Area-wide dynamic line ratings based on weather measurements

Size: px
Start display at page:

Download "Area-wide dynamic line ratings based on weather measurements"

Transcription

1 SESSION B2-106 Area-wide dynamic line ratings based on weather measurements R. PUFFER 1), M. SCHMALE 2), B. RUSEK 3), C. NEUMANN 3), M. SCHEUFEN 1) 1) RWTH Aachen University, Aachen, Germany, 2) TenneT TSO GmbH, Bayreuth, Germany, 3) Amprion GmbH, Dortmund, Germany SUMMARY The load of overhead lines has increased due to raised transmission of electrical energy within Europe as well as in the consequence of a growing feed-in from regenerative energy resources. The transmission capacities of overhead lines (OHL) are limited and already in many cases the bottlenecks which restrict the power flows. Dynamic rating is a measure to increase the ampacity of overhead lines depending on the actual weather situation. In the first section this paper focuses on the description and evaluation of different methods and tools for OHL ampacity determination. The conductor temperature is measured directly with a sensor as well as determined indirectly using a weather station close to the line and commercially available weather data. Different scenarios where the measured wind speed is higher than the wind at the line due to shadowing effects are taken into account. The results show that the conductor temperature determination from weather data may be done with a maximal adequacy of about 5 K in the conductor temperature range up to 50 C. This fact means that the dynamic line rating is applicable but some safety margins have to be implemented. It is also shown that investigations on the thermal behaviour at low wind speeds seem to be necessary. In the second section the focus is on the implementation of a dynamic rating system into the 380 kv transmission grid and the necessary measures to increase the ampacity up to 3,150 A. This dynamic rating system uses the ambient temperature and the wind speed to determine the dynamic ampacity of the line. Retrofitting in substations such as replacing circuit breakers and current transformers as well as measures at overhead lines such as inspecting joints and raising towers had to be taken. Dynamic aspects of the transmission system are discussed. The protection concept was revised in order to allow a quick location of faults even in the case of a single technical component failure. The operational experience using the dynamic rating system proves that it fits very well with the existing control centre s techlogy. The distinct increase in dynamic current rating compared to static rating verifies the technical and ecomical capability. KEYWORDS Ampacity, monitoring system, up rate, overhead line, thermal limit, meteorological data, real time thermal rating, dynamic rating puffer@ifht.rwth-aachen.de 1

2 1. Introduction To enable the ongoing connection of regenerative energy sources in a timely manner, there is a need for flexible measures to better utilise the existing transmission grid. One of those measures is dynamic rating of overhead lines. Based on the thermal balance of the conductor it can be determined that the meteorological conditions (wind speed, angle of oncoming flow of wind and ambient air temperature) affect the temperature of the line conductors considerably. With certain combinations of these meteorological factors, the influence results in a cooling effect, thus much more heat caused by the current flow can be generated without exceeding the maximum operating temperature. This means, that an overhead line can be loaded more intensively (above minal current). This effect can also be used for a temporary increase of the line capacity (dynamic line rating). Thus it is possible to increase the ampacity of the line and at the same time to maintain the maximum allowable values for the conductor temperature and the clearance to ground or objects. This paper is divided into two main parts. The first section focuses on the methods for determination of the conductor ampacity. For this purpose, the three methods (one direct and two indirect) will be compared in terms of adequacy. The second section focuses on the measures necessary to enable a retrofitting of existing 380 kv overhead lines in order to prepare them for dynamic rating. The most significant among these measures were the introduction of dynamic rating, essential actions in the overhead line sections like rising towers and inspection and replacement of primary technical equipment in the substations. Further the ampacity increases of OHL operated with dynamic rating are presented. 2. Comparison of methods for ampacity determination 2.1 Principal methods and tools For dynamic line rating, the conductor temperature can be used. The interesting questions are how to acquire the temperature, which adequacy is necessary and which monitoring system is the most suitable from the ecomical point of view. In order to answer these questions, a pilot installation of two monitoring systems at Amprion GmbH (German TSO) was established (figure 1). The first system measures directly the temperature of the conductor by means of two passive surface acoustic wave (SAW) sensors SAW 1 and SAW 2 located in two conductors of one circuit. The second system (ls - local station) bases on an indirect method using a thermal model for the calculation of conductor temperature under consideration of the meteorological conditions. In this case, a weather station is placed in the vicinity of the conductor. The cost of the pilot systems and the technical effort was quite high. Taking into account the actual costs Fig. 1 Pilot installation of monitoring systems with SAW sensors and local weather station of the measuring devices, the effort for the installation and the necessary line outages the installation of such systems throughout the network is t ecomical. The application of weather stations similar to (ls) does t require de-energising of the line and the installation cost expenditure is significantly lower. However, the necessity to equip all lines with weather stations still remains. The simplest solution is to use already available weather stations, which are located in the vicinity of the monitored line, and to project the measured meteorological conditions on the line. Therefore, the pilot project was extended by an additional indirect method (rs - remote station) which calculates the conductor temperature using the commercially available meteorological data. The aims of the project are to define the adequacy of conductor temperature determination from the meteorological data, provided by the local and remote weather station and to find the most suitable system from ecomical point of view. puffer@ifht.rwth-aachen.de 2

3 2.2 The thermal model of the conductor For the indirect method the CIGRE-thermal model of conductor [2] is used. The principle of the model is well kwn; the thermal balance of the line, i. e. introduced heat and dissipated heat, must be equal at any time (equation 1). P ( T ) + P + P + P = P ( T ) + P ( T ) + P (1) j c m c s r c where : P j - current losses, P m magnetisation losses, P s -solar radiation, P c - corona losses; P k - convection, P n rain, P r radiation Kwing the weather conditions and some constant conductor parameters, the ampacity at which the conductor reaches its maximum permissible temperature (in this case 80 C) which also corresponds to the maximum permissible conductor sag can be calculated according to equation 1 (see also figure 2). The calculation of conductor temperature based on the load current and the weather conditions is quite complex, because of k c n Fig. 2 Principle of calculation of maximal conductor temperature and conductor kwn load current numerous dependencies on the conductor temperature itself. The direct derivation of conductor temperature (with a few simplifications) is possible [7]. This equation may also be solved by an iterative approach (figure 2). The temperature of the conductor (T c ) will be varied until both sides of equation (1) are almost equal (error < 0.1 C). 2.3 Statistical approach The investigations cover almost 2 year of measurements almost 50,000 data sets with 15 min resolution. The most suitable approach for analysis of such amount of data is a statistical approach [8]. Hence in this work, the relative frequency of different parameters [11] will be applied. From this statistical evaluation given in figure 3 it can be derived for both sensors SAW 1 and SAW 2 that the conductor temperatures were lower than 10 C in 30% of time period considered and for 10% of time period considered higher than 30 C. This shows that the conductor temperatures are far below the permissible limit of 80 C and that there is a potential for increasing the ampacity which can be utilised by overhead line monitoring. 2.4 Shadowing scenarios The weather conditions which are measured by local and remote weather stations give information about the condition in this particular location [8][9]. Since the overhead lines may be many kilometres long, the weather conditions along the line will t be the same and particularly affected by different wind speeds and directions. Additionally, a shadowing effect has to be taken into account, if the line passes valleys or forest aisles [10]. Therefore, four scenarios with varying wind speed and direction will be considered to simulate shadowing effects (table 1). The principle of application of shadowing effect is shown in figure 2. scenarition wind speed wind direc- S1 v = 0.6 m/s φ = 90 S2 v = v real /2 & min(v) = 0.6 m/s φ = φ real & min(φ) = 30 S3 v = v real /2 & φ = 30 min(v) = 0.6 m/s S4 restrictions φ = φ real & min(φ) = 30 Tab. 1: Different shadowing scenarios, where v real is the measured wind speed an v is the wind speed used for ampacity calculation 2.5 Measured conductor temperatures and possible ampacities In the considered period of time a variety of different weather and load conditions have been measured. The conductor temperatures varied between -10 and 50 C and the load current between 0 and 100% of conductor minal current (figure 3). That means that the complete current range was covered, but the maximum conductor temperature of 80 C was t reached. puffer@ifht.rwth-aachen.de 3

4 Fig. 3: Measured conductor temperature (A) and currents of the monitored overhead line (B) 2.6 Discussion of results The two sensors of the conductor temperature measuring system (SAW 1 and SAW 2) are mounted on two conductors of the same circuit, but at different heights. Due to the phase arrangement of the circuit on the tower, sensor SAW 2 on conductor 2 is mounted about 3 meters higher than sensor SAW 1 on conductor 1. The wind profile and herewith the cooling effect is depending on the height above ground. Thus the cooling of the higher located conductor 2 should be more intensive than the cooling of conductor 1. The resulting conductor temperatures should differ. This dependency on wind conditions can be seen in figure 4, curve (1). The positive deviations from T c _saw1 show that for 90% of considered period the temperature of the lower conductor is few degrees higher. Since the temperature Tc_saw1 is higher than Tc_saw2, the conductor sag of conductor 1 will be larger than of conductor 2. Therefore, the temperature of the conductor 1 (Tc_saw1) will be chosen as reference value. The temperature of the conductor (T c ) is calculated using CIGRE-model and different shadowing scenarios. The weather conditions are measured by local weather station (ls) and remote weather station (rs). The difference between calculated conductor temperatures (M2 and M3) and directly measured conductor temperature (M1) is shown in figure 4. The cumulative frequency distribution of these deviations for exemplary study cases is also shown. Fig. 4: Frequency of differences between measured and calculated conductor temperature for different shadowing scenarios depending on the location of weather station (ls-local, rs-remote) The curves in figure 4 can be analysed as follows: Positive deviations mean that measured conductor temperature (Tc_saw1) is higher than the calculated temperature. This condition implies a risk to exceed the maximum allowed conductor temperature. puffer@ifht.rwth-aachen.de 4

5 Negative deviations are allowed, since the conductor temperature is in the permissible range. In this case, the maximal ampacity will t be reached in any case. Scenario S1 (only temperature, curve (8): This scenario gives the best adequacy because only 1% of deviations is higher than 5 C. However, it does t utilise the maximum of conductor ampacity, because 80% of deviations are negative. Interesting is, that the use of ambient temperature and standard rmative weather conditions (v = 0.6 m/s, φ = 90 ) still produces positive deviations in 20% of data points. Hence, it can be concluded that either there are worse weather conditions than those in standard or the models are t good eugh at those small wind speeds. This fact requires further investigations. Scenario S2, (half wind speed, φ = φ real & min(φ)=30, curves (6) & (7)): This scenario applies the real wind direction in the model, in contrary to scenario S3 at which a constant angle of wind direction is used. It is well to be seen in particular, if the curves for local station (5) and (7) are compared. The positive deviations are almost equal to the use of temperature only (scenario S1). The method provides a very good safety margin. Hence, the distribution curve for a local station is very narrow and the scenario has a good safety margin, this location of the weather station and this shadowing scenario give the best representation of the conductor temperature. Scenario S3 (half wind speed, φ = 30, curves (4) and (5)): For the local station there are about 50% of positive deviations and for the remote station slightly less than 40%. However, only about 5% of deviations are higher than 5 C. On the negative side of axis the calculations according to data from remote station exhibits much more inadequacy than for data coming from local station. Scenario S4 (wind speed with restrictions, curves (2) and (3)): Almost 80% of deviations are positive. However, only 10% of deviations are higher than 5 C. Here, the calculated temperature is lower than the measured one. The direct use of wind speed with restrictions for calculation of conductor temperature is apparently t adequate eugh. The local weather station is located at a similar height above ground as the conductor; therefore it should provide comparable results. The reason for this effect which mainly appears at low wind speeds (see figure 5A) may occur due to inadequacy in weather measurements, the conductor models and/or dynamic thermal behaviour of conductor. Moreover, the sensors measuring the temperature directly are calibrated for wind speeds in range of 4 m/s and may produce small deviations at low wind speeds. According to discussion above, the scenario S2 is the most accurate for ampacity determination. But the results also show that there is method which can determine the conductor temperature very exactly. In case of ls_s2 (local weather, half wind speed, and taking into account wind directions) a deviation of 5 C may be reached. It has to be mentioned here, that this deviation refers only to the conductor temperatures up to 50 C. Above this value, observations have been made. puffer@ifht.rwth-aachen.de 5

6 Fig 5: Deviations of theoretically calculated conductor temperature to the measured conductor temperature dependent of the wind speed (A), ambient temperature (B) and the season of the year (C) The dependency of the deviations between measured conductor temperature and calculated temperature using the local and the remote weather conditions at scenario 2 is shown in figure 5. At higher wind speeds the deviations become smaller (figure 5A). The dependency on the ambient temperature (figure 5B) cant be detected at the first look. The dependency on the season of the year (figure 5C) is also difficult to recognise. Obviously the largest deviations occur within few days (peaks in figure 5C) and at ambient temperatures of about 10 C (peak in figure 5B). For clarification of these details further investigations are needed. 3. Area-wide dynamic rating of 380 kv overhead lines An important rth to south connection in the German grid of TenneT TSO GmbH is located between the cities of Hamburg and Frankfurt (see figure 6). To adjust the grid to the new boundary conditions it is necessary to build new lines as well as to improve the efficiency of the existing infrastructure. The policy is to fully utilise the existing infrastructure first and to have new lines erected only for further demand. An overview of the necessary measures to be taken in order to increase the transmission capability of this part of the grid is given in figure 7. In the 380 kv transmission grid it is essential to keep up the stability of the system. By raising the maximum allowable ampacities the development of a new protection concept became necessary. Also a concept to maintain system safety for higher utilisation was required. As a result facilities providing reactive power had to be installed and changes to the protection system were carried out. Netherlands TenneT Denmark Energienet.dk Amprion Frankfurt EnBW Sweden Svenska Kraftnät Hamburg 50Hertz Transmission Czech Republic CEPS Austria TIWAG APG Fig. 6: Retrofitted connection between Hamburg and Frankfurt puffer@ifht.rwth-aachen.de 6

7 check design temperature increase design temp. special inspection replace check joints replace check substation check protection and dynamic aspects replace adapt, replace everything done? magnetic field threshold implementation of ampacity algorithm adapt max. ampacity overhead line dynamic rating applicable weather station and location documentation Fig. 7: Workflow of necessary measures for dynamic rating implementation 3.1 Dynamic aspects of the transmission system The transmission capacity is increased by raising the ampacity of the 380 kv bottleneck circuits to 3,150 A. With an increasing utilisation of the currently existing connections without adding new transport capabilities from the rth to the south, the risk of loosing the generator stability (phase angle stability) increases as well (see figure 8). The stability limits mainly depend on the grid impedances (inductive and capacitive). Also the protection system is affected by high minal currents, in regard to selectivity and reliability. It is more difficult to safely detect and isolate faults. High minal currents make it hard to differentiate between operational and fault currents without the chance of incorrect tripping. P P DLR U1 U = sinδ X 2 P2 reduction of transmission angle increasing transmission capacity with expansiof transmission system P 1 without expansiof transmission system static boundary 0 45 stable instable Übertragungswinkel transmission angle Fig. 8: transmission angle as a function of the transmission capacity (DLR Dynamic Line Rating) Where P 1 is the feeding power and P 2 is the load power, P DLR is the increased feeding power using dynamic line rating, U 1 and U 2 are the voltages at the beginning and the end of the line, and δ is the angle between current and voltage To improve the transport capacity of the grid the system boundaries which arise from system stability and grid protection have to be taken into account during the grid planning process. Analysing the possibilities of enhancing the capacity of the main transmission corridors from rth to south system many studies were conducted. As a part of the EWIS study (European Wind Integration Study) the results were verified in an European context, considering coordinated robust scenarios (European market model for power plant operation) and measures (e. g. the grids at the borders to the Czech Republic, Poland, Austria, Benelux or Denmark). puffer@ifht.rwth-aachen.de 7

8 3.2 Protection of the transmission system The protection concept was revised in order to allow a quick location of faults even in the case of a single technical component failure. The analysis of the calibration principles of the protection system revealed that raising the boundary protection current and accordingly a less sensitive tripping setting on its own was t sufficient to meet the increased requirements. In addition the influence of large transmission angles on the measuring precision of the distance relays in the event of electric ark faults and compensation currents in healthy lines at a single line fault are factors of consideration. 3.3 Realization of necessary measures The ampacity of a high voltage circuit can be limited by the primary equipment in the substation bays and by the overhead lines. The equipment used in the substation bays can generally be retrofitted to match the ampacity that can be achieved using the dynamic rating of the line. In order to determine presently available ampacity, the weather data has been evaluated. This evaluation shows that in about 80 % of the year a weather dependent ampacity of 3,150 A is possible (see figure 9). 5,000 weather dependent ampacity [A] 4,000 3,000 2,000 4,000 A 3,150 A four bundle conductor ACSR 240/40: 2,580 A 2,500 A 2,000 A 1, time [%] Fig. 9: Available ampacity with dynamic rating of the connection between Hamburg and Frankfurt 3.4 Measures in substations In the substations the following primary equipment has been reviewed and replaced as needed: circuit breaker current transformer isolating switch voltage transformer switch bay lines For the circuit breaker, current transformer, isolating switch and for some voltage transformers (special types) the rated currents were checked. For equipment with thermal ratings below 3,150 A, the device had to be replaced. The switch bay lines and bus bars were checked in regard to their short circuit capability. Insufficiently dimensioned components have been replaced. The above mentioned measures took a great amount of planning and coordination because of the limited operability of the grid during the intervention and the aim t to cause any impact on customers. puffer@ifht.rwth-aachen.de 8

9 3.5 Measures at overhead lines Since the usable ampacity of an overhead line depends among other things on the specific design temperature, generally the ampacity can be increased by raising the clearance. If the specific design temperature of lines is lower than the rated conductor temperature an ampacity increase can usually be reached by the elevation of selected towers. However, the elevation of a 380 kv line tower yields a couple of challenges. For example, in order to elevate a 10 ton tower, special cranes are needed which have to approach the tower if necessary over provisional tracks (figure 10). Fig. 10: Pictures of inserting additional body sections in a 380 kv tower near Stade The joints in the line section were completely inspected on site. Only intact connection components remained in the line whereas conspicuous components were replaced. The condition of joints was determined using infra-red thermography. Raising the ampacity of an overhead line raises the maximum value of the magnetic field as well. Calculations of the magnetic field were carried out in order to assure the compliance with legal specifications. 3.6 Implementation of dynamic rating into the operating system In order to improve the ampacity of 380 kv lines a dynamic rating system has been developed and implemented into the existing operating system of TenneT TSO in Germany. This monitoring system uses the ambient temperature and the wind speed to determine the dynamic current rating of the line. It is directly linked to the control centre and delivers a dynamic current rating. There is need for any direct measurement of the conductor temperature to determine the dynamic current rating. The operational experience using the dynamic rating system for the operation of 380 kv lines proves that it interposes very well with the existing control centre s techlogy. The distinct increase in dynamic current rating compared to static rating verifies the technical and ecomical capability. puffer@ifht.rwth-aachen.de 9

10 4. Conclusion Many overhead line monitoring systems (direct and indirect temperature determination methods) are presently available on the market. The determination of conductor temperature using weather data is riddled with many inadequacies. Hence, the conductor temperature determination from weather data may be done with a maximal adequacy of about 5 K in the conductor temperature range up to 50 C. The findings of this paper show that the accuracy of indirect monitoring systems is comparable with direct monitoring systems considering adequate safety margins. Moreover, investigations on the thermal behaviour at low wind speeds seem to be necessary as well as better understanding at what time the largest deviations to the measured conductor temperature occur. A dynamic rating system using weather measured in substations to calculate the ampacity was installed on 800 km of 380 kv overhead lines. Different retrofitting measures like checking the joints, changing substation equipment, raising towers and verifying the stability criteria of the grid had to be done. The operational experience using the dynamic rating system delivers a distinct increase in dynamic current rating which verifies the technical and ecomical capability of the system. BIBLIOGRAPHY [1] Dräger, H.-J.; Hussels, D.; Puffer, R.; Development and Implementation of a Monitoring- System to Increase the Capacity of Overhead Lines, Paper B2-101, Cigré Session 2008 [2] Cigré, Technical Brochure 207; The Thermal Behaviour of Overhead conductors, August 2002 [3] H. Kühn, F. Martin, M. Schmale, R. Puffer, W. Winter; Mehr Energie von Nord nach Süd, ew 3/2011 and 4/2011 [4] M. Schmale, R. Puffer; Freileitungen sicher betreiben und Reserven nutzen, netzpraxis, Jg. 49 (2010), Heft 11 [5] Blumenroth, F., Löbl, H., Großmann, S., Puffer, R. Hussels, D.: Ageing of high current joints in power transmission ans distribution systems, Cired 2007, paper 537 [6] Schmale, M.; Puffer, R.; Dräger, H.-J.; Experience with a Dynamic Rating System to Increase the Ampacity of 380-kV Overhead Lines, Cigré Symposium Bologna 2011 [7] Temiva, R.; Hinrichsen, V.; Freese, J.; Hudasch, M.; Bebensee, R.; Neumann, C.: Betriebserfahrungen mit passiven funkabfragbaren OFW-Sensoren zur Messung der Temperatur von Freileitungsleiterseilen und Trennschalterkontakten, ETG Tagung, 2006 [8] Lange, M.; Focken, U.: Studie zur Abschätzung der Netzkapazität in Mitteldeutschland in Wetterlagen mit hoher Windeinspeisung, Studie energy & meteo systems, Oldenburg, 2008; gefördert vom BMU [9] Roman, H. Dangrieß, G.; Darendorf, S. Struck, T.: Freileitungsmonitoring im Hochspannungsnetz - Theoretisches Potenzial. ew Jg. 108 (2009), Heft 12, S [10] Roman, H. Dangrieß, G.;Darendorf, S. Struck, T.: Freileitungsmonitoring im Hochspannungsnetz - Reales Potenzial. ew Jg. 108 (2009), Heft 13, S [11] Neumann, C.; Rusek, B.; Puffer, R.: Weather dependent loading of overhead lines based on statistical consideration of weather data (in German). ETG Congress, Duesseldorf, 27. to 28. October 2009, Report 3-7 puffer@ifht.rwth-aachen.de 10

ANALYSIS OF DIFFERENT DYNAMIC LINE RATING SYSTEM CONFIGURATIONS IN A DISTRIBUTION LINE

ANALYSIS OF DIFFERENT DYNAMIC LINE RATING SYSTEM CONFIGURATIONS IN A DISTRIBUTION LINE 23 rd International Conference on Electricity Distribution Lyon, 15-18 June 215 Paper 176 ANALYSIS OF DIFFERENT DYNAMIC LINE RATING SYSTEM CONFIGURATIONS IN A DISTRIBUTION LINE Jon G. OLAZARRI, A. Javier

More information

elgian energ imports are managed using forecasting software to increase overall network e 칁 cienc.

elgian energ imports are managed using forecasting software to increase overall network e 칁 cienc. Elia linemen install Ampacimon real time sensors that will communicate with the dynamic thermal ratings software to control energy import levels over this transmission line. OV RH AD TRAN MI ION D namic

More information

Increasing Transmission Capacities with Dynamic Monitoring Systems

Increasing Transmission Capacities with Dynamic Monitoring Systems INL/MIS-11-22167 Increasing Transmission Capacities with Dynamic Monitoring Systems Kurt S. Myers Jake P. Gentle www.inl.gov March 22, 2012 Concurrent Cooling Background Project supported with funding

More information

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power

More information

Guide for Application of Direct Real-Time Monitoring Systems

Guide for Application of Direct Real-Time Monitoring Systems 498 Guide for Application of Direct Real-Time Monitoring Systems Working Group B2.36 June 2012 Guide for Application of Direct Real- Time Monitoring Systems Working Group B2.36 Members R. Stephen (ZA)

More information

Dynamic Line Rating for overhead lines V6

Dynamic Line Rating for overhead lines V6 Dynamic Line Rating for overhead lines V6 CE TSOs current practice RGCE SPD WG 30 March 2015 1. Contents 1. Contents... 2 2. Introduction... 3 3. Main Terminology... 3 4. The background and the aim of

More information

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur 1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-current carrying part) or some electrical part of the

More information

Correlation between Lightning Impacts and Outages of Transmission Lines. H-D. BETZ Nowcast GmbH Munich Germany

Correlation between Lightning Impacts and Outages of Transmission Lines. H-D. BETZ Nowcast GmbH Munich Germany CIGRE C4 Colloquium on Power Quality and Lightning Sarajevo, Bosnia and Herzegovina, 13 16 May, 2012 Paper 01. Correlation between Lightning Impacts and Outages of Transmission Lines I. UGLEŠIĆ V. MILARDIĆ

More information

Study of Time Correlation Between Lightning Data Recorded by LLS and Relay Protection

Study of Time Correlation Between Lightning Data Recorded by LLS and Relay Protection 2012 International Conference on Lightning Protection (ICLP), Vienna, Austria Study of Time Correlation Between Lightning Data Recorded by LLS and Relay Protection Ivo Uglešić, Viktor Milardić, Bojan Franc

More information

URD Cable Fault Prediction Model

URD Cable Fault Prediction Model 1 URD Cable Fault Prediction Model Christopher Gubala ComEd General Engineer Reliability Analysis 2014 IEEE PES General Meeting Utility Current Practices & Challenges of Predictive Distribution Reliability

More information

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS European Copper Institute COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS David Chapman August 2011 ECI Available from www.leonardo-energy.org Document Issue Control Sheet Document Title: Publication

More information

Facing the winter challenges for railways in Europe - Winter & Railways Fact Sheet Root Causes Rolling Stock and Infrastructure UIC Survey Evaluation

Facing the winter challenges for railways in Europe - Winter & Railways Fact Sheet Root Causes Rolling Stock and Infrastructure UIC Survey Evaluation RAIL SYSTEM FORUM SECTOR «ROLLING STOCK» SECTOR «INFRASTRUCTURE» Facing the winter challenges for railways in Europe - Winter & Railways Fact Sheet Root Causes Rolling Stock and Infrastructure UIC Survey

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME: EE 2303 - TRANSMISSION & DISTRIBUTION YEAR / SEM: III/V UNIT-I TRANSMISSION SYSTEM INTRODUCTION PART-A 1. What is

More information

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions FAULT CURRENT F F13-13 FAULT CURRENT - Contents 1. Introduction 2. Types of fault conditions 3 fault current must be determined 3.1 Purposes for which of prospective fault current magnitudes are used 3.2

More information

Experiences with Superconducting Cable & Fault Current Limiter in a German City Center Mark Stemmle

Experiences with Superconducting Cable & Fault Current Limiter in a German City Center Mark Stemmle Experiences with Superconducting Cable & Fault Current Limiter in a German City Center Mark Stemmle mark.stemmle@nexans.com i-pcgrid Workshop San Francisco, CA March 30 th, 2017 Agenda Introduction - Basics

More information

Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation

Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation Adesina, Lambe Mutalub Department of Engineering & Standardization, Eko Electricity Distribution Plc, 24/25, Marina, Lagos Island,

More information

Short description CTC V.6.2. Current and temperature calculations of overhead conductors.

Short description CTC V.6.2. Current and temperature calculations of overhead conductors. Short description CTC V.6.2 Current and temperature calculations of overhead conductors www.sw-fr.com 1 Program features Steady-state current and temperature calculation of overhead conductors with three

More information

I, THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD

I, THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD Krishna Dwivedi*, Kulwant Dhankar**, Smita Ganjare*** & Hemant More**** Assistant Professor, Mechanical Department, LTCOE, Navi Mumbai, Maharashtra Abstract:

More information

Ampacity simulation of a high voltage cable to connecting off shore wind farms

Ampacity simulation of a high voltage cable to connecting off shore wind farms Ampacity simulation of a high voltage cable to connecting off shore wind farms Pelster 1, Wenger 1 1 Wenger Engineering GmbH, Einsteinstr. 55, 89077 Ulm, mail@wenger-engineering.com Abstract: The ampacity

More information

NORDIC AND BALTIC GRID DISTURBANCE STATISTICS 2015

NORDIC AND BALTIC GRID DISTURBANCE STATISTICS 2015 NORDIC AND BALTIC GRID DISTURBANCE STATISTICS 23.01.2017 REGIONAL GROUP NORDIC 1 INTRODUCTION... 4 1.1 DESCRIPTION OF THE REPORT... 4 1.2 CONTACT PERSONS... 5 1.3 VOLTAGE LEVELS IN THE NORDIC AND BALTIC

More information

Design of a measurement arrangement for estimating the icing duration of wind turbines prior erection

Design of a measurement arrangement for estimating the icing duration of wind turbines prior erection Design of a measurement arrangement for estimating the icing duration of wind turbines prior erection Master thesis Sebastian Haym 1 Cooperation partners for this master thesis Michael J. Moser, Hubert

More information

OFFSHORE INTEGRATION STUDY. Analysis, benchmark and mitigation of storm and ramping risks from offshore wind power in Belgium 05/02/2018

OFFSHORE INTEGRATION STUDY. Analysis, benchmark and mitigation of storm and ramping risks from offshore wind power in Belgium 05/02/2018 OFFSHORE INTEGRATION STUDY Analysis, benchmark and mitigation of storm and ramping risks from offshore wind power in Belgium 05/02/2018 This study has been developed in close collaboration with 1 TABLE

More information

System Impact Assessment Addendum #2 Greenfield & St. Clair Energy Centres

System Impact Assessment Addendum #2 Greenfield & St. Clair Energy Centres IESO_REP_0292 System Impact Assessment Addendum #2 Greenfield & St. lair Energy entres onnection Assessment & Approval Process Issue 3.0 Greenfield Energy entre AA I 2004-167 Applicant: Greenfield Energy

More information

THERMAL BEHAVIOR OF DISTRIBUTION TRANSFORMERS IN SUMMERTIME AND SEVERE LOADING CONDITIONS

THERMAL BEHAVIOR OF DISTRIBUTION TRANSFORMERS IN SUMMERTIME AND SEVERE LOADING CONDITIONS THERMAL BEHAVIOR OF DISTRIBUTION TRANSFORMERS IN SUMMERTIME AND SEVERE LDING CONDITIONS Cesare RAVETTA Massimo SAMANNA Angelo STUCCHI Antonio BOSSI Aem Elettricità Italy Aem Elettricità Italy Aem Calore

More information

Grid Issues and Challenges Addressed by High Temperature Superconductor (HTS) Technology

Grid Issues and Challenges Addressed by High Temperature Superconductor (HTS) Technology CIGRÉ US National Committee 21, rue d Artois, F-75008 PARIS Grid of the Future Symposium http : //www.cigre.org Kansas City, October 28-30, 2012 Grid Issues and Challenges Addressed by High Temperature

More information

CECOER. Renewable Energy Control Center. How technologies have boosted remote operations. Agder Energi-konferansen

CECOER. Renewable Energy Control Center. How technologies have boosted remote operations. Agder Energi-konferansen CECOER Renewable Energy Control Center How technologies have boosted remote operations Agder Energi-konferansen 2018 30.-31. mai, Kristiansand GLOBAL LEADER IN INFRASTRUCTURE, WATER, SERVICES AND RENEWABLE

More information

Paper No Advanced prevention against icing on high voltage power lines

Paper No Advanced prevention against icing on high voltage power lines 2 nd South East European Regional CIGRE Conference, Kyiv 2018 SEERC Paper No. 2-64 Advanced prevention against icing on high voltage power lines B. NEMETH 1, V. LOVRENČIĆ 2, M. JARC 2, A. IVEC 2, M. KOVAČ

More information

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation A. Xemard, J. Michaud, A. Guerrier, I. Uglesic, G. Levacic, M. Mesic Abstract-- The upgrade of an overhead

More information

Electric Distribution Storm Hardening Initiatives. Paul V. Stergiou Distribution Engineering October 14 th, 2015

Electric Distribution Storm Hardening Initiatives. Paul V. Stergiou Distribution Engineering October 14 th, 2015 Consolidated Edison Company of New York, Inc. Electric Distribution Storm Hardening Initiatives Paul V. Stergiou Distribution Engineering October 14 th, 2015 Energy For New York City And Westchester 3.3

More information

Chapter 2. Planning Criteria. Turaj Amraee. Fall 2012 K.N.Toosi University of Technology

Chapter 2. Planning Criteria. Turaj Amraee. Fall 2012 K.N.Toosi University of Technology Chapter 2 Planning Criteria By Turaj Amraee Fall 2012 K.N.Toosi University of Technology Outline 1- Introduction 2- System Adequacy and Security 3- Planning Purposes 4- Planning Standards 5- Reliability

More information

Modern techniques of ice-load assessment and icing maps creation for the design of overhead transmission lines used in the Russian Federation

Modern techniques of ice-load assessment and icing maps creation for the design of overhead transmission lines used in the Russian Federation Modern techniques of ice-load assessment and icing maps creation for the design of overhead transmission lines used in the Russian Federation Vladimir LUGOVOI, Sergey CHERESHNIUK, Larisa TIMASHOVA JSC

More information

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN PANEL BOARDS ADDRESSED TO HAZARDOUS AREAS - PART THREE July 04 THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE In this third part. we want to speak about how important is the correct sizing of the

More information

Renewables and the Smart Grid. Trip Doggett President & CEO Electric Reliability Council of Texas

Renewables and the Smart Grid. Trip Doggett President & CEO Electric Reliability Council of Texas Renewables and the Smart Grid Trip Doggett President & CEO Electric Reliability Council of Texas North American Interconnected Grids The ERCOT Region is one of 3 North American grid interconnections. The

More information

The WOLF system: forecasting wet-snow loads on power lines in Italy

The WOLF system: forecasting wet-snow loads on power lines in Italy Chongqing, China May 8-13, 2011 The WOLF system: forecasting wet-snow loads on power lines in Italy M. Lacavalla, P. Bonelli, G. Mariani, P. Marcacci, G. Stella Research on the Energy Systems - RSE S.p.A.

More information

EE 451 Power System Stability

EE 451 Power System Stability EE 451 Power System Stability Power system operates in synchronous mode Power system is subjected to a wide range of disturbances (small and large) - Loads and generation changes - Network changes - Faults

More information

First South East European Regional CIGRÉ Conference, Portoroz 2016 P23. Application of an Ice-Alarm in the OTLM System

First South East European Regional CIGRÉ Conference, Portoroz 2016 P23. Application of an Ice-Alarm in the OTLM System First South East European Regional CIGRÉ Conference, Portoroz 2016 SEERC P23 Application of an Ice-Alarm in the OTLM System N. GUBELJAK 1, V. LOVRENČIĆ 2, B. BANIĆ 3, M. PINTERIČ 4, A. IVEC 5, M. JARC

More information

The Study of Overhead Line Fault Probability Model Based on Fuzzy Theory

The Study of Overhead Line Fault Probability Model Based on Fuzzy Theory Energy and Power Engineering, 2013, 5, 625-629 doi:10.4236/epe.2013.54b121 Published Online July 2013 (http://www.scirp.org/journal/epe) The Study of Overhead Line Fault Probability Model Based on Fuzzy

More information

Optimizing the energy consumption and operational availability of point heaters using weather forecasts

Optimizing the energy consumption and operational availability of point heaters using weather forecasts Computers in Railways XIV 757 Optimizing the energy consumption and operational availability of point heaters using weather forecasts C. Weiß, T. Käsemann & K. A. Klinge i3mainz Institute for Spatial Information

More information

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES POWER SEMICONDUCT BASED ELECTRIC DRIVES [Time: 3 Hrs] [Max. Marks: 80] Instructions: Solve any six questions from Q.No (1 or 2), Q.No (3 or 4), Q.No (5 or 6), Q.No (7 or 8), Q.No (9 or 10), Q.No (11 or

More information

Reactive Power Solutions

Reactive Power Solutions GE Digital Energy Reactive Power Solutions Effects of Series Capacitors on Line Protection Relaying Design and Settings Presented by: Paul Datka, GE Energy Consulting Luis Polanco, GE Energy Consulting

More information

A technique for simultaneous parameter identification and measurement calibration for overhead transmission lines

A technique for simultaneous parameter identification and measurement calibration for overhead transmission lines A technique for simultaneous parameter identification and measurement calibration for overhead transmission lines PAVEL HERING University of West Bohemia Department of cybernetics Univerzitni 8, 36 4 Pilsen

More information

A Novel Approach for Increasing the Reliability of Power Transmission Lines in Galloping Conditions

A Novel Approach for Increasing the Reliability of Power Transmission Lines in Galloping Conditions 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http: //www.cigre.org 2014 Grid of the Future Symposium A Novel Approach for Increasing the Reliability of Power Transmission Lines in Galloping

More information

Reducing Contingency-based Windfarm Curtailments through use of Transmission Capacity Forecasting

Reducing Contingency-based Windfarm Curtailments through use of Transmission Capacity Forecasting Reducing Contingency-based Windfarm Curtailments through use of Transmission Capacity Forecasting Doug Bowman Southwest Power Pool Jack McCall Lindsey Manufacturing Co. CIGRE US National Committee 2017

More information

BUREAU OF INDIAN STANDARDS. Draft Indian Standard GUIDELINES FOR INFRARED THERMOGRAPHY INSPECTION OF ELECTRICAL INSTALLATIONS ICS 19.

BUREAU OF INDIAN STANDARDS. Draft Indian Standard GUIDELINES FOR INFRARED THERMOGRAPHY INSPECTION OF ELECTRICAL INSTALLATIONS ICS 19. For BIS Use Only Doc: MTD 21 (5044)W BUREAU OF INDIAN STANDARDS Draft Indian Standard GUIDELINES FOR INFRARED THERMOGRAPHY INSPECTION OF ELECTRICAL INSTALLATIONS ICS 19.100 Not to be reproduced without

More information

Network Quality and Reliability of Supply

Network Quality and Reliability of Supply Network Quality and Reliability of Supply Performance Report 2010/11 Prepared by: Operations Asset & Works Audited by: Qualeng Left blank intentionally DMS 3444560 2 CONTENTS Horizon Power service area

More information

Module 6 : Preventive, Emergency and Restorative Control. Lecture 27 : Normal and Alert State in a Power System. Objectives

Module 6 : Preventive, Emergency and Restorative Control. Lecture 27 : Normal and Alert State in a Power System. Objectives Module 6 : Preventive, Emergency and Restorative Control Lecture 27 : Normal and Alert State in a Power System Objectives In this lecture you will learn the following Different states in a power system

More information

ANALYSIS OF ELECTROMAGNETIC FIELDS IN INTERCONNECTING SUBSTATIONS BETWEEN WTG AND NATIONAL POWER SYSTEM

ANALYSIS OF ELECTROMAGNETIC FIELDS IN INTERCONNECTING SUBSTATIONS BETWEEN WTG AND NATIONAL POWER SYSTEM U..B. Sci. Bull., Series C, Vol. 76, Iss. 1, 014 ISSN 86 3540 ANALYSIS OF ELECTROMAGNETIC FIELDS IN INTERCONNECTING SUBSTATIONS BETWEEN WTG AND NATIONAL OWER SYSTEM Gabriela Nicoleta SAVA 1, Sorina COSTINAŞ

More information

Incorporating Dynamic Line Ratings to Alleviate Transmission Congestion, Increase Wind Resource Utilization, and Improve Power Market Efficiency

Incorporating Dynamic Line Ratings to Alleviate Transmission Congestion, Increase Wind Resource Utilization, and Improve Power Market Efficiency 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium Incorporating Dynamic Line Ratings to Alleviate Transmission Congestion, Increase Wind

More information

International Studies about the Grid Integration of Wind Generation

International Studies about the Grid Integration of Wind Generation International Studies about the Grid Integration of Wind Generation Dr.-Ing. Markus Pöller/DIgSILENT GmbH Internation Studies About Grid Integration of Wind Generation Grid Integration of Wind Generationin

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer LDSR 0.3-TP/SP1 I P R N = 300 ma For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Closed

More information

Procedure To Be Adopted When Working on High Voltage Mechanically Switched Capacitors with Damping Network (MSCDN)

Procedure To Be Adopted When Working on High Voltage Mechanically Switched Capacitors with Damping Network (MSCDN) 1. SCOPE This document details the procedures to be adopted when working on High Voltage Mechanically Switched Capacitors with. 2. ISSUE RECORD This is a Reference document. The current version is held

More information

BVES Annual Reliability Public Presentation 2016 Performance

BVES Annual Reliability Public Presentation 2016 Performance BVES Annual Reliability Public Presentation 2016 Performance December 13, 2017 Agenda Company Overview What is Electric Utility Reliability? Requirements & Definitions Reliability Indices 2016 Reliability

More information

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Power System Stability and Control Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Contents Chapter 1 Introduction to Power System Stability

More information

Effect of core balance current transformer errors on sensitive earth-fault protection in compensated MV networks

Effect of core balance current transformer errors on sensitive earth-fault protection in compensated MV networks 24th International Conference & Exhibition on Electricity Distribution CIRED) 12-15 June 2017 Session 3: Operation, control and protection Effect of core balance current transformer errors on sensitive

More information

Chapter Six. Corona:

Chapter Six. Corona: Chapter Six Corona: When an alternating potential difference is applied across two conductors whose spacing is large as compared to their diameters, there is no apparent change in the condition of atmospheric

More information

Transmission Powerlines and Your Safety

Transmission Powerlines and Your Safety HIGH VOLTAGE Transmission Powerlines and Your Safety A Survival Guide A community safety campaign endorsed by Introduction ElectraNet is responsible for the safe, reliable and secure operation of South

More information

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity VX Enclosure System Technical documentation PE conductor connection, current carrying capacity Enclosure system VX Contents Contents. General remarks. Introduction. Notes on the design of the earthing

More information

TRANSMISSION LINES. All aluminum alloy conductor (AAAC) Aluminum conductor alloy reinforced (ACAR)

TRANSMISSION LINES. All aluminum alloy conductor (AAAC) Aluminum conductor alloy reinforced (ACAR) TRANSMISSION LINES. Transmission Structures An overhead transmission line consists of conductor, insulators, support structures and in most cases shield wires. Overhead power transmission lines are classified

More information

Keywords: Superconducting Fault Current Limiter (SFCL), Resistive Type SFCL, MATLAB/SIMULINK. Introductions A rapid growth in the power generation

Keywords: Superconducting Fault Current Limiter (SFCL), Resistive Type SFCL, MATLAB/SIMULINK. Introductions A rapid growth in the power generation IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Performance of a 3.3kV Resistive type Superconducting Fault Current Limiter S.Vasudevamurthy 1, Ashwini.V 2 1 Department of Electrical

More information

GENERATOR INTERCONNECTION APPLICATION

GENERATOR INTERCONNECTION APPLICATION GENERATOR INTERCONNECTION APPLICATION FOR BUY-ALL/SELL-ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 1 MW Electric Utility Contact Information Great Lakes Energy

More information

Southern California Edison Wildfire Mitigation & Grid Resiliency

Southern California Edison Wildfire Mitigation & Grid Resiliency Southern California Edison Wildfire Mitigation & Grid Resiliency California State Legislative Conference Committee on Wildfire Preparedness and Response August 7, 2018 CALIFORNIA S WILDFIRE RISK Year-Round

More information

TeSys circuit-breakers

TeSys circuit-breakers Presentation Thermal-magnetic motor circuit-breakers types GV2, GV and GV7 GV2-ME, GV2-P, GV-ME and GV7-R motor circuit-breakers are -pole thermal-magnetic circuit-breakers specifically designed for the

More information

Power System Seminar Presentation Wind Forecasting and Dispatch 7 th July, Wind Power Forecasting tools and methodologies

Power System Seminar Presentation Wind Forecasting and Dispatch 7 th July, Wind Power Forecasting tools and methodologies Power System Seminar Presentation Wind Forecasting and Dispatch 7 th July, 2011 Wind Power Forecasting tools and methodologies Amanda Kelly Principal Engineer Power System Operational Planning Operations

More information

ATTACHMENT Mitigating Systems

ATTACHMENT Mitigating Systems ATTACHMENT 71111.01 INSPECTABLE AREA: Adverse Weather Protection CORNERSTONE: Initiating Events Mitigating Systems EFFECTIVE DATE: January 1, 2010 INSPECTION BASES: Weather conditions leading to loss of

More information

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9 PUB NLH 1 Page 1 of 1 Q. Provide Hydro s list of outage cause codes and indicate how troublemen are managed and trained to properly use the codes. Explain the method used to report outage causes. A. Hydro

More information

Vegetation Related Transmission Outage Report

Vegetation Related Transmission Outage Report Vegetation Related Transmission Outage Report Third 2013 3353 Peachtree Road NE Suite 600, North Tower Atlanta, GA 30326 404-446-2560 www.nerc.com Executive Summary The NERC Board of Trustees Compliance

More information

Expedited Filing Draft August 22, 2017

Expedited Filing Draft August 22, 2017 Applicability 1 Section 304.9 applies to: (a) (b) Requirements Expedited Filing Draft August 22, 2017 the legal owner of a wind or solar aggregated generating facility connected to the interconnected electric

More information

APPLICATION OF A LINE AMPACITY MODEL AND ITS USE IN TRANSMISSION LINES OPERATIONS

APPLICATION OF A LINE AMPACITY MODEL AND ITS USE IN TRANSMISSION LINES OPERATIONS Journal of ELECTRICAL ENGINEERING, VOL. 65, NO. 4, 214, 221 227 APPLICATION OF A LINE AMPACITY MODEL AND ITS USE IN TRANSMISSION LINES OPERATIONS Jaroslav Šnajdr Jan Sedláček Zdeněk Vostracký A conductor

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION THERMAL MANAGEMENT OF SURFACE MOUNTED TANTALUM CAPACITORS Ian Salisbury AVX-Kyocera Group Company Paignton, England TQ4 7ER Abstract: This paper covers thermal management of surface

More information

THIRD GENERATION SYSTEM PROTECTION SCHEME PROJECT FOR ZEYA HYDRO POWER PLANT

THIRD GENERATION SYSTEM PROTECTION SCHEME PROJECT FOR ZEYA HYDRO POWER PLANT THIRD GENERATION SYSTEM PROTECTION SCHEME PROJECT FOR ZEYA HYDRO POWER PLANT Andrey GROBOVOY Power System Emergency Control Laboratory Ltd. - Russia andrey.grobovoy@ieee.org Elena DEDUKHINA Zeya Hydro

More information

SIGNIFICANCE OF TRANSPOSITION FOR 220KV TOWER

SIGNIFICANCE OF TRANSPOSITION FOR 220KV TOWER International Journal of Latest Research in Science and Technology Volume 4, Issue 5: Page No.4-8, September-October 2015 http://www.mnkjournals.com/ijlrst.htm ISSN (Online):2278-5299 SIGNIFICANCE OF TRANSPOSITION

More information

Transient Analysis of a 150 kv Fault Current Limiting High Temperature Superconducting Cable

Transient Analysis of a 150 kv Fault Current Limiting High Temperature Superconducting Cable Transient Analysis of a kv Fault Current Limiting High Temperature Superconducting Cable Vandana S. Mehairjan 1, Marjan Popov 2, Alex Geschiere 1, Will L. Kling 3 Abstract The interconnection of electrical

More information

MCB NB1-63H Miniature Circuit Breaker

MCB NB1-63H Miniature Circuit Breaker NB-H Miniature Circuit Breaker. General. Function protection of circuits against short-circuit currents, protection of circuits against overload currents, switch, isolation, NB-H circuit-breakers are used

More information

Modeling and Simulation of Air Insulated and Gas Insulated Substations

Modeling and Simulation of Air Insulated and Gas Insulated Substations International Journal of Electrical Engineering. ISSN 0974-2158 Volume 11, Number 2 (2018), pp. 177-187 International Research Publication House http://www.irphouse.com Modeling and Simulation of Air Insulated

More information

Director, Operations Services, Met-Ed

Director, Operations Services, Met-Ed Director, Operations Services, Met-Ed Pennsylvania House Republican Policy Committee Hearing on Storm Response Tobyhanna Township Municipal Building Pocono Pines, Pa. August 9, 2018 Planning and Forecast

More information

Superconducting Fault Current Limiters

Superconducting Fault Current Limiters Superconducting Fault Current Limiters First Friday Club 1 st April 2011 Gerhard Novak UK Technical Manager Joachim Bock Managing Director, Nexans Superconductors 1 Smart Grid Solutions 2 Fault current

More information

KINGS COLLEGE OF ENGINEERING Punalkulam

KINGS COLLEGE OF ENGINEERING Punalkulam KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK

More information

Test method to assess the suitability of materials and surfaces to avoid problems from static electricity by measurement of capacitance loading

Test method to assess the suitability of materials and surfaces to avoid problems from static electricity by measurement of capacitance loading 1 of 15 JCI 12 October 2001 Test method to assess the suitability of materials and surfaces to avoid problems from static electricity by measurement of capacitance loading 1 Introduction This document

More information

Investigation into the computational techniques of power system modelling for a DC railway

Investigation into the computational techniques of power system modelling for a DC railway Power Supply System Analysis, Design and Planning 123 Investigation into the computational techniques of power system modelling for a DC railway A. Finlayson 1, C. J. Goodman 2 & R. D. White 1 1 Atkins

More information

Commissioning and Testing of AVR and PSS

Commissioning and Testing of AVR and PSS Commissioning and Testing of AVR and PSS Excitation System Upgrade and commissioning challenges Vetti Bala Principal C&I Engineer G E N E S I S E N E R G Y L I M I T E D Contents Asset Testing - AVR AVR

More information

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid J. McCall, J. Yuan, D. Folts, N. Henderson, American Superconductor D. Knoll, Southwire M. Gouge, R. Duckworth, J.

More information

Combined HTS Cable and Fault Current Limiter Project in Germany

Combined HTS Cable and Fault Current Limiter Project in Germany Combined HTS Cable and Fault Current Limiter Project in Germany Mathias Noe, Institute for Technical Physics, KIT Mark Stemmle, Nexans Germany Frank Schmidt, Nexans Germany Frank Merschel, RWE Joachim

More information

PREDICTION OF TEMPERATURE VARIATIONS FOR INDUSTRIAL BUS DUCT SYSTEM UNDER FORCED CONVECTION COOLING WITH VARIOUS ASPECT RATIOS USING MATLAB

PREDICTION OF TEMPERATURE VARIATIONS FOR INDUSTRIAL BUS DUCT SYSTEM UNDER FORCED CONVECTION COOLING WITH VARIOUS ASPECT RATIOS USING MATLAB International Journal of Mechanical Engineering and Technology (IJMET) Volume 9, Issue 2, February 2018, pp. 734 741 Article ID: IJMET_09_02_076 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=9&itype=2

More information

International Workshop on Wind Energy Development Cairo, Egypt. ERCOT Wind Experience

International Workshop on Wind Energy Development Cairo, Egypt. ERCOT Wind Experience International Workshop on Wind Energy Development Cairo, Egypt ERCOT Wind Experience March 22, 21 Joel Mickey Direcr of Grid Operations Electric Reliability Council of Texas jmickey@ercot.com ERCOT 2 2

More information

Wind power and management of the electric system. EWEA Wind Power Forecasting 2015 Leuven, BELGIUM - 02/10/2015

Wind power and management of the electric system. EWEA Wind Power Forecasting 2015 Leuven, BELGIUM - 02/10/2015 Wind power and management of the electric system EWEA Wind Power Forecasting 2015 Leuven, BELGIUM - 02/10/2015 HOW WIND ENERGY IS TAKEN INTO ACCOUNT WHEN MANAGING ELECTRICITY TRANSMISSION SYSTEM IN FRANCE?

More information

Derogation Criteria for the Requirements for Generators Network Code

Derogation Criteria for the Requirements for Generators Network Code Derogation Criteria for the Requirements for Generators Network Code Decision Paper Reference: CER/17/084 Date Published: 13/04/2017 Closing Date: 0 Executive Summary Commission Regulation (EU) 2016/631

More information

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL 1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:

More information

CLIMATE CHANGE ASSESSMENT. A. Climate Change Risk Assessment and Adaptation Measures

CLIMATE CHANGE ASSESSMENT. A. Climate Change Risk Assessment and Adaptation Measures Solar Transmission Sector Project (RRP IND 49214) CLIMATE CHANGE ASSESSMENT I. Transmission System at Bhadla, Rajasthan A. Climate Change Risk Assessment and Adaptation Measures High temperature Risk is

More information

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018 Periodic Inspection and Testing of Electrical Installations Sample Test (2391-051) Version 1.3 July 2018 Sample Questions Version and date Change detail Section 1.3 July 2018 Modified questions/answers

More information

DISTRIBUTION SYSTEM ELECTRIC INFRASTRUCTURE RELIABILITY PERFORMANCE INDICATORS

DISTRIBUTION SYSTEM ELECTRIC INFRASTRUCTURE RELIABILITY PERFORMANCE INDICATORS EB-- Exhibit D Page of DISTRIBUTION SYSTEM ELECTRIC INFRASTRUCTURE RELIABILITY PERFORMANCE INDICATORS FIVE-YEAR HISTORICAL RELIABILITY PERFORMANCE THESL tracks System Average Interruption Frequency Index

More information

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study.

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study. Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study. Marcelo Rodrigo García Saquicela, Ernesto Ruppert Filho, José Luis Azcue

More information

Exploring Six-Phase Transmission Lines for Increasing Power Transfer With. Limited Right Of Way. Xianda Deng

Exploring Six-Phase Transmission Lines for Increasing Power Transfer With. Limited Right Of Way. Xianda Deng Exploring Six-Phase Transmission Lines for Increasing Power Transfer With Limited Right Of Way by Xianda Deng A Thesis Presented in Partial Fulfillment of the Requirements for the Degree Master of Science

More information

Dynamic simulation of DH house stations

Dynamic simulation of DH house stations Article Dynamic simulation of DH house stations Jan Eric Thorsen, Director, DHS Application Centre, Danfoss A/S www.danfoss.com Jan Eric Thorsen, Director, DHS Application Centre, Danfoss A/S Presented

More information

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER 1 RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER Dr. Swarn S. Kalsi, David Madura, and Michael Ross American Superconductor Corporation (USA) Abstract: A high-temperature

More information

DESIGN AND FINITE ELEMENT ANALYSIS OF A TRANSFORMER TANK A REVIEW PAPER

DESIGN AND FINITE ELEMENT ANALYSIS OF A TRANSFORMER TANK A REVIEW PAPER DESIGN AND FINITE ELEMENT ANALYSIS OF A TRANSFORMER TANK A REVIEW PAPER Gajjar Dhruvesh Ashokbhai, Prof R R Patel, Prof S P Joshi Gajjar Dhruvesh Ashokbhai,, Student ME, Mechanical Engineering, BVM Engg

More information

DISTRIBUTION CONDUCTOR STRINGING EQUIPMENT & TECHNIQUES

DISTRIBUTION CONDUCTOR STRINGING EQUIPMENT & TECHNIQUES DISTRIBUTION CONDUCTOR STRINGING EQUIPMENT & TECHNIQUES FOR THE 21 ST CENTURY PRESENTED AT: SOUTHWEST TRAINING EXPO FEBRUARY, 2000 PRESENTED BY: JOHN R. WHITT SR. VICE PRESIDENT 1 When the decision is

More information

High Temperature Overhead Conductor Rating Considerations

High Temperature Overhead Conductor Rating Considerations High Temperature Overhead Conductor Rating Considerations Joseph Coffey Director Overhead Transmission, Prysmian Group/General Cable Littleton, Colorado Abstract Transmission utilities are deploying an

More information

Applications of GIS in Electrical Power System

Applications of GIS in Electrical Power System Applications of GIS in Electrical Power System Abdulrahman M. AL-Sakkaf 201102310 CRP 514 May 2013 Dr. Baqer M. AL-Ramadan Abstract GIS has been widely used in various areas and disciplines. This paper

More information

CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING

CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING 20 CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING 2.1 INTRODUCTION It is becoming more common to find use of shunt capacitors for the application of powerfactor

More information

Numerical Calculation and Analysis on the Surface Electric Field Characteristics of Hot-Line Robot

Numerical Calculation and Analysis on the Surface Electric Field Characteristics of Hot-Line Robot 2017 International Conference on Computer Science and Application Engineering (CSAE 2017) ISBN: 978-1-60595-505-6 Numerical Calculation and Analysis on the Surface Electric Field Characteristics of Hot-Line

More information