ASTM C 1363-11 THERMAL PERFORMANCE TEST REPORT Rendered to: UNIVERSAL PULTRUSIONS, LLC PRODUCT: Fiberglass Door Slab Summary of Results Thermal Transmittance (Btu/hr.ft².F), U-factor Overall Thermal Resistance (hr.ft².f/btu), R-value(Ru) 0.13 7.42 Reference should be made to ATI Report No. for complete test specimen description and data. 849 Western Avenue North St. Paul, MN 55117 phone: 651-636-3835 fax: 651-636-3843 www.archtest.com
ASTM C 1363-97 THERMAL PERFORMANCE TEST REPORT Rendered to: UNIVERSAL PULTRUSIONS, LLC PO Box 1289, 100 Tillco Drive Marshall, Arkansas 72650 Report No: Test Date: Report Date: Expiration Date: 03/21/12 04/09/12 03/21/16 Test Sample Identification: Series/Model: Fiberglass Door Slab Overall Size: 35-3/4" wide x 84" tall Test Procedure: The thermal performance was determined in general accordance with ASTM C 1363-11, Standard Test Method for the Thermal Performance of Building Assemblies by Means of Hot Box Apparatus. Test Results Summary: Thermal Transmittance, U-factor (U): Overall Thermal Resistance(Air-to-Air), (Ru): Thermal Resistance(Surface-to-Surface), (Rc): 0.135 7.42 6.05 Btu/hr.ft².F (hr.ft².f)/btu (hr.ft².f)/btu 849 Western Avenue North St. Paul, MN 55117 phone: 651-636-3835 fax: 651-636-3843 www.archtest.com
Page 2 of 6 Test Sample Description Overall Size: 35-3/4" wide x 84" tall Specimen Thickness: 1-3/4" Construction: The specimen was comprised of a 1-1/2" thick polyisocyanurate core sandwiched between two 0.135" thick fiberglass skins. Measured Test Data Areas 1. Test Specimen Projected Area (As) 20.85 ft 2 2. Metering Box Opening Area (Amb) 32.26 ft 2 3. Metering Box Baffle Area (Ab1) 32.11 ft 2 Heat Flows 1. Total Measured Input into Metering Box (Qtotal) 250.47 Btu/hr 2. Metering Box Wall Heat Flow (Qmb) 13.71 Btu/hr 3. EMF vs Heat Flow Equation (equivalent information) 0.0224*EMF + 6.93 4. Net Specimen Heat Loss (Qs) 197.29 Btu/hr The sample was inspected for the formation of frost or condensation, which may influence the surface temperature measurements. The sample showed no evidence of condensation/frost at the conclusion of the test. A calibration of the ATI 'thermal test chamber' in St. Paul, Minnesota was conducted in October 2011.
Page 3 of 6 Thermal Performance Test Conditions 1. Average Metering Room Air Temperature (t h ) 69.80 F 2. Average Cold Side Air Temperature (t c ) -0.41 F 3. Average Guard/Environmental Air Temperature 71.00 F 4. Metering Room Average Relative Humidity 10.07 % 5. Measured Cold Side Wind Velocity (Perpendicular Flow) 14.36 mph 6. Measured Static Pressure Difference Across Test Specimen 0.00" ± 0.04"H 2 O Results 1. 2. 3. 4. 5. 6. Thermal Conductance (C) Thermal Resistance (Rc) Overall Thermal Resistance (R u ) Warm Side Surface Resistance (R h ) Cold Side Surface Resistance (R c ) Warm Side Surface Conductance (h h ) 0.165 Btu/hr ft² F 6.05 hr ft² F/Btu 7.42 hr ft² F/Btu 1.16 hr ft² F/Btu 0.21 hr ft² F/Btu 0.86 Btu/hr ft² F 7. Cold Side Surface Conductance (h c ) 4.75 Btu/hr ft² F 8. Thermal Transmittance (U) 0.135 Btu/hr ft² F Test Duration 1. The environmental systems were started at 13:31 hrs., 03/20/12 2. The test parameters were considered stable for two consecutive four hour test periods 00:26 hrs., 03/21/12 to 08:26 hrs., 03/21/12. 3. The thermal performance test results were derived from 04:26 hrs, 03/21/12 to 08:26 hrs, 03/21/12.
Page 4 of 6 Surface Temperatures (as viewed from interior) 6 5 4 3 2 1 Individual Surface Temperature Measurements Thermocouple Warm Side (F) Cold Side (F) Thermocouple Warm Side (F) Cold Side (F) 1 52.83 1.21 4 63.81 1.27 2 63.65 1.19 5 64.17 1.43 3 53.64 1.91 6 54.89 2.46 1. Average Warm Side Surface Temperature 58.83 F 2. Average Cold Side Surface Temperature 1.58 F
Page 5 of 6 Representative samples of the test specimen and a copy of this report will be retained by ATI for a period of four years. This report is the exclusive property of the client so named herein and relates only to the fenestration product tested. This report may not be reproduced, except in full, without the approval of the laboratory. Results obtained are tested values and do not constitute an opinion or endorsement by this laboratory. This report does not constitute certification of this product, which may only be granted by an Independent Administrator. For ARCHITECTURAL TESTING, INC. Michael D. Topitzhofer Technician Michael P. Resech Senior Project Manager Individual-In-Responsible-Charge MDT:mpr Attachments: None
Page 6 of 6 Revision Log Rev. # Date Page(s) Revision(s) 0 04/09/12 All Original Report Issue. Work requested by Keith Jensen of Universal Pultrusions, LLC