TEC22x6(H)-2 Series LONWORKS Network Thermostats with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control

Size: px
Start display at page:

Download "TEC22x6(H)-2 Series LONWORKS Network Thermostats with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control"

Transcription

1 TEC22x6(H)-2 Series LONWORKS Network Thermostats with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control Technical Bulletin Code No. LIT-2075 Issued August 25, 2006 Supersedes May 25, 2006 Network Variables (NVs) and Configuration Properties (CPs) List Network Variable Inputs (NVIs) Using the nviheatcool, nviauxheatenable, and SeqOpera Variables nviremlockout Command Table Network Variable Outputs (NVOs) Configuration Network Variables Commissioning the Thermostat Using a LONWORKS Network Configuration Tool... 8 Understanding LONWORKS Network Configuration Tools Differences Changing the Thermostat s Settings Using a LONWORKS Network Configuration Tool Service Pin Status Light-Emitting Diode (LED) Adding a Thermostat to the NAE LONWORKS Thermostat Mapping Preparation Space Comfort Controller Object ncigenopts Thermostat Command Table Commanding the Maximum Heating Setpoint Commanding the Minimum Cooling Setpoint Commanding the Cal RS Commanding the Occupied/Unoccupied Cooling and Heating Setpoints Relative Humidity Settings ncirhmodel Thermostat Command Table Commanding the Cal RH Troubleshooting TEC22x6(H)-2 Series LONWORKS Network Thermostats with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control Technical Bulletin

2 Technical Specifications TEC22x6(H)-2 Series LonWorks Network Thermostats with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control

3 TEC22x6(H)-2 Series LONWORKS Network Thermostats with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control Technical Bulletin Network Variables (NVs) and Configuration Properties (CPs) List Table shows the NVs and CPs for the TEC22x6-2 Series thermostats. Each Network Variable Input (NVI), Network Variable Output (NVO), and Network Configuration Input (NCI) has a reference number, and some objects have a subcategory number. The Sub column lists the thermostat s Enumeration (Enum) options for each NV or CP. The Byte column shows the byte number for each of the entry fields in the ncigenopts Status/Command screen. Note: When viewed using a LONWORKS network configuration tool, the ncigenopts screen is a 25 byte field, one for each entry field. Table : NVs and CPs by Model (Part of 3) No. Sub Byte NV or CP Name Model TEC226-2 TEC226H-2 TEC TEC2226H-2 TEC TEC2236H-2 TEC TEC2246H-2 TEC TEC2256H-2 0 nvispacetemp X X X X X nvioutdoortemp X X X X X 2 nvisetpoint X X X X X 3 nvispacerh X X 4 nvifanspeedcmd X X X X X 5 nviauxheatenable X X X X X 6 nviocccmd X X X X X 7 nviapplicmode X X X X X 8 nviheatcool X X X X X 9 nviremlockout X X X X X 0 nvidhumilck X X nviauxout X X X X X 2 nvospacetemp X X X X X 3 nvodischairtemp X X X X X 4 nvospacerh X X 5 nvoeffectoccup X X X X X 6 nvounitstatus X X X X X mode x x x x x 2 heat_output_primary x x x x x 3

4 Table : NVs and CPs by Model (Part 2 of 3) No. Sub Byte NV or CP Name Model TEC226-2 TEC226H-2 TEC TEC2226H-2 TEC TEC2236H-2 TEC TEC2246H-2 TEC TEC2256H-2 3 heat_output_secondary 4 cool_output x x x x x 5 econ_output 6 fan_output x x x x x 7 in_alarm x x x x x 7 nvosccstatus X X X X X State Terminal BO2 x x x 2 State Terminal BO x x 3 State Terminal BO4 x x 4 State Terminal BO3 x x x 5 State Terminal BO5 x x x x x 6 Fan Low x x x x x 7 Fan Medium x x x x x 8 Fan High x x x x x 9 UI 3 Status x x x x x 0 BI 2 Status x x x x x BI Status x x x x x 2 Service Alarm x x x x x 3 Filter Alarm x x x x x 4 Window Opened x x x x x 5 Dehumidification Active x x 8 nvoterminalload X X X X X 9 ncisetpts X X X X X occupied_cool x x x x x 2 standby_cool 3 unoccupied_cool x x x x x 4 occupied_heat x x x x x 5 standby_heat 6 unoccupied_heat x x x x x 20 ncirhmodel X X RHdisplay x x 2 RHsetpoint x x 3 DehumHyst x x 4 DehumCool x x 5 RHcalib x x 2 ncigenopts X X X X X 0 Control Type x x 2 Drive Time x x x 4

5 Table : NVs and CPs by Model (Part 3 of 3) No. Sub Byte NV or CP Name Model TEC226-2 TEC226H-2 TEC TEC2226H-2 TEC TEC2236H-2 TEC TEC2246H-2 TEC TEC2256H Cycles Per Hour x x x 4 3 Reverse Acting Output (RA/DA) x x 5 4 BI Configuration x x x x x 6 5 BI 2 Configuration x x x x x 7 6 UI 3 Configuration x x x x x 8 7 MenuScroll x x x x x 9 8 Auto Mode x x x x x 0 9 Temperature Scale x x x x x 0 Number of Pipe (System) x x x x x 2 Sequence of Operation x x x x x 3 2 Fan Menu x x x x x 4 3 Maximum Heating Setpoint (Range) x x x x x 5 4 Maximum Heating Setpoint (Value) x x x x x 6 5 Minimum Cooling Setpoint (Range) x x x x x 7 6 Minimum Cooling Setpoint (Value) x x x x x 8 7 Setpoint Type x x x x x 9 8 Temporary Occupancy Time x x x x x 20 9 Door Time x x x x x 2 20 Deadband x x x x x 22 2 Calibration Room Sensor (Range) x x x x x Calibration Room Sensor (Value) x x x x x Auxiliary Contact BO 5 Configuration x x x x x Reheat Output BO 5 Time Base x x x x x 22 ncisccmodel X X X X X 0 Thermostat Model Number x x x x x 2 Software Version x x x x x 23 ncihvactype X X X X X 24 ncisndhrtbt X X X X X 25 nciminouttm X X X X X 26 ncircvhrtbt X X X X X 27 ncimajver X X X X X 28 nciminver X X X X X 5

6 Network Variable Inputs (NVIs) Table 2: NVIs (Part of 4) Parameter NVI Name and SNVT Type Room Temperature Outdoor Air Temperature Occupied Cooling and Heating Setpoints Room Humidity nvispacetemp SNVT_temp_p nvioutdoortemp SNVT_temp_p nvisetpoint SNVT_temp_p nvispacerh SNVT_lev_percent Range and Enumeration Definition Valid Range: 4 F/ -0.0 C to 22 F/50.0 C Default Null (release) Value: 62.8 F/ C or (0x7FFF) represents invalid data. Note: This NVI allows the temperature setpoint for the occupied and standby mode to be changed via the network. When bound or written to, the internal temperature reading (internal sensor) is no longer used. Valid Range: -40 F/-40.0 C to 22 F/50.0 C Default Null (release) Value: 62.8 F/ C or (0x7FFF) represents invalid data. Note: This NVI provides outdoor air temperature information to the thermostat from a network value temperature value. The thermostat automatically displays the value when bound. Valid Range: Occupied Cooling 54 F/2 C to 00 F/37.5 C Valid Range: Occupied Heating 40 F/4.5 C to 90 F/32.0 C Standby Cool Setpoint (Not used.) Standby Heat Setpoint (Not used.) Default Null (release) Value: 62.8 F/ C or (0x7FFF) represents invalid data. Note: This NVI allows the temperature setpoints for the occupied mode to be changed via the network. The unoccupied setpoints are not changed. Valid Range: 0 to 00% Default Null Value: (0x7FFF). Note: This NVI is the measured room humidity in percent monitored by the thermostat. Note: This network variable is subject to the Receive HeartBeat Time, nvircvhrtbt. 6

7 Table 2: NVIs (Part 2 of 4) Parameter NVI Name and SNVT Type Fan Mode Sequence of Operations and Auxiliary Heat nvifanspeedcmd SNVT_switch nviauxheatenable SNVT_switch Range and Enumeration Definition Fan Menu Value 0 0 0xFF 0 0xFF 2 0 0xFF 3 0 0xFF 4 0 0xFF State Value Equivalent Percent % 0.5 to 33% 33.5 to 66.5% 67 to 00% 00% 0% 0.5 to 50% 50.5 to 00% 00% 0% 0.5 to 33% 33.5 to 66.5% 67 to 00% 00% 0% 0.5 to 50% 50.5 to 00% 00% 0% 0.5 to 00% 00% Requested Fan Speed Off - Not used. Off - Not used. Low Medium High 3 - Not used. Auto - Not used. Off - Not used. Off - Not used. Low High 2 - Not used. Auto - Not used. Off - Not used. Off - Not used. Low Medium High 3 - Not used. Auto Off - Not used. Off - Not used. Low High 2 - Not used. Auto Off - Not used. Off - Not used. On (High) On - Not used. Auto Note: This NVI is used to bind an external fan speed switch to the node or to allow any supervisory device to override the fan speed controlled by the node s control algorithm. It is used in conjunction with the FanMenu byte in ncigenopts. State Value Equivalent Auxiliary Heat Operation Percentage 0 Disabled (Not used.) 0 0% Disabled to to to 99.5% Partially Enabled (Not used.) 00% Enabled 0xFF Enabled (Invalid) Note: This NVI enables or disables the auxiliary heat stage. It is used in conjunction with nviheatcool and SeqOper. See Table 3 for information on using the nviheatcool, nviauxheatenable, and SeqOpera Variables. 7

8 Table 2: NVIs (Part 3 of 4) Parameter NVI Name and SNVT Type Occupancy System Mode nviocccmd SNVT_occupancy nviapplicmode SNVT_hvac_mode Range and Enumeration Definition 0 = OC_OCCUPIED = OC_UNOCCUPIED 2 = OC_BYPASS (Not used.) 3 = OC_STANDBY (Not used.) 0XFF = OC_NUL (Release to internal schedule) Note: This NVI commands the Space Comfort Controller into different occupancy modes. It is typically sent by a supervisory node to manually control occupancy modes, or to override the scheduled occupancy. Default Null Value: OC_NUL = 0xFF 0 = HVAC_AUTO (Default) = HVAC_HEAT 2 = HVAC_MRNG_WRMUP (Not used.) 3 = HVAC_COOL 4 = HVAC_NIGHT_PURGE (Not used.) 5 = HVAC_PRE_COOL (Not used.) 6 = HVAC_OFF 7 = HVAC_TEST (Not used.) 8 = HVAC_EMERG_HEAT (Not used.) 9 = HVAC_FAN_ONLY (Not used.) 0 = HVAC_FREE_COOL (Not used.) = HVAC_ICE (Not used.) 2 = HVAC_MAX_HEAT (Not used.) 3 = HVAC_ECONOMY (Not used.) 4 = HVAC_DEHUMID (Not used.) 5 = HVAC_CALIBRATE (Not used.) 6 = HVAC_EMERG_COOL (Not used.) 7 = HVAC_EMERG_STEAM (Not used.) 0XFF = HVAC_NUL (Not used.) Note: This NVI coordinates the Space Comfort Controller with any supervisory controller providing the supply energy - for example, hot or cold water. It is used as heat/cool changeover. It is also used in conjunction with nviapplicmode and SeqOper. 8

9 Table 2: NVIs (Part 4 of 4) Parameter NVI Name and SNVT Type Sequence of Operation Lockout DHumiLCK Aux Contact Fan Mode nviheatcool SNVT_hvac_mode nviremlockout SNVT_count nvidhumilck UNVT_nvi/nvo network input nviauxout SNVT_switch nvifanspeedcmd SNVT_switch Range and Enumeration Definition SeqOpera Menu Value Definition HVAC_AUTO (Default) HVAC_HEAT HVAC_MRNG_WRMUP (Not used.) HVAC_COOL HVAC_NIGHT_PURGE (Not used.) HVAC_PRE_COOL (Not used.) HVAC_OFF HVAC_TEST (Not used.) HVAC_EMERG_HEAT (Not used.) HVAC_FAN_ONLY (Not used.) HVAC_FREE_COOL (Not used.) HVAC_ICE (Not used.) HVAC_MAX_HEAT (Not used.) HVAC_ECONOMY (Not used.) HVAC_DEHUMID (Not used.) HVAC_CALIBRATE (Not used.) HVAC_EMERG_COOL (Not used.) HVAC_EMERG_STEAM (Not used.) 0XFF = HVAC_NUL (Not used.) See Table 3 for information on SeqOpera variables. See Table 3 for information on SeqOpera variables. Note: This NVI coordinates the Space Comfort Controller with any node that needs to control the heat/cool changeover of the unit. It is overridden by nviapplicmode, unless nviapplicmode is HVAC_AUTO. If nviapplicmode is HVAC_AUTO, then nviheatcool determines the effective mode of the unit. See Table 3 for information on using the nviheatcool, nviauxheatenable, and SeqOpera variables. See Table 4 for Lockout information. Note: This NVI enables or disables user access to the thermostat. 0 = Dehumidification not allowed (Default) = Dehumidification allowed Note: This NVI is used to enable or disable dehumidification. This NVI s Value and State must both be set to 0 to disable dehumidification. This NVI s Value and State must both be set to to enable dehumidification. 0 = Auxiliary contact Off = Auxiliary contact On 5 = Follow secondary network command Note: If this NVI is used to remotely command the Auxiliary Output (BO5), then the Auxiliary Output must be configured to a value of 5 for this function to operate. Not used.. If one setpoint of a pair of heating and cooling setpoints (for example, Occupied Heat Setpoint and Occupied Cool Setpoint) is overridden, the other setpoint of the pair may be automatically adjusted by the thermostat to maintain the minimum deadband between the two setpoints. 9

10 Using the nviheatcool, nviauxheatenable, and SeqOpera Variables Table 3: nviheatcool, nviauxheatenable, and SeqOpera Variables Current nviheatcool nviauxheatenable SeqOpera If nviheatcool Changed to: SeqOpera 2- and 4-Pipe Application 3 = HVAC_COOL Disabled 0 = Cooling only 0 = HVAC_AUTO = HVAC_HEAT 3 = HVAC_COOL Enabled 2 = Cooling and 0 = HVAC_AUTO Reheat = HVAC_HEAT = HVAC_HEAT Disabled = Heating only 0 = HVAC_AUTO 3 = HVAC_COOL = HVAC_HEAT Enabled 3 = Heating and 0 = HVAC_AUTO Reheat 3 = HVAC_COOL 4-Pipe Application 0 = HVAC_AUTO Disabled 4 = Cooling only 0 = HVAC_HEAT 3 = HVAC_COOL 0 = HVAC_AUTO Enabled 5 = Cooling and Reheat nviremlockout Command Table Table 4: nviremlockout Command Table Parameter Lockout NV and SNVT Types nviremlockout SNVT_count Lockout Menu Value Network Variable Outputs (NVOs) Table 5: NVOs (Part of 4) Parameter NVO Name and SNVT Type Room Temperature nvospacetemp SNVT_temp_p Occupied Temperature Setpoints 0 = HVAC_HEAT 3 = HVAC_COOL System Mode Settings 4 = Cool/Heat 4 Pipes = Heating only 5 = Cool/Heat 4 Pipes and Reheat 3 = Heating and Reheat 4 = Cool/Heat 4 Pipes 0 = Cooling only 5 = Cool/Heat 4 Pipes and Reheat 2 = Cooling and Reheat = Heating only 0 = Cooling only 3 = Heating and Reheat 2 = Cooling and Reheat Fan Mode Settings Unoccupied Override 0 Yes access Yes access Yes access Yes access Yes access Yes access Yes access No access 2 Not used. No access No access Not used. 3 Not used. No access No access Not used. 4 No access No access No access Yes access 5 No access No access No access No access Note: This NVI enables or disables user access to the thermostat. Range and Enumeration Definition Valid Range: 4 F/-0.0 C to 22 F/50.0 C Default Null (release) Value: 62.8 F/ C or (0x7FFF) represents invalid data. This value is sent as an invalid value in the event of a sensor failure. Note: This NVO monitors the effective space temperature sensor that the Space Comfort Controller is using for control. It echoes the internal value on the device temperature sensor or that of nvispacetemp if it is bound, or a value is written to it. 0

11 Table 5: NVOs (Part 2 of 4) Parameter NVO Name and SNVT Type Supply Temperature Room Humidity Occupancy nvodischairtemp SNVT_temp_p nvospacerh SNVT_lev_percent nvoeffectoccup SNVT_occupancy Range and Enumeration Definition Valid Range: -40 F/-40.0 C to 22 F/50.0 C Default Null (release) Value: 62.8 F/ C or (0x7FFF) represents invalid data. Note: This NVO monitors the temperature of the air that leaves the Space Comfort Controller. UI3 needs to be configured to (SS) supply air sensor monitoring. Valid Range: 0 to 00%. The value 0x7FFF = % is sent as an invalid value to indicate a humidity sensor failure. Note: This NVO indicates the space humidity in percent. 0 = OC_OCCUPIED = OC_UNOCCUPIED 2 = OC_BYPASS 3 = OC_STANDBY (Not used.) 4 = OC_NUL Note: This NVO indicates the actual occupancy mode of the unit. This information is typically reported to a supervisory controller or provided to another Space Comfort Controller to coordinate the operation of multiple units. OC_BYPASS can be initiated by either nviocccmd or a local input. NvoEffectOccup is only in OC_BYPASS for the duration of the ToccTime (ncigenopts), until reinitiated by either a transition of the local input or an update to nviocccmd.

12 Table 5: NVOs (Part 3 of 4) Parameter NVO Name and SNVT Type Unit Status nvounitstatus SNVT_hvac_status Range and Enumeration Definition Sub Name Valid Value 0 Mode = HVAC_HEAT 2 = HVAC_MRNG_WRMUP (Not used.) 3 = HVAC_COOL 4 = HVAC_NIGHT_PURGE (Not used.) 5 = HVAC_PRE_COOL (Not used.) 6 = HVAC_OFF 7 = HVAC_TEST (Not used.) 8 = HVAC_EMERG_HEAT (Not used.) 9 = HVAC_FAN_ONLY (Not used.) 0 = HVAC_FREE_COOL (Not used.) = HVAC_ICE (Not used.) 2 = HVAC_MAX_HEAT (Not used.) 3 = HVAC_ECONOMY (Not used.) 4 = HVAC_DEHUMID (Not used.) 5 = HVAC_CALIBRATE (Not used.) 6 = HVAC_EMERG_COOL (Not used.) 7 = HVAC_EMERG_STEAM (Not used.) 0XFF = HVAC_NUL (Not used.) Note: This NVO reports the Space Comfort Controller inputs and outputs status. It combines the operating mode, the capacity of heating and cooling used, and an indication if any alarms are present in the object. 02 heat_output_primary 0-00%, 0xFFF (invalid) 03 heat_output_secondary Not used. 04 cool_output 0-00%, 0xFFF (invalid) 05 econ_output Not used. 06 fan_output 0-00%, 0xFFF (invalid) 07 in_alarm 0 = No alarms = Alarm On 0x7FF (Alarm disabled) Not used. Note: This NVO is available to report the Space Comfort Controller status. It combines the operating mode, the capacity of heating and cooling used, and an indication if any alarms are present in the object. 2

13 Table 5: NVOs (Part 4 of 4) Parameter NVO Name and SNVT Type Thermostat I/O Status Heating/Cooling Demand nvosccstatus UNVT_fc_thermo nvoterminalload SNVT_lev_percent Range and Enumeration Definition Sub Name Valid Value Default Value 0 State Terminal BO2 02 State Terminal BO 03 State Terminal BO4 04 State Terminal BO3 05 State Terminal BO5 0 = Off = On 0 = Off = On 0 = Off = On 0 = Off = On 0 = Off = On 0 = Off 0 = Off 0 = Off 0 = Off 0 = Off 06 Fan Low Not used. 07 Fan Med Not used. 08 Fan High Not used. 09 UI 3 Status 0 BI 2 Status BI Status 2 Service Alarm 3 Filter Alarm 4 Window Opened 5 Dehumi dification Active -40 F/-40.0 C to 22 F/50.0 C 0 = Activated = Not activated 0 = Activated = Not activated 0 = No alarm = Alarm On 0 = No alarm = Alarm On 0 = No alarm = Alarm On 0 = Dehumidification not active = Dehumidification active = Not activated = Not activated = Not activated 0 = No alarm 0 = No alarm 0 = No alarm 0 = Dehumidification not active Note: This NVO reports the status of the Space Comfort Controller inputs and outputs. Valid Range: -00% to +00% Note: This NVO indicates the current heat/cool energy demand of the unit. Positive values indicate that cooling energy is in use by the space comfort controller, whereas negative values indicate that heating energy is in use by the space comfort controller.. OC_BYPASS can be initiated by either nviocccmd or a local input. NvoEffectOccup is only in OC_BYPASS for the duration of the ToccTime (ncigenopts), until reinitiated by either a transition of the local input or an update to nviocccmd. 3

14 Configuration Network Variables Table 6: Configuration Network Variables (Part of 5) Parameter NCI Name and SNVT, UNVT or SCPT Name Range and Enumeration Definition Temperature Setpoints RH Options ncisetpts SNVT_temp_setpt ncirhmodel UNVT_gen_opts This NV defines the space temperature setpoints for various heat, cool, and occupancy modes. The stand-by setpoints can be modified, but are not used by the controller, as it does not support Stand-By occupancy mode. Sub Mode Min. Max. Default 0 occupied_cool 54 F/2 C 00 F/ 75 F/24 C 37.5 C 02 standby_cool Not used. Not Not used. used. 03 unoccupied_cool 54 F/2 C 00 F/ 80 F/26.5 C 37.5 C 04 occupied_heat 40 F/4.5 C 90 F/ 72 F/22 C 32 C 05 standby_heat Not used. Not Not used. used. 06 unoccupied_heat 40 F/4.5 C 90 F/ 32 C 62 F/6.5 C Sub Name Vaild Range Default RH Display 0 = Not active 0 = Active 2 RH Setpoint 30 to 00% RH 50% RH 3 DehumHsyt 2 to 20% RH 5% RH 4 DehumCool 20 to 00% RH 00% RH 5 RHcalib -5 to +5% RH 0% RH Note: This CP defines the space humidity parameters and their settings. See Table 2 for information on commanding these parameters. 4

15 Table 6: Configuration Network Variables (Part 2 of 5) Parameter NCI Name and Range and Enumeration Definition SNVT, UNVT or SCPT Name Thermostat s ncigenopts Sub Name Valid Range Default Common CPs UNVT_fc_gen_opts 0 Control Type 0 = On/Off 0 = Floating 02 Drive Time 0.5 to 9 minutes 3 minutes (0.5 increments) 03 Cycles Per hour 3, 4, 5, 6, 7, and 8 CPH 4 CPH 04 Reverse Acting Output 0 = Direct Acting (DA) = Reverse Acting (RA) 05 BI 2 0 = None = Rem NSB 2 = Motion NO 3 = Motion NC 4 = Window 06 BI2 2 0 = None = Door Dry 2 = Override 3 = Filter 4 = Service 07 UI3 2 0 = None = COC/NH 2 = COC/NC 3 = COS 4 = SS

16 Table 6: Configuration Network Variables (Part 3 of 5) Parameter NCI Name and SNVT, UNVT or SCPT Name Range and Enumeration Definition Thermostat s Common CPs (continued) ncigenopts UNVT_fc_gen_opts 08 Menu Scroll 0 = No scroll = Scroll active 09 Auto Mode 0 = Not active = Active 0 Temperature Scale Pipes # Main Out Configuration 2 Sequence of Operation 0 = C = F 2.0 = 2-Pipe (Heat/ Cool same output) 4.0 = 4-Pipe (Heat/ Cool different outputs) 0 = Cooling Only = Heating Only 2 = Cooling & Reheat 3 = Heating & Reheat 4 = Cooling/Heating 4-Pipes 5 = Cooling/Heating 4-Pipes and Reheat 3 Fan Menu 0 = Low-Med-High = Low-High 2 = Low-Med-High- Auto 3 = Low-High-Auto 4 = On-Auto 4 Heat Maximum Setpoint 5 Cool Minimum Setpoint 40 to 90 F (4.5 to 32 C) 54 to 00 F (2 to 37.5 C) 6 Setpoint Type 0 = Permanent = Temporary 7 Temporary Occ Time 0,, 2, 3, up to 24 hours 8 Door Time, 2, 3, up to 0 minutes 9 Deadband 2, 3, 4, or 5 F ( to 2.5 C) 20 Calibration Room Sensor 2 Aux Contact Config 22 Reheat Time Base -5 to +5 F (-2.5 to 2.5 C) 0 = Aux Contact used for reheat 0 = 5 minutes = 0 seconds 0 F 0 = 2-Pipe = 4-Pipe = Heating Only 4 = On-Auto 90 F (32 C) 54 F (2 C) 0 2 hours 2 minutes 2 F ( C) 0 F (0 C) Note: This NV defines the thermostat s common configuration parameters and their settings

17 Table 6: Configuration Network Variables (Part 4 of 5) Parameter NCI Name and Range and Enumeration Definition SNVT, UNVT or SCPT Name Sub Name Valid Range Default Thermostat s Model Number ncisccmodel UNVT_model_num ber 0 Thermostat Model 4 = TEC = TEC226H-2 43 = TEC = TEC = TEC2236H-2 46 = TEC2226H-2 47 = TEC = TEC = TEC2256H-2 50 = TEC2246H-2 5 = Not used. Depends on model in use. 02 Software Version 0 0 Note: This NV defines the model number and software version of the thermostat. 7

18 Table 6: Configuration Network Variables (Part 5 of 5) Parameter NCI Name and Range and Enumeration Definition SNVT, UNVT or SCPT Name HVAC Unit Type ncihvactype Value Identifier Name Identifier SNVT_hvac_type 0 HVT_GENERIC - Not used. Generic HVT_FAN_COIL Fan Coil 2 HVT_VAV VAV Terminal 3 HVT_HEAT_PUMP Heat Pump 4 HVT_ROOFTOP Rooftop Unit 5 HVT_UNIT_VENT - Not used. Unit Ventilator 6 HVT_CHIL_CEIL - Not used. Chilled Ceiling 7 HVT_RADIATOR Radiator 8 HVT_AHU - Not used. Air Handling Unit 9 HVT_SLF_CONT - Not used. Self-Contained Unit Invalid HVT_NUL - Not used. Not used. Note: This NV helps you identify the type of equipment being monitored. Maximum Send Time Minimum Send Time Minimum Receive Time Major Hardware or Software Revisions Minor Hardware or Software Revisions ncisendhrtbt SNVT_time_sec nciminouttm SNVT_time_sec ncircvhrtbt SNVT_time_sec ncimajver SCPT_maj_ver nciminver SCPT_min_ver Valid Range: 0 seconds to 6,553.4 seconds Default Null Value: 0.0 seconds (no automatic update) Note: Setting ncisendhrtbt to 0 disables the Send Heartbeat mechanism. Note: This NV defines the maximum period of time that expires before the specified NVOs are automatically updated. Valid Range: 0 seconds to 6,553.4 seconds Default Null Value: 0.0 seconds (no minimum send time) Note: Setting ncircvhrtbt to 0 disables the Minimum Send Time mechanism. Note: This NV defines the minimum period of time between automatic NVO transmissions. Valid Range: 0 seconds to 6,553.4 seconds Default Null Value: 0.0 seconds (no failure detected) Note: Setting ncircvhrtbt to 0 disables the Receive Heartbeat mechanism. Note: This NV is used to control the maximum time that elapses after the last update to a specified NVI before the Space Comfort Controller starts to use its default values. Valid Range: 0 to 255 Note: This NV defines the major module hardware and software revisions. Valid Range: 0 to 255 Note: This NV defines the minor module hardware and software revisions.. If one setpoint of a pair of heating and cooling setpoints (for example, Occupied Heat Setpoint and Occupied Cool Setpoint) is overridden, the thermostat may automatically adjust the other setpoint of the pair to maintain the minimum deadband between the two setpoints. 2. The Binary Input (BI) object type status is available even if the configuration is set to None. 8

19 Commissioning the Thermostat Using a LONWORKS Network Configuration Tool A thermostat must first be commissioned using a LONWORKS network configuration tool before it can be added to the LON Integration Network Automation Engine (NAE). This process implements the initial configuration and assigns the Neuron ID of the thermostat. Understanding LONWORKS Network Configuration Tools Differences LONWorks network configuration tools use different numbering schemes in their Status/Command screens. In the ncigenopts Status/Command screen, Metasys system Connectivity to LONWORKS network (MCL) Tool begins its first data entry location with Byte 0, whereas Lonwatcher begins with Byte. The byte entry location number depends on which Tool you are using. Figure shows the ncigenopts Status/Command screen in MCL Tool on the left, with the equivalent Lonwatcher screen on the right. Figure : MCL Tool and Lonwatcher Status/Command Screens Table 7: LONWORKS Network Configuration Tool Terminology Differences LONWORKS Network Configuration Tool ncigenopts Screen MCL Tool Byte 0 to Byte 24 Lonwatcher Byte to Byte 25 LonMaker Tool Not directly changeable 9

20 Changing the Thermostat s Settings Using a LONWORKS Network Configuration Tool Once a thermostat is configured and online, you can use a LONWORKS network configuration tool to change its default settings. This means you do not have to go to the thermostat and manually make the changes. To change most of the thermostat s configuration properties: Note: See Table 4 for Lockout command information.. Using a LONWORKS network configuration tool, open the the thermostat s ncigenopts Status/Command screen. Note: See Table 7 for the byte entry location numbering differences. 2. From Table 9 find the desired configuration property and enter the corresponding value into its respective byte location in the ncigenopts Status/Command screen. Note: Some configuration properties require you to enter a range number in a specific byte location, followed by a corresponding value in the next byte location. You must enter both the range number and value before commanding the thermostat. 3. Enter additional configuration property changes if desired. 4. Command the thermostat. The new configuration changes are implemented. Service Pin To broadcast the thermostat s Neuron ID over the LONWORKS network, simultaneously press and hold the Up Arrow and Down Arrow for 5 seconds. The Status LED flashes once every 5 seconds to indicate the thermostat s Neuron ID is being broadcast on the LONWORKS network. For manual entry, the Neuron ID is also on a label on the Echelon chip under the thermostat cover. Status Light-Emitting Diode (LED) The status LED shows the operational status of the thermostat. The Status LED is a small green light under the thermostat cover (under the LONWORKS daughter board on the left edge when facing the thermostat). Table 8: Status LED Explanation Status LED Condition Explanation Continuously On Flashing at a 0.5 Hz Rate Continuously Off The thermostat does not have an application loaded in its memory. The thermostat has an application loaded in its memory but is unconfigured. Use a LONWORKS network management tool to bind the thermostat to a LONWORKS network. The thermostat has an application loaded in its memory and is bound to a LONWORKS network. 20

21 Adding a Thermostat to the NAE Once a thermostat has been commissioned, you must add it to the NAE before you can map its points. To do this, select the LONWORKS Integration under the NAE (refresh the tree view if required to see a newly added LONWORKS Integration) and choose Field Device from the Insert menu. Assisted Definition using Auto Discovery is the easiest way to add a new thermostat online; however, this step requires that the new thermostat is connected and ready to communicate. Refer to the LONWORKS Network Integration with NAE Technical Bulletin (LIT-20668) for instructions on how to add a LONWORKS device. LONWORKS Thermostat Mapping Preparation Before mapping a TEC22x6-2 Thermostat into a Network Automation Engine (NAE):. Decide which point objects within the thermostat you need to map. Only map the point objects that you need to view on a regular basis, because excessive mapping lowers system performance. Suggested point objects for mapping include: Room Temp, System Mode, Fan Status, Occupied Heat Setpoint, Occupied Cool Setpoint, Unoccupied Heat Setpoint, and Unoccupied Cool Setpoint. In addition, alarm points may be mapped if they are used, and other point objects may be mapped if required. Use the Engineering view to examine infrequently used point objects. 2. Verify that a LONWORKS Integration is defined in the NAE. The commissioned thermostat is mapped as a LONWORKS device under a LONWORKS Integration. Refer to the LONWORKS Network Integration with NAE Technical Bulletin (LIT-20668) for instructions on how to define a LONWORKS network Integration. At this point, you can map the thermostat and the required point objects inside the thermostat. 2

22 Space Comfort Controller Object Figure 2: TEC22x6(H)-2 Space Comfort Controller Object 22

23 ncigenopts Thermostat Command Table Use the information in Table 9 to configure the thermostat remotely. Table 9: ncigenopts Thermostat Command Table (Part of 4) MCL Tool Byte Number (LonWatcher Byte Number) Stat Menu Name Description Byte and Range 0 () CntrlTyp Control type - Defines the type of operation needed for Output. On/Off is N.O. or N.C. 24 VAC 2-position valves. Floating is modulating 3-wire control of 24 VAC floating valves. Note: Model TEC2226-2, TEC2226H-2, TEC2236-2, and TEC2236H-2 only. (2) FL time Drive time Note: Model TEC2226-2, TEC2226H-2, TEC2236-2, and TEC2236H-2 only. 2 (3) cph On/Off control in Cycles Per Hour (CPH) Note: Model TEC226-2, TEC226H-2, TEC2226-2, TEC2226H-2, TEC2236-2, and TEC2236H-2 only. 3 (4) RA/DA Reverse acting output Note: Model TEC2246-2, TEC2246H-2, TEC2256-2, and TEC2256H-2 only. 0 = On/Off = Floating (Default) = 0.5 minutes 2 =.0minute 3 =.5 minutes 4 = 2.0 minutes 5 = 2.5 minutes 6 = 3.0 minutes 7 = 3.5 minutes 8 = 4.0 minutes 9 = 4.5 minutes 0 = 5.0 minutes = 5.5 minutes 2 = 6.0 minutes 3 = 6.5 minutes 4 = 7.0 minutes 5 = 7.5 minutes 6 = 8.0 minutes 7 = 8.5 minutes 8 = 9.0 minutes 3 = 3 CPH 4 = 4 CPH 5 = 5 CPH 6 = 6 CPH 7 = 7 CPH 8 = 8 CPH 0 = Direct Acting = Reverse Acting 4 (5) BI Configuration of Binary Input 0 = None = Rem NSB 2 = MotionNO 3 = MotionNC 4 = Window 5 (6) BI2 Configuration of Binary Input2 0 = None = DoorDry 2 = RemOVR 3 = Filter 4 = Service 23

24 Table 9: ncigenopts Thermostat Command Table (Part 2 of 4) MCL Tool Byte Number (LonWatcher Byte Number) Stat Menu Name Description Byte and Range 6 (7) UI3 Configuration of Universal Input3. 0 = None = COC/NH 2 = COC/NC 3 = COS 4 = SS 7 (8) MenuScro Enables menu scrolling. 0 = Off = Scroll not active = On = Scroll active 8 (9) AutoMode Auto Mode enable 0 = Not Active (Default) = Active 9 (0) C or F Displayed temperature scale. 0 = C = F 0 () Pipe No Defines the type of system installed. (2) SeqOpera Determines the sequence of operation. 0 = 2-Pipe = 4-Pipe (Default) 0 = Cooling Only = Heating Only (Default) 2 = Cooling with Reheat 3 = Heating with Reheat 4 = Heating/Cooling 4-Pipe 5 = Heating/Cooling 4-Pipe with Reheat Note: 4 and 5 only available on if Out conf set to 4-Pipe. 2 (3) Fan Menu Determines the fan mode. 0 = Low-Med_High = Low-High 2 = Low-Med-High-Auto 3 = Low-High-Auto 4 = On-Auto (Default) 3 (4) Heat max Occupied and Unoccupied maximum Heating setpoint range number. 4 (5) Heat max Occupied and Unoccupied maximum Heating setpoint value number. 5 (6) Cool min Occupied and Unoccupied minimum Cooling setpoint range number. 6 (7) Cool min Occupied and Unoccupied minimum Cooling setpoint value number. 7 (8) Set type Temporary setpoint enable. 0 = Permanent = Temporary Enter the setpoint s range number from Table 0. Enter the setpoint s value number from Table 0. Enter the setpoint s range number from Table. Enter the setpoint s value number from Table. 24

25 Table 9: ncigenopts Thermostat Command Table (Part 3 of 4) MCL Tool Byte Number (LonWatcher Byte Number) Stat Menu Name Description Byte and Range 8 (9) TOccTime Minimum occupancy time. 0 = 0 Hours = Hours 2 = 2 Hours (Default) 3 = 3 Hours 4 = 4 Hours 5 = 5 Hours 6 = 6 Hours 7 = 7 Hours 8 = 8 Hours 9 = 9 Hours 0 = 0 Hours = Hours 2 = 2 Hours 3 = 3 Hours 4 = 4 Hours 5 = 5 Hours 6 = 6 Hours 7 = 7 Hours 8 = 8 Hours 9 = 9 Hours 20 = 20 Hours 2 = 2 Hours 22 = 22 Hours 23 = 23 Hours 24 = 24 Hours 9 (20) Door Time Engages the Unoccupied mode if the door stays open minimally for the time specified. = minute 2 = 2 minutes 3 = 3 minutes 4 = 4 minutes 5 = 5 minutes 6 = 6 minutes 7 = 7 minutes 8 =8 minutes 9 = 9 minutes 0 = 0 minutes 25

26 Table 9: ncigenopts Thermostat Command Table (Part 4 of 4) MCL Tool Byte Number (LonWatcher Byte Number) Stat Menu Name Description Byte and Range 20 (2) Deadband Sets the minimum deadband between the heating and cooling setpoints. 2 (22) Cal RS Sets the desired room air sensor calibration (offset). The offset can be added to or subtracted from the actual displayed room temperature. 22 (23) Cal RS Sets the desired room air sensor calibration (offset). The offset can be added to or subtracted from the actual displayed room temperature. 23 (24) Aux cont Determines the auxiliary contact function and configuration. Commanding the Maximum Heating Setpoint = 2 F 7 = 3 F 22 = 4 F 28 = 5 F Enter the range number from Table 2. Enter the value number from Table (25) Reheat Reheat time base 0 = 5 minutes = 0 seconds 0 = Aux Contact function Not used. or used for reheat. Note: If Sequence is set to Reheat through network or local, ignore this parameter (Sequence, 2, or 5). The output directly follows the occupancy of the thermostat. = Aux N.O., Occupied = Contact Closed 2 = Aux N.C. Occupied = Contact Open The output follows the secondary network occupancy command. 3 = Not used. 4 = Not used. 5 = Aux On/Off control from a separate and dedicated network variable. Enter the range number (MCL Tool Byte Number 3, Lonwatcher Byte Number 4) and value number (MCL Tool Byte Number 4, Lonwatcher Byte Number 5) (Table 0) in their respective byte entry boxes of the ncigenopts screen and command the thermostat. Note: You must enter both values before commanding the thermostat. 26

27 Table 0: Maximum Heat Setpoint Range Adjustment Values MaxHeat Setpoint Setting Range Byte 3 (4) Value Byte 4 (5) MaxHeat Setpoint Setting Range Byte 3 (4) Value Byte 4 (5) MaxHeat Setpoint Setting Range Byte 3 (4) 40 F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F 00 5 F F F F F F F F F F F F 2 53 F F F F F F 2 54 F F F F F F F F F F F F F F F F F 9 Value Byte 4 (5). Lonwatcher Range byte location numbers and Value byte location numbers shown in parenthesis. See Table 7 for more information on Bit/Byte use in each LONWORKS network configuration tool. 27

28 Commanding the Minimum Cooling Setpoint Using a LONWORKS network configuration tool, enter the range byte (MCL Tool Byte Number 5, Lonwatcher Byte Number 6) and value byte (MCL Tool Byte Number 6, Lonwatcher Byte Number 7) in their respective byte entry boxes of the ncigenopts screen and command the thermostat. You must enter both values before commanding the thermostat. Table : Minimum Cooling Setpoint Range Adjustment Values MinCool Range Value MinCool Range Value MinCool Range Value Setpoint Byte 5 Byte 6 Setpoint Byte 5 Byte 6 Setpoint Byte 5 Byte 6 Setting (6) (7) Setting (6) (7) Setting (6) (7) 54 F F F F F F F F F F F F 2 56 F F F F F F 2 57 F F F F F F F F 9 89 F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F Lonwatcher Range byte location numbers and Value byte location numbers shown in parentheses. See Table 7 for more information on Bit/Byte use in each LONWORKS network configuration tool. 28

29 Commanding the Cal RS Using a LONWORKS network configuration tool, enter the range number (MCL Tool Byte Number 2, Lonwatcher Byte Number 22) and value number (MCL Tool Byte Number 22, Lonwatcher Byte Number 23) (Table 2) in their respective byte entry boxes of the ncigenopts screen and command the thermostat. Note: You must enter both values before commanding the thermostat. Table 2: Cal RS Command Settings Cal RS Setting Byte 2 (22) Range Byte 22 (23) Value 5 F 2 4 F F F 0 F F F F F F F Lonwatcher Range byte location numbers and Value byte location numbers are shown in parentheses. See Table 7 for more information on byte use in each LONWORKS network configuration tool. Commanding the Occupied/Unoccupied Cooling and Heating Setpoints Using a LONWORKS network configuration tool, enter the occupied cooling, unoccupied cooling, occupied heating, and unoccupied setpoint temperatures in their respective entry boxes of the ncisetpt screen and command the thermostat. Note: Enter the temperature in degrees Fahrenheit. The temperature must be within the Maximum Heat and Minimum Cooling setpoint ranges. Use Table 3 to command the Occupied/Unoccupied Cooling and Heating Setpoints. Table 3: ncisetpt Command Table Setpoint Min. Max. Default Occupied Cooling 54 F/2 C 00 F/37.5 C 75 F/24 C Unoccupied Cooling 54 F/2 C 00 F/37.5 C 80 F/26.5 C Occupied Heating 40 F/4.5 C 90 F/32 C 72 F/22 C Unoccupied Heating 40 F/4.5 C 90 F/32 C 62 F/6.5 C. If one setpoint of a pair of heating and cooling setpoints (for example, Occupied Heat Setpoint and Occupied Cool Setpoint) is overridden, the thermostat may automatically adjust the other setpoint of the pair to maintain the minimum deadband between the two setpoints. 29

30 Relative Humidity Settings Relative humidity settings for the TEC2236-2, TEC2236H-2, TEC2256-2, and TEC2256H-2 thermostats are commanded in the ncirhmodel screen.the only exception is nvidhumilck, which is used to enable or disable dehumidification for the thermostat. ncirhmodel Thermostat Command Table Use the information in Table 4 to configure the thermostat remotely. Table 4: ncirhmodel Thermostat Command Table (Part of 2) MCL Tool Byte Number (Lonwatcher Byte Number) Stat Menu Name Description 0 () %RH disp Displays the RH value below the room temperature. (2) Not used. 2 (3) %RH set Dehumidification setpoint. Note: Only used if demumidification sequence is enabled. 3 (4) Not used. Byte and Range 0 = Do not display room RH (Default). = Display room RH. 30 = 30% RH 3 = 3% RH = 50% RH (Default) = 94% RH 95 = 95% RH Note: Range is 30 to 95% RH. 30

31 Table 4: ncirhmodel Thermostat Command Table (Part 2 of 2) MCL Tool Byte Number (Lonwatcher Byte Number) Stat Menu Name Description Byte and Range 4 (5) DehuHyst Humidity control hysterisys. Note: Only used if dehumidification sequence is enabled. 5 (6) Not used. 6 (7) DehuCool Maximum dehumudification cooling output. This is the maximum cooling valve position when dehumidification is enabled. Note: This can be used to balance smaller reheat loads installed in regards to the capacity of the cooling coil. 7 (8) cal RH Cal RH Range number Note: Offset that can be added to or subtracted from the actual displayed humidity value. 8 (9) cal RH Cal RH Value number Note: Offset that can be added to or subtracted from the actual displayed humidity value. Commanding the Cal RH 2 = 2% RH 3 = 3% RH 4 = 4% RH 5 = 5% RH (Default) 6 = 6% RH... 9 = 9% RH 20 = 20% RH Note: Range is 2 to 20% RH. 20 = 20% valve position 2 = 2% valve position 22 = 22% valve position 23 = 23% valve position 24 = 24% valve position = 99% valve position 00 = 00% valve position (Default) Note: Range is 20 to 00%. Enter the cal RH Range number from Table 5 for Cal RH Range settings. Enter the Cal RH Value number from Table 5 for Cal RH Value settings. Using a LONWORKS network configuration tool, enter the Byte 7 (8) range number and Byte 8 (9) value number (Table 2) in their respective byte entry boxes of the ncirhmodel screen and command the thermostat. 3

32 Note: You must enter both values before commanding the thermostat. These settings are only for the TEC2236-2, TEC2236H-2, TEC2256-2, and TEC2256H-2 models. Table 5: Cal RH Command Settings Cal RH Setting Range Byte 7 (8) Value Byte 8 (9) 5% RH 0 5 4% RH 0 4 3% RH 0 3 2% RH 0 2 % RH 0 0% RH 0 0 9% RH 0 9 8% RH 0 8 7% RH 0 7 6% RH 0 6 5% RH 0 5 4% RH 0 4 3% RH 0 3 2% RH 0 2 % RH 0 0% RH 0 0 -% RH % RH % RH % RH % RH % RH % RH % RH % RH % RH % RH % RH % RH % RH % RH Lonwatcher Range byte location numbers and Value byte location numbers are shown in parentheses. See Table 7 for more information on byte use in each LONWORKS network configuration tool. 32

33 Troubleshooting Table 6: Troubleshooting Details Symptom Cause Solution(s) No Display on the Thermostat Keyboard menu does not access all functions. Temperature setpoints revert to original value after a certain time. Thermostat does not call for heating. Thermostat does not call for cooling. Digital display shows missing digits or erratic segments. Reheat does not operate. Heating or cooling does not function properly. Absent or incorrect supply voltage Overloaded power transformer Keyboard locked Temporary setpoint active for a period of time set by parameter TOccTime Wrong mode selected Thermostat in Unoccupied mode Heating setpoint is satisfied Wrong mode selected Thermostat in Unoccupied mode Cooling setpoint is satisfied Defective display Wrong mode selected Wrong reversing valve configuration Note: TEC2246-2, TEC2246H-2, TEC2256-2, and TEC2256H-2 only.. Check power supply voltage between RC and C to be from 9-30 VAC. 2. Check for tripped fuse or circuit breaker. Verify that the transformer used is powerful enough (enough VAs) to supply all controlled devices including the thermostat Change configuration parameter nviremlockout to value 0 to access all levels of the menu. To do a permanent change to the setpoints, you must enter the Set type menu and change it from Temporar to Permnent, then modify the setpoints to the desired temperature Select heating mode. Select Override to force the thermostat Occupied heating setpoint. Raise the Heating setpoint. Select cooling mode. Select Override to force the thermostat Occupied cooling setpoint. Lower the cooling setpoint. Replace thermostat. From the SeqOpera menu, set the value to 2, 3 or 5. From the Rev Valve setting select either:. DA (Direct Acting) 0 to 00% = 0 to 0 VDC or 2. RA (Reverse Acting) 0 to 00% = 0 to 0 VDC 33

34 Technical Specifications TEC22x6(H)-2 Series LONWORKS Network Thermostats with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control Power Requirements Relay/Triac Contact Rating Analog Output Rating On/Off and Floating Control Proportional Control Fan Relay Output Rating Auxiliary Triac Output Output Rating Digital Inputs Temperature Sensor Type Wire Size LONWORKS Network Standard Temperature Range Backlit Display Heating Control Cooling Control 9 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or Safety Extra-Low Voltage (SELV) 30 VAC,.0 A Maximum, 3.0 A In-Rush 0 to 0 VDC into 2k ohm Resistance (Minimum) 30 VAC,.0 A Maximum, 3.0 A In-Rush 30 VAC,.0 A Maximum, 3.0 A In-Rush Voltage-Free Contacts across Terminal Scom to Terminals BI, BI2, or UI3 Local 0k ohm Negative Temperature Coefficient (NTC) Thermistor Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 8 AWG (.0 mm Diameter) Recommended 64 Devices Maximum without a Repeater, 27 Devices Maximum with a Repeater; 6,250 ft (,905 m) Maximum (Bus Topology) F/-40.0 C to 22.0 F/50.0 C in 0.5 Increments 40.0 F/4.5 C to 90.0 F/32.0 C 54.0 F/2.0 C to 00.0 F/38.0 C Accuracy Temperature ±0.9F /±0.5C at 70.0 F/2.0 C Typical Calibrated Humidity ±5% RH from 20 to 80% RH at 50 to 90 F (0 to 32 C) Minimum Deadband 2F /C between Heating and Cooling Ambient Operating 32 to 22 F (0 to 50 C); 95% RH Maximum, Noncondensing Conditions Storage -22 to 22 F (-30 to 50 C); 95% RH Maximum, Noncondensing Compliance United States UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to CFR 47, Part 5, Subpart B, Class A LONMARK Certification 3.4 (pending) Canada UL Listed, File E27734, CCN XAPX7, Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003 Europe CE Mark, EMC Directive 89/336/EEC, standards EN and EN Australia and C-Tick Mark, Australia/NZ Emissions Compliant New Zealand Shipping Weight 0.75 lb (0.34 kg) The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Controls Group 507 E. Michigan Street Milwaukee, WI Metasys is a registered trademark of Johnson Controls, Inc. All other marks herein are the marks of their respective owners Johnson Controls, Inc. Published in U.S.A. 34

TEC BACnet MS/TP Network Series Thermostat Controllers Technical Bulletin

TEC BACnet MS/TP Network Series Thermostat Controllers Technical Bulletin TEC BACnet MS/TP Network Series Thermostat Controllers Technical Bulletin Code No. LIT-12011592 Issued June 22, 2010 Supersedes December 1, 2009 Introduction..........................................................

More information

VT8600 Series BACnet Integration

VT8600 Series BACnet Integration VT8600 Series BACnet Integration BACnet Integration for VT8600 Series Room Controller BACnet CONTROLLER Version 2 2 Table of Contents INTRODUCTION BACnet Compatibility Specifications 3 Analog Objects 4

More information

Water terminal control solutions

Water terminal control solutions Water Terminal Control Solutions Water terminal control solutions Carrier offers a wide range of fan coil units designed to meet the needs of different systems and applications: from cabinet units in the

More information

Remote Display Unit. Installers Handbook Copyright 2001 AirSense Technology Ltd. LM Remote Display Unit Installers Handbook Issue 1.

Remote Display Unit. Installers Handbook Copyright 2001 AirSense Technology Ltd. LM Remote Display Unit Installers Handbook Issue 1. Remote Display Unit Installers Handbook Copyright 2001 AirSense Technology Ltd AirSense, ClassiFire, FastLearn PipeCAD, SenseNET, Stratos-HSSD and Stratos-Quadra are trademarks. HSSD is a Registered Trademark.

More information

Minute Impulse Clock Controller I01DN

Minute Impulse Clock Controller I01DN 99b-mi USER S MANUAL Minute Impulse Clock Controller Mon Jun 01, 2009 12:00:00 PM DST HOLD ENTER KEY TO BEGIN CANCEL HR I01DN 97 West Street Medfield, MA 02052 U.S.A. (508) 359-4396 Pg. 2 of 20 TABLE OF

More information

OPERATING MANUAL. EIB-Kombisensor AS 315 N

OPERATING MANUAL. EIB-Kombisensor AS 315 N EIB-Kombisensor AS 315 N OPERATING MANUAL EIB-Kombisensor AS 315 N 1 Contents Page 3 1. Description 4 1.1 Automated Operations 1.1.1 Sun System 1.1.2 Half-Light System 5 1.1.3 Wind System 1.1.4 Rain System

More information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -A - Introduction - Thank for your purchasing MITSUBISHI ELECTRIC MELPRO TM D Series Digital Protection

More information

MULTI-OUTPUT PROGRAMMABLE CONTROLLERS MODELS UMX-4 & UMX-8

MULTI-OUTPUT PROGRAMMABLE CONTROLLERS MODELS UMX-4 & UMX-8 February 1994 20/20 Interface Products MULTI-OUTPUT PROGRAMMABLE CONTROLLERS MODELS & DESCRIPTION The is a Multi-output Programmable Controller which expands the input or output capability of building

More information

5SJ4...-.HG Circuit Breakers to IEC and UL 489

5SJ4...-.HG Circuit Breakers to IEC and UL 489 Siemens AG 009 5SJ...-.HG Circuit Breakers to IEC and UL 89 BETA Low-Voltage Circuit Protection Compliance with industry standards is a must in today's manufacturing environment. Worldwide acceptance is

More information

KN Series Boiler HeatNet V3 LonWorks Network Variables V1.10

KN Series Boiler HeatNet V3 LonWorks Network Variables V1.10 This document lists and briefly describes the LonWorks variables available on KN Series Boilers with a HeatNet V3 control board. Some variables reference a specific boiler. The following substitutions

More information

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution Instruction 0001-22-2--00 Vacuum Circuit Breaker Operator Module Type 3AH 4.16kV to 38kV Power Transmission & Distribution Hazardous voltages and high-speed moving parts. Will cause death, serious injury

More information

TECHNICAL MANUAL 820 LX / 910 LX / 1300 LX

TECHNICAL MANUAL 820 LX / 910 LX / 1300 LX TECHNICAL MANUAL 820 LX / 910 LX / 1300 LX LANCER reserves the right to modify, constantly its documentation for its improvement. The values of adjustments indicated in the displays of this manual are

More information

32 Input AC Block I/O Module

32 Input AC Block I/O Module Input AC Module Cat. No. 79-A0 Series B Installation Mount the block I/O module in a vertical (recommended) or horizontal position. Allow sufficient room around the block for cooling air to flow through

More information

Installation Operation Commissioning Maintenance

Installation Operation Commissioning Maintenance NA 09.13 H 09-2011 Microchip and LCD display electronic regulation and signaling electronic module for liquid coolers and heat pumps Installation Operation Commissioning Maintenance 1 CONTENTS 1 IMPORTANT

More information

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER CAUTION: This equipment is designed for connection to mains voltages and must be used in accordance with this guide. If it is not, the safety protection

More information

INSTRUCTION MANUAL FOR MM10 Relay

INSTRUCTION MANUAL FOR MM10 Relay INSTRUCTION MANUAL FOR MM10 Relay Motor Protection Relay Front Panel Overview V1 250614 MM10 Motor Protection Relay a I L1 b I L2 I L3 c h i d e I L1 Figure 1: Front panel overview f g I L2 a Run LED b

More information

PHOENIX CONTACT - 04/2016. Features

PHOENIX CONTACT - 04/2016. Features Signal conditioner Data sheet 100238_de_06 1 Description PHOENIX CONTACT - 04/2016 Features The MCR-C-UI-UI(-450)-DCI(-NC) 3-way isolation amplifier is used to electrically isolate and convert analog signals.

More information

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER ISOCON-6 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss or expense resulting

More information

technical bulletin Installation Instructions: Wall-Mount Dewpoint Probe ( )

technical bulletin Installation Instructions: Wall-Mount Dewpoint Probe ( ) Installation Instructions: Wall-Mount Dewpoint Probe (809-2011) The HMW90 Wall-Mount Dewpoint Probe (P/N 809-2011) HMW90 measures dewpoint for indoor applications such as anti-sweat heater control and

More information

16 Input AC Block I/O Module

16 Input AC Block I/O Module 6 Input AC Module Cat. No. 79-6A0 Series B Installation Mount the block I/O module in a vertical (recommended) or horizontal position. Allow sufficient room around the block for cooling air flow through

More information

Installation Instructions: ICON Anti-Condensate Controller

Installation Instructions: ICON Anti-Condensate Controller TECHNICAL BULLETIN Installation Instructions: ICON Anti-Condensate Controller System Overview The ICON Anti-Condensate Controller System (pat. pend.) is a stand-alone controller for antisweat heaters in

More information

O P E R A T I N G M A N U A L

O P E R A T I N G M A N U A L OPERATING MANUAL WeatherJack OPERATING MANUAL 1-800-645-1061 The baud rate is 2400 ( 8 bits, 1 stop bit, no parity. Flow control = none) To make sure the unit is on line, send an X. the machine will respond

More information

Operating Instructions for Digital Manometer. Model: MAN-SD

Operating Instructions for Digital Manometer. Model: MAN-SD Operating Instructions for Digital Manometer Model: MAN-SD 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...4 5. Operating Principle...4 6. Mechanical Connection...5

More information

HERU Modbus. Reference Modbus addresses for HERU (Gen 3)

HERU Modbus. Reference Modbus addresses for HERU (Gen 3) HERU Modbus Reference Modbus addresses for HERU 62-250 (Gen 3) Modbus Registers HERU v0.7.xls Coil status (1bit) RW 5.6.2016 Coil status Discrete Output (1bit) R/W Modbus Register Name Description Application

More information

Product manual. Mylos KNX Shutter actuator 2CSY1104C/S

Product manual. Mylos KNX Shutter actuator 2CSY1104C/S Product manual Mylos KNX Shutter actuator 2CSY1104C/S Contents Contents 1 Technical features... 3 1.1 Technical data... 3 1.2 Connection diagram... 4 2 Commissioning... 5 2.1 Parameters... 5 2.1.1 General...

More information

SECTION 1 - WHAT IS A BTU METER? BTU's = Flow x ΔT Any ISTEC BTU Meter System consists of the following main components:

SECTION 1 - WHAT IS A BTU METER? BTU's = Flow x ΔT Any ISTEC BTU Meter System consists of the following main components: SECTION 1 - WHAT IS A BTU METER? ISTEC BTU Meters measure energy usage by multiplying flow rate and temperature difference. As the water (or other liquid) passes through these lines, the multi-wing turbine

More information

Data Bulletin. SEPAM 49RMS Application Note Protection for Motor Applications Class Number SEPAM 49RMS Protection for Motor Applications

Data Bulletin. SEPAM 49RMS Application Note Protection for Motor Applications Class Number SEPAM 49RMS Protection for Motor Applications Data Bulletin 3000DB08 09/008 LaVergne, TN, USA SEPAM 49RMS Application Note Protection for Motor Applications Class Number 3000 SEPAM 49RMS Protection for Motor Applications Introduction Thermal protection

More information

OPERATION MANUAL. 3 in 1, IR, Type K/J/R/E/T, Pt 100 ohm THERMOMETER. Model : TM-2000

OPERATION MANUAL. 3 in 1, IR, Type K/J/R/E/T, Pt 100 ohm THERMOMETER. Model : TM-2000 3 in 1, IR, Type K/J/R/E/T, Pt 100 ohm THERMOMETER Model : TM-2000 Your purchase of this THERMOMETER marks a step forward for you into the field of precision measurement. Although this THERMOMETER is a

More information

MODEL: R7K4FML3. Remote I/O R7K4F Series. POWER INPUT DC power R: 24 V DC (Operational voltage range: ±10 %; ripple 10 %p-p max.)

MODEL: R7K4FML3. Remote I/O R7K4F Series. POWER INPUT DC power R: 24 V DC (Operational voltage range: ±10 %; ripple 10 %p-p max.) Remote I/O R7KF Series I/O MODULE (-III) POWER INPUT DC power R: V DC (Operational voltage range: ±0 %; ripple 0 %p-p max.) 0 (8.7). (.) 7(.8) mm (inch) [] OPTIONS (multiple selections) Output data read

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer LDSR 0.3-TP/SP1 I P R N = 300 ma For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Closed

More information

St art. rp m. Km /h 1: : : : : : : : : : : : :5 2.5.

St art. rp m. Km /h 1: : : : : : : : : : : : :5 2.5. modified 22/05/14 t 3:5 2.5 3:5 5.0 3:5 7.5 4:0 0.0 4:0 2.5 4:0 5.0 4:0 7.5 4:1 0.0 4:1 2.5 4:1 5.0 4:1 7.5 4:2 0.0 Km /h 0 25 50 75 100 125 150 175 200 225 rp m 0 250 0 500 0 750 0 100 00 125 00 1 2 3

More information

Pressure Display Controller

Pressure Display Controller MODEL DW Display Controller Low The Model DW pressure controller accurately monitors and controls very low pressures. It combines in one enclosure a low pressure transducer, a digital display and two alarms

More information

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018 Periodic Inspection and Testing of Electrical Installations Sample Test (2391-051) Version 1.3 July 2018 Sample Questions Version and date Change detail Section 1.3 July 2018 Modified questions/answers

More information

SC125MS. Data Sheet and Instruction Manual. ! Warning! Salem Controls Inc. Stepper Motor Driver. Last Updated 12/14/2004

SC125MS. Data Sheet and Instruction Manual. ! Warning! Salem Controls Inc. Stepper Motor Driver.   Last Updated 12/14/2004 SC125MS Stepper Motor Driver Salem Controls Inc. Last Updated 12/14/2004! Warning! Stepper motors and drivers use high current and voltages capable of causing severe injury. Do not operate this product

More information

Default values for unit DX-S standard.

Default values for unit DX-S standard. Default values for unit DX-S standard. UNIFLAIR ITALIA spa 1. USER (U) : USER PASSWORD 22. 2. FACTORY (F) : FACTORY PASSWORD 177. Prob PROBES Tipo Min Max U.M. Var. Def Presence Superv /1 Presence external

More information

MODEL 107 TEMPERATURE PROBE INSTRUCTION MANUAL

MODEL 107 TEMPERATURE PROBE INSTRUCTION MANUAL MODEL 107 TEMPERATURE PROBE INSTRUCTION MANUAL REVISION: 6/00 COPYRIGHT (c) 1983-2000 CAMPBELL SCIENTIFIC, INC. This is a blank page. Warranty and Assistance The MODEL 107 TEMPERATURE PROBE is warranted

More information

ON SITE SYSTEMS Chemical Safety Assistant

ON SITE SYSTEMS Chemical Safety Assistant ON SITE SYSTEMS Chemical Safety Assistant CS ASSISTANT WEB USERS MANUAL On Site Systems 23 N. Gore Ave. Suite 200 St. Louis, MO 63119 Phone 314-963-9934 Fax 314-963-9281 Table of Contents INTRODUCTION

More information

The Ordering Code for various standard model Recorders with an AC supply and without any additional options are as follows:

The Ordering Code for various standard model Recorders with an AC supply and without any additional options are as follows: The basic PC software is supplied free with the recorder. There is an additional charge for the extensive Data Acquisition Software supplied with communication of RS-232/422/485 or Ethernet. The Ordering

More information

ISSP User Guide CY3207ISSP. Revision C

ISSP User Guide CY3207ISSP. Revision C CY3207ISSP ISSP User Guide Revision C Cypress Semiconductor 198 Champion Court San Jose, CA 95134-1709 Phone (USA): 800.858.1810 Phone (Intnl): 408.943.2600 http://www.cypress.com Copyrights Copyrights

More information

IR F ( C) ENGLISH INSTRUCTION MANUAL. Thermometer

IR F ( C) ENGLISH INSTRUCTION MANUAL. Thermometer INSTRUCTION MANUAL Thermometer DUAL-LASER TARGETING 12:1 DISTANCE- TO-SPOT RATIO AUTO-SCAN MAX/MIN/AVG/DIFF HIGH/LOW ALARM BACKLIT DISPLAY AUTO POWER-OFF ADJUSTABLE EMISSIVITY IR5 2m -22 752 F (-30 400

More information

Safety Precautions WARNING If critical situations that could lead to user s death or serious injury is assumed by mishandling of the product.

Safety Precautions WARNING If critical situations that could lead to user s death or serious injury is assumed by mishandling of the product. Safety Precautions Observe the following notices to ensure personal safety or to prevent accidents. To ensure that you use this product correctly, read this User s Manual thoroughly before use. Make sure

More information

Motors Automation Energy Transmission & Distribution Coatings. Servo Drive SCA06 V1.5X. Addendum to the Programming Manual SCA06 V1.

Motors Automation Energy Transmission & Distribution Coatings. Servo Drive SCA06 V1.5X. Addendum to the Programming Manual SCA06 V1. Motors Automation Energy Transmission & Distribution Coatings Servo Drive SCA06 V1.5X SCA06 V1.4X Series: SCA06 Language: English Document Number: 10003604017 / 01 Software Version: V1.5X Publication Date:

More information

Automatic titrators, TitroMatic

Automatic titrators, TitroMatic 112 TitroMatic These are the fourth generation of CRISON titrators. CRISON has over 25 years experience in this field and knows that, for certain applications, the performance and cost of large titrator

More information

ABB i-bus KNX Analogue Input AE/A 2.1

ABB i-bus KNX Analogue Input AE/A 2.1 Product Manual ABB i-bus KNX Analogue Input AE/A 2.1 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/A 2.1. Subject to changes and errors excepted. Exclusion

More information

MODELS Number WW4.x For Europe & Others V 50HZ

MODELS Number WW4.x For Europe & Others V 50HZ MODELS Number NA4.x For USA/Canada/Mexico 110-120V 60HZ MODELS Number WW4.x For Europe & Others 210-240V 50HZ Thank you for purchasing the Sunflex 24 Plus Daylight Controller, The most flexible and innovative

More information

Differential Pressure Sensor

Differential Pressure Sensor Differential Pressure Sensor MDP200 Series Features Pressure range up to ±500Pa with high accuracy of ±3.0% m.v. Pressure based on thermal micro-flow measurement Outstanding hysteresis and repeatability

More information

xlogic SuperRelay is a compact and expandable CPU replacing mini PLCs, multiple timers, relays and counters.

xlogic SuperRelay is a compact and expandable CPU replacing mini PLCs, multiple timers, relays and counters. SuperRelay S U P E R R E L A Y, T H E P E R F E C T A L T E R N A T I V E T O L O W C O S T P L C s A N D B A S I C R E L A Y S I N T H I S B R O C H U R E : ELC 18 Standard Models ELC 18 Economy Models

More information

CTC 155 / 350 / 660 Dry-block calibrator

CTC 155 / 350 / 660 Dry-block calibrator CTC 155 / 350 / 660 Dry-block calibrator Wide temperature range: CTC-155: -25 to 155 C CTC-350: 28 to 350 C CTC-660: 28 to 660 C Fast calibration External reference sensor External sensor control Easy

More information

Operation Manual Contents subject to change without notice

Operation Manual Contents subject to change without notice 318513 Operation Manual Contents subject to change without notice Version 1.0 Issue AA TABLE OF CONTENTS 1. INTRODUCTION and INSTALLATION... 1 General and Safety Information... 1 Specifications... 1 Contents...

More information

XR Analog Clock - Manual Setting Model Troubleshooting Guide

XR Analog Clock - Manual Setting Model Troubleshooting Guide Primex XR 72MHz Synchronized Time Solution XR Analog Clock - Manual Setting Model Troubleshooting Guide 2018 Primex. All Rights Reserved. The Primex logo is a registered trademark of Primex. All other

More information

ea980r Digital Anemometer User Manual

ea980r Digital Anemometer User Manual ea980r Digital Anemometer User Manual 1. Overview Thank you for purchasing the ennologic ea980r anemometer, a high quality instrument which measures 8 parameters: Wind Speed (mph, m/s, ft/min, knots, km/h)

More information

Drive electronics pq12

Drive electronics pq12 Drive electronics pq12 Amplifier module with constant current controller for proportional valves Control of one solenoid Easy mounting directly on bearing rails acc. to EN 50022 Standard voltage and current

More information

Hadrons Desktop U.S. Atomic Clock & Weather Station

Hadrons Desktop U.S. Atomic Clock & Weather Station Hadrons Desktop U.S. Atomic Clock & Weather Station SN004 Instructions Read and save these instructions. Dear Sharper Image Customer, Thank you for your purchase of a Sharper Image product. We appreciate

More information

CALEFFI. Modulating digital controller for heating and cooling. 161 series 01122/08 GB. replaces dp 01122/05

CALEFFI. Modulating digital controller for heating and cooling. 161 series 01122/08 GB. replaces dp 01122/05 Modulating digital controller for heating and cooling series REGI ERED SI EN ISO 00:000 Cert. n FM UNI EN ISO 00:000 Cert. n 000 0/0 G replaces dp 0/0 Function The controller can be used with three-point

More information

Latest generation testo air velocity & IAQ probes with cable handle. Instruction manual

Latest generation testo air velocity & IAQ probes with cable handle. Instruction manual Latest generation testo air velocity & IAQ probes with cable handle Instruction manual Contents Contents 1 About this document... 5 2 Safety and disposal... 5 3 System description... 6 4 Description of

More information

WE RE HERE TO HELP: 1 (844) LIGHTCLOUD

WE RE HERE TO HELP: 1 (844) LIGHTCLOUD Welcome Controller LCCONTROL20/D10 WE RE HERE TO HELP: 1 (844) LIGHTCLOUD 1 (844) 544-4825 support@lightcloud.com Contents Lightcloud Controller NPT Nut O-ring Instruction Manual Wire Nuts x 4 x 2 Specifications

More information

Rain Watch TM Set up Manual. IC System with Rain Bird IC CONNECT

Rain Watch TM Set up Manual. IC System with Rain Bird IC CONNECT Rain Watch TM Set up Manual IC System with Rain Bird IC CONNECT December 2018 Table of Contents Required materials to configure Rain Watch TM... 3 Installation... 4 Location... 4 Field Installation...

More information

M2 SERIES THERMOSTATS 0 F to 240 F, Narrow Differential, Hermetically Sealed ½

M2 SERIES THERMOSTATS 0 F to 240 F, Narrow Differential, Hermetically Sealed ½ M2 SERIES THERMOSTATS 0 F to 240 F, Narrow Differential, Hermetically Sealed ½ Introduction The Klixon M2 thermostat is constructed with a snap acting bimetal disc that serves as the actuating element.

More information

Operating instructions Magnetic-inductive flow meter. SM6x01 SM7x01 SM8x / / 2015

Operating instructions Magnetic-inductive flow meter. SM6x01 SM7x01 SM8x / / 2015 Operating instructions Magnetic-inductive flow meter UK SM6x01 SM7x01 SM8x01 80223585 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...4

More information

E2T0 DVP

E2T0 DVP 29-5-26 5116868-E2T DVP-11363-1 ENGLISH Thank you for choosing Delta s DVP series PLC. DVP4TC-E2 temperature measurement module receives 4 points of external thermocouple temperature sensors (J-type, K-type,

More information

Device Specifications

Device Specifications Manual Device Specifications PART NUMBER LCGATEWAY ELECTRICAL The Lightcloud Gateway is designed to be hard-wired to AC power by a qualified electrician. INPUT 120-277 VAC, 50/60 Hz 60-45mA BATTERY Li-ion

More information

Singer. Incremental Comfort Systems. K, EK Vintage F. Last Manufactured: Replacement Parts List No Revision C 04/2012

Singer. Incremental Comfort Systems. K, EK Vintage F. Last Manufactured: Replacement Parts List No Revision C 04/2012 Replacement Parts List No. 055231000 Revision C 04/2012 Singer Incremental Comfort Systems K, EK 07-15 Vintage F Last Manufactured: 1976 To find your Daikin Applied parts distributor, call 1-800-377-2787

More information

473-SHX Dew Point Mirror

473-SHX Dew Point Mirror Humidity and Temperature Reference Hygrometer For Temperature up to 125 C Precise and stable chilled mirror dew point mirror technology High temperature optical components High temperature sample fan Cable

More information

BECKMAN COULTER QbD1200 Total Organic Carbon Analyzer Critical Measurements Made Simple

BECKMAN COULTER QbD1200 Total Organic Carbon Analyzer Critical Measurements Made Simple BECKMAN COULTER QbD1200 Total Organic Carbon Analyzer Critical Measurements Made Simple Reliable TOC measurements Stop throwing away your first rep. QbD1200 has virtually eliminated sample-to-sample carryover

More information

89BSD CALCULATION METHOD APPLICATION NOTE

89BSD CALCULATION METHOD APPLICATION NOTE FUNCTIONAL DESCRIPTION GENERAL The 89BSD consists of a piezoresistive sensor and a sensor interface IC. The main function of the sensor interface IC is to convert the uncompensated analogue output voltage

More information

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers Section 5 TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers Rev. 5/10/2010 1 Section 5 Form for Event ID and Event Type Number Data TO s

More information

INSTRUCTION MANUAL Milwaukee Refractometer MA881 Refractometer for Invert Sugar Measurements

INSTRUCTION MANUAL Milwaukee Refractometer MA881 Refractometer for Invert Sugar Measurements www.milwaukeeinst.com INSTRUCTION MANUAL Milwaukee Refractometer MA881 Refractometer for Invert Sugar Measurements www.milwaukeeinst.com 1 Instruction Manual MA881 Refractometer for Invert Sugar Measurements

More information

24 volts (0.25 amps current-limited)

24 volts (0.25 amps current-limited) Question 1 Questions Suppose the lamp refuses to light up. A voltmeter registers 24 volts between test points C and D: A C E + 24 volts (0.25 amps current-limited) B D F First, list all the possible (single)

More information

i.mx 6 Temperature Sensor Module

i.mx 6 Temperature Sensor Module NXP Semiconductors Document Number: AN5215 Application Note Rev. 1, 03/2017 i.mx 6 Temperature Sensor Module 1. Introduction All the i.mx6 series application processors use the same temperature sensor

More information

FIII LonWorks Bridge Network Variables v2.32

FIII LonWorks Bridge Network Variables v2.32 Input/Output Variables (Read/Write) nviheatdemand SNVT_switch 100 Heat Demand/Request. Setting the state member of this variable will put the boiler in heating mode. state value Interpretation 0 0 no heat

More information

MAGPOWR TENSION CONTROL DLCA NET-SLIM. User Manual. Digital Load Cell Amplifier MI 850A358 1 A

MAGPOWR TENSION CONTROL DLCA NET-SLIM. User Manual. Digital Load Cell Amplifier MI 850A358 1 A MAGPOWR TENSION CONTROL DLCA NET-SLIM User Manual EN Digital Load Cell Amplifier MI 850A358 1 A CONTENTS 1.0 INTRODUCTION 4 1.1 About these operating instructions... 4 1.2 Product overview... 5 1.2.1 Additional

More information

CR10XTCR THERMOCOUPLE REFERENCE

CR10XTCR THERMOCOUPLE REFERENCE CR10XTCR THERMOCOUPLE REFERENCE REVISION: 01/01/03 COPYRIGHT (c) 1995-2003 CAMPBELL SCIENTIFIC, INC. This is a blank page. WARRANTY AND ASSISTANCE The CR10XTCR THERMOCOUPLE REFERENCE is warranted by CAMPBELL

More information

SS V Subminiature, radial leaded, time-delay fuses

SS V Subminiature, radial leaded, time-delay fuses Supersedes August 2013 250 V Subminiature, radial leaded, time-delay fuses Pb HALOGEN HF FREE Product description Radial leaded, time delay with low breaking capacity Designed to IEC60127-3 Sheet 4 Plastic

More information

GRUNDFOS DATA BOOKLET MAGNA, UPE. Series 2000 circulator pumps

GRUNDFOS DATA BOOKLET MAGNA, UPE. Series 2000 circulator pumps GRUNDFOS DATA BOOKLET MAGNA, UPE Series circulator pumps Contents Product data MAGNA/UPE 3 Duty range 3 Characteristic features 3 Benefits 3 Applications 3 eating systems 3 Pumped liquids 3 Type key Performance

More information

Digital Controller Operation

Digital Controller Operation A Family Company Manufacturing In The USA Since 1969 Full Gauge Digital Controller Operation This manual is specific to the operation and diagnostic guides of the Full Gauge digital controller used in

More information

Operating instructions Magnetic-inductive flow sensor SM6004 SM7004 SM / / 2014

Operating instructions Magnetic-inductive flow sensor SM6004 SM7004 SM / / 2014 Operating instructions Magnetic-inductive flow sensor SM6004 SM7004 SM8004 80003223 / 00 05 / 2014 Contents 1 Preliminary note...3 1.1 Symbols used...3 2 Safety instructions...4 3 Functions and features...5

More information

Installation and Operation Manual. AllSync Plus Wired Clocks

Installation and Operation Manual. AllSync Plus Wired Clocks and Operation Manual AllSync Plus Wired Clocks Part # H004881 Rev. 4 September 2018 Safety Precautions AllSync Plus Clock & Operation Manual Troubleshooting General Operation Introduction Safety Precautions

More information

6-way valve with room temperature controller. Balanced climate control. World premiere! e. Cost and energy economies

6-way valve with room temperature controller. Balanced climate control. World premiere! e. Cost and energy economies 6-way valve with room temperature controller. Balanced climate control. We set standards. www.belimo.eu World premiere! e Virtuoso performance to raise comfort and cut costs. Sustainable well-being hinges

More information

RECORD AND ANALYSE THE PRESSURE-ENTHALPY DIAGRAM FOR A COMPRESSION HEAT PUMP

RECORD AND ANALYSE THE PRESSURE-ENTHALPY DIAGRAM FOR A COMPRESSION HEAT PUMP Thermodynamics Heat cycles Heat Pump RECORD AND ANALYSE THE PRESSURE-ENTHALPY DIAGRAM FOR A COMPRESSION HEAT PUMP Demonstrate how an electric compression heat pump works Quantitatively investigate of the

More information

Digital Stored Grain Quality Management. BinMaster Level Controls Lincoln, Nebraska, USA

Digital Stored Grain Quality Management. BinMaster Level Controls Lincoln, Nebraska, USA Digital Stored Grain Quality Management BinMaster Level Controls Lincoln, Nebraska, USA Why monitor stored grain? Early detection protects against losses Reduce shrink to maximize grain weight and profit

More information

SSi Super Systems Inc.

SSi Super Systems Inc. Model DPC2530 Continuous Digital Dew Point Analyzer For measurement of: Endothermic Atmosphere Exothermic Atmosphere Nitrogen / Hydrogen Atmosphere Plant Air Systems SPECIFICATIONS Measurement Range: -50

More information

PTS Volt DC surface mount resettable PTC devices. Technical Data Applications. Agency information.

PTS Volt DC surface mount resettable PTC devices. Technical Data Applications. Agency information. Supersedes August 2014 Pb HALOGEN HF FREE Applications USB Peripherals Disk drives Power tools Rechargeable battery pack protection Plug and play protection for motherboards and peripherals Mobile phones

More information

ZNR Transient/Surge Absorbers (Type E)

ZNR Transient/Surge Absorbers (Type E) ZNR Transient/Surge Absorbers Type : E The ZNR Type E is capable of handling larger surge energy than Type D in applications to protect electronic equipment or semiconductor devices from switching and

More information

No /06e. Technical Manual Multistage-Temperature-/Differential Controller TAR x700

No /06e. Technical Manual Multistage-Temperature-/Differential Controller TAR x700 Technical Manual Multistage-Temperature-/Differential Controller x700 Software Version 0078 o. 5303-0/06e 700 3700 5700 9700 3700 5700 9700 l Suitable as : Multistage Controller or Differential Controller

More information

DS 300. Electronic Pressure Switch. with IO-Link interface. Stainless Steel Sensor. accuracy according to IEC 60770: 0.35 % FSO.

DS 300. Electronic Pressure Switch. with IO-Link interface. Stainless Steel Sensor. accuracy according to IEC 60770: 0.35 % FSO. DS 00 Electronic Pressure Switch with IO-Link interface Stainless Steel Sensor accuracy according to IEC 60770: 0.5 % FSO Nominal pressure from 0... 00 mbar up to 0... 600 bar Digital output signal IO-Link

More information

CR10TCR THERMOCOUPLE REFERENCE

CR10TCR THERMOCOUPLE REFERENCE CR10TCR THERMOCOUPLE REFERENCE REVISION: 12/96 COPYRIGHT (c) 1995-1996 CAMPBELL SCIENTIFIC, INC. This is a blank page. WARRANTY AND ASSISTANCE The CR10TCR THERMOCOUPLE REFERENCE is warranted by CAMPBELL

More information

GW Professional Weighing Scale. User Manual SNOWREX INTERNATIONAL CO., LTD. SRGW

GW Professional Weighing Scale. User Manual SNOWREX INTERNATIONAL CO., LTD. SRGW GW Professional Weighing Scale User Manual SNOWREX INTERNATIONAL CO., LTD. SRGW 20100415 Table of Contents Table of Contents...1 Specifications... 2 Basic specification... 2 Series specification(ec TYPE/OIML

More information

PNEUMATIC ENTHALPY COMPARATOR

PNEUMATIC ENTHALPY COMPARATOR PNEUATIC ENTHALPY COPARATOR APS ANALYSTS OF PNEUATIC SYSTES LIITED analystsofpneumatic@bellnet.ca http://www.apscontrols.ca PHONE: (9) 6-2333 FAX: (9) 6-2444 CONTENTS PAGE - Preface ------------------------------------------

More information

DC/DC regulator Input V Output up to 16 A

DC/DC regulator Input V Output up to 16 A PMC 4000 series Contents Product Program...................... 2 Mechanical Data...................... 3 Connections......................... 3 Absolute Maximum Ratings............. 4 Input...............................

More information

Peterborough Distribution Inc Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5

Peterborough Distribution Inc Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5 Peterborough Distribution Inc. 1867 Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5 November 15, 2017 Ontario Energy Board PO Box 2319 27 th Floor, 2300 Yonge St Toronto ON M4P 1E4

More information

473 Dew Point Hygrometer

473 Dew Point Hygrometer High Performance Chilled Mirror Hygrometer With Cable Mounted Measuring Heads Highly precise chilled mirror dew point technology Cable mounted dew point and temperature measurement Aspirated and direct

More information

Application Note - SolarEdge Inverters, Power Control Options

Application Note - SolarEdge Inverters, Power Control Options Version 3, December 2017 Application Note - SolarEdge Inverters, Power Control Options Version History Version 3 (December 2017) Added Active Power ramp up option Added new active power phase balancing

More information

POINTS OF CAUTION BEFORE USE...

POINTS OF CAUTION BEFORE USE... INSTRUCTION MANUAL NPN DISCRETE INPUT & NPN TRANSISTOR OUTPUT MODULE, 6 points each (-I/-II, e-con connector) MODEL BEFORE USE... Thank you for choosing M-System. Before use, check the contents of the

More information

Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000,

Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000, Digital Current Transducer HLSR-PW series I P N = 16... 50 A Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000, Bitstream output from on onboard Sigma Delta modulator. For the electronic measurement

More information

Certificate: / 9 September 2014

Certificate: / 9 September 2014 Test report: 936/21219977/A of 26 March 214 Initial certification: 5 August 214 Date of expiry: 4 August 219 Publication: BAnz AT 5 August 214 B11, chapter III, no. 2.1 Approved application The certified

More information

MKIII -MB USER S GUIDE 09/18/18. Rev. 3

MKIII -MB USER S GUIDE 09/18/18. Rev. 3 MKIII -MB USER S GUIDE 09/18/18 Rev. 3 Copyright 2018 by RainWise, Inc. All rights reserved. No part of this work may be reproduced in any form except by written permission of the publisher. All rights

More information

Activity 1: Investigating Temperature

Activity 1: Investigating Temperature Contents Activity Overview... 5 Quick Start Guide... 5 Software Installation... 5 Hardware Setup... 6 mytemp Getting Started Program... 10 General Tips and Tricks... 11 Activity 1: Investigating Temperature...

More information

GMVC8. ComfortNet -Compatible. Heating Input: 70, ,000 BTU/h. Two-Stage, Variable-Speed Gas Furnace

GMVC8. ComfortNet -Compatible. Heating Input: 70, ,000 BTU/h. Two-Stage, Variable-Speed Gas Furnace 80% AFUE Heating Input: 70,000 115,000 BTU/h ComfortNet -Compatible Two-Stage, Variable-Speed Gas Furnace Standard Features Aluminized steel, dual-diameter tubular heat exchanger Two-stage gas valve operates

More information

CiA Draft Standard Proposal CANopen. Application Profile for Lift Control Systems. Part 2: Virtual device definitions

CiA Draft Standard Proposal CANopen. Application Profile for Lift Control Systems. Part 2: Virtual device definitions CiA Draft Standard Proposal 417-2 CANopen Application Profile for Lift Control Systems Part 2: Virtual device definitions This is a draft standard proposal and may be changed without notification. Version

More information

WLDS-20 Mk2 MAJOR WATER LEAK DETECTION SYSTEM INSTALLATION & COMMISSIONING

WLDS-20 Mk2 MAJOR WATER LEAK DETECTION SYSTEM INSTALLATION & COMMISSIONING WLDS-20 Mk2 MAJOR WATER LEAK DETECTION SYSTEM INSTALLATION & COMMISSIONING DESCRIPTION: An electronic control panel used in conjunction with two pulse meters (water meters with pulse output proportional

More information