Available online at ScienceDirect. Energy Procedia 78 (2015 )

Similar documents
ScienceDirect. Experimental study of influence of movements on airflow under stratum ventilation

On the influence of several parameters in energy model calibration: the case of a historical building

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

PROPOSAL OF SEVEN-DAY DESIGN WEATHER DATA FOR HVAC PEAK LOAD CALCULATION

TREES Training for Renovated Energy Efficient Social housing

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Taking the garbage out of energy modeling through calibration

Conduction Transfer Function vs Finite Difference: comparison in terms of accuracy, stability and computational time

Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015

Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015

SOFTWARE FOR WEATHER DATABASES MANAGEMENT AND CONSTRUCTION OF REFERENCE YEARS

STUDENT MODELLING COMPETITION

GENERATING FUTURE WEATHER FILES FOR RESILIENCE

Sensitivity analysis and validation of an EnergyPlus model of a house in Upper Austria

PREDICTING OVERHEATING RISK IN HOMES

TRANSPARENT INNOVATIVE MATERIALS: ENERGETIC AND LIGHTING PERFORMANCES EVALUATION

THERMAL COMFORT IN HIGHLY GLAZED BUILDINGS DETERMINED FOR WEATHER YEARS ON ACCOUNT OF SOLAR RADIATION. Dominika Knera 1 and Dariusz Heim 1

Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015

Available online at ScienceDirect. Energy Procedia 78 (2015 )

On the energy demands of small appliances in homes

PAUL RUDOLPH Oriental Masonic Gardens

Investigations on effect of the orientation on thermal comfort in terraced housing in Malaysia

VISUALIZING CLIMATE DATA AS A 3D CLIMATE TORUS

Generation of a reduced temperature year as an input data for building climatization purposes: an application for Palermo (Italy)

DEVELOPMENT OF COOLING LOAD TEMPERATURE DIFFERENTIAL VALUES FOR BUILDING ENVELOPES IN THAILAND

Δ q = ( ψ L) HDH (1) here, Δq is the additional heat transfer caused by the thermal bridge, Ψ and L are the linear thermal transmittance and length of

A PRELIMINARY MODEL OF USER BEHAVIOUR REGARDING THE MANUAL CONTROL OF WINDOWS IN OFFICE BUILDINGS

ABOUT UNCERTAINTIES IN SIMULATION MODELS FOR BUILDING SYSTEMS CONTROL

PROCESSING RAW WEATHER DATA INTO WEATHER FILES ACCEPTABLE FOR BUILDING ENERGY PERFORMANCE SIMULATION TOOLS

FUNDAMENTALS OF HVAC

APlocate: Location and Weather User Guide

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Winter Thermal Comfort in 19 th Century Traditional Buildings of the Town of Florina, in North-Western Greece

Institut national des sciences appliquées de Strasbourg GENIE CLIMATIQUE ET ENERGETIQUE APPENDICES

NEGST. New generation of solar thermal systems. Advanced applications ENEA. Comparison of solar cooling technologies. Vincenzo Sabatelli

Defining Normal Weather for Energy and Peak Normalization

The AWS based operational urban network in Milano: achievements and open questions.

Experimental measurements and analysis of the indoor conditions in Italian museum storerooms: a study case

EFFECT OF INTERNAL LONG WAVE RADIATION AND CONVECTION ON FENESTRATION SIMULATION

Multivariate Regression Model Results

Derivation of meteorological reference year with hourly interval for Italy

OFFICE DE CONSULTATION PUBLIQUE DE MONTRÉAL

A SIMPLE MODEL FOR THE DYNAMIC COMPUTATION OF BUILDING HEATING AND COOLING DEMAND. Kai Sirén AALTO UNIVERSITY

Occupant Behavior Related to Space Cooling in a High Rise Residential Building Located in a Tropical Region N.F. Mat Hanip 1, S.A. Zaki 1,*, A. Hagish

CityBEM: an Open Source Implementation and Validation of Monthly Heating and Cooling Energy Needs for 3D Buildings in Cities

Evaluation of solar fraction on north partition wall for various shapes of solarium by Auto-Cad

This is the published version.

CityBEM: Monthly Heating and Cooling Energy Needs for 3D Buildings in Cities

Measurements of the angular distribution of diffuse irradiance

AN INTERNATIONAL SOLAR IRRADIANCE DATA INGEST SYSTEM FOR FORECASTING SOLAR POWER AND AGRICULTURAL CROP YIELDS

Better Weather Data Equals Better Results: The Proof is in EE and DR!

Evaluation the impact tilt angle on the sun collectors

Building Thermal Energy Simulations Supported by the CityGML Energy ADE

LOADS, CUSTOMERS AND REVENUE

peak half-hourly New South Wales

ARCHITECTURE IN THE DAYLIGHT

Demand Forecasting Reporting Period: 19 st Jun th Sep 2017

FORECAST ACCURACY REPORT 2017 FOR THE 2016 NATIONAL ELECTRICITY FORECASTING REPORT

Available online at ScienceDirect. Energy Procedia 49 (2014 ) SolarPACES 2013

EnergyPlus Weather File (EPW) Data Dictionary

Simulation Study of Building Envelope Performance Using Microclimatic Meteorological Data

Effect of Solar Radiation Control on Electricity Demand Costs an Addition to the DOE Cool Roof Calculator

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

2013 WEATHER NORMALIZATION SURVEY. Industry Practices

Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha

FIRST CORRELATIONS FOR SOLAR RADIATION ON CLOUDY DAYS IN ITALY

COMMERCIAL HEAT GAIN - HEAT LOSS CALCULATION LOAD FORM

UBC Social Ecological Economic Development Studies (SEEDS) Sustainability Program. Student Research Report

peak half-hourly Tasmania

Daylighting Buildings Nexus November 12, 2009

ScienceDirect. Experimental study on the sun tracking ability of a spherical solar collector

TRANSMISSION BUSINESS LOAD FORECAST AND METHODOLOGY

Small size single-axis PV trackers: control strategies and system layout for energy optimization

Solar Radiation Protections on Façades: A Case Study in a Hot Semi-Humid Climate

SMART GRID FORECASTING

How to evaluate daylight. Initiated by the VELUX Group

CZECH TECHNICAL UNIVERSITY IN PRAGUE FACULTY OF MECHANICAL ENGINEERING DEPARTMENT OF ENVIRONMENTAL ENGINEERING

Solar Irradiance Modelling And Uncertainty On Building Hourly Profiles Of Heating And Cooling Energy Needs

THERMAL INERTIA OF HOLLOW WALL BLOCKS: ACTUAL BEHAVIOR AND MYTHS

COMPUTER PROGRAM FOR THE ANGLES DESCRIBING THE SUN S APPARENT MOVEMENT IN THE SKY

STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION

3D UNSTEADY STATE ANALYSIS OF THERMAL PERFORMANCE OF DIFFERENTLY INSULATED FLOORS IN CONTACT WITH THE GROUND

Luminous Data Analysis and Quality Assurance of Climate Based Daylighting Simulation. Francesco Anselmo

U.P.B. Sci. Bull., Series C, Vol. 79, Iss. 1, 2017 ISSN

Inverse modeling of buildings with floor heating and cooling systems for benchmarking operational energy use

Available online at ScienceDirect. Energy Procedia 57 (2014 ) ISES Solar World Congress

Inverse modeling of buildings with floor heating and cooling systems for a real-time benchmark of the operational energy use

NUMERICAL ANALYSIS OF HEAT STORAGE AND HEAT CONDUCTIVITY IN THE CONCRETE HOLLOW CORE DECK ELEMENT

INFLUENCE OF THE AVERAGING PERIOD IN AIR TEMPERATURE MEASUREMENT

Parametric Study on the Dynamic Heat Storage Capacity of Building Elements Artmann, Nikolai; Manz, H.; Heiselberg, Per Kvols

WEATHER NORMALIZATION METHODS AND ISSUES. Stuart McMenamin Mark Quan David Simons

Double-Skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of Direct Solar Radiation

SWAT WEATHER DATABASE TOOL

Generation of an Annual Typical Meteorological Solar Radiation for Armidale NSWAustralia

Available online at ScienceDirect. Energy Procedia 81 (2015 )

A Typical Meteorological Year for Energy Simulations in Hamilton, New Zealand

3D-SDI contribution to energy-efficient cities 3D CityModels for Energy Demand Simulation

Potential daylight resources between tropical and temperate cities a case study of Ho Chi Minh City and Moscow

Solar Control in Traditional Architecture, Potentials for Passive Design in Hot and Arid Climate

Transcription:

Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 2560 2565 6th International Building Physics Conference, IBPC 2015 The influence of different hourly typical meteorological years on dynamic simulation of buildings Giacomo Chiesa a *, Mario Grosso a a Politecnico di Torino, Dept. Architecture and Design, Viale Mattioli 39, 10125 Torino, Italy Abstract This paper presents a parametric study on the effect of different TMY (Typical Meteorological Year) datasets on the results of energy dynamic simulation. The analysis was carried out running the software Design Builder with EnergyPlus code on a sample residential building located in three Italian cities and using two different TMY data sets: EnergyPlus and CTI (Italian Thermo- Technical Committee). As a support of the simulation results to be confirmed to a larger scale (the whole Italian territory), an analysis on the two TMY data sets was carried out by calculating CDH (Cooling Degree Hours) and HDD (Heating Degree Days) for 21 Italian locations together with annual global horizontal radiation and average annual mean daily wind velocity. The discrepancies found between the software data set and the more updated and locally validated CTI data set undermine the accuracy of simulation results hence flawing the energy performance assessment criteria based on those results. 2015 The Authors. Published by by Elsevier Ltd. Ltd. This is an open access article under the CC BY-NC-ND license Peer-review (http://creativecommons.org/licenses/by-nc-nd/4.0/). under responsibility of the CENTRO CONGRESSI INTERNAZIONALE SRL. Peer-review under responsibility of the CENTRO CONGRESSI INTERNAZIONALE SRL Keywords: dynamic simulation; hourly typical meteorological years; building simulations; energy performance 1. Introduction The use of dynamic energy simulation of buildings is increasing among both design professionals and scientists. Furthermore, the use of dynamic simulation for energy performance evaluation is required in some environmental certification protocols (e.g., LEED US based on ASHRAE 90.1-2013) as well as for design optimisation of innovative passive and hybrid energy saving technologies. Although there are several methods for calculating the indoor temperatures and the energy demand of a building, for complex geometries or special requirements, detailed simulation code are necessary [1]. As a climate data input, dynamic energy simulation codes need TMY based on hourly values, * Corresponding author. Tel.: +39-0110904371. E-mail address: giacomo.chiesa@polito.it 1876-6102 2015 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/). Peer-review under responsibility of the CENTRO CONGRESSI INTERNAZIONALE SRL doi:10.1016/j.egypro.2015.11.280

Giacomo Chiesa and Mario Grosso / Energy Procedia 78 ( 2015 ) 2560 2565 2561 which are not always easily accessible or available. In addition, for a given location, there might be different sources of meteorological databases, whose TMYs, even if elaborated in accordance with international standards (e.g. UNI EN ISO 15927-4), may diverge significantly. 1.1. Methodology and climate sources This paper focuses on the effect of different TMY datasets on the results of energy dynamic simulation. Firstly, a climate analysis was conducted on 21 Italian Province Capitol Cities by calculating CDH and HDD using different TMY sources (Fig. 1-a) as well as wind velocity and solar radiation monthly-averaged data. Secondly, a test on a sample residential building located in three Italian cities, Novara, Rome and Taranto, was performed to evaluate the effect of TMY divergence on the results of dynamic energy simulations using Design Builder with EnergyPlus code (Fig. 1-b). The discrepancies found affect significantly the results from dynamic energy performance simulation hence flawing the energy performance assessment criteria based on those results. Two TMY databases were used: a) the one embedded inside EnergyPlus - a code internationally recognised and used worldwide by professionals - and based on different weather data sources; b) a database recently elaborated by CTI with ENEA and the Italian Ministry of economic development for the 110 Italian Province Capitol Cities [2-3]. The EnergyPlus weather data for Italian cities refer to two sources: the International Weather for Energy Calculation (IWEC), typical weather files 2001 ASHRAE [4], and the Italian Climatic data collection Gianni De Giorgio (IGDG), based on recorded data from 1951-70 period [5]. Fig. 1. (a) Considered 21 locations and their specific heating climate zone according to the Italian legislation; (b) selected weather stations for dynamic simulations. 2. Climate analysis A climate analysis was carried out comparing cooling and heating typical conditions of the 21 locations represented in Fig. 1-a without taking building characteristics into account. The variation of ambient temperature for the different data sets was compared on a hourly basis using the parameters HDD and CDH, representing, respectively, heating and cooling conditions. In addition, monthly-averaged solar radiation and wind velocity data were compared. 2.1. Analysis on ambient temperature data 2.1.1. Heating Degree Days HDD was calculated for the 21 chosen Italian locations using the two above mentioned TMY data sets and compared as well to HDD values set by law (DPR 412-93, attachment A). EnergyPlus data were compared to CTI data for the 21 locations and two to three sources for a smaller sample of cities (Fig. 2). HDD was calculated according to UNI EN ISO 15927-6:2008, on a base temperature (ϑ b) set to 20 C, using the following equation: (1) Where:

2562 Giacomo Chiesa and Mario Grosso / Energy Procedia 78 ( 2015 ) 2560 2565 if ϑ h<20 C then ϑ h(20) = (20 - ϑ h ) else ϑ h(20) = 0 n = period of the heating season set by law and varying with climate zone (see Fig. 1-a). Fig. 2 shows a comparison between the HDD values derived from the chosen databases for each location. This comparison highlights some discrepancies as discussed below. Fig. 2 (b) is a zoom on seven locations for three different EnergyPlus weather data sources. Fig. 2. (a) HDD values for 21 Italian Province Capitol Cities calculated from the EnergyPlus and CTI data sources as well as taken from the Italian law; (b) HDD for 7 cities where EnergyPlus weather data set can be taken from two or three meteorological stations. 2.1.2. Cooling Degree Hours The influence of different TMY data sets on simulation for cooling energy analyses was evaluated using the index CDH, calculated by summing the positive hourly differences in temperature between the average hourly environmental DBT (ϑ h) and a fixed base temperature, assumed as 26 C. Calculation was conducted for a fixed extended summer period from May to October for all considered locations using the following equation: for positive values only (2) Fig. 3. (a) CDH values for 21 Italian Province Capitol Cities calculated using EnergyPlus and CTI data sources; (b) CDH values for 7 cities using CTI data and two or three weather stations available on EnergyPlus. Fig. 3 shows the differences between calculated CDH 26 based on CTI and EnergyPlus data sources for each locality. The two series of data show a discrepancy higher than for HDDs. A drastically reduced cooling need is apparent when using all EnergyPlus datasets compared to the CTI s in the majority of considered locations, especially in Southern Italy, where climate is hotter. These differences result to an underestimation of cooling needs by the simulation program due to not updated weather data set which is not taking into account the most recent global warming trend as instead is done by the CTI s. 2.2. Analysis on solar radiation and wind velocity data Data for the considered locations of total annual global solar radiation intensity on horizontal surface and annualaveraged daily mean wind velocity, compared amid the different weather sources, are shown in Fig. 4, respectively, (a) and (b).

Giacomo Chiesa and Mario Grosso / Energy Procedia 78 ( 2015 ) 2560 2565 2563 Fig. 4. Comparison amid different weather data sources, in the considered locations: a) total annual global solar radiation on horizontal surface - for the ENEA database see [6]; b) annual-averaged daily mean wind velocity. 2.3. Discussion of results Results of the climate analysis carried out on ambient temperature data are summarised in Fig. 5, which reports the frequency of relative difference of HDD and CDH values taken from EnergyPlus and CTI s data. It is apparent that the higher discrepancy occurs during the cooling period, e.g., in Potenza (621 Vs 3678 CDH) and Taranto (2451 Vs 7665 CDH). In winter, the majority of differences occurs in a range between ±10% of the reference HDD. An assessment of the trends related to solar radiation and wind velocity can be inferred from Fig. 4. Regarding solar radiation, data from the EnergyPlus source are, in general, underestimated in comparison to the other sources. This can lead to an underestimation of the cooling load, and an overestimation of heating load, in simulation programmes using that code. Data on wind velocity from the EnergyPlus source are overestimated in most locations compared to the CTI source, while are closer to the UNI-10349 source. This can lead to an overestimation of the potential reduction of cooling load due to wind-driven controlled natural ventilation in EnergyPlus simulations. Fig. 5. Percentage differences between index values from EnergyPlus and CTI s: (a) heating period; (b) cooling period. 3. Dynamic simulation In order to check the validity of the above described results when considering building characteristics into account, the influence of different TMY data on dynamic simulation was tested by using a reference residential building on three different Italian locations Novara, Rome, and Taranto comparing EnergyPlus weather data and CTI TMY elaborated as *.epw files. Fig. 6. Reference model: (a) axonometric view; (b) plan of the ground floor.

2564 Giacomo Chiesa and Mario Grosso / Energy Procedia 78 ( 2015 ) 2560 2565 3.1. Reference model The reference model is a two-storey residential building with one independent apartment at each floor. Total occupied net floor area is 246 m 2 with four persons per apt. and the net area of unoccupied attic space is 89.7 m 2. In Fig. 6, an axonometric view and a plan of the ground floor with rooms layout are shown. The main input values of the simulation, i.e., related to thermo-physical characteristics of construction elements, environmental control parameters, and schedules are shown in the following tables. The HVAC configuration is of a simple type, i.e., with ideal calculation of energy loads. Table 1. Thermo-physical parameters. Element U value (W/m 2 K) Internal heat capacity (kj/m 2 K) Roof slope slab 2.93 4.02 Top ceiling slab 0.25 32.61 Ground floor slab 0.34 93.96 External walls 0.29 134.80 Partitions 2.29 73.51 Total solar transmission Windows 1.96 0.69 0.62 Light transmission Table 2. Environmental control parameters Set-point temperature ( C) Target Lighting energy Air flow rate Heating Cooling illuminance (lux) (W/m 2 100lux) (l/s -person) 20 (12 backup) 26 (28 backup) 150 5 10 Table 3. Schedules. Activity/space Period Occupation (hours) Temperature Heating (hours) Temperature Cooling (hours) On Off Backup On Off Backup Living-kitchen-laundry Weekdays 7 9; 18 24 7 24 24 7 15 19 19 21 12 15 Weekends 8 19; 22 24 7 10 10 20 20 7 19 12 12 19 Holidays 10 12 7 10 10 20 20 7 19 12 12 19 Bedroom-bathroom Weekdays 24 8 19 24 8 19 24 8 12 17 24 12 17 24 Weekends 24 10 20 24 10 20 24 10 24 12 12 24 Holidays 24 10 20 24 10 20 24 10 24 12 12 24 Corridor-stairs Weekdays 9 10; 18 19 On during occupation schedule Weekends 10 11; 23 24 On during occupation schedule Holidays 9 10 On during occupation schedule 3.2. Results Amid the several simulation output data yielded by DesignBuilder with EnergyPlus, only the ones related to annual energy use for space heating and cooling were analysed for the purpose of this study. Results show (Fig. 7) that the divergences between EnergyPlus and CTI s TMYs, found through the above described climate analysis, affect energy use prediction significantly although with a lower quantitative impact. This was expected, since building envelop and environmental control systems mitigate climate parameters fluctuation over time. However, the differences found between output data related to the two TMYs reach about 17% for cooling and 39 % for heating. As expected, underestimates of cooling load occur using EnergyPlus TMY as compared to the most

Giacomo Chiesa and Mario Grosso / Energy Procedia 78 ( 2015 ) 2560 2565 2565 updated CTI s. Consistently, an overestimate of heating load were found except for the city of Rome, probably due to the different location of the reference meteorological stations. Fig. 7. (a) Annual simulated energy intensity for heating and cooling of the reference model based on the two TMYs; (b) relative differences. 3.3. Limitations of the study This study has investigated the influence of TMY data on dynamic energy simulation considering two data sources, a wide spectrum of Italian locations for the climate analysis, and three locations for estimating the effect on a building model. However, these limitations do not undermine the study s results although further applications to a larger variety of climate zones and building types could consolidate them, hence reinforcing the need for a climate data harmonisation and their better use in energy dynamic simulation. 4. Conclusion The results of this paper lead to the useful conclusion that the choice of a given weather file source influences the accuracy of predicted energy needs especially in summer. This outcome suggests an urgent need of developing a consistent uniformly elaborated and periodically updated climate database of TMY data for reference locations, representing all varieties of European as well as World climate zones. Moreover, TMY have to be made interoperable between various simulation codes. This is an important point especially when different building technological choices are compared using dynamic simulation programs for optimising energy performance and cost-effectiveness in various locations and climate zones. In addition, a better fit of simulation output to a real building context could help architects and engineers in their effort to design more energy efficient buildings, hence contributing to global warming mitigation. References [1] Lomas KJ. The U.K. Applicability Study: an Evaluation of Thermal Simulation Program for Passive Solar House Design. Building and Environment 1996; 31(3):197-206. [2] Baggio P, Corrado V, Murano G, Riva G. Definizione degli anni tipo climatici delle province del Nord Italia. La Termotecnica 2010; 9: 61-68. [3] Riva G, Murano G, Corrado V, Baggio P, Antonacci G. Definizione degli anni tipo climatici delle province delle regioni italiane del centro sud. Report RdS/2011/9, 2011. Roma; Agenzia Nazionale per le Nuove Tecnologie, l'energia e lo Sviluppo Economico Sostenibile (ENEA): 2011. [4] ASHRAE. International Weather for Energy Calculations (IWEC Weather Files) User Manual and CD-ROM; 2001. [5] Mazzarella L. Dati climatici G. De Giorgio. Proceedings of giornata di studio Giovanni De Giorgio. Milano: Politecnico di Milano; 1997. [6] ENEA, http://clisun.casaccia.enea.it/pagine/tabelleradiazione.htm#radiazionetabelle, viewed April 2015.