New correlations for the standard EN 1264

Size: px
Start display at page:

Download "New correlations for the standard EN 1264"

Transcription

1 New correlations for the standard EN 164 Federico Boldrin, Michele De arli, Giacomo Ruaro DFT Dipartimento di Fisica Tecnica, Università degli Studi di Padova, Italy orresponding SUMMARY The standard EN 164 is born as technical standard for designing and installing radiant floors for heating purposes. In the last years a revision of the standard took place in order to extend the existing calculation method for determining heat flow output also to other radiant systems (walls and ceilings) and operating conditions (heating and cooling). Nevertheless there are some aspects which have not so far been taken into account, like backward heat flows or how to determine, in cooling conditions, minimum surface temperature and related cooling capacity of the radiant system. In this paper the concepts for correctly consider those aspects are shown and the introduction of correlations and equations which can be integrated in the standard are presented. INTRODUTION The Standard EN 164 [1,, 3, 4] includes a simplified method for sizing radiant floors, by defining pipe spacing, pipe diameter and material type of insulation etc. Although it is a simplified method, its application has some limits, therefore it cannot always be applicable. The existing method has one limit, i.e. the determination of the downward heat flow, which is not directly specified and it is roughly estimated when defining the mass flow rate of the system. The new draft of standard makes possible to size not only radiant floors, but also radiant ceiling and walls, by defining different heat exchange coefficients on the surfaces (Table 1). It is also defined how to calculate the cooling heating capacity in steady state conditions, but it is not clear how to fix by calculations the limits of the cooling capacity, since a minimum surface temperature in cooling conditions has to be set. Table 1. Total heat exchange coefficients [W m - K -1 ] proposed in the draft of the standard heating cooling Wall 8 8 Floor eiling BAKWARDS EAT FLOW EVALUATION When sizing a radiant system, reference to the operative temperature has to be made. (i.e. both the radiant and convective heat exchanges with the surroundings are considered). Once calculated the heat loss due to external surfaces, thermal bridges, and the ventilation load, the heating specific capacity of the radiant system is the ratio between the calculated load and the area of the radiant system. The radiant system can be thought as a heat exchanger, having on

2 one side the water and on the other side a medium with infinite heat capacity (the room). The heating capacity is proportional to (Δϑ ) n, where n can be approximated to 1, since 1,00 < n < 1,05 and where Δϑ is the mean logarithmic temperature: ϑv ϑr ( ) Δϑ = ϑv ϑ1 / ln, (1) ϑr ϑ1 For calculating the heat exchange coefficient in EN 164 a simplified method, based on parameters reported in tables, is proposed, leading to the equation: mi K = B (a i ), () The resulting specific heating capacity of radiant systems is defined by the equation: m 1 (a i ) Δ i i i q = B ϑ, (3) The backwards heat flow can be roughly approximated considering the heat flowing in the adjacent space calculated through the following equation: ( ϑ ) q U w ϑ =, (4) The backwards thermal transmittance U may be calculated as inverse of the one dimension resistance of the whole structure from the conditioned room to the adjacent space R tot (or the inverse U tot -value), once known the upward resistance R 1 (or the inverse U 1 ), which can be calculated via the following equation (q 1 is calculated by equation 3): ( ϑ ) q1 U 1 w ϑ1 =, (5) The thermal transmittance from pipes level to the adjacent room can be calculated as follows: U 1 = R = R tot 1 R 1 1 = U tot 1 U1 1, (6) ASE STUDIES The models used in the analysis are EN164 method, Finite Element Method (FEM) and Finite Difference Method (FDM) for types A and B systems []. FEM can be considered as a reference method, since it allows to model the geometry of a circular pipe; FDM is also a correct method. Usually such models are based on a rectangular mesh and therefore there is the need to correctly model systems containing circular pipes. In heating case the pipe can be approximated by a square having length [6]: and internal resistance l = π r, (7) R = D ln[ r /( r d )]/( π k ), (8) p

3 As detailed methods two commercial software have been used: STRAUSS for FEM and EAT for FDM. The water inside pipes has been considered in turbulent flow (inner convection resistance negligible) and the same water temperature has been used in the different cases. Pipe material is PE-X (k = 0.35 W m -1 K -1 ). Thermal conductivity of the concrete layer where pipes are embedded has been set to 1. W m -1 K -1. The structural slab below the systems is 00 mm thick and two values for the thermal conductivity have been fixed: 0.67 W m -1 K -1 and 1. W m -1 K -1. Type A Simulations have been carried out by considering the data reported in Table 1. For both the conditioned and the adjacent rooms the same temperature (0 ) has been used. Pipes have 0 mm external diameter and mm thick. Pipe distances have been varied from 50 mm to 375 mm. As for the concrete layer and the position of the pipe within it, data can be seen in Table. Two values of floor covering materials have been simulated (0.015 m K W -1 and 0.0 m K W -1 thermal resistance respectively). The insulation layer is 30 mm thick and thermal conductivity is 0.04 W m -1 K -1. Table. Thickness of the concrete layer and position of the pipe within it Thickness of the concrete layer [mm] Position of the pipe above the insulation [mm] Type B Simulations have been carried out by using the same boundary conditions of Type A. Two circular pipes have been considered: 0 mm external diameter ( mm thick) and 10 mm external diameter (1.7 mm thick). Pipes are directly in contact with thermal insulation and distances between pipes have been varied from 50 mm to 450 mm. Three floor covering materials have been simulated (0.015 m K W -1, 0.15 m K W -1 and 0.0 m K W -1 thermal resistances). The concrete layer above pipes is 60 mm. The insulation layer is 30 mm or 40 mm thick and thermal conductivity is 0.04 W m -1 K -1. The additional conductive element above pipes is 0.5 mm thick with 5 W m -1 K -1 thermal conductivity. Two dimensions have been considered: continuous covering (L = T) or 10 mm distance between each device (L = T 0.01 m). RESULTS AND DISUSSION Since simulations have been performed under the same conditions and with fixed temperature, in order to generalize the results reference has to be made in each simulation to the results of the FEM method q ref, thus defining the heat flow ratio Ξ: Type A Ξ = q / q ref, (9) Results for the conditioned room heat flow ratio Ξ 1 and the adjacent room heat flow ratio Ξ are reported in Table 3. As it can be seen, FDM gives the same results as FEM. Existing method is also accurate regarding heat flux from pipes to the conditioned room. The adjacent

4 room heat flow calculated via equation (4) is not accurate and precision decreases as the pipes spacing enlarges (Figure 1). The heat flowing in the adjacent room Ξ is dependent most of all on the covering material R λ,b. Tile covering (0.015 m K W -1 ) and 0 mm wood covering (0.15 m K W -1 ) are the two extreme cases, i.e. for each pipes distance and resistance of covering layer, the value is always between the curves represented in Figure 1. It is therefore possible to consider the pipes spacing and the floor covering resistance as parameters for correcting the values of Ξ through the equation (coefficients are reported in Table 4): q [ λ, B λ, B λ B ] b d f ( ϑ ϑ )( a R T ) + ( c R T ) + ( e R ) =, (10) U w, At the end the proposed equation gives the results reported in the last column of Table 3. The error is slightly higher when pipe distance is great, but the result is on the safety side. Table 3. onditioned room heat flux ratio Ξ 1 and adjacent room heat flux ratio Ξ for Type A Ξ 1 Ξ FDM EN 164 FDM equation (4) equation (10) Mean value St. dev Table 4. oefficients for evaluating the heat flux in the adjacent room to be used in eq. (10) a b c d e f Type B Results for the conditioned room heat flow ratio Ξ 1 and for the adjacent room heat flow ratio Ξ are reported in Table 5. Also in this case FDM gives the same results as FEM. Existing method is accurate regarding heat flux from pipes to the upper room. The heat flow in the adjacent room calculated via equation (4) is not accurate and precision decreases as the pipes spacing enlarges (Figure ). The heat flow ratio Ξ is depending most of all by the pipes spacing T and external diameter D of the pipe, but it does not depend on insulation layer thickness. It is possible to write the following equation for determining the heat flux towards the adjacent room (coefficients are reported in Table 6): q = U [ ] b 3 d f h ( ϑ )( a D T ) + ( c D T ) + ( e D T ) + ( g D ) ϑ, (11) w In this way for each pipes spacing the curve is always between the curves reported in the diagram of Figure. The proposed equation gives the results reported in the last column of Table 5. The error is slightly higher when pipe distance is great, but also heat flow in the conditioned room is not very accurate in these cases.

5 Downward heat flow ratio for Type A R λ,b = 0.15 m K W -1 R λ,b = 0.0 m K W Pipe spacing [mm] Figure 1. Values of Ξ in the case of existing method based on equation (4) for Type A. Downward heat flow ratio for Type B D = 10 mm D = 0 mm Poli. ( ) Poli. ( ) Pipe spacing [mm] Figure. Values of Ξ in the case of existing method based on equation (4) for Type B Table 5. onditioned room heat flux ratio Ξ 1 and adjacent room heat flux ratio Ξ for Type B Ξ 1 Ξ FDM EN 164 FDM equation (4) equation (10) Mean value St. dev

6 Table 6. oefficients for evaluating the adjacent room heat flux to be used in eq. (11) a b c d e f g h MINIMUM TEMPERATURE IN OOLING ONDITION ANALYSIS The existing EN 164 takes into account the heat output from the radiant floor and it fixes a surface temperature which cannot be exceeded. For radiant floor 9 for the occupancy space, 35 for outside area. For radiant ceiling the surface temperature is related to the radiant asymmetry, but it is usually better not to exceed 35. For radiant walls the maximum allowed temperature is related to the risk of burning, i.e. about 40. Maximum surface temperature is the average surface temperature, i.e. the maximum surface temperature above or below the pipe in the section where water temperature is equal to: ϑ = ϑ + Δϑ, (1) w 1 When calculating the thermal output of a radiant floor in cooling conditions, the minimum allowable surface temperature must be taken into account. Such temperature for a radiant floor is 19, while for the other radiant systems the dew point temperature is the reference temperature. It must be underlined that such surface temperature is above the section where the supply water temperature occurs. The question is how to consider in a proper way the minimum temperature, once it is known the maximum output of the radiant system, since the cooling capacity has to be determined in the section where water temperature is equal to: ϑ w = ϑ Δϑ, (13) 1 The idea is to evaluate, for the maximum heating capacity, the average temperature of the surface and determine the difference between such temperature and the maximum surface temperature. Therefore the following equation can be written: Δ ϑ = ϑ ϑ + q / α ), (14) surf,max ( 1 At the same time for the cooling capacity a similar equation can be calculated: ase studies Δϑ = ( ϑi q / α ) ϑ, (15) surf, min Detailed simulations have been carried out for different systems with FDM, since the accuracy of the method has been previously demonstrated. The analysis has been carried out with the reference limit temperatures reported in Table 7. Simulations have been carried out by considering for the heat transfer coefficients the data reported in Table 1. The water inside pipes has been considered in turbulent flow (i.e. convective inner resistance negligible). Pipes have 0 mm external diameter and mm thick. Material is PE-X (k = 0.35 W m -1 K -1 ). Table 7. Surface temperature limits [ ] considered in this work heating ooling Wall Floor eiling 9 19

7 Type A Internal resistance due to water convection in the pipe has been considered negligible Pipe distances have been varied from 50 mm to 300 mm. The concrete layer is 60 mm thick and the position of the pipe within it has been set above insulation layer or in the centre of the concrete layer. Three values of floor covering materials have been simulated: 0 m K W -1, m K W -1 and 0.0 m K W -1 thermal resistance respectively. Thermal conductivity of the concrete layer where pipes are embedded has been set to 1. W m -1 K -1. The insulation layer is 30 mm thick and thermal conductivity is 0.04 W m -1 K -1. The structural slab is 00 mm thick with 0.9 W m -1 K -1 thermal conductivity. Type B In this case pipes are directly in contact with thermal insulation and distances between pipes have been varied from 50 mm to 300 mm. Four floor covering materials have been simulated, having thermal resistances 0 m K W -1, m K W -1, 0.15 m K W -1 and 0.0 m K W -1. The concrete layer above pipes is 70 mm thick and thermal conductivity has been set to 1. W m -1 K -1. The insulation layer is 30 mm thick and thermal conductivity is 0.04 W m -1 K -1. The structural slab is 00 mm thick with 0.67 W m -1 K -1 thermal conductivity. The additional conductive element above pipes is 0.5 mm thick and its thermal conductivity is 5 W m -1 K -1. The dimension of the conductive covering equal to the pipes spacing (L = T). Results and discussion The two temperature differences given by equations (1) and (13) have the same value only when the overall heat transfer coefficient is the same for heating and cooling and if the following condition is valid: ϑ 1 ϑsurf,min = ϑsurf,max ϑ1, (16) Since equation (16) cannot be achieved and the heat transfer coefficients are not always the same for heating and cooling conditions, the error Λ can be calculated as follows: Λ = Δϑ Δ, (17) ϑ Results of Λ for a set of simulations are reported in Figure 3 for type A and in Figure 4 for Type B. The overall thermal resistance from pipes level to conditioned room R tot as well as the pipes spacing are the factors that mostly influence the results. The hypothesis of a linear relationship between Λ and pipes space T leads to the following equation: Λ = a R T + c R, (18) b tot where the coefficients are reported in Table 8 for the different cases. In this case the minimum temperature can be directly calculated, once known the maximum allowable heating output for all configurations of radiant systems: b tot ( q / α Λ ϑ + ϑ ϑ ϑ ) qv α surf,max 1 surf,min + 1 =, (19)

8 where q V means the cooling output in the section of the supply temperature (i.e. in the section where the water enters in the room). Equation (19) can be solved for the different systems, leading to: q V ( q Λ p) = α / α, (0) where p = for a radiant floor, p = 13 for a radiant wall and p = 8 for a radiant ceiling. Once known the heat flow q V, the calculation of the supply water temperature is possible, since K c is known: ϑ = ϑ 1 q / K, (1) V V From the supply water temperature, once fixed the maximum temperature difference between supply and return, it is possible to evaluate the maximum cooling output of the system q TYPE A - ENTRE OF TE ONRETE LAYER T[mm] R λ Rlb = 0 R λ Rlb = 0,015 R λb Rlb = 0, Figure 3. Values of Λ [ ] for Type A (floor) 0.0 TYPE B T[mm] R λb Rb = 0 R λb Rb = R λb Rb = 0.15 R λb Rb = Figure 4. Values of Λ [ ] for Type B (floor)

9 Table 8. oefficients to be used in equation (18) a B c A 30 mm above insulation Floor A 0 mm above insulation B A 30 mm above insulation Wall A 0 mm above insulation B A 30 mm above insulation eiling A 0 mm above insulation B ONLUSIONS When pipes are approximated thorough equations () and (3) the use of FDM leads to no error and the accuracy can be assumed to be the same as FEM. As for hating flow behind the pipes, both for type A and B, correlation for determining the correct values are proposed and seem to be accurate (error less than % in the worst case for type B). Also modification for taking into account minimum temperature of supply water temperature in cooling conditions, starting by the value (calculated or measured) of the maximum allowable heating output, has been proposed and it seems to be accurate enough (on cooling heat flux less than %). SYMBOLS α a i B D d k k p l L m i q ref r R R λ, B T U 1 U Δϑ ϑ V ϑ R ϑ w ϑ 1 ϑ overall heat flow coefficient from surface to space multiplication factors which depend on thermal and geometrical characteristics of the radiant system coefficient characteristic of the radiant system external diameter of the pipe thickness of the pipe thermal conductivity thermal conductivity of the pipe equivalent length of the square approximating the pipe for FDM simulations length of conductive layer above pipes for type B radiant systems exponential factors which depend on thermal and geometrical characteristics of the radiant system reference heat flow from FEM in the considered simulations external radius of the pipe equivalent internal resistance of the pipes for FDM simulations resistance of the covering layer distance between pipes thermal transmittance from pipes level to conditioned space thermal transmittance from pipes level to backwards mean logarithmic temperature supply temperature of the water return temperature of the water mean temperature of the water temperature of conditioned room temperature of backwards room

10 ϑ suf,max maximum average surface temperature ϑ suf,min minimum surface temperature at supply point Δ ϑ difference between surface average and maximum/minimum surface temperature Ξ heat flow ratio Λ error when considering Δϑ in heating and cooling case cooling case heating case REFERENES 1. EN EN Part 1, Floor heating Systems and components. Definitions and symbols.. EN EN Part, Floor heating Systems and components. Determination of the thermal output. 3. EN EN Part 3, Floor heating Systems and components. Dimensioning. 4. EN EN Part 4, Floor heating Systems and components. Installation. 5. ENT130WG pren Part 5, eating and cooling surfaces integrated in floors, ceilings and walls - Determination of heating output and cooling output. 6. Blomberg, T eat A P-program for heat transfer in two dimensions. Manual with brief theory and examples. Lund Group for omputational Building Physics, Sweden.

3D UNSTEADY STATE ANALYSIS OF THERMAL PERFORMANCE OF DIFFERENTLY INSULATED FLOORS IN CONTACT WITH THE GROUND

3D UNSTEADY STATE ANALYSIS OF THERMAL PERFORMANCE OF DIFFERENTLY INSULATED FLOORS IN CONTACT WITH THE GROUND 3D UNSTEADY STATE ANALYSIS OF THERMAL PERFORMANCE OF DIFFERENTLY INSULATED FLOORS IN CONTACT WITH THE GROUND Giovanni Pernigotto, Giacomo Pernigotto, Marco Baratieri 2*, Andrea Gasparella 2 University

More information

INVESTIGATION OF THE PERFORMANCE OF COOLING PANELS: CEILING AND FLOOR PANElS.

INVESTIGATION OF THE PERFORMANCE OF COOLING PANELS: CEILING AND FLOOR PANElS. INVESTIGATION OF THE PERFORMANCE OF COOLING PANELS: CEILING AND FLOOR PANElS. * M. Hammad, Al Helo, S. And Khlaif, B. University of Jordan. Mechanical Engineering Department. hammad@ju.edu.jo 1.0 ABSTRACT:

More information

Energy and Buildings

Energy and Buildings Energy and Buildings 42 (2010) 1753 1758 Contents lists available at ScienceDirect Energy and Buildings journal homepage: www.elsevier.com/locate/enbuild A calculation method for the floor surface temperature

More information

Simulation of Free Convection with Conjugate Heat Transfer

Simulation of Free Convection with Conjugate Heat Transfer Simulation of Free Convection with Conjugate Heat Transfer Hong Xu, Chokri Guetari, Kurt Svihla ANSYS, Inc. Abstract This study focuses on free convective and conjugate heat transfer in a naturally ventilated,

More information

If there is convective heat transfer from outer surface to fluid maintained at T W.

If there is convective heat transfer from outer surface to fluid maintained at T W. Heat Transfer 1. What are the different modes of heat transfer? Explain with examples. 2. State Fourier s Law of heat conduction? Write some of their applications. 3. State the effect of variation of temperature

More information

Documentation of the Solutions to the SFPE Heat Transfer Verification Cases

Documentation of the Solutions to the SFPE Heat Transfer Verification Cases Documentation of the Solutions to the SFPE Heat Transfer Verification Cases Prepared by a Task Group of the SFPE Standards Making Committee on Predicting the Thermal Performance of Fire Resistive Assemblies

More information

Principles of Food and Bioprocess Engineering (FS 231) Exam 2 Part A -- Closed Book (50 points)

Principles of Food and Bioprocess Engineering (FS 231) Exam 2 Part A -- Closed Book (50 points) Principles of Food and Bioprocess Engineering (FS 231) Exam 2 Part A -- Closed Book (50 points) 1. Are the following statements true or false? (20 points) a. Thermal conductivity of a substance is a measure

More information

Prediction of Thermal Comfort and Ventilation Efficiency for Small and Large Enclosures by Combined Simulations

Prediction of Thermal Comfort and Ventilation Efficiency for Small and Large Enclosures by Combined Simulations Institute for Thermodynamics and Building Energy Systems, Dresden University of Technology Prediction of Thermal Comfort and Ventilation Efficiency for Small and Large Enclosures by Combined Simulations

More information

Numerical Analysis of Comfort and Energy Performance of Radiant Heat Emission Systems

Numerical Analysis of Comfort and Energy Performance of Radiant Heat Emission Systems Numerical Analysis of Comfort and Energy Performance of Radiant Heat Emission Systems. Fabian Ochs, Mara Magni, Michele Bianchi Janetti, Dietmar Siegele Unit for Energy Efficient Buildings, UIBK z / [m]....3...9

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at   ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 2176 2183 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

Essay 4. Numerical Solutions of the Equations of Heat Transfer and Fluid Flow

Essay 4. Numerical Solutions of the Equations of Heat Transfer and Fluid Flow Essay 4 Numerical Solutions of the Equations of Heat Transfer and Fluid Flow 4.1 Introduction In Essay 3, it was shown that heat conduction is governed by a partial differential equation. It will also

More information

5. AN INTRODUCTION TO BUILDING PHYSICS

5. AN INTRODUCTION TO BUILDING PHYSICS 5. AN INTRODUCTION TO BUILDING PHYSICS P. Wouters, S. Martin ABSTRACT This chapter places the System Identification Competition in a broader context of evaluating the thermal performances of building components.

More information

EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS

EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS 800 1500 6240 1600 1500 840 Proceedings of BS2015: EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS Nozomi

More information

Real Temperature Distribution on the Surface of Underfloor Heating

Real Temperature Distribution on the Surface of Underfloor Heating Real Temperature Distribution on the Surface of Underfloor Heating Henryk G. Sabiniak *1, Karolina Wiśnik 2 1, 2 Institute of Environmental Engineering and Building Installations, Technical University

More information

Numerical Evaluation of Long-Term Performance of Borehole Heat Exchanger Fields

Numerical Evaluation of Long-Term Performance of Borehole Heat Exchanger Fields Presented at the COMSOL Conference 2009 Milan Numerical Evaluation of Long-Term Performance of Borehole Heat Exchanger Fields A. Priarone *, S. Lazzari, E. Zanchini Dipartimento di Ingegneria Energetica,

More information

Aalborg Universitet. Publication date: Document Version Publisher's PDF, also known as Version of record

Aalborg Universitet. Publication date: Document Version Publisher's PDF, also known as Version of record Aalborg Universitet Experimental Investigation of the Influence of Different Flooring Emissivity on Night- Time Cooling using Displacement Ventilation Dreau, Jerome Le; Karlsen, Line Røseth; Litewnicki,

More information

HEAT TRANSFER CAPABILITY OF A THERMOSYPHON HEAT TRANSPORT DEVICE WITH EXPERIMENTAL AND CFD STUDIES

HEAT TRANSFER CAPABILITY OF A THERMOSYPHON HEAT TRANSPORT DEVICE WITH EXPERIMENTAL AND CFD STUDIES HEAT TRANSFER CAPABILITY OF A THERMOSYPHON HEAT TRANSPORT DEVICE WITH EXPERIMENTAL AND CFD STUDIES B.M. Lingade a*, Elizabeth Raju b, A Borgohain a, N.K. Maheshwari a, P.K.Vijayan a a Reactor Engineering

More information

ISO INTERNATIONAL STANDARD. Thermal bridges in building construction Linear thermal transmittance Simplified methods and default values

ISO INTERNATIONAL STANDARD. Thermal bridges in building construction Linear thermal transmittance Simplified methods and default values INTERNATIONAL STANDARD ISO 14683 First edition 1999-06-15 Thermal bridges in building construction Linear thermal transmittance Simplified methods and default values Points thermiques dans les bâtiments

More information

Building heat system sizing

Building heat system sizing May 6th, 203 MVK60 Heat and Mass Transfer Project report Building heat system sizing Arnaud BELTOISE Dept. of Energy Sciences, Faculty of Engineering, Lund University, Box 8, 2200 Lund, Sweden . Introduction

More information

THERMAL DYNAMIC BEHAVIOR OF SINGLE COMPONENT: EXPERIMENTAL ANALYSIS AND NUMERICAL MODELING

THERMAL DYNAMIC BEHAVIOR OF SINGLE COMPONENT: EXPERIMENTAL ANALYSIS AND NUMERICAL MODELING U.P.B. Sci. Bull., Series C, Vol. 74, Iss. 1, 2012 ISSN 1454-234x THERMAL DYNAMIC BEHAVIOR OF SINGLE COMPONENT: EXPERIMENTAL ANALYSIS AND NUMERICAL MODELING Paolo BAGGIO 1, Alessandro PRADA 2 In the present

More information

Field evaluation of the performance of a radiant heating/cooling ceiling panel system

Field evaluation of the performance of a radiant heating/cooling ceiling panel system Proceedings of 8 th Windsor Conference: Counting the Cost of Comfort in a changing world Cumberland Lodge, Windsor, UK, 1-13 April 214. London: Network for Comfort and Energy Use in Buildings, http://nceub.org.uk

More information

Thermally activated wall system with latent heat thermal energy storage comparison of 1D and 3D model

Thermally activated wall system with latent heat thermal energy storage comparison of 1D and 3D model Thermally activated wall system with latent heat thermal energy storage comparison of 1D and 3D model Pavel Charvat 1, Lubomir Klimes 1,2, Milan Ostry 2 1 Faculty of Mechanical Engineering, Brno University

More information

Project #1 Internal flow with thermal convection

Project #1 Internal flow with thermal convection Project #1 Internal flow with thermal convection MAE 494/598, Fall 2017, Project 1 (20 points) Hard copy of report is due at the start of class on the due date. The rules on collaboration will be released

More information

Computer Evaluation of Results by Room Thermal Stability Testing

Computer Evaluation of Results by Room Thermal Stability Testing Computer Evaluation of Results by Room Thermal Stability Testing HANA CHARVÁTOVÁ 1, MARTIN ZÁLEŠÁK 1 Regional Research Centre CEBIA-Tech, Department of Automation and Control Engineering Faculty of Applied

More information

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at  ScienceDirect. Energy Procedia 78 (2015 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 3222 3227 6th International Building Physics Conference, IBPC 2015 Calibration procedures for multidimensional heat transfer

More information

arxiv: v1 [physics.app-ph] 25 Mar 2018

arxiv: v1 [physics.app-ph] 25 Mar 2018 Improvement of heat exchanger efficiency by using hydraulic and thermal entrance regions arxiv:1803.09255v1 [physics.app-ph] 25 Mar 2018 Abstract Alexey Andrianov a, Alexander Ustinov a, Dmitry Loginov

More information

Air distribution systems. Linear whirl outlet WL...

Air distribution systems. Linear whirl outlet WL... Air distribution systems Linear whirl outlet WL... DS 0 E 1.013 Preliminary remarks Mode of operation The linear whirl outlet generates turbulent mixing ventilation. It can be installed on or in a wall

More information

Viscous dissipation and temperature dependent shear thinning rheology

Viscous dissipation and temperature dependent shear thinning rheology Viscous dissipation and temperature dependent shear thinning rheology M. Filippucci 1, A. Tallarico 1, M. Dragoni 2 1 Dipartimento di Scienze della Terra e Geoambientali, Università degli Studi di Bari

More information

NUMERICAL ANALYSIS OF HEAT STORAGE AND HEAT CONDUCTIVITY IN THE CONCRETE HOLLOW CORE DECK ELEMENT

NUMERICAL ANALYSIS OF HEAT STORAGE AND HEAT CONDUCTIVITY IN THE CONCRETE HOLLOW CORE DECK ELEMENT NUMERICAL ANALYSIS OF HEAT STORAGE AND HEAT CONDUCTIVITY IN THE CONCRETE HOLLOW CORE DECK ELEMENT Michal Pomianowski 1, Per Heiselberg 1, Rasmus Lund Jensen 1, and Hicham Johra 1 1 Aalborg University,

More information

Environmental Engineering. Family of heating appliances

Environmental Engineering. Family of heating appliances Fakulta strojní Ústav techniky prostředí Family of heating appliances Ing. Ondrej Hojer, Ph.D. Table of contents: A) Design of Floor heating B) Design of a safety valve and an expansion vessel C) Introduction

More information

This paper has been downloaded from the Building and Environmental Thermal Systems Research Group at Oklahoma State University (www.hvac.okstate.

This paper has been downloaded from the Building and Environmental Thermal Systems Research Group at Oklahoma State University (www.hvac.okstate. This paper has been downloaded from the Building and Environmental Thermal Systems Research Group at Oklahoma State University (www.hvac.okstate.edu) The correct citation for the paper is: Spitler, J.D.,

More information

Simplifying a model of short subsequent sections containing a common detailed cross-section.

Simplifying a model of short subsequent sections containing a common detailed cross-section. Excerpt from the Proceedings of the COMSOL Conference 010 Paris Simplifying a model of short subsequent sections containing a common detailed cross-section. J. Krah Aker Solutions Snar yveien 36, 1364

More information

TREES Training for Renovated Energy Efficient Social housing

TREES Training for Renovated Energy Efficient Social housing TREES Training for Renovated Energy Efficient Social housing Intelligent Energy -Europe programme, contract n EIE/05/110/SI2.420021 Section 2 Tools 2.1 Simplified heating load calculation Tamas CSOKNYAI

More information

1. Nusselt number and Biot number are computed in a similar manner (=hd/k). What are the differences between them? When and why are each of them used?

1. Nusselt number and Biot number are computed in a similar manner (=hd/k). What are the differences between them? When and why are each of them used? 1. Nusselt number and Biot number are computed in a similar manner (=hd/k). What are the differences between them? When and why are each of them used?. During unsteady state heat transfer, can the temperature

More information

EE-489 Modeling Project: Behavior of the. Temperature Changes in a Room

EE-489 Modeling Project: Behavior of the. Temperature Changes in a Room EE-489 Modeling Project: Behavior of the 1 Temperature Changes in a Room Younes Sangsefidi, Saleh Ziaieinejad, Tarik Wahidi, and Takouda Pidename, Abstract A precise heat flow model, which predicts the

More information

a. Fourier s law pertains to conductive heat transfer. A one-dimensional form of this law is below. Units are given in brackets.

a. Fourier s law pertains to conductive heat transfer. A one-dimensional form of this law is below. Units are given in brackets. QUESTION An understanding of the basic laws governing heat transfer is imperative to everything you will learn this semester. Write the equation for and explain the following laws governing the three basic

More information

Thermal Unit Operation (ChEg3113)

Thermal Unit Operation (ChEg3113) Thermal Unit Operation (ChEg3113) Lecture 3- Examples on problems having different heat transfer modes Instructor: Mr. Tedla Yeshitila (M.Sc.) Today Review Examples Multimode heat transfer Heat exchanger

More information

Building physics. Reinforced concrete/reinforced concrete. Steel/reinforced concrete. Timber/reinforced concrete. Steel/steel.

Building physics. Reinforced concrete/reinforced concrete. Steel/reinforced concrete. Timber/reinforced concrete. Steel/steel. Building physics Building physics Reinforced concrete/reinforced concrete Steel/reinforced concrete Timber/reinforced concrete Steel/steel 1 Thermal bridges Definition of thermal bridges Thermal bridges

More information

Long-Term Performance of Borehole Heat Exchanger Fields with Groundwater Movement

Long-Term Performance of Borehole Heat Exchanger Fields with Groundwater Movement Excerpt from the Proceedings of the COMSOL Conference 2 Paris Long-Term Performance of Borehole Heat Exchanger Fields with Groundwater Movement S. Lazzari *,1, A. Priarone 2 and E. Zanchini 1 1 Dipartimento

More information

Principles of Food and Bioprocess Engineering (FS 231) Problems on Heat Transfer

Principles of Food and Bioprocess Engineering (FS 231) Problems on Heat Transfer Principles of Food and Bioprocess Engineering (FS 1) Problems on Heat Transfer 1. What is the thermal conductivity of a material 8 cm thick if the temperature at one end of the product is 0 C and the temperature

More information

Air Diffusion Designing for Comfort

Air Diffusion Designing for Comfort Air Diffusion Designing for Comfort Occupant Comfort Air Diffusion Selection ADPI Air Diffusion Performance index Ventilation Effectiveness Induction Room Space Induction Design Criteria ISO7730 ASHRAE

More information

RESEARCH OF COMPOSITE CONSTRUCTIONS IMPACT ON THE ENERGY EFFICIENCY OF BUILDINGS

RESEARCH OF COMPOSITE CONSTRUCTIONS IMPACT ON THE ENERGY EFFICIENCY OF BUILDINGS University of Latvia, Faculty of Physics and Mathematics Laboratory for Mathematical Modelling of Environmental and Technological Processes RESEARCH OF COMPOSITE CONSTRUCTIONS IMPACT ON THE ENERGY EFFICIENCY

More information

PART 2 THERMAL RESPONSE. DIF SEK Part 2: Thermal Response 0/ 44

PART 2 THERMAL RESPONSE. DIF SEK Part 2: Thermal Response 0/ 44 DIF SEK PART 2 THERMAL RESPONSE DIF SEK Part 2: Thermal Response 0/ 44 Resistance to fire - Chain of events Θ Loads 1: Ignition Steel columns time 2: Thermal action 3: Mechanical actions R 4: Thermal response

More information

Ceiling Radiant Cooling Panels Employing Heat-Conducting Rails: Deriving the Governing Heat Transfer Equations

Ceiling Radiant Cooling Panels Employing Heat-Conducting Rails: Deriving the Governing Heat Transfer Equations Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.

More information

EFFECT OF DISTRIBUTION OF VOLUMETRIC HEAT GENERATION ON MODERATOR TEMPERATURE DISTRIBUTION

EFFECT OF DISTRIBUTION OF VOLUMETRIC HEAT GENERATION ON MODERATOR TEMPERATURE DISTRIBUTION EFFECT OF DISTRIBUTION OF VOLUMETRIC HEAT GENERATION ON MODERATOR TEMPERATURE DISTRIBUTION A. K. Kansal, P. Suryanarayana, N. K. Maheshwari Reactor Engineering Division, Bhabha Atomic Research Centre,

More information

Air distribution systems. Adjustable radial outlet RA-V...

Air distribution systems. Adjustable radial outlet RA-V... Air distribution systems Adjustable radial outlet RA-V... DS E 0.2013 Construction design Preliminary remarks KRANTZ KOMPONENTEN has developed its wellknown, successful radial outlet into an adjustable

More information

PROBLEM Node 5: ( ) ( ) ( ) ( )

PROBLEM Node 5: ( ) ( ) ( ) ( ) PROBLEM 4.78 KNOWN: Nodal network and boundary conditions for a water-cooled cold plate. FIND: (a) Steady-state temperature distribution for prescribed conditions, (b) Means by which operation may be extended

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 0077-2 First edition 2003-0-0 Thermal performance of windows, doors and shutters Calculation of thermal transmittance Part 2: Numerical method for frames Performance thermique

More information

EXPERIMENTAL ANALYSIS OF AIR-CONDITIONING IN HOSPITAL ROOMS BY MEANS OF LIGHT RADIANT CEILINGS

EXPERIMENTAL ANALYSIS OF AIR-CONDITIONING IN HOSPITAL ROOMS BY MEANS OF LIGHT RADIANT CEILINGS EXPERIMENTAL ANALYSIS OF AIR-CONDITIONING IN HOSPITAL ROOMS BY MEANS OF LIGHT RADIANT CEILINGS Renato M. Lazzarin renato@gest.unipd.it Francesco Castellotti caste@gest.unipd.it Filippo Busato busato@gest.unipd.it

More information

Review: Conduction. Breaking News

Review: Conduction. Breaking News CH EN 3453 Heat Transfer Review: Conduction Breaking News No more homework (yay!) Final project reports due today by 8:00 PM Email PDF version to report@chen3453.com Review grading rubric on Project page

More information

Heat-Accumulation Stoves: Numerical Simulations of Two Twisted Conduit Configurations

Heat-Accumulation Stoves: Numerical Simulations of Two Twisted Conduit Configurations Heat-Accumulation Stoves: Numerical Simulations of Two Twisted Conduit Configurations *Scotton P., *Rossi D., **Barberi M., **De Toni S. *University of Padova, Department of Geosciences ** Barberi Srl,

More information

MECHANISM BEHIND FREE /NATURAL CONVECTION

MECHANISM BEHIND FREE /NATURAL CONVECTION CONVECTIVE HEAT TRANSFER By: Prof K. M. Joshi, Assi. Professor, MED, SSAS Institute of Technology, Surat. MECHANISM BEHIND FREE /NATURAL CONVECTION The stagnate layer of fluid in immediate vicinity of

More information

Capacitors And Dielectrics

Capacitors And Dielectrics 1 In this small e-book we ll learn about capacitors and dielectrics in short and then we ll have some questions discussed along with their solutions. I ll also give you a practices test series which you

More information

ELEC9712 High Voltage Systems. 1.2 Heat transfer from electrical equipment

ELEC9712 High Voltage Systems. 1.2 Heat transfer from electrical equipment ELEC9712 High Voltage Systems 1.2 Heat transfer from electrical equipment The basic equation governing heat transfer in an item of electrical equipment is the following incremental balance equation, with

More information

ISO INTERNATIONAL STANDARD. Thermal insulation for building equipment and industrial installations Calculation rules

ISO INTERNATIONAL STANDARD. Thermal insulation for building equipment and industrial installations Calculation rules INTERNATIONAL STANDARD ISO 12241 Second edition 2008-06-15 Thermal insulation for building equipment and industrial installations Calculation rules Isolation thermique des équipements de bâtiments et des

More information

Study on Thermal Load Calculation for Ceiling Radiant Cooling Panel System

Study on Thermal Load Calculation for Ceiling Radiant Cooling Panel System Study on Thermal Load Calculation for Ceiling Radiant Cooling Panel System Sei Ito, Yasunori Akashi, Jongyeon Lim Shimizu Corporation, Tokyo, Japan University of Tokyo, Tokyo, Japan Abstract The ceiling

More information

NATURAL CONVECTION OF AIR IN TILTED SQUARE CAVITIES WITH DIFFERENTIALLY HEATED OPPOSITE WALLS

NATURAL CONVECTION OF AIR IN TILTED SQUARE CAVITIES WITH DIFFERENTIALLY HEATED OPPOSITE WALLS Proceedings of the International onference on Mechanical Engineering 0 (IME0 8-0 December 0, Dhaka, Bangladesh IME- NATURAL ONVETION OF AIR IN TILTED SQUARE AVITIES WIT DIFFERENTIALLY EATED OPPOSITE WALLS

More information

ENERGY DISTRIBUTION ANALYSIS IN A LOW HEAD FRANCIS TURBINE DURING THERMODYNAMIC EFFICIENCY MEASUREMENTS

ENERGY DISTRIBUTION ANALYSIS IN A LOW HEAD FRANCIS TURBINE DURING THERMODYNAMIC EFFICIENCY MEASUREMENTS ENERGY DISTRIBUTION ANALYSIS IN A LOW HEAD FRANCIS TURBINE DURING THERMODYNAMIC EFFICIENCY MEASUREMENTS Gianalberto Grego, Fabio F. Muciaccia W.E.S.T. Srl, Milan, Italy west-hydro@libero.it ABSTRACT The

More information

Energy flows and modelling approaches

Energy flows and modelling approaches Energy flows and modelling approaches Energy flows in buildings external convection infiltration & ventilation diffuse solar external long-wave radiation to sky and ground local generation fabric heat

More information

Ceiling mounted radiant panels calculations of heat output in heating and cooling application

Ceiling mounted radiant panels calculations of heat output in heating and cooling application Ceiling mounted radiant panels calculations of heat output in heating and cooling application Lawrence Drojetzki 1,*, and Janusz Wojtkowiak 1 1 Poznan University of Technology, Institute of Environmental

More information

HEAT TRANSFER AND FLOW CHARACTERISTICS OF A BACKWARD-FACING STEP FLOW WITH MIST

HEAT TRANSFER AND FLOW CHARACTERISTICS OF A BACKWARD-FACING STEP FLOW WITH MIST Paper No. IMPRES13-119 HEAT TRANSFER AND FLOW CHARACTERISTICS OF A BACKWARD-FACING STEP FLOW WITH MIST Masaki HIGA 1,*, Izuru SENAHA, Yoshitaka MIYAFUJI 3, Sumio KATO and Shoichi MATSUDA 1 Graduate School

More information

Building Envelope Requirements Overview Page 3-4

Building Envelope Requirements Overview Page 3-4 Building Envelope Requirements Overview Page 3-4 The benefit of a high reflectance surface is obvious: while dark surfaces absorb the sun s energy (visible light, invisible infrared. and ultraviolet radiation)

More information

DEFINING THE PERFORMANCE OF THE DOUBLE SKIN FAÇADE WITH THE USE OF THE SIMULATION MODEL

DEFINING THE PERFORMANCE OF THE DOUBLE SKIN FAÇADE WITH THE USE OF THE SIMULATION MODEL Eighth International IBPSA Conference Eindhoven, Netherlands August -4, 003 DEFINING THE PERFORMANCE OF THE DOUBLE SKIN FAÇADE WITH THE USE OF THE SIMULATION MODEL Wojtek Stec & Dolf van Paassen Energy

More information

Transactions on Engineering Sciences vol 18, 1998 WIT Press, ISSN

Transactions on Engineering Sciences vol 18, 1998 WIT Press,   ISSN Mixed convection in a horizontal circular channel in high pressure conditions A. Maj, W. Nowak, A. Stachel Technical University of Szczecin, department of Heat Engineering, al Piastow 19, 70-310 Szczecin,

More information

A Numerical Investigation on Active Chilled Beams for Indoor Air Conditioning

A Numerical Investigation on Active Chilled Beams for Indoor Air Conditioning Excerpt from the Proceedings of the COMSOL Conference 2008 Hannover A Numerical Investigation on Active Chilled Beams for Indoor Air Conditioning Cammarata G., Petrone G. * Department of Industrial and

More information

Analytical Studies of the Influence of Regional Groundwater Flow by on the Performance of Borehole Heat Exchangers

Analytical Studies of the Influence of Regional Groundwater Flow by on the Performance of Borehole Heat Exchangers Analytical Studies of the Influence of Regional Groundwater Flow by on the Performance of Borehole Heat Exchangers Claesson, Johan; Hellström, Göran Published in: [Host publication title missing] Published:

More information

I, THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD

I, THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD Krishna Dwivedi*, Kulwant Dhankar**, Smita Ganjare*** & Hemant More**** Assistant Professor, Mechanical Department, LTCOE, Navi Mumbai, Maharashtra Abstract:

More information

Iterative calculation of the heat transfer coefficient

Iterative calculation of the heat transfer coefficient Iterative calculation of the heat transfer coefficient D.Roncati Progettazione Ottica Roncati, Ferrara - Italy Aim The plate temperature of a cooling heat sink is an important parameter that has to be

More information

Freezing Around a Pipe with Flowing Water

Freezing Around a Pipe with Flowing Water 1 Introduction Freezing Around a Pipe with Flowing Water Groundwater flow can have a significant effect on ground freezing because heat flow via convection is often more effective at moving heat than conduction

More information

ELECO'2001. Paper Submission Form

ELECO'2001. Paper Submission Form ELECO'2001 Paper Submission Form Name of Presenting Author... Cuneyt OYSU Address... Kocaeli Üniversitesi Mekatronik Mühendisliği Bölümü Veziroğlu Kampüsü 41040 İzmit/Kocaeli Phone (262) 5282467 (532)

More information

PART 5-1: Compartment fire

PART 5-1: Compartment fire PART 5-1: Compartment fire P. Schaumann T. Trautmann University of Hannover Germany J. Žižka Czech Technical University in Prague Czech Republic 1 TASK The gas temperature of a fully engulfed fire in an

More information

Overall Heat Transfer Coefficient

Overall Heat Transfer Coefficient Overall Heat Transfer Coefficient A heat exchanger typically involves two flowing fluids separated by a solid wall. Heat is first transferred from the hot fluid to the wall by convection, through the wall

More information

A fire resistance assessment case history G.C. and M.E. Giuliani

A fire resistance assessment case history G.C. and M.E. Giuliani A fire resistance assessment case history G.C. and M.E. Giuliani In general A structure subjected to fire must be safe for the time necessary for the escape of the people and for the safe operation of

More information

HEAT EXCHANGER. Objectives

HEAT EXCHANGER. Objectives HEAT EXCHANGER Heat exchange is an important unit operation that contributes to efficiency and safety of many processes. In this project you will evaluate performance of three different types of heat exchangers

More information

q x = k T 1 T 2 Q = k T 1 T / 12

q x = k T 1 T 2 Q = k T 1 T / 12 Conductive oss through a Window Pane q T T 1 Examine the simple one-dimensional conduction problem as heat flow through a windowpane. The window glass thickness,, is 1/8 in. If this is the only window

More information

Chapter 7. Three Dimensional Modelling of Buoyancy-Driven Displacement Ventilation: Point Source

Chapter 7. Three Dimensional Modelling of Buoyancy-Driven Displacement Ventilation: Point Source Chapter 7 Three Dimensional Modelling of Buoyancy-Driven Displacement Ventilation: Point Source 135 7. Three Dimensional Modelling of Buoyancy- Driven Displacement Ventilation: Point Source 7.1 Preamble

More information

ROOM AVERAGE VELOCITY EQUATION A TOOL TO IMPROVE DESIGN OF THERMAL COMFORT CONDITIONS

ROOM AVERAGE VELOCITY EQUATION A TOOL TO IMPROVE DESIGN OF THERMAL COMFORT CONDITIONS ROOM AVERAGE VELOCITY EQUATION A TOOL TO IMPROVE DESIGN OF THERMAL COMFORT CONDITIONS K Hagström *, O Hakkola and T Moilanen Halton Solutions, Kausala, Finland ABSTRACT For a long time PPD index defined

More information

Radiant Heating Panel Thermal Analysis. Prepared by Tim Fleury Harvard Thermal, Inc. October 7, 2003

Radiant Heating Panel Thermal Analysis. Prepared by Tim Fleury Harvard Thermal, Inc. October 7, 2003 Radiant Heating Panel Thermal Analysis Prepared by Tim Fleury Harvard Thermal, Inc. October 7, 2003 Analysis Objective Perform a thermal test on a small sample of the concrete to determine the Thermal

More information

Modelling and Experimental Validation Possibilities of Heat Transfer Room Model

Modelling and Experimental Validation Possibilities of Heat Transfer Room Model Excerpt from the Proceedings of the COMSOL Conference 2010 Paris Modelling and Experimental Validation Possibilities of Heat Transfer Room Model Author M. Zalesak 1, Author V. Gerlich *,1 1 Author Tomas

More information

1 Conduction Heat Transfer

1 Conduction Heat Transfer Eng690 - Formula Sheet 2 Conduction Heat Transfer. Cartesian Co-ordinates q x xa x A x dt dx R th A 2 T x 2 + 2 T y 2 + 2 T z 2 + q T T x) plane wall of thicness 2, x 0 at centerline, T s, at x, T s,2

More information

Aeroacoustic simulation of automotive ventilation outlets

Aeroacoustic simulation of automotive ventilation outlets Aeroacoustic simulation of automotive ventilation outlets J.-L. Adam a, D. Ricot a, F. Dubief a and C. Guy b a Renault SAS, 1 avenue du golf, 78288 Guyancourt, France b Ligeron, Les Algorithmes Bâtiment

More information

Calculating equation coefficients

Calculating equation coefficients Fluid flow Calculating equation coefficients Construction Conservation Equation Surface Conservation Equation Fluid Conservation Equation needs flow estimation needs radiation and convection estimation

More information

Study on the improved recuperator design used in the direct helium-turbine power conversion cycle of HTR-10

Study on the improved recuperator design used in the direct helium-turbine power conversion cycle of HTR-10 Study on the improved recuperator design used in the direct helium-turbine power conversion cycle of HTR-10 Wu Xinxin 1), Xu Zhao ) 1) Professor, INET, Tsinghua University, Beijing, P.R.China (xinxin@mail.tsinghua.edu.cn)

More information

Calculating the heat transfer coefficient of frame profiles with internal cavities

Calculating the heat transfer coefficient of frame profiles with internal cavities Calculating the heat transfer coefficient of frame profiles with internal cavities SUBMITTED: December 2001 REVISED: January 2004 PUBLISHED: March 2004 Peter A. Noyé, M.Sc (Eng) Department of Civil Engineering,

More information

Laminar flow heat transfer studies in a twisted square duct for constant wall heat flux boundary condition

Laminar flow heat transfer studies in a twisted square duct for constant wall heat flux boundary condition Sādhanā Vol. 40, Part 2, April 2015, pp. 467 485. c Indian Academy of Sciences Laminar flow heat transfer studies in a twisted square duct for constant wall heat flux boundary condition RAMBIR BHADOURIYA,

More information

cavity was considered as a regular and uniform layer, thus thermal behaviors within the hollow core concrete element as presented in Figure 1 could no

cavity was considered as a regular and uniform layer, thus thermal behaviors within the hollow core concrete element as presented in Figure 1 could no A Simplified Method for Stationary Heat Transfer of a Hollow Core Concrete Slab Used for TABS T. Yu 1,*, P. Heiselberg 2, B. Lei 1, M. Pomianowski 2 1 School of Mechanical Engineering, Southwest Jiaotong

More information

ME 331 Homework Assignment #6

ME 331 Homework Assignment #6 ME 33 Homework Assignment #6 Problem Statement: ater at 30 o C flows through a long.85 cm diameter tube at a mass flow rate of 0.020 kg/s. Find: The mean velocity (u m ), maximum velocity (u MAX ), and

More information

Air distribution systems. Radial outlet RA-N2...

Air distribution systems. Radial outlet RA-N2... Air distribution systems Radial outlet RA-N... DS E 0.01 Radial outlet RA-N Preliminary remark KRANTZ KOMPONENTEN radial outlets RA-N have fixed radial vanes and are available with circular or square face.

More information

Thermal and dynamical characterization of the plume above a cylindrical heat source

Thermal and dynamical characterization of the plume above a cylindrical heat source Thermal and dynamical characterization of the plume above a cylindrical heat source J.R. Fontaine, J. Blaise, INRS, France P. Hynynen, FIOH, Finland R. Devienne, LEMTA, France Introduction Numerous industrial

More information

Thermo-Fluid Dynamics of Flue Gas in Heat Accumulation Stoves: Study Cases

Thermo-Fluid Dynamics of Flue Gas in Heat Accumulation Stoves: Study Cases Thermo-Fluid Dynamics of Flue Gas in Heat Accumulation Stoves: Study Cases Scotton P. Rossi D. University of Padova, Department of Geosciences Excerpt from the Proceedings of the 2012 COMSOL Conference

More information

The Electrodynamics of a Pair of PV Modules with Connected Building Resistance

The Electrodynamics of a Pair of PV Modules with Connected Building Resistance Proc. of the 3rd IASME/WSEAS Int. Conf. on Energy, Environment, Ecosystems and Sustainable Development, Agios Nikolaos, Greece, July 24-26, 2007 563 he Electrodynamics of a Pair of s with Connected Building

More information

Mathematical Modelling of Ceramic Block Heat Transfer Properties

Mathematical Modelling of Ceramic Block Heat Transfer Properties Proceedings of the 3 RD INTERNATIONAL CONFERENCE ADVANCED CONSTRUCTION 18-19 October, 2012, Kaunas, Lithuania Kaunas University of Technology, Faculty of Civil Engineering and Architecture Studentu st.

More information

Response function method

Response function method Response function method Response function method An analytical approach to the solution of ordinary and partial differential equations using the Laplace transform: An equation in the time domain is transformed

More information

THERMAL PROPERTIES OF THERMOBLOCK 9LB25-O

THERMAL PROPERTIES OF THERMOBLOCK 9LB25-O SCHOOL OF MINING AND METALLURGICAL ENG. LABORATORY OF METALLURGY Technical Report ΤΕ 07/2018 THERMAL PROPERTIES OF THERMOBLOCK 9LB25-O : MAY 2018 Table of Contents 1. INTRODUCTION...3 2. METHODOLOGY...3

More information

HEAT AND MASS TRANSFER. List of Experiments:

HEAT AND MASS TRANSFER. List of Experiments: HEAT AND MASS TRANSFER List of Experiments: Conduction Heat Transfer Unit 1. Investigation of Fourier Law for linear conduction of heat along a simple bar. 2. Study the conduction of heat along a composite

More information

COVENANT UNIVERSITY NIGERIA TUTORIAL KIT OMEGA SEMESTER PROGRAMME: MECHANICAL ENGINEERING

COVENANT UNIVERSITY NIGERIA TUTORIAL KIT OMEGA SEMESTER PROGRAMME: MECHANICAL ENGINEERING COVENANT UNIVERSITY NIGERIA TUTORIAL KIT OMEGA SEMESTER PROGRAMME: MECHANICAL ENGINEERING COURSE: MCE 524 DISCLAIMER The contents of this document are intended for practice and leaning purposes at the

More information

Study of air curtains used to restrict infiltration into refrigerated rooms

Study of air curtains used to restrict infiltration into refrigerated rooms Study of air curtains used to restrict infiltration into refrigerated rooms Gregory Verhaeghe 1, Marnix Van Belleghem 1, Arnout Willockx 1, Ivan Verhaert 1, Michel De Paepe 1 1 Ghent University, Department

More information

STUDY OF A PASSIVE SOLAR WINTER HEATING SYSTEM BASED ON TROMBE WALL

STUDY OF A PASSIVE SOLAR WINTER HEATING SYSTEM BASED ON TROMBE WALL STUDY OF A PASSIVE SOLAR WINTER HEATING SYSTEM BASED ON TROMBE WALL Dr. G.S.V.L.Narasimham Chief Research Scientist, RAC, Dept. of Mechanical Engineering, Indian Institute of Science,Bengaluru- 560012,

More information

1 Conduction Heat Transfer

1 Conduction Heat Transfer Eng6901 - Formula Sheet 3 (December 1, 2015) 1 1 Conduction Heat Transfer 1.1 Cartesian Co-ordinates q x = q xa x = ka x dt dx R th = L ka 2 T x 2 + 2 T y 2 + 2 T z 2 + q k = 1 T α t T (x) plane wall of

More information

TRANSPARENT INNOVATIVE MATERIALS: ENERGETIC AND LIGHTING PERFORMANCES EVALUATION

TRANSPARENT INNOVATIVE MATERIALS: ENERGETIC AND LIGHTING PERFORMANCES EVALUATION TRANSPARENT INNOVATIVE MATERIALS: ENERGETIC AND LIGHTING PERFORMANCES EVALUATION C. Buratti, E. Moretti Department of Industrial Engineering, Perugia University Via G. Duranti, 67-06125 Perugia, Italy.

More information