conditions for a streamer formation in the gas are fulfilled. Streamer formation is both pressure and field dependent, and therefore depends on the electrode profile, geometry of the contaminating particle, its position in the gap between electrodes if it is free, and on the instantaneous value of the ambient field. The condition for streamer formation is given by; (6) xc ( x ) dx K (9) 327

Particle Intiated Breakdown Inside Gas Insulated Switchgear Where, ά(x)=α(x)-η(x), α(x) and η(x) are the first ionization coefficient and the coefficient of attachment, respectively; both being functions of field and thus of geometry. The distance xc from the particle s tip is where the net ionization is zero, normally known as the ionization boundary. There is some controversy over the value of K, the discharge constant. The value of K for pure gases in the pressure range of 1 to 4 kpa is obtained as follows using the breakdown data given in CIGRE paper [17]; K for pure N 2 is (5±.5). Malik and Qureshi [18] assumed that K has a value in between 5 and 25 for the different SF 6 gas mixtures. In this study for breakdown voltages we take the value of K = 18.42 for SF 6 gas and SF 6 - gas mixture but K=5 for N 2 gas and K=27 for CO 2 gas. 6.Breakdown Voltage Results for Gas Mixtures with Particle Contamination A. Effect of Gas Pressure on the Breakdown Voltage The effect of fractional concentration of SF 6 gas in mixture under different gas pressure with particle contamination is shown in Figures. 15, 16 and 17. From these figures we can see that, if the fractional concentration of SF 6 increase in mixture, the breakdown voltage is also Figure 15. Effect of gas pressure for SF 6 :CO 2 :Air mixture on BreakdownVoltage for a gap with particle contamination increased. Also, the breakdown voltage for mixture is increased as the pressure of mixture increases. From Figure 15, it can be observed that as fractional concentration of SF 6 gas in mixture increases, breakdown voltage increases but as fractional concentration of CO 2 & Air gases decreases in mixture, breakdown voltage increases. From Figure 16, it can be observed that as fractional concentration of N 2 & Air gases decreases in mixture, breakdown voltage increases. From Figure 17 at fixed percentage of SF 6 gas in mixture, increasing percentage of N 2 gas and decreasing percentage of Air in the same mixture increasing the breakdown voltage, we note that breakdown voltage for (5%SF 6 +8%N 2 +15%Air) is greater than (5%SF 6 +5%N 2 +9%Air) by 22.2%. Also at fixed percentage of SF 6 gas in mixture, increasing percentage of CO 2 gas and decreasing percentage of Air in the same mixture increasing the breakdown voltage, we note that breakdown voltage for (5%SF 6 +8%CO 2 +15%Air) is greater than (5%SF 6 +5%CO 2 +9%Air) by 12.6%. 328

Sayed A. Ward, et al. Figure 16. Effect of gas pressure for SF 6 :N 2 :Air mixture on BreakdownVoltage for a gap with particle contamination Figure 17. Effect of gas pressure for 5%SF 6 -gas mixture on BreakdownVoltage for a gap with particle contamination B. Effect of Gap Spacing Between Two Parallel Plates onbreakdown Voltage From Figures18 and 19, If fractional concentration of SF 6 gas increased in mixture with decreasing percentage of N 2 or CO 2 gas and also decreasing percentage of Air gas in the same mixture, hence the breakdown voltage increases. 329

Particle Intiated Breakdown Inside Gas Insulated Switchgear Figure18.Effect of gap spacing on Breakdown Voltage forsf 6 :N 2 :Air gas mixture at P=3KPa Figure 19.Effect of gap spacing on Breakdown Voltage forsf 6 :CO 2 :Air gas mixture at P=3KPa C. Effect of the Dimensions for Particle Contamination on Breakdown Voltage The effect of particle dimensions (particle radius and particle length) on the breakdown voltage for SF 6 -gas mixture with different concentration of SF 6 in mixture is shown in Figures 2 and 21. From Figure 2, as hemispherical radius of particle increases, the breakdown voltage increases and also as fractional concentration of SF 6 -gas in mixture increases, the breakdown voltage increases. From Figure 21, as particle length increases, the breakdown voltage decreases but as fractional concentration of SF 6 -gas in mixture increases, the breakdown voltage increases also. 33

Sayed A. Ward, et al. Breakdown Voltage (KV) 12 1 8 6 4 2 5%SF6+5%N2+45%AIR 2%SF6+4%N2+4%AIR 5%SF6+25%N2+25%AIR 9%SF6+5%N2+5%AIR.1.2.3.4.5 Hemispherical radius, mm Figure 2.Effect of hemispherical radius of particle on Breakdown Voltage for SF 6 :N 2 :Airgas mixture at P=3KPa Breakdown Voltage (KV) 12 1 8 6 4 2 5%SF6+5%N2+45%AIR 2%SF6+4%N2+4%AIR 5%SF6+25%N2+25%AIR 9%SF6+5%N2+5%AIR 1 2 3 4 5 Particle Length, mm Figure 21.Effect of particle length on Breakdown Voltage for SF 6 :N 2 :Air gas mixture at P=3KPa 7. Comparison between Breakdown Voltage for Gap with particlecontamination and clean gap Figure 22 shows the difference between breakdown voltage in case of clean gap compared with breakdown voltage in case of presence of particle contamination in the gap with L=2mm and r=.2mm and also shows the effect of gas pressure on breakdown voltage for various fractional concentration of SF 6 gas in mixture in case of clean gap and also with particle contamination. At P=5KPa and G=2mm, the breakdown voltage in case of clean gap for SF 6 -N 2 gas mixture with 5% SF 6 concentration is 46KV but in case of gap with particle contamination, the breakdown voltage is 71.5KV, i.e breakdown voltage for gap with particle contamination decreases approximately by 15.5% from it's value in case of clean gap. 331

Particle Intiated Breakdown Inside Gas Insulated Switchgear Figure 22. Effect of gas pressure on breakdown voltage for clean gap and gap with particlecontamination for a various fractional concentrations of SF 6 -N 2 gas mixture 8. Conclusions In this study, two electrostatic modeling which consists of two parallel plates with earthed particle and other with hovering particle are presented. The electric field at upper tip of the wire particle increases as the particle length increases and decreases as the wire particle radius increases. The electric field is maximum at upper tip and lower tip of the hovering wire particle and minimum at the middle of particle surface. The breakdown voltage increases as fractional concentration of SF 6 gas increases in mixture and also with increasing the pressure of mixture. At fixed percentage of SF 6 gas in mixture, with increasing the percentage of N 2 gas and decreasing the percentage of Air in the same mixture, the breakdown voltage increases, the breakdown voltage for (5%SF 6 +8%N 2 +15%Air) gas mixture is greater than that for (5%SF 6 +5%N 2 +9%Air) gas mixture by about 22.2%. At fixed percentage of SF 6 gas in mixture, with increasing the percentage of CO 2 gas and decreasing the percentage of Air in the same mixture, the breakdown voltage increases, the breakdown voltage for (5%SF 6 +8%CO 2 +15% %Air) gas mixture is greater than that for (5%SF 6 +5%CO 2 + 9%Air) gas mixture by about 12.6% %. The breakdown voltage increases as the hemispherical radius of the particle increases, while it decreases as the particle length increases. At P=5kPa, G=2mm, L=2mm and r=.2mm for 5%SF 6 -N 2 gas mixture, the breakdown voltage for gap with particle contamination decreases approximately by 15.5% from it's value in case of clean gap Finally, it can be concluded that the probability of breakdown voltage for gap with particle contamination is greaterr than that for clean gap. References [1]. Sayed A. Ward, " Optimum SF 6 -N 2, SF 6 -Air, SF 6 -CO 2 Mixtures Based on Particle Contamination ", Conference Record of the 2 IEEE International Symposium on Electrical Insulation, Anaheim, CA USA, pp.292-295, 2. [2]. M.M Morcos, S. Zhang, K.D. Srivastava, " Mangement of Particle Contamination in GIS/ /GITL by Electrode Coating" ", CIGRÉ, Paper 15-41, 22. [3]. M.M Morcos, S.A. Ward, H. Anis, K.D. Srivastava and S.M. Gubanski, "Insulationn Integrity of GIS/GITL Systems and Management of Particle Contamination", IEEEE Electrical Insulation Magazine, Vol. 16, No. 5, pp.25-37, 2. 332

Sayed A. Ward, et al. [4]. W. Pfeiffer, D. Schoen, " Requirements for Gaseous Insulation for Application in GITL Considering N 2, N 2 O and CO 2 with Low Content SF 6 ", Conference Record of IEEE International Symposium on Electrical Insulation, Indianapolis, IN USA, pp.536-539, 24. [5]. Sayed A. Ward, " The Breakdown Voltages for Compressed Gas-Insulated Systems with Contamination Considering the Space Charge Effect", Conference Record of IEEE International Symposium on Electrical Insulation, Montreal, Quebec, Canada, pp.87-9, 1996. [6]. Sayed A. Ward, "Influence of Conducting Particles on the Breakdown Voltages of SF 6 -N 2 mixture", High Voltage Engineering Symposium, Conference Publication No. 467, IEE, pp.187-192, 1999. [7]. H.R. Hiziroglu, J.Griggs, M.S.Dincer, "Breakdown Voltages in Argon+SF 6 Mixtures Subjected to Impulse Voltages ", Annual Report, Conference on Electrical Insulation and Dielectric Phenomena, IEEE, pp.786-788, 22. [8]. Hitoshi Okubo, Naoto Koshino, Naoki Hayakawa, "Electrical insulation characteristics of CO 2 and CO 2 gas mixtures under non-uniform electric field", Annual Report Conference on Electrical Insulation and Dielectric Phenomena, IEEE, pp.538-541, 23. [9]. H.Saitoh, K.Morita, T.Kikkawa, N.Hayakawa, H.Okubo, "Impulse Partial Discharge and Breakdown Characteristics of Rod-plane Gaps in N 2 /SF 6 gas mixtures", IEEE Transactions on Dielectrics and Electrical Insulation, Vo1.9, N.4, pp.544-55, 22. [1]. Y. Hoshina, M. Sato, M. Shiiki, M. Hanai, E. Kaneko,"Lightning impulse breakdown characteristics of SF 6 alternative gases for gas-insulated switchgear", IEE Proc.-Sci. Meas. Technol., Vol. 153, No. 1, pp.1-6, 26. [11]. Masayuki Hikita, Shinya Ohtsuka, Shigemitsu Okabe, Shuhei Kaneko, "Insulation Characteristics of Gas Mixtures including Perfluorocarbon Gas", IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 15, No.4, pp.115-122, 28. [12]. David Meeker, "Finite Element Method Magnetics, Version 4.2, User s Manual", September 26. [13]. N. H. Malik, A. H. Qureshi, "A review of electrical breakdown in mixtures of SF 6 and other gases", IEEE Transaction on Electrical Insulation, Vol. EI- 14, No. 1, pp. 1-13, 1979. [14]. A Rein, " Breakdown mechanisms and breakdown criteria in gases: Measurement of discharge parameters. A literature survey", Bioctra, No. 32, pp. 43-6, 1974. [15]. S. Berger, "Onset of breakdown voltage reduction by electrode surface roughness in air and SF6", IEEE Trans. on PAS, Vol. PAS-95, No. 4, pp. 173-179, 1976. [16]. N. H. Malik and A. H. Qureshi, "Breakdown mechanisms in sulphur-hexafluoride", IEEE Trans. on Elect. Insul., Vol. EI-12, No. 3, pp. 135-145, 1978. [17]. T. w. Dakin, G. Luxa, G. Oppermann, J. Vigreux, G. Wind, H. Winkeln- Kemper, "Breakdown of gases in uniform fields, Paschen curves for nitrogen, air and sulphurhexaflouride", Electra. CIGRE Paper No.32, pp.64-7, 1974. [18]. N. H. Malik, A. H. Qureshi, "Breakdown gradients in SF 6 -N 2, SF 6 -Air and SF 6 - CO 2 mixtures", IEEE Transaction on Electrical Insulation, Vol. EI- 15, No. 5, pp. 413-418, 198. 333

Particle Intiated Breakdown Inside Gas Insulated Switchgear Sayed A. Ward was born in Cairo, Egypt, on December 24, 1961. He received the B.Sc. degree in electrical engineering with honor in 1984 and the M.Sc. degree in high-voltage Engineering in 1988, both from Zagazig University, Shoubra, Cairo, Egypt. He received the Ph.D. degree in highvoltage engineering in 1992 from Cairo University. He is currently a professor with the Electrical Engineering Department, Faculty of Engineering (Shoubra), Cairo, Egypt. His research activity includes studying the gas discharge phenomena in GIS, breakdown voltage study in GIS systems for compressed gases and gas mixtures. Also his research activity includes breakdown in Insulating Oils and DGA oil analysis in power transformers. Mousa A. Abd-Allah was born in Cairo, Egypt, on August 16, 1961. He received the B.Sc. degree in electrical Engineering with honor in 1984 and the M.Sc. degree in High Voltage Engineering in 1988, both from Zagazig university, benha branch, Cairo, Egypt. He received the Ph.D. degree in High Voltage Engineering in 1992 from Cairo university. He is currently a professor with the Electrical Engineering department, Faculty of Engineering at Shoubra,Benha university. His research activity includes Electromagnetic Field Assessment and Mitigation around Electrical Equipments, Gas discharge in gas insulated systems, Electromagnetic Compatibility, Transient Phenomenon in Power Networks. Amr A. Youssef was born in Cairo, Egypt, on July 31, 1985. He received the B.Sc. degree in electrical engineering with honor degree in 27 from Faculty of Engineering at Shoubra, Benha University, Cairo, Egypt. On December 28, he received his work in this faculty as an instructor in the Electrical Engineering Department. In 211, he will receive the M.Sc. degree in electrical engineering from this faculty. Currently he is an assistant lecturer at Electrical Engineering Department in this faculty and also PH.D researcher in high voltage engineering.his research activity includes studying the characteristics of various gas mixtures, electric field and breakdown voltage calculations around single and multi-contaminating particles inside GIS and GITL. 334