NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC.

Similar documents
NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NORTH EAST WINDOWS USA, INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed

SHANGHAI MYLCH WINDOWS & DOORS THERMAL PERFORMANCE TEST REPORT

THERMAL PERFORMANCE TEST REPORT

Test Results: Results of the test period on 06/19/16 using the Equivalent CTS Method: Thermal transmittance at test conditions (U s ):

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC.

AIR-INS inc. 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) Fax : (450)

Report No: NCTL NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

Report No: NCTL S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15. Test Specimen

NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: CMI ARCHITECTURAL PRODUCTS, INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: PARAMOUNT WINDOWS CORPORATION. SERIES/MODEL: 4000 TYPE: Fixed

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 7400 TYPE: Fixed

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC. PRODUCT: Fiberglass Door Slab

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: INTERNATIONAL ARCHITECTURAL PRODUCTS, INC. DBA: UNITED STATES ALUMINUM

NFRC THERMAL TEST SUMMARY REPORT January 27, 1999 Test Specimen

NFRC SOLAR HEAT GAIN COEFFICIENT TEST REPORT. Rendered to: CLEAR FOCUS IMAGING

Simulation Report (Revised) Rendered To: Showcase Custom Vinyl Windows 1002 Olde Towne Drive Irving, TX 75061

SIMULATION TEST REPORT NCTL E0A0

WINDOW SIMULATION REPORT

Standard Test Method for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Using Hot Box Methods 1

PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. PRODUCT: SUN TUNNEL Domes TYPES: Acrylic and Polycarbonate

PERFORMANCE TEST REPORT. Rendered to: WORLDWIDE DOOR COMPONENTS, INC. PRODUCTS: PVC and Composite Door Jamb Material

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT

ASTM C STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLOW METER APPARATUS

TEST METHOD FOR THERMAL TRANSMITTANCE AND AIR INFILTRATION OF GARAGE DOORS

REPORT NUMBER: MID-001 ORIGINAL ISSUE DATE: April 22, 2016 REVISED DATE: NA. EVALUATION CENTER Intertek 8431 Murphy Drive Middleton, WI 53562

Determination of installed thermal resistance into a roof of TRISO-SUPER 12 BOOST R

Determination of thermal transmittance of window (test title)

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND

National Fenestration Rating Council. Incorporated. NFRC [E0A1] Procedure for Determining Fenestration Product Condensation Resistance Values

Reflectec Thermal Fabric & Reflectec Fiberboard

Winter Night. Thermos 6mm Outdoors # #

CAE 463/524 Building Enclosure Design Fall 2012

Window air permeability measurement, watertightness and resistance to wind load (designation of the test)

CAE 331/513 Building Science Fall 2016

17.01 Maxblock Sunshades by Tubelite Description

QIRT th International Conference on Quantitative InfraRed Thermography

THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS. Agnieszka A. Lechowska 1, Jacek A. Schnotale 1

TEST OF MEASURED SOLAR HEAT GAIN VARIATION WITH RESPECT TO TEST SPECIMEN TILT

AR/IA 241 LN 231 Lecture 4: Fundamental of Energy

ISO INTERNATIONAL STANDARD

Solar Energy Cooking with the Sun

METHOD OF IN-SITU MEASUREMENT OF THERMAL INSULATION PERFORMANCE OF BUILDING ELEMENTS USING INFRARED CAMERA

Sound Absorption Test Intertek. kraft paper softwall + softblock modular system. m o l o d e s i g n, l t d

Building Envelope Requirements Overview Page 3-4

Use of Phase-Change Materials to Enhance the Thermal Performance of Building Insulations

ISO INTERNATIONAL STANDARD. Thermal performance of windows, doors and shutters Calculation of thermal transmittance Part 1: Simplified method

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

TEST REPORT. Page 1 of 11

REPORT NUMBER: GZU-001 ORIGINAL ISSUE DATE:

DeFelsko PosiTector Dew Point Meter with Anemometer (DPMA)

FG 623 Window Wall. Optional Features Integrates with standard Kawneer windows

TEST REPORT. Test Method : See the attached sheets.

Calculating the heat transfer coefficient of frame profiles with internal cavities

INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS

Vincent Barraud SOPREMA BASICS OF THERMAL INSULATION

Department of Mechanical Engineering ME 96. Free and Forced Convection Experiment. Revised: 25 April Introduction

Determining of Thermal Conductivity Coefficient of Pressed Straw (Name of test)

WITH LOW EMISSIVITY GLASS

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045

PERFORMANCE EVALUATION OF REFLECTIVE COATINGS ON ROOFTOP UNITS

Guide Specifications Section

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6266/ARL-SA6274 Revision 0 ARL

Solar Radiation 230 BTU s per Hr/SF. Performance Glazing Coatings, Layers & Gases

IBHS Roof Aging Program Data and Condition Summary for 2015

Warm surfaces warm edges Insulated glass with thermally improved edge seal

RIVERBANK ACOUSTICAL LABORATORIES

CRYOGENIC CONDUCTION COOLING TEST OF REMOVABLE PANEL MOCK-UP FOR ITER CRYOSTAT THERMAL SHIELD

TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES

Performance Assessment of PV/T Air Collector by Using CFD

THE IMPLICATION OF ENERGY EFFICIENT BUILDING ENVELOPE DETAILS FOR ICE AND SNOW FORMATION PATTERNS ON BUILDINGS

ACCEPTANCE PROCEDURE FOR ROMET ROTARY METER BODIES AND/OR MECHANICAL NON-CONVERTING AND CONVERTING MODULES

Thermal and mechanical modeling of thermal breaks in structural steel point transmittances

JULY, 2016 E.C Architects - Please contact your Kawneer representative for further assistance.

REPORT NUMBER: GZU -001 ORIGINAL ISSUE DATE:

Solar Flat Plate Thermal Collector

A L I O N Technical Center. Test Report. Port Coquitlam, British Columbia, Canada

DEVELOPMENT OF THE MEASURING SYSTEM FOR ANALYSING THE THERMAL PROPERTIES OF CLOTHING

5. AN INTRODUCTION TO BUILDING PHYSICS

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6956 Revision 1 ARL

Order No. G Date: September 8, 2010 REPORT NO CRT-001 TEST OF SMF/PAPI SYSTEM RENDERED TO

For sunshades using the Zee blades wind loads are reduced by 10 psf.

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6712/ARL-SA6713 Revision 0 ARL

The Electrodynamics of a Pair of PV Modules with Connected Building Resistance

Customer: Ashton Industrial Sales Ltd. South Road, Harlow Essex CM20 2AR UNITED KINGDOM. Project/Customer: Profilex HM spacer

Fluid Power Institute Summary Report. Burst Pressure Evaluation Project #52224

Uncertainty Workshop: Overview of uncertainty factors in HTGHPs

BACK TO BASICS: PIPE INSULATION

Flexitest Switch Assemblies Type FT-19R and FT-19RX Supersedes DB March 2008

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: PNEUTEK, INC.

Today s A/C systems include:

REQUEST FOR PROPOSALS

Introduction to Infrared Thermometry

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6986/ARL-SA6987 Revision 0 ARL

ARCHITECTURE IN THE DAYLIGHT

Cat# LED Linear High Bay 100W

Energy and Insolation Review 2

E N L I G H T E N E D L I V I N G

Transcription:

NFRC 102-2014 THERMAL PERFORMANCE TEST REPORT Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: 45X - High Performance Dual Thermally Broken Storefront TYPE: Glazed Wall Systems (Site-built) Summary of Results Standardized Thermal Transmittance (U-Factor) 0.30 Unit Size: 78-3/4" x 78-3/4" (2000 mm x 2000 mm) (Model Size) Layer 1: 1/4" PPG Solarban z75 (e=0.018*, #2) Gap 1: 0.53" TS-D: Technoform TGI Wave Spacer 90% Argon* Layer 2: 1/4" Clear Reference must be made to Report No. F4786.04-116-46, dated 04/27/16 for complete test specimen description and data.

NFRC 102-2014 THERMAL PERFORMANCE TEST REPORT Rendered to: C.R. LAURENCE CO., INC. 2503 E. Vernon Avenue Los Angeles, California 90058-1826 Report Number: Test Date: Report Date: F4786.04-116-46 03/11/16 04/27/16 Test Sample Identification: Series/Model: 45X - High Performance Dual Thermally Broken Storefront Type: Glazed Wall Systems (Site-built) Overall Size: 78-3/4" x 78-3/4" (2000 mm x 2000 mm) (Model Size) NFRC Standard Size: 78.7" x 78.7" (2000 mm wide x 2000 mm high) Test Sample Submitted by: Test Sample Submitted for: Oldcastle BuildingEnvelope - Terrell, Texas Validation for Initial Certification (Production Line Unit) no Plant Qualification This report is a reissue of the original Report No. F4786.01-116-46. This report is reissued in the name of C.R. Laurence Co., Inc. through written authorization of Oldcastle BuildingEnvelope. Test Procedure: U-Factor tests were performed in a Guarded Hot Box in accordance with NFRC 102-2014, Procedure for Measuring the Steady-State Thermal Transmittance of Fenestration Systems. Test Results Summary: Standardized U-factor (Ust): 0.30 Btu/hr ft 2 F (CTS Method)

F4786.04-116-46 Page 2 of 8 Test Sample Description: Frame: Material: Size: Daylight Opening: Exterior Color: Interior Color: Corner Joinery: AT (0.22"): Aluminum with Thermal Breaks - All Members 78-3/4" x 78-3/4" (Model Size) 36-3/8" x 74-3/4" (x2) Glazing Method: Exterior Clear Exterior Finish: Anodized Clear Interior Finish: Anodized Square Cut / Screws / Sealed Glazing Information: Layer 1: 1/4" PPG Solarban z75 (e=0.018*, #2) Gap 1: Layer 2: 0.53" 1/4" TS-D: Technoform TGI Wave Spacer Clear Gas Fill Method: Single-Probe Method* 90% Argon* *Stated per Client/Manufacturer N/A Non-Applicable

F4786.04-116-46 Page 3 of 8 Test Sample Description: (Continued) Weatherstripping: Description FG-1133 gasket Quantity Location 1 row Interior and exterior glazing perimeter Hardware: Description Aluminum glass stop Quantity Location 2 Exterior sill AT (1.38") vertical filler 3 Verticals Drainage: Drainage Method Size Quantity Location No visible weeps

F4786.04-116-46 Page 4 of 8 Thermal Transmittance (U-factor) Measured Test Data Heat Flows 1. Total Measured Input into Metering Box (Qtotal) 995.67 Btu/hr 2. Surround Panel Heat Flow (Qsp) 51.24 Btu/hr 3. Surround Panel Thickness 8.00 inches 4. Surround Panel Conductance 5. Metering Box Wall Heat Flow (Qmb) 0.0236 Btu/hr ft 2 F 11.71 Btu/hr 6. EMF vs Heat Flow Equation (equivalent information) 0.0116*EMF + -0.102 7. Flanking Loss Heat Flow (Qfl) 7.59 Btu/hr 8. Net Specimen Heat Loss (Qs) 925.13 Btu/hr Areas 1. Test Specimen Projected Area (As) 43.07 ft 2 2. Test Specimen Interior Total (3-D) Surface Area (Ah) 48.61 ft 2 3. Test Specimen Exterior Total (3-D) Surface Area (Ac) 48.61 ft 2 4. Metering Box Opening Area (Amb) 75.11 ft 2 5. Metering Box Baffle Area (Ab1) 70.84 ft 2 6. Surround Panel Interior Exposed Area (Asp) 32.04 ft 2 Test Conditions 1. Average Metering Room Air Temperature (t h ) 69.80 F 2. Average Cold Side Air Temperature (t c ) -0.41 F 3. Average Guard/Environmental Air Temperature 71.26 F 4. Metering Room Average Relative Humidity 2.14 % 5. Metering Room Maximum Relative Humidity 2.26 % 6. Metering Room Minimum Relative Humidity 2.09 % 7. Measured Cold Side Wind Velocity (Perpendicular Flow) 12.66 mph 8. Measured Warm Side Wind Velocity (Parallel Flow) NA mph 9. Measured Static Pressure Difference Across Test Specimen 0.00" ± 0.04"H 2 O Average Surface Temperatures 1. Metering Room Surround Panel 68.18 F 2. Cold Side Surround Panel 0.35 F Results 1. Thermal Transmittance of Test Specimen (U s ) 2. Standardized Thermal Transmittance of Test Specimen (U st ) 0.31 Btu/hr ft 2 F 0.30 Btu/hr ft 2 F

F4786.04-116-46 Page 5 of 8 Thermal Transmittance (U-factor) Calculated Test Data CTS Method 1. Warm Side Emittance of Glass (e1) 0.84 2. Cold Side Emittance of Glass 0.84 3. Warm Side Frame Emittance* 0.80 4. Cold Side Frame Emittance* 0.80 5. Warm Side Sash/Panel/Vent Emittance* N/A 6. Cold Side Sash/Panel/Vent Emittance* N/A 7. Warm Side Baffle Emittance (eb1) 0.92 8. Cold Side Baffle Emittance (eb2) N/A 9. Equivalent Warm Side Surface Temperature 54.10 F 10. Equivalent Cold Side Surface Temperature 3.91 F 11. Warm Side Baffle Surface Temperature 68.79 F 12. Cold Side Baffle Surface Temperature N/A F 13. Measured Warm Side Surface Conductance (h h ) 1.37 Btu/hr ft 2 F 14. Measured Cold Side Surface Conductance (hc) 4.97 Btu/hr ft 2 F 15. Test Specimen Thermal Conductance (Cs) 0.43 Btu/hr ft 2 F 16. Convection Coefficient (Kc) 0.33 Btu/(hr ft 2 F 1.25 ) 17. Radiative Test Specimen Heat Flow (Qr1) 480.21 Btu/hr 18. Conductive Test Specimen Heat Flow (Qc1) 444.92 Btu/hr 19. Radiative Heat Flux of Test Specimen (qr1) 11.15 Btu/hr ft 2 F 20. Convective Heat Flux of Test Specimen (qc1) 10.33 Btu/hr ft 2 F 21. Standardized Warm Side Surface Conductance (hsth) 1.19 Btu/hr ft 2 F 22. Standardized Cold Side Surface Conductance (hstc) 5.28 Btu/hr ft 2 F 23. Standardized Thermal Transmittance (Ust) 0.30 Btu/hr ft 2 F Test Duration 1. The environmental systems were started at 17:48 hours, 03/10/16. 2. The test parameters were considered stable for two consecutive four hour test periods from 22:04 hours, 03/10/16 to 06:04 hours, 03/11/16. 3. The thermal performance test results were derived from 02:04 hours, 03/11/16 to 06:04 hours, 03/11/16. The reported Standardized Thermal Transmittance (Ust) was determined using CTS Method, per Section 9.2(A) of NFRC 102. *Stated per NFRC 101

F4786.04-116-46 Page 6 of 8 Glazing Deflection: Left Glazing Right Glazing Edge Gap Width Estimated center gap width upon receipt of specimen in laboratory (after stabilization) Center gap width at laboratory ambient conditions on day of testing Center gap width at test conditions 0.53" 0.53" 0.47" 0.50" 0.47" 0.50" 0.41" 0.41" Glass collapse determined using a digital glass and air space meter The sample was inspected for the formation of frost or condensation, which may influence the surface temperature measurements. The sample showed no evidence of condensation/frost at the conclusion of the test. test method does not include procedures to determine the heat flow due to either air movement through the specimen or solar radiation effects. As a consequence, the thermal transmittance results obtained do not reflect performances which are expected from field installations due to not accounting for solar radiation, air leakage effects, and the thermal bridge effects that have the potential to occur due to the specific design and construction of the fenestration system opening. The latter can only be determined by in-situ measurements. Therefore, it is important to recognize that the thermal transmittance results obtained from this test method are for ideal laboratory conditions and should only be used for fenestration product comparisons and as input to thermal performance analyses which also include solar, air leakage The test sample was installed in a vertical orientation, the exterior of the specimen was exposed to the cold side. The direction of heat transfer was from the interior (warm side) to the exterior (cold side) of the specimen. The ratings were rounded in accordance to NFRC 601, NFRC Unit and Measurement Policy. The data acquisition frequency is 5 minutes. Required annual calibrations for the Architectural Testing Inc., an Intertek company ("Intertek- ATI"), 'thermal test chamber' (ICN 000001) in York, Pennsylvania were last conducted in May 2015 in accordance with Intertek-ATI calibration procedure. A CTS Calibration verification was performed June 2015. A Metering Box Wall Transducer and Surround Panel Flanking Loss Characterization was performed July 2015.

F4786.04-116-46 Page 7 of 8 This report is a reissue of the original Report No. F4786.01-116-46. This report is reissued in the name of C.R. Laurence Co., Inc. through written authorization of Oldcastle BuildingEnvelope. "Ratings included in this report are for submittal to an NFRC licensed IA for certification purposes and are not meant to be used for labeling purposes. Only those values identified on a valid Certification Authorization Report (CAR) are to be used for labeling purposes." Intertek-ATI will service this report for the entire test record retention period. Test records that are retained such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Intertek-ATI for the entire test record retention period. The test record retention end date for this report is March 11, 2020. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen tested. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. For INTERTEK-ATI Tested By: Reviewed By: Ryan P. Moser Senior Technician Shon W. Einsig Senior Technician Individual-In-Responsible-Charge RPM:kmm F4786.04-116-46 Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: CTS Calibration Data (1) Appendix-B: Surround Panel Wiring Diagram (1) Appendix-C: Baffle Wiring Diagram (1) Appendix-D: Submittal Form and Drawings (13)

F4786.04-116-46 Page 8 of 8 Revision Log Rev. # Date Page(s) Revision(s).04R0 04/27/16 All Original Report Issue - Reissue of Report No. F4786.01-116-46 in the name of C.R. Laurence Co., Inc. This report produced from controlled document template ATI 00025(a), revised 01/21/2016.

Appendix A: CTS Calibration Data F4786.04-116-46 1. CTS Test Date 05/11/14 2. CTS Size 43.06 ft 2 3. CTS Glass/Core Conductance 0.42 Btu/hr ft 2 F 4. Warm Side Air Temperature 69.80 F 5. Cold Side Air Temperature -0.39 F 6. Warm Side Average Surface Temperature 54.35 F 7. Cold Side Average Surface Temperature 3.88 F 8. Convection Coefficient (Kc) 0.33 Btu/(hr ft 2 F 1.25 9. Measured Cold Side Surface Conductance (hc) 4.97 Btu/hr ft 2 F ) 10. Measured Thermal Transmittance 0.30 Btu/hr ft 2 F

Appendix B: Surround Panel Wiring Diagram F4786.04-116-46 +1 +2 +3 +4 +5 +6 +7 +8

Appendix C: Baffle Wiring Diagram F4786.04-116-46 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30

Appendix D: Submittal Form and Drawings F4786.04-116-46