Air Diffusion Designing for Comfort
|
|
- Alaina Gibson
- 5 years ago
- Views:
Transcription
1
2 Air Diffusion Designing for Comfort
3 Occupant Comfort Air Diffusion Selection ADPI Air Diffusion Performance index Ventilation Effectiveness Induction Room Space Induction Design Criteria ISO7730 ASHRAE 55p Design & Selection Software Products
4 Occupant Comfort
5 Comfort Limits ASHRAE Standard and ISO ADPI Air Diffusion Performance Index / Comfort Index When is a person comfortable? A person is thermally comfortable when their body heat loss equals their heat production without them sensing any changes in temperature.
6 Body Heat Loss or Gain Heat Loss or Gain can occur through: Conduction transfer of heat across a body Convection transfer from a body to its surroundings Radiation transfer through electromagnetic waves Evaporation sweat
7 Personal Comfort Variables - Clothing - Activity - Metabolic rate
8 Space Comfort Variables - Dry bulb temperature - Relative humidity - Air velocity - Noise
9 ASHRAE Defines Comfort ASHRAE Definition of Comfort Fanger s comfort index or PMV.
10 ASHRAE Definition of Comfort ASHRAE/ISO 7730 standard defines comfort as: - Maintaining a temperature of C - Relative humidity of 25 60% - Maximum velocity within the occupied zone of 0.25 m/s Cooling & 0.15m/s Heating
11 Effect of Air Motion on Comfort The percentage of dissatisfied occupants at the Neck Region.
12 Effect of Air Motion on Comfort The percentage of dissatisfied occupants at the Ankle Region.
13 Design Criteria ISO7730-ASHRAE 55P-APDI Thermal Resistance of Clothing - Clo Value Provided Metabolic there Rate is Occupants sufficient Physical heating Activity & cooling to meet the thermal and humidity control requirements, comfort is almost completely a Air Temperature Optimum Operative Temperature function Air Velocity of the Mean space Space air distribution. Velocity S.A. Mumma, Ph.D P.E., Fellow ASHRAE Relative Humidity Mean Radiant Temperature
14 Air Diffusion Selection
15 Air Distribution Air Diffusion Design & Selection
16 Defining the Occupied Space
17 Terminal Velocity Terminal Velocity Tv m.75 m/s.50 m/s.25 m/s 7.3 m 15.6m
18 Free Expansion A free jet will expand at 22. Zone 1 Zone 2 Zone 3 Zone 4 Laminar, induction increases Laminar, induction increases Exit velocity with initial induction Laminar/Turbulent, maximum Room induction
19
20 Hot and Cold Jets If the supply air is warmer than the room temperature, it will rise. However if the supply air is cooler than the room air, it will drop. General Rule: T0.25 is effected at 2% per Degree T
21 Example 5 0 C Delta T Heating 10% T 0.25 Throw@0.25m/s General Rule: 0.25 is effected at 2% per Degree T
22 With overhead heating, the air slows down and turns upwards at roughly 0.50 to 0.75m/s. Considerations 0.5 to 0.75m/s
23 Furniture against wall Considerations
24 Colliding jets Air Diffusion Mistakes
25 ADPI Air Diffusion Performance Index
26 ADPI Effective Draft Temperature Effective Draft Temperature is calculated by: q = ( - )- ( - ) t x t c 8 V x 0.15 where : q = t t x c V x = = = effective draft temperature (K) local jet dry-bulb temperature ( C) control room dry-bulb temperature ( C) local jet centreline velocity (m/s)
27 ADPI & Effective Draft Temperature The ADPI is the percentage of locations where measurements are taken which have an: Acceptable _ Effective Draft Temperature. Total number of q within acceptance Total number of values measured X 100 An acceptable value for Effective Draft Temperature is within and , with a velocity of less than 0.35m/s
28 ASHRAE Definition of Comfort PMV Comfort as a function of air velocity and temperature.
29 ADPI Effective Draft Temperature
30 Air Diffusion Performance Index Effective draft temperature, q ( t -t )-8( V -0.15) = x c x t c 1700mm 1100mm 600mm 100mm q 1 q 100 t x and V x
31 ADPI Air Diffusion Performance Index Effective draft temperature, q ( t -t )-8( V -0.15) = x c x Room Temp = 22 0 C 30 Test points at 0.1m/s, 20 C 35 points at 0.2m/s, 21 C 20 points at 0.3m/s, 22 C 15 points at 0.4m/s, 22 C so if 30 points = points = points = points = -2 ADPI = 85 q = 1 = ( tx - tc )-8( Vx ) ( 20-22) -8( ) = -1.6 q2 = -1.4 q = q4 = ADPI = = 0.85 = 85%
32 Air Diffusion Performance Index Selection Guide
33 Air Diffusion Performance Index Ratio T Throw distance at terminal velocity 0.25m/s L Characteristic room length
34 Terminal Velocity Tv m.75 m/s.50 m/s.25 m/s 7.3 m 15.6
35 Characteristic Room Length L Characteristic room length for various Air Diffusion Products Diffuser Type High Sidewall Register Circular Ceiling Diffuser & Swirl Diffusers Sill Grille Ceiling Slot Diffuser Light Troffer Diffusers Perforated, Louvered Ceiling Diffusers Characteristic Length (L) Distance to wall perpendicular to jet Distance to closest wall or intersecting air jet Length of room in direction of flow Distance to wall or mid plane between outlets Distance to mid plane between outlets plus distance from ceiling to top of occupied zone Distance to wall or mid plane between outlets
36 ADPI Selection Example
37 Example Mapping Throw 6 m 2.7 m A consulting engineer is selecting a diffuser for the room above. The room requires 250 l/s at an NC no greater than 35.
38 Example Mapping Throw 1.5 m 3 m 1.5 m 2.7 m 0.4 m 0.4 m They selected 2 x CFP600/12, with 125l/s for each. Total air quantity 250l/s, with a throw of 0.25m/s. An NC value of 14. Will the occupants be comfortable?
39 Example Using ADPI ADPI 130W/m2 for 80 target - ratio = m 3m 1.5m 2.7m 0.4m 0.4m T ADPI calculation = = = L 1.5
40 Example Mapping Throw If our selection 1 x CFP600/24 Radial Swirl diffuser. Total volume 250l/s - Throw - NC = 26 Will the occupants be comfortable? 3m 3m 2.7 m
41 Example Using ADPI ADPI 130W/m2 for 80 target - ratio = m 3 m 2.7 m T ADPI calculation = = = L 3
42 ADPI Selection T L
43 ADPI Selection T L
44 ADPI Selection
45 ADPI Design Expectations APDI - Ensures proper Selection, Application and Deployment of Air Diffusion Equipment High APDI equates to High Air Change Effectiveness (ACE) Value ADPI Method is suitable for heating at <10 0 C ΔT ADPI method is effective for CAD (as low 5 0 C) Cold Air Distribution Design Manual TR Research Project )
46 Ventilation Effectiveness
47 Ventilation Effectiveness Air Change Effectiveness (ACE) ANSI/ASHRAE Standard ASHRAE Fundamentals F Principally it is an evaluation of effective mixing of the Supply/Outdoor with Room/ Space Air
48 Induction
49 Induction, High Induction & Induction Ratios High Induction means High Exit Velocity High Induction means High Pressure Higher pressure offsets (CAD) Design Savings High Induction = Smaller Air flows or more Diffusers or more Noise
50 Induction, High Induction & Induction Ratio Room Air Induction Equation There is no accepted published method Qx for determining = = the C induction Vo ratio of an Qo Vx individual diffusion product Induction Ratio Q Where: Induction Ratio = Primary Qx: Air / Induced Air Qx = Qo X C Vo Vx Qo: = Supply volume m3/s = Induction volume at Distance Vo: = Discharge Velocity m/s Vx: = Velocity at distance m/s = Entrainment Coefficient 1.4 for infinite slots and 2.0 for round free axial jets Temperature Measurements C: of Primary Air, Discharge Air and Induced Air
51 Holyoake Swirl Diffusers Series CFP CFP - 600/24 Aeff: m2 Veff: 0.7-3m/s Air Flow: L/S Pa: 2-13 NC <10-30 CFP - 600/20 Aeff: m2 Veff: 0.5-3m/s Air Flow: L/S Pa: 6-12 NC CFP - 600/12 Aeff: m2 Veff: 0.5-3m/s Air Flow: L/S Pa: 2-18 NC <10-20 Flexible Volume range suitable for VAV Systems High Mixing Turbulent Radial Swirl Air Pattern Good induction Low Pressure - Low Noise High Range VAV Blade Design and Turbulent Radial Mixing
52 Induction, Room Induction - Room Induction Ratios Q Air Volume 200L/S = 2.16 m/s Exit Velocity Air Volume100L/S = 1.08m/s Exit Velocity Swirl Diffuser Tv@0.25m/s Swirl Diffuser Tv@0.20m/s (Figure 9) 3456 L/S Room Induction Ratio Q = Air Volume 200L/S = 2.16 m/s Exit Velocity CFP/600/20 (Figure 8) 1080 L/S Room Induction Ratio Q = 10.8 Air Volume100L/S = 1.08m/s Exit Velocity Swirl Diffuser Tv@0.15m/s Swirl Diffuser Tv@0.10m/s 5760 L/S 2160 L/S (Figure 11) Room Induction Ratio Q = 28.8 (Figure 10) Room Induction Ratio Q = 21.6
53 Design Criteria ISO7730 ASHRAE 55P PVM Predicted Mean Vote - PPD
54 Design Criteria ISO7730-ASHRAE 55P-APDI Thermal Resistance of Clothing - Clo Value Metabolic Rate Occupants Physical Activity Air Temperature Optimum Operative Temperature Air Velocity Mean Space Velocity Relative Humidity Mean Radiant Temperature
55 Thermal Comfort Considerations & Obligations Design to a Predetermined PMV-PPD As a function of: Clothing, Metabolic Rate. Air temp, Radiant Temp, Velocity, Humidity <6% PD <10% PD <15% PD Establish Optimum Operative Temperature Range <6% PD <10% PD <15% PD Establish the draft rating DR PD (mean velocity) encompassing: Local Air Temperature, Local air velocity, local turbulence intensity <15% PD <20% PD <25% PD 0.62 DR 34 -ta v ( )( ) ( 0.37 v 3.14) = Tu
56 Thermal Comfort Considerations & Obligations Determine Ventilation rate for Perceived Indoor Air Quality as a result of Occupant numbers and Building Materials <15% PD <20% PD <30% PD Establish your Ventilation rate for Air Quality as a result of Occupant numbers and Building Materials <15% PD <20% PD <30% PD Confirm Design Ventilation Effectiveness Green Star requires Veff 0.95
57 Thermal Comfort Considerations & Obligations Establish required Flow Rate for Thermal Design in accordance with optimal operating temperature Ensure Acoustics meet Environment standards Category (A) Category (B) Category (C) Establish and Confirm ADPI Rating >80 Effective Draft Temperature : local temperature, room average temperature, local velocity ( tx -tc)-8( -0.15) q = Vx
58 Calculation for PMV for resultant PPD
59 Design & Selection Software
60
61 Air Distribution Design Program ADE:5.4
62
63
64
65
66
67
68
69
70
71 Products
72 Architectural Louvers
73 CSDF Fixed Pattern Linear Slot
74
75 CSD-P Flangeless Linear
76
77 LF1200 Flangeless Extruded Linear Bar Diffuser
78
79 Thankyou for Listening
80 Predicted Mean Vote Percentage Dissatisfied P. Ole Fanger Director, Professor, D.Sc. International Centre for Indoor Environment and Energy Technical University of Denmark, Building 402 DK-2800 Lyngby, Denmark.
Thermal behavior and Energetic Dispersals of the Human Body under Various Indoor Air Temperatures at 50% Relative Humidity
Thermal behavior and Energetic Dispersals of the Human Body under Various Indoor Air Temperatures at 50% Relative Humidity Hakan CALISKAN Usak University, Department of Mechanical Engineering, Usak, Turkey
More informationCeiling Radiant Cooling Panels Employing Heat-Conducting Rails: Deriving the Governing Heat Transfer Equations
Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.
More informationEnvironmental Engineering
Environmental Engineering 1 Indoor Environment and Thermal Comfort Vladimír Zmrhal (room no. 814) Master degree course 1 st semester (winter) Dpt. of Environmental Engineering 1 Environmental Engineering
More informationROOM AVERAGE VELOCITY EQUATION A TOOL TO IMPROVE DESIGN OF THERMAL COMFORT CONDITIONS
ROOM AVERAGE VELOCITY EQUATION A TOOL TO IMPROVE DESIGN OF THERMAL COMFORT CONDITIONS K Hagström *, O Hakkola and T Moilanen Halton Solutions, Kausala, Finland ABSTRACT For a long time PPD index defined
More informationOPERATIVE TEMPERATURE SIMULATION OF ENCLOSED SPACE WITH INFRARED RADIATION SOURCE AS A SECONDARY HEATER
OPERATIVE TEMPERATURE SIMULATION OF ENCLOSED SPACE WITH INFRARED RADIATION SOURCE AS A SECONDARY HEATER L. Hach 1, K. Hemzal 2, Y. Katoh 3 1 Institute of Applied Physics and Mathematics, Faculty of Chemical
More informationCAE 331/513 Building Science Fall 2017
CAE 331/513 Building Science Fall 2017 September 19, 2017 Human thermal comfort Advancing energy, environmental, and sustainability research within the built environment www.built-envi.com Twitter: @built_envi
More informationISO 7730 INTERNATIONAL STANDARD
INTERNATIONAL STANDARD ISO 7730 Third edition 2005-11-15 Ergonomics of the thermal environment Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices
More informationBSE Public CPD Lecture Numerical Simulation of Thermal Comfort and Contaminant Transport in Rooms with UFAD system on 26 March 2010
BSE Public CPD Lecture Numerical Simulation of Thermal Comfort and Contaminant Transport in Rooms with UFAD system on 26 March 2010 Organized by the Department of Building Services Engineering, a public
More informationA Simulation Tool for Radiative Heat Exchangers
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 A Simulation Tool for Radiative Heat Exchangers Yunho Hwang yhhwang@umd.edu
More informationAalborg Universitet. Comparison between Different Air Distribution Systems Nielsen, Peter Vilhelm. Publication date: 2006
Aalborg Universitet Comparison between Different Air Distribution Systems Nielsen, Peter Vilhelm Publication date: 2006 Document Version Publisher's PDF, also known as Version of record Link to publication
More informationRELATIONSHIPS BETWEEN OVERALL THERMAL SENSATION, ACCEPTABILITY AND COMFORT
RELATIONSHIPS BETWEEN OVERALL THERMAL SENSATION, ACCEPTABILITY AND COMFORT Yufeng Zhang 1, and Rongyi Zhao 2 1 State Key Laboratory of Subtropical Building Science, South China University of Technology,
More informationModeling Human Thermoregulation and Comfort. CES Seminar
Modeling Human Thermoregulation and Comfort CES Seminar Contents 1 Introduction... 1 2 Modeling thermal human manikin... 2 2.1 Thermal neutrality... 2 2.2 Human heat balance equation... 2 2.3 Bioheat equation...
More informationCFD as a Tool for Thermal Comfort Assessment
CFD as a Tool for Thermal Comfort Assessment Dimitrios Koubogiannis dkoubog@teiath.gr G. Tsimperoudis, E. Karvelas Department of Energy Technology Engineering Technological Educational Institute of Athens
More informationKrantz Components. Variable twist outlet with guide ring DD-VL... jet straightener DD-VG... Air distribution systems
Variable twist outlet with guide ring DD-VL... jet straightener DD-VG... Air distribution systems DS E 01. with guide ring or jet straightener Preliminary remarks The variable twist outlet with guide ring
More informationCircular duct grille
Dimensions B+0 A+0 A B Description is a rectangular ventilation grille with vertical adjustable bars for direct installation in circular ducts. The grille can be used for both supply and exhaust air. The
More informationPrinciples and Applications of Building Science Dr. E Rajasekar Department of Civil Engineering Indian Institute of Technology, Roorkee
Principles and Applications of Building Science Dr. E Rajasekar Department of Civil Engineering Indian Institute of Technology, Roorkee Lecture - 04 Thermal Comfort in Built Environment 2 In previous module,
More informationVariable swirl diffusers
Swirl diffusers, Variable swirl diffuser OD- Application Diffuser is designed for air conditioning of rooms with floor to ceiling highs of to 0 m and high induction requirements. It is suitable for large
More informationCircular duct grille. Dimensions. Description. Maintenance The grille should be removed to gain access to the duct.
Dimensions B+0 A+0 A B Description RGS is a rectangular ventilation grille with vertical adjustable bars for direct installation in circular ducts. The grille can be used for both supply and exhaust air.
More informationIndoor Environment Quality. Study the world Capture the elements Environmental testing made easy. MI 6201 Multinorm. MI 6401 Poly.
Study the world Capture the elements Environmental testing made easy MI 6401 Poly MI 6201 Multinorm MI 6301 FonS Find out more about Indoor Environment Quality parameters testing Indoor Environmental Quality
More informationHealthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland
Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0076 ISBN: 978-83-7947-232-1 Experimental Study of the Airflow Distribution Close to the Human Body with a Downward Plane Jet Marie
More informationCh. 12 Human Thermal Comfort and Indoor Air Quality
Ch. 12 Human Thermal Comfort and Indoor Air Quality -2-12.1 Introduction - Temperature & Humidity Control - IAQ Indoor Air Quality : control of indoor airborne contaminants 12.2 Energy balance on the human
More informationSwirl diffusers, Variable swirl diffusers
0 Variable swirl diffusers SLOT IFFUSERS, ROUN UCT IFFUSERS SWIRL IFFUSERS, VARIABLE SWIRL IFFUSERS CIRCULAR IFFUSERS, SQUARE IFFUSERS VENTILATING GRILLES, VENTILATING VALVES, Variable swirl diffusers
More informationKrantz. Variable twist outlet with guide ring DD-VL... jet straightener DD-VG... Air distribution systems
Krantz Variable twist outlet with guide ring DD-VL... jet straightener DD-VG... Air distribution systems DS E 01.18 Variable twist outlet with guide ring or jet straightener Preliminary remarks The variable
More informationHD32.2 WBGT Index HD32.3 WBGT-PMV. [ GB ] - WBGT index. - PMV index and PPD
HD32.2 WBGT Index HD32.3 WBGT-PMV [ GB ] - WBGT index. - PMV index and PPD [ GB ] [ GB ] Description HD32.2 WBGT Index is an instrument made by Delta Ohm srl for the analysis of WBGT index (Wet Bulb Glob
More informationMODELLING THERMAL COMFORT FOR TROPICS USING FUZZY LOGIC
Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 MODELLING THERMAL COMFORT FOR TROPICS USING FUZZY LOGIC Henry Feriadi, Wong Nyuk Hien Department of Building, School of Design
More informationEXPERIMENTAL ANALYSIS OF AIR-CONDITIONING IN HOSPITAL ROOMS BY MEANS OF LIGHT RADIANT CEILINGS
EXPERIMENTAL ANALYSIS OF AIR-CONDITIONING IN HOSPITAL ROOMS BY MEANS OF LIGHT RADIANT CEILINGS Renato M. Lazzarin renato@gest.unipd.it Francesco Castellotti caste@gest.unipd.it Filippo Busato busato@gest.unipd.it
More informationAir distribution systems. Linear whirl outlet WL...
Air distribution systems Linear whirl outlet WL... DS 0 E 1.013 Preliminary remarks Mode of operation The linear whirl outlet generates turbulent mixing ventilation. It can be installed on or in a wall
More informationTHERMAL COMFORT IN HIGHLY GLAZED BUILDINGS DETERMINED FOR WEATHER YEARS ON ACCOUNT OF SOLAR RADIATION. Dominika Knera 1 and Dariusz Heim 1
THERMAL COMFORT IN HIGHLY GLAZED BUILDINGS DETERMINED FOR WEATHER YEARS ON ACCOUNT OF SOLAR RADIATION Dominika Knera 1 and Dariusz Heim 1 1 Department of Heat and Mass Transfer, Lodz University of Technology
More informationKrantz. RL-C2 radial slot outlet. Air distribution systems
RL-C2 radial slot outlet Air distribution systems DS E 04.1 Introduction The RL-C2 radial slot outlet with circular face generates a turbulent mixed flow. It is used for supply and return air distribution
More informationNUMERICAL MODELLING OF TEMPERATURE AND AIR FLOW DISTRIBUTION IN ENCLOSED ROOM
NUMERICAL MODELLING OF TEMPERATURE AND AIR FLOW DISTRIBUTION IN ENCLOSED ROOM Igor Bonefacic 1, Bernard Frankovic 2, Ivan Vilicic 3, Vladimir Glazar 4 Faculty of Engineering, Vukovarska 58, Rijeka, Croatia,
More informationPrediction of Thermal Comfort and Ventilation Efficiency for Small and Large Enclosures by Combined Simulations
Institute for Thermodynamics and Building Energy Systems, Dresden University of Technology Prediction of Thermal Comfort and Ventilation Efficiency for Small and Large Enclosures by Combined Simulations
More informationARCH 348 BUILDING AND ENVIRONMENTAL SYSTEMS
ARCH 348 BUILDING AND ENVIRONMENTAL SYSTEMS Instructor: Prof. Dr. Uğur Atikol Web site for instructor: http://staff.emu.edu.tr/uguratikol/ Web site for the course: http://staff.emu.edu.tr/uguratikol/en/teaching/courses/arch348-building-andenvironmental-systems-in-architecture
More informationNozzles. About Lindab. Comfort and Design. Product overview / symbols. Theory. Ceiling diffusers. Ceiling diffusers - visible.
Nozzles About Lindab Comfort and Design Product overview / symbols Theory Ceiling diffusers Ceiling diffusers - visible Plenum boxes Wall diffusers Nozzles Ventiduct Grilles Displacement diffusers VAV
More informationMEASUREMENT OF THE AIRFLOW AND TEMPERATURE FIELDS AROUND LIVE SUBJECTS AND THE EVALUATION OF HUMAN HEAT LOSS
MEASUREMENT OF THE AIRFLOW AND TEMPERATURE FIELDS AROUND LIVE SUBJECTS AND THE EVALUATION OF HUMAN HEAT LOSS GH Zhou 1, DL Loveday 1, AH Taki 2 and KC Parsons 3 1 Department of Civil and Building Engineering,
More informationNUMERICAL ANALYSIS OF THERMAL COMFORT PARAMETERS IN LIVING QUARTERS
acta mechanica et automatica, vol.5 no.4 (2011) NUMERICAL ANALYSIS OF THERMAL COMFORT PARAMETERS IN LIVING QUARTERS Aneta BOHOJŁO * * phd student, Faculty of Mechanical Engineering, Bialystok University
More informationKrantz. Radial slot outlet with square blade array RL-Q2... circular blade array RL-R2... Air distribution systems DS 4186 E 09.
Krantz Radial slot outlet with square blade array RL-Q2... circular blade array RL-R2... Air distribution systems DS 86 E 09./1 with square and circular blade array Preliminary remark The radial slot outlet
More informationHD32.2 WBGT Index HD 32.2 INSTRUMENT FOR THE ANALYSIS OF THE WBGT INDEX
HD32.2 WBGT Index HD32.2 instrument can detect simultaneously the following quantities Globe thermometer temperature Tg. Wet bulb temperature with natural ventilation Tn. Environment temperature T. Starting
More informationIn the Psy. Ch., plot point o, r, h r = 51.0 kj/kg, h o = 85 kj/kg
& Marking Scheme (Page 1 of 8 ) 1. (a)(i) In the Psy. Ch., plot point o, r, h r = 51.0 kj/kg, h o = 85 kj/kg SHR = rs/rt = 63/70 = 0.9 Draw a line with SHR= 0.9 from r and intercept at s or cc in such
More informationSection 3.5 Thermal Comfort and Heat Stress
Section 3.5 Thermal Comfort and Heat Stress Table 3.6 Metabolic rate as a function of physical activity for a 70 kg adult man (abstracted from ASHRAE, 1997). activity metabolic rate (W) metabolic rate
More informationCoupled CFD/Building Envelope Model for the Purdue Living Lab
Proceedings of the 2012 High Performance Buildings Conference at Purdue, 2012 (Accepted) 3457, Page, 1 Coupled CFD/Building Envelope Model for the Purdue Living Lab Donghun KIM (kim1077@purdue.edu), James
More informationField evaluation of the performance of a radiant heating/cooling ceiling panel system
Proceedings of 8 th Windsor Conference: Counting the Cost of Comfort in a changing world Cumberland Lodge, Windsor, UK, 1-13 April 214. London: Network for Comfort and Energy Use in Buildings, http://nceub.org.uk
More informationSTUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION
STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION K Sakai 1*, E Yamaguchi 2, O Ishihara 3 and M Manabe 1 1 Dept. of Architectural Engineering,
More informationSwirl diffusers, Variable swirl diffusers Swirl diffusers
IMP Klima, Variable swirl diffusers Swirl diffuser OD- Fixed grille For air supply or exhaust Recommended temperature difference between supplied and internal air in the room is between 0 to 0 K Low static
More informationAn Investigation on the Human Thermal Comfort from a Glass Window
Article An Investigation on the Human Thermal Comfort from a Glass Window Nopparat Khamporn a and Somsak Chaiyapinunt b Department of Mechanical Engineering, Faculty of Engineering, Chulalongkorn niversity,
More informationseries 50-PR Square perforated face diffusers
series 50-PR Square perforated face diffusers www.koolair.com Series 50-PR 1 Square perforated face diffusers CONTENTS Square perforated face diffusers 54-FR Description 2 Coding and dimensions 3 Quick
More informationAnna Majchrzycka THERMAL COMFORT
WEST POMERANIAN UNIVERSITY OF TECHNOLOGY, SZCZECIN, POLAND THE FACULTY OF MECHANICAL ENGINEERING AND MECHATRONICS Anna Majchrzycka THERMAL COMFORT ASHRAE STANDARD 55-66 Thermal comfort is defined as that
More informationAvailable online at ScienceDirect. Procedia Engineering 121 (2015 )
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 2176 2183 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International
More informationSWIRL DIFFUSERS SWIRL DIFFUSERS OD-8
SWIRL IFFUSERS O- St RAL 900 Swirl diffuser O- Square or round front plate with radial deflector arrangement Plastic deflectors Possible volume control damper in spigot C SWIRL IFFUSERS O- K 00/ O- R 00/
More informationAir distribution systems. Adjustable radial outlet RA-V...
Air distribution systems Adjustable radial outlet RA-V... DS E 0.2013 Construction design Preliminary remarks KRANTZ KOMPONENTEN has developed its wellknown, successful radial outlet into an adjustable
More informationCeiling Diffuser. Type ADLR with circular face. Type ADLR-Q with square face 2/16/EN/8
2/16/EN/8 Ceiling Diffuser Type ADLR with circular face Type ADLR-Q with square face TROX GmbH Telephone +49/28 45/2 02-0 Telefax +49/28 45/2 02-2 65 Heinrich-Trox-Platz e-mail trox@trox.de D-47504 Neukirchen-Vluyn
More informationOpen PRAIRIE: Open Public Research Access Institutional Repository and Information Exchange
South Dakota State University Open PRAIRIE: Open Public Research Access Institutional Repository and Information Exchange Theses and Dissertations 2016 The Effects of Diffuser Exit Velocity and Distance
More informationThermal Comfort. Appendices: A: Dry Heat Loss calculations. file://k:\marketing\homepage\gammel%20homepage\website\books\thermal\therm...
Page 1 of 25 Thermal Comfort This booklet is an introduction to thermal comfort. It explains procedures to evaluate the thermal environment and methods applied for its measurement. Contents What is Thermal
More informationINDIAN INSTITUTE OF TECHNOLOGY ROORKEE NPTEL NPTEL ONLINE CERTIFICATION COURSE. Refrigeration and Air-conditioning. Lecture-37 Thermal Comfort
INDIAN INSTITUTE OF TECHNOLOGY ROORKEE NPTEL NPTEL ONLINE CERTIFICATION COURSE Refrigeration and Air-conditioning Lecture-37 Thermal Comfort with Prof. Ravi Kumar Department of Mechanical and Industrial
More informationSlot diffuser. Type VSD35 2/2.6/B/3. with 35 mm wide slot
2/2.6/B/3 Slot diffuser Type VSD35 with 35 mm wide slot TROX UK Ltd Telephone +44 (0) 1842 754545 Caxton Way Telefax +44 (0) 1842 763051 Thetford e-mail trox@troxuk.co.uk Norfolk IP24 3SQ www.troxuk.co.uk
More informationAir distribution systems. Radial outlet RA-N2...
Air distribution systems Radial outlet RA-N... DS E 0.01 Radial outlet RA-N Preliminary remark KRANTZ KOMPONENTEN radial outlets RA-N have fixed radial vanes and are available with circular or square face.
More informationTHE THERMAL ENVIRONMENT LEVEL ASSESMENT BASED ON HUMAN PERCEPTION
THE THERMAL ENVIRONMENT LEVEL ASSESMENT BASED ON HUMAN PERCEPTION M. V. Jokl Czech Technical University, Czech Republic Corresponding email: miloslav.jokl@fsv.cvut.cz SUMMARY A new way of e ermal level
More informationKrantz Components. Twist outlet DD-N... for ceiling installation. Air distribution systems
Krantz Components Twist outlet DD-N... for ceiling installation Air distribution systems DS E 0. Twist outlet Preliminary remarks and construction design Preliminary remarks Twist outlets for ceiling installation
More informationNumerical simulation of human thermal comfort in indoor environment
Numerical simulation of human thermal comfort in indoor environment TIBERIU SPIRCU 1, IULIA MARIA CÂRSTEA 2, ION CARSTEA 3 1, 2 University of Medicine and Pharmacy "Carol Davila, Bucharest ROMANIA E_mail:spircut@yahoo.com
More informationDetermination of the Acceptable Room Temperature Range for Local Cooling
ICEB6, Shenzhen, China Maximize IAQ, Vol. I-1-4 Determination of the Acceptable Room Temperature Range for Local Cooling Yufeng Zhang Rongyi Zhao Assistant Professor Professor South China University of
More informationLinear ceiling diffuser
L-0--01e Linear ceiling diffuser Type LDD / LDDL Contents Realisation Application Safety instructions Contents Realisation Application Safety instructions Dimensions 3 Dimensions Installation Quick selection
More informationSwirl Diffuser. Type SDW T 2.2/1/B/1. recommended for room heights from approx m
T 2.2/1/B/1 Swirl Diffuser Type SDW recommended for room heights from approx. 2.60... 4.00 m TROX UK Ltd Caxton Way Thetford Norfolk IP24 3SQ Telephone +44(0) 1842 54545 Telefax +44(0) 1842 63051 e-mail
More informationSubjective Thermal Comfort in the Environment with Spot Cooling System
Subjective Thermal Comfort in the Environment with Spot ing System Hayato Ohashi 1, Hitomi Tsutsumi 1, Shin-ichi Tanabe 1, Ken-ichi Kimura 1, Hideaki Murakami 2, Koji Kiyohara 3 1 Department of Architecture,
More informationNozzle diffuser. Dimensions
Nozzle diffuser GTI Dimensions Installation Ød Description GTI is a flexible supply air nozzle that is suitable for ventilation of large areas. The nozzle can be used for both heated and cooled air and
More informationThe diagram below. to the by the. outlet into. calculation. Since TRANSMISSION VIA STRUCTURE. Vibration Via Supports Duct Breakout
NOISE CONTROL IN VENTILATING SYSTEMS INTRODUCTION The diagram below shows the various noise sources and transmission paths of plant rooms and ventilation systems. For the ventilation system this can be
More informationA Numerical Analysis of Indoor Thermal Environment and Human Thermophysiological Responses under Natural Ventilation S. Iizuka 1,*, T. Sakoi 2, T. Sai
A Numerical Analysis of Indoor Thermal Environment and Human Thermophysiological Responses under Natural Ventilation S. Iizuka 1,*, T. Sakoi 2, T. Saito 1, and S. Kuno 1 1 Graduate School of Environmental
More informationGTH. Rectangular double deflection grille QUICK FACTS
Rectangular double deflection grille QUICK FACTS For supply air Adjustable air deflectors Cleanable Installed using mounting frames FHB / FHA or commissioning box TRG Available in alternative colours A
More informationALC. ALBATROSS Supply air terminal for large airflows
ALBATROSS Supply air terminal for large airflows Quick facts Large airflows Suitable for cooling or heating Manual or motorised adjustment Pressure drop independent of selected spread pattern Can be used
More informationDevelopment of a Simplified Cooling Load Design Tool for Underfloor Air Distribution (UFAD) Systems
Development of a Simplified Cooling Load Design Tool for Underfloor Air Distribution (UFAD) Systems Stefano Schiavon, Kwang Ho Lee, Fred Bauman, and Tom Webster Center for the Built Environment University
More informationNumerical Analysis of Comfort and Energy Performance of Radiant Heat Emission Systems
Numerical Analysis of Comfort and Energy Performance of Radiant Heat Emission Systems. Fabian Ochs, Mara Magni, Michele Bianchi Janetti, Dietmar Siegele Unit for Energy Efficient Buildings, UIBK z / [m]....3...9
More informationScienceDirect. Experimental study of influence of movements on airflow under stratum ventilation
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 7 (15 ) 7 11 th International Building Physics Conference, IBPC 15 Experimental study of influence of movements on airflow under
More informationA Discussion of Low Reynolds Number Flow for the Two-Dimensional Benchmark Test Case
A Discussion of Low Reynolds Number Flow for the Two-Dimensional Benchmark Test Case M. Weng, P. V. Nielsen and L. Liu Aalborg University Introduction. The use of CFD in ventilation research has arrived
More informationThermal environment in indoor spaces with under-floor air distribution systems: 2. Determination of design parameters (1522-
Xue, G., Lee, K.S., Jiang, Z., and Chen, Q. 01. Thermal environment inindoor spaces with underfloor air distribution systems:. Determination of design parameters (15 RP), HVAC&R Research, 18(6), 119 101.
More informationCHAPTER 3. The sun and the seasons. Locating the position of the sun
zenith 90 observer summer solstice 75 altitude angles equinox 52 winter solstice 29 Figure 3.1: Solar noon altitude angles for Melbourne SOUTH winter midday shadow WEST summer midday shadow summer EAST
More informationHEAT TRANSFER 1 INTRODUCTION AND BASIC CONCEPTS 5 2 CONDUCTION
HEAT TRANSFER 1 INTRODUCTION AND BASIC CONCEPTS 5 2 CONDUCTION 11 Fourier s Law of Heat Conduction, General Conduction Equation Based on Cartesian Coordinates, Heat Transfer Through a Wall, Composite Wall
More informationCOMFORT IN CLOSED SPACES ACCORDING TO THERMAL COMFORT AND INDOOR AIR QUALITY
PERIODICA POLYTECHNICA SER. MECH. ENG. VOL. 44, NO. 2, PP. 249 264 (2000) COMFORT IN CLOSED SPACES ACCORDING TO THERMAL COMFORT AND INDOOR AIR QUALITY Levente HERCZEG, Tamás HRUSTINSZKY and László KAJTÁR
More informationTHERMODYNAMIC ASSESSMENT OF HUMAN THERMAL ENVIRONMENT INTERACTION
S. Boregowda et al., Int. Journal of Design & Nature. Vol. 2, No. 4 (2007) 310 318 THERMODYNAMIC ASSESSMENT OF HUMAN THERMAL ENVIRONMENT INTERACTION S. BOREGOWDA, R. HANDY & W. HUTZEL Department of Mechanical
More informationEXPERIMENTAL AND SIMULATION TEMPERATURE EVALUATION WHICH DETERMINE THERMAL COMFORT
EXPERIMENTAL AND SIMULATION TEMPERATURE EVALUATION WHICH DETERMINE THERMAL COMFORT ubomír Hargaš, František Drkal, Vladimír Zmrhal Department of Environmental Engineering, Faculty of Mechanical Engineering,
More informationarxiv: v1 [cs.sy] 5 Oct 2017
On the Interaction between Personal Comfort Systems and Centralized HVAC Systems in Office Buildings Rachel Kalaimani, Milan Jain, Srinivasan Keshav, Catherine Rosenberg arxiv:1710.02064v1 [cs.sy] 5 Oct
More informationSWIFT Ceiling. Square ceiling air diffuser for supply air QUICK FACTS
Square ceiling air diffuser for supply air QUICK FACTS Flush design Also available in a version for extract air. Designed for modular suspended ceilings (600 x 600 mm) Quick Access Adapter for systemized
More informationQasim Hammodi Hassan*, Sabah Tarik Ahmed**, Ala'a Abbas Mahdi***
International Journal of Scientific & Engineering Research, Volume 5, Issue 4, April-2014 32 Numerical Simulation of Air Velocity and Temperature Distribution in an Office Room ventilated by Displacement
More informationAssignability of Thermal Comfort Models to nonstandard
Department of Architecture Institute of Building Climatology Assignability of Thermal Comfort Models to nonstandard Occupants P. Freudenberg Dresden, 12.06.2013 Thermal Comfort Models: Motivation Objectives
More informationNew correlations for the standard EN 1264
New correlations for the standard EN 164 Federico Boldrin, Michele De arli, Giacomo Ruaro DFT Dipartimento di Fisica Tecnica, Università degli Studi di Padova, Italy orresponding email: michele.decarli@unipd.it
More informationCDD/CDR. Single cone ceiling diffusers for supply air. Quick facts. Quick guide CDD/CDR A I R F L O W - S O U N D L E V E L
Single cone ceiling diffusers for supply air Quick facts Spread pattern can be shielded Used with commissioning box ALS Cleanable Adjustable slot Perforated diffuser face = CDD Imperforated diffuser face
More informationSlot diffusers. Slot diffusers, Round duct diffusers. Slot diffusers. Slot diffusers LD-13, LD-14
, Round duct diffusers D-, D- Application D- and D- slot diffusers are designed for the supply of air in rooms with floor to ceiling heights of.5 to m for supplying either cold or warm air, in particular
More informationVentilating grilles, Ventilating valves
01 Ventilating grilles Grilles with thermostatic regulation Special grilles Ventilating valves Staircase swirl diffusers SOT DIFFUSERS, ROUND DUCT DIFFUSERS SWIR DIFFUSERS, VARIABE SWIR DIFFUSERS CIRCUAR
More informationDisplacement Flow Diffusers
T 1.3/1/EN/2 Displacement Flow Diffusers Types QLE QLF for low turbulence air supply TROX GmbH Telephone +9/28 /2 02-0 Telefax +9/28 /26 Heinrich-Trox-Platz e-mail trox@trox.de D0 Neukirchen-Vluyn www.troxtechnik.com
More informationKSV. Slot diffusers. Ordering code. Description. Linear diffusers 1 / 16
Linear diffusers 1 / 1 KSV Slot diffusers Ordering code Number of slots Diffuser Length (mm) KSV - 1... - 19 Description KSV is an air terminal element primarily designated for air supply. It is suitable
More informationPELICAN Ceiling. Square ceiling air diffuser for supply air and extract air
Ceiling Square ceiling air diffuser for supply air and extract air Quick facts Flexible distribution pattern, yet the acoustic data remains the same One K-factor regardless of distribution pattern Designed
More informationTHE EVALUATION ON INDOOR THERMAL COMFORT INDEX
03-030 The 2005 World Sustainable Building Conference, THE EVALUATION ON INDOOR THERMAL COMFORT INDEX Xie Yingbai Ph.D Yu Zhun Yang Xianliang Institute of Energy and Power Engineering, North China Electric
More informationSimplified Numerical Models for Complex Air Supply Diffusers Jelena Srebric *, Ph.D.
Srebric, J. and Chen, Q. 2002. Simplified numerical models for complex air supply diffusers, HVAC&R Research, 8(3), 277-294. Simplified Numerical Models for Complex Air Supply Diffusers Jelena Srebric
More informationUse. Worth noting. Key figures. Installation. lindab fasadium
Contact, Overview, Index Guideline heating and cooling Plexus Professor / Professor Plus Premum / Premax / Solus Architect Polaris I & S Plafond Podium Celo Cabinett Capella Carat Atrium / Loggia Regula
More informationSWIFTTM. Ceiling. Square ceiling air diffuser for supply air
SWIFTTM Ceiling SWIFT Ceiling Square ceiling air diffuser for supply air Quick facts Flush design Also available in a version for extract air. Designed for modular suspended ceilings (600 x 600 mm) Quick
More informationMONITORING AND EVALUATION OF A PROTOTYPE BUILDING IN TROPICAL CLIMATE REGARDING THERMAL COMFORT
MASTERARBEIT MONITORING AND EVALUATION OF A PROTOTYPE BUILDING IN TROPICAL CLIMATE REGARDING THERMAL COMFORT ausgeführt zum Zwecke der Erlangung des akademischen Grades eines Diplom-Ingenieurs unter der
More informationThermal Comfort, Weather-Type, and Consumer Behavior: Influences on Visitor Attendance at Four U.S. Metropolitan Zoos
Thermal Comfort, Weather-Type, and Consumer Behavior: Influences on Visitor Attendance at Four U.S. Metropolitan Zoos David R. Perkins Doctoral Candidate, ABD & NSF Graduate Fellow Department of Geography
More informationCDD/CDR. Circular ceiling diffuser for supply air QUICK FACTS
Circular ceiling diffuser for supply air QUICK FACTS Spread pattern can be shielded Used with commissioning box ALS Cleanable Adjustable slot Perforated diffuser face = CDD Non-perforated diffuser face
More informationWorth noting. Introduction. Key figures. lindab architect. Picture 1. Architect Circum, Luna and Prisma.
Contact, Overview, Index Guideline heating and cooling Plexus Professor / Professor Plus Premum / Premax / Solus Architect Polaris I & S Plafond Podium Celo Cabinett Capella Carat Fasadium Atrium / Loggia
More informationAir Flow Modeling in a Mechanically Ventilated Room
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Air Flow Modeling in a Mechanically Ventilated Room T. P. Ashok Babu National
More informationINVESTIGATION OF THE PERFORMANCE OF COOLING PANELS: CEILING AND FLOOR PANElS.
INVESTIGATION OF THE PERFORMANCE OF COOLING PANELS: CEILING AND FLOOR PANElS. * M. Hammad, Al Helo, S. And Khlaif, B. University of Jordan. Mechanical Engineering Department. hammad@ju.edu.jo 1.0 ABSTRACT:
More informationQuantifying Factors Affecting Sidewall Air Inlet Performance
Agricultural and Biosystems Engineering Publications Agricultural and Biosystems Engineering 2000 Quantifying Factors Affecting Sidewall Air Inlet Performance Mark E. Oberreuter APS, Inc. Steven J. Hoff
More informationEUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS. FCP 2008 testing procedures FCP acoustical test method pag. 1
EUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS FCP 2008 testing procedures FCP acoustical test method pag. 1 CONTENTS 1 - PURPOSE... 3 2 - NORMATIVE REFERENCES... 3 3 - DEFINITIONS... 3 3.1
More information