Experimental study of dynamic thermal behaviour of an 11 kv distribution transformer

Similar documents
THERMAL BEHAVIOR OF DISTRIBUTION TRANSFORMERS IN SUMMERTIME AND SEVERE LOADING CONDITIONS

Accurate Location of Transformer Hottest Spot by FEM and Thermal Models

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 4, OCTOBER

HOTTEST SPOT AND LIFE EVALUATION OF POWER TRANSFORMER DESIGN USING FINITE ELEMENT METHOD

Estimation of Current Transformer Insulation Life with an Effect of Environmental Variables

Thermal model of oil power transformers with a tap changer

CIGRE SC A2 & D1 JOINT COLLOQUIUM 2011, KYOTO JAPAN. Assessment of Overload Capabilities of Power Transformers by Thermal Modelling.

Numerical investigation to study effect of radiation on thermal performance of radiator for onan cooling configuration of transformer

Predicting transformer temperature rise and loss of life in the presence of harmonic load currents

CIGRE SC A2 & D1 JOINT COLLOQUIUM 2011, KYOTO JAPAN. Water Saturation Limits and Moisture Equilibrium Curves of Alternative Insulation Systems

Technical Notes. Introduction. PCB (printed circuit board) Design. Issue 1 January 2010

Extensions to the Finite Element Technique for the Magneto-Thermal Analysis of Aged Oil Cooled-Insulated Power Transformers

The development of a Roebel cable based 1 MVA HTS transformer

I. Permission to publish. II. Offprint order. III. Copyright Transfer Statement (sign only if not submitted previously) Dear Christel Pierru,

CFD CALIBRATED THERMAL NETWORK MODELLING FOR OIL-COOLED POWER TRANSFORMERS

A Method for Estimating Transformer Temperatures and Elapsed Lives Considering Operation Loads

Technical note on calibration. - IEC model performance based on primary transformer load test

Excerpt from the Proceedings of the COMSOL Conference 2010 Paris

CHAPTER 3 CONVENTIONAL DESIGN SOLUTIONS

Determining Thermal Life Expectancy Of Power Transformer Under Non Linear Loads Using FEM By ANSYS And MATLAB

Estimation of Hottest Spot Temperature in Power Transformer Windings with NDOF and DOF Cooling

Optimization of condition-based asset management using a predictive health model

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

Hot Spot Temperature Analysis in 3 Phase Transformers Using FEM Method

Effect of Temperature on Condition Assessment of Oil-Paper Insulation using Polarization- Depolarization Current

JWG A2/D1.41 HVDC transformer insulation: Oil conductivity 1

Accurate Joule Loss Estimation for Rotating Machines: An Engineering Approach

Commissioning testing of a 1 MVA Superconducting transformer featuring 2G HTS Roebel cable

1. Introduction. 2. Use of COMSOL Multiphysics

Improved Transformer Thermal Models

THERMAL MODELING OF ELECTRICAL UTILITY TRANSFORMERS

DUBLIN INSTITUTE OF TECHNOLOGY Kevin Street, Dublin 8.

Thermal Modeling of Electrical Transformers

METALLIZED POLYPROPYLENE AC FILTERING CAPACITORS

Electrical Power Cables Part 2 Cable Rating Calculations

ELEC9712 High Voltage Systems. 1.2 Heat transfer from electrical equipment

Simulating Thermal Conditions around Core Bolts when Transformer is Experiencing Ferroresonance

Research on Transformer Condition-based Maintenance System using the Method of Fuzzy Comprehensive Evaluation

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits

NUMERICAL AND EXPERIMENTAL INVESTIGATION OF THE TEMPERATURE DISTRIBUTION INSIDE OIL-COOLED TRANSFORMER WINDINGS

Risk mitigation in the development of a Roebel cable based 1 MVA HTS transformer

Recent Improvements in K-Factor Models

3D Simulation of the Plunger Cooling during the Hollow Glass Forming Process Model, Validation and Results

Study of a Transformer Thermal System

The influence of thermal properties on power transmission characteristics of HVDC cables a factor analysis

Comparing Various Moisture Determination Methods for Power Transformers MAIK KOCH*, MICHAEL KRÜGER, STEFAN TENBOHLEN

By: Jin Huifei Supervisor: Dr.hab. ir.e Gulski (prof. of PUT) Lukasz Chmura, MSc

Thermal Modeling of Electrical Utility Transformer

Analyzing the Effect of Ambient Temperature and Loads Power Factor on Electric Generator Power Rating

Thermal Characterization of Packaged RFIC, Modeled vs. Measured Junction to Ambient Thermal Resistance

Cryogenic and Electrical Test Results of a 30 M HTS Power Cable

Thermal Model Parameters Transformers

Medium Power Film Capacitors

ELECTRICAL AND THERMAL DESIGN OF UMBILICAL CABLE

Modelling of Oil-filled Transformer

KTY-84. Product information for which Carbex bears no responsibility is provided by the manufacturer.

Medium Power Film Capacitors

ANALYSIS OF DIFFERENT DYNAMIC LINE RATING SYSTEM CONFIGURATIONS IN A DISTRIBUTION LINE

ENERGY DISTRIBUTION ANALYSIS IN A LOW HEAD FRANCIS TURBINE DURING THERMODYNAMIC EFFICIENCY MEASUREMENTS

Keywords: Superconducting Fault Current Limiter (SFCL), Resistive Type SFCL, MATLAB/SIMULINK. Introductions A rapid growth in the power generation

Damping resistor design consideration

Critical Investigation of Heat Transfer in Oil Cooled Transformer

Solar Flat Plate Thermal Collector

O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM

Experimental Evaluation of Natural Heat Transfer in Façade Integrated Triangular Enclosures

Development of high-efficiency Stirling cryocoolers for high temperature superconducting motors

THERMAL ANALYSIS OF UMBILICAL CABLES

Modelling and Analysis of the JET EP2 Neutral Beam Full Energy Ion Dump Curved End Plate

FEATURES APPLICATIONS DESCRIPTION QUICK REFERENCE DATA. PILKOR components

EFFECT OF DISTRIBUTION OF VOLUMETRIC HEAT GENERATION ON MODERATOR TEMPERATURE DISTRIBUTION

Chapter 6: Efficiency and Heating. 9/18/2003 Electromechanical Dynamics 1

International Journal of Advance Engineering and Research Development THERMAL ANALYSIS OF POWER TRANSFORMER USING FEM

Keywords: HVDC cable, Analytical calculation, PMLTCT, PMITD.

Physics 43, Fall 1995 Lab 1 - Boltzmann's Law

High Power Transformers Failures due to Flow Electrification: Tools for Understanding the Electrostatic Hazard.

INTERNATIONAL STANDARD

Applied Thermal Engineering

Electrical Breakdown Properties of Oil-paper Insulation under Pulsating Voltage Influenced by Temperature

Latest Status of High Temperature Superconducting Cable Projects

Selecting the current rating for equipment

U LED modules, converters and systems GENERAL ILLUMINATION. Umodule SPOT P320-2 umodule SPOT C.PHASED NTC

UNIT FOUR SOLAR COLLECTORS

Tick the box next to those resources for which the Sun is also the source of energy.

BETTER DESIGN AND NEW TECHNOLOGIES IMPROVE LASER POWER MEASUREMENT INSTRUMENTATION

Elman Recurrent Neural Network in Thermal Modeling of Power Transformers

LED light engine / OLED LED linear / area

U LED modules, converters and systems GENERAL ILLUMINATION. Umodule SPOT P310-2 umodule SPOT C.PHASED NTC

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

The Electrodynamics of a Pair of PV Modules with Connected Building Resistance

Dynamic Loading of Substation Distribution Transformers: Detecting Unreliable Thermal Models. and Improving the Accuracy of Predictions

50 W Power Resistor, Thick Film Technology, TO-220

Diagnosis of Electrical Performance and Aging Behavior of Transformer Dielectrics

TankExampleNov2016. Table of contents. Layout

Thermal Power Calibration of the TRIGA Mark II Reactor

Insulation Resistance and Polarization of Rotating Machines

Calibration of Temperature Block Calibrators

Thermal Resistance Measurement

Experimental Study of Convective Heat Transfer and Thermal Performance in the Heat-Sink Channel with Various Geometrical Configurations Fins

Thermal analysis of superconducting undulator cryomodules

Transcription:

24th International Conference & Exhibition on Electricity Distribution (CIRED) 12-15 June 2017 Session 1: Network components Experimental study of dynamic thermal behaviour of an 11 kv distribution transformer Rafael Villarroel, Qiang Liu, Zhongdong Wang School of Electrical and Electronic Engineering, The University of Manchester, Manchester, UK E-mail: zhongdong.wang@manchester.ac.uk ISSN 2515-0855 doi: 10.1049/oap-cired.2017.1102 www.ietdl.org Abstract: This study investigates the dynamic thermal behaviour of a 200 kva, 11/0.433 kv mineral oil filled and oil natural air natural cooled distribution transformer manufactured with 16 fibre optic sensors inside the tank. The transformer was subjected to extended temperature rise tests under multiple levels of constant loadings, i.e. 0.7, 1.0 and 1.25 pu to derive the thermal parameters required in the International Electrotechnical Commission thermal model for estimating the hot-spot temperature (HST). Measured and estimated HSTs are compared through a validation test simulating a short period overloading up to 1.8 pu for 2 h. Based on the data availability, three scenarios or cases are proposed to derive thermal parameters. Thermal parameters derived based the internal fibre optic sensor measurements provide the best estimation of HST. 1 Introduction Reliability of transformers is essential for the safe operation of distribution networks. One of the main failure mechanisms of distribution transformers is bubble formation under overheated conditions, which is predominately determined by the hot-spot temperature (HST) inside the transformer. In addition, HST is essential to estimate the life expectancy of transformer insulation system [1]. The dynamic thermal rating (DTR) of distribution transformers requires understanding the thermal behaviour of transformers under dynamic load scenarios. The key to DTR is to estimate the HST, based on which the rating of transformer can be optimised responsively and predictably. The HST is described as the sum of the ambient temperature, the top-oil temperature rise and the hot-spot-to-top-oil gradient in IEEE C57.91 [2]. It should be referred to the adjacent top-oil temperature inside the winding [3], where the oil temperature increases linearly from bottom to top and the temperature of the winding rise is parallel to the oil temperature rise, with a constant difference g r between the two straight lines [3]. Fibre optic sensors have been widely used to measure temperature distribution and the HST for power transformers [4, 5]. In this work, the same technique is used to carry out a set of temperature rise tests for a 11 kv distribution transformer, where different cases of available information are proposed to analyse their effect on the HST derivation. Referring to the International Electrotechnical Commission (IEC) thermal model [3], a set of new thermal parameters are then determined based on the experimental results. An additional test simulating a short period overloading is undertaken to verify the newly derived thermal parameters. 2 Tested transformer The transformer used in this work is a 200 kva, 11/0.433 kv distribution transformer with oil natural air natural cooling mode and filled with mineral oil. It has been specially manufactured with 16 fibre optic temperature sensors embedded into different locations carefully chosen in order to capture the HST and the topand bottom-oil temperatures inside the tank. 3 Experimental description A set of extended temperature rise tests on the transformer were carried out according to IEC 60076-2 [6], where the short-circuit method was used. 3.1 Experimental setup The short-circuit method followed the procedure specified in IEC standard 60076-2 [6]. During the test, the low-voltage terminals of the transformer were short circuited using a solid copper link, and the transformer is then subjected to a test current corresponding to the calculated total losses (load losses plus no-load losses) [7]. A schematic diagram of the experimental setup is shown in Fig. 1. Top oil temperatures were measured by thermocouples at the oil pocket on the top of the transformer and top of the radiator (upper tube to the radiator), whereas bottom oil temperature at the bottom of the radiator (lower tube to the radiator). In addition to the thermocouples placed outside of the tank, temperatures inside the transformer were measured by fibre optic sensors installed at the top of the low-voltage (LV) and high-voltage (HV) windings to register the HST as well as sensors installed in a Bakelite frame next to the inlet and outlet of the radiator to measure the top and bottom temperatures. Ambient temperature around the transformer was also measured by four thermocouples immersed in small oil-filled containers at 1 m high from ground and at a distance of 2 m from each side of the transformer according to [6], and the average of their readings is used for the evaluation of the ambient temperature. 3.2 Extended temperature rise tests The steady-state oil temperature rise at top and bottom of the transformer as well as the average winding temperatures are measured at constant load profiles of 0.7, 1.0 and 1.25 pu according to IEC 60076-2 [6]. At the beginning of the test, the transformer is subjected to a test current corresponding to the total losses (load losses plus no-load losses) at the 1.0 pu, until reaching the steady state, where the rate of change of top-oil temperature rise had fallen below 1 K/h and remained there for a period of 3 h. In the second step, the test 158 This is an open access article published by the IET under the Creative Commons

Table 1 Absolute temperatures in C from temperature rise tests Temperature 0.7, pu 1.0, pu 1.25, pu average ambient 18.8 17.6 18.3 HST (LV phase A) 56.9 80.6 102.0 internal top oil 44.4 60.3 76.5 internal bottom oil 35.9 50.4 65.0 oil pocket 40.9 55.2 69.8 external top oil 37.8 51.0 63.9 external bottom oil 33.3 46.2 59.7 Fig. 1 Experimental setup of temperature rise tests current is reduced to the current corresponding to the load losses for a duration of 1 h. In the final step, the load supply is disconnected, and the average winding resistance measurement starts. The average winding temperatures are determined from the continuous resistance measurements. Due to the winding resistance value decreases with time, measurements must be extrapolated backwards in time to the instant of shutdown to obtain the winding resistance value at that time. The duration of the winding resistance cooling down curve should be at least two times the thermal time constant of the winding [6], then the total duration of the measurements was 30 min, according to the characteristics of the transformer used, and measurements were taken in intervals of 15 s. The procedure applied to 1.0 pu load profile was repeated to 0.7 and 1.25 pu load profiles to complete the extended temperature rise tests. 4 Experimental results The hottest temperature was always measured at the top of the LV winding in phase A, furthest away from the radiator, from a total of eight sensors distributed at the top of HV and LV windings. The dynamic profiles of HST recorded during the extended temperature rise tests at 0.7, 1.0 and 1.25 pu are shown in Fig. 2. Top-oil temperatures were measured at different locations inside and outside the transformer tank. Measurements at internal top oil give the highest values followed by oil pocket and then external top oil. Bottom-oil temperatures were also recorded at internal and external locations, where measurements at internal bottom oil give higher values than those at external bottom oil. Table 1 summarises the measured temperatures at the oil pocket, internal top oil and bottom oil, external top oil and bottom oil, hotspot at the LV winding in phase A and ambient, which are used in this work to derive the thermal parameters. 5 IEC thermal model The thermal model in standard IEC 60076-7 [3] was adopted to estimate the HST. It considers the HST as a function of time, for varying load current and ambient temperature. Therefore, a HST corresponding to a load factor of K is given by [3] where { } [ ]x u h ()=u t a + Du oi () + Du or 1 + R K2 1 + R f 1 ()+A t Du oi () { A = Du hi () + H g r K y } Du hi () f2 () t f 1 (t) = (1 e ( t)/(k 11 t o ) ) ( f 2 (t) =k 21 1 e ( t)/(k 22 t w ) ) ( (k21 1) 1 e ( t)/(t 0 /k 22 ) ) Function f 1 (t) describes the increase of the top-oil temperature rise according to the unit of the steady-state value, while f 2 (t) describes the relative increase of the hot-spot-to-top-oil gradient. Parameters required to implement (1) are: thermal model constants k 11, k 21 and k 22 which are given in [3]; θ h is the HST, θ a is the ambient temperature, Δθ o and Δθ or are the top-oil temperature rise in steady state at the load considered and at rated losses, respectively, Δθ h is the hot-spot-to-top-oil gradient at the load considered, K is the load factor used during the tests, R is the ratio of load losses at rated current to no-load losses obtained from routine tests, H is the hot-spot factor (HSF), and g r is the average-winding-to-average-oil temperature gradient at rated current. Oil exponent (x), winding exponent (y), oil time constant (t o ) and winding time constant (t w ) are thermal parameters to be determined by implementation of the differential equations solution method proposed in [3]. (1) 6 Derivation of thermal parameters To study the effect of the locations of the sensors on the estimation of the HST, three different scenarios/cases are proposed to derive thermal parameters. Cases proposed and studied in this work are given as follows: Fig. 2 Hotspot temperature in LV windings (phase A) at different constant load profiles Case 1 is based on the estimation of the HST using thermal parameters proposed in the standard IEC 60076-7 [3]. This case This is an open access article published by the IET under the Creative Commons 159

represents the scenario that temperature rise test results are not available. Therefore it uses conservative values, i.e. the temperature rise limit required in IEC 60076-2 [6], top-oil temperature rise of 60 K over ambient temperature and HST rise of 18 K over top-oil temperature. Case 2 estimates the HST using derived thermal parameters from temperature rise tests based on external temperature measurements, therefore values at the top and bottom of the radiator pipe and oil pocket are used to estimate the top-oil temperature and the average oil temperature. HST is not directly measured in this case, so it is then derived from the HSF of 1.1 suggested for distribution transformers [3]. This case is commonly used in factory when internal fibre optic sensors are not available. Case 3 estimates the HST using derived thermal parameters from measured temperatures inside the transformer based on fibre optic sensors. HST is directly measured by fibre optic sensors inside the winding. This case is not frequently used in factory due to the complexity and cost of the fibre optic sensors installation. However, it seems necessary in terms of understanding a specific thermal design and corresponding thermal parameters. Fig. 4 Derivation of the oil exponent (x) for cases 2 and 3 6.1 Oil time constant (t o ) As it is mentioned in [8], the oil time constant can be derived by curve fitting of the top-oil temperature rise. Fig. 3 shows the top-oil temperature rise and exponential fitting curves for cases 2 and 3 proposed in this work, to determine the oil time constant at 1.0 pu load profile. Oil time constant for case 1 is taken from IEC 60076-7 [3]. Oil time constant values obtained are: case 1 = 180 min (taken from [3]), case 2 = 216 min and case 3 = 244 min. 6.2 Winding time constant (t w ) A numerical extrapolation method of cooling down curve proposed in [6] was used to determine the winding time constant. This method can be used to fit an analytical function to a set of timewise equidistant temperature readings. The winding time constants (t w ) were then calculated for both cases 2 and 3 based on the average oil temperature from thermocouples/fibre optic sensors placed at the aforementioned locations as well as the average winding resistance measurements. Winding time constant values obtained are: case 1 = 4 min (taken from [3]), case 2 = 9.6 min and case 3 = 9.4 min. 6.3 Oil exponent (x) According to IEC 60076-7 [3] when the transformer reaches the steady state, the top-oil temperature rise can be determined by [3] Du o = [ ]x 1 + R K2 1 + R Du or (2) where R and Δθ o are obtained from routine test and extended temperature rise tests, respectively, then the oil exponent (x) can be [ obtained by plotting the ratio of Δθ o /Δθ or against the value of (1 + R K 2 ] )/(1 + R) in a log log plot. Derivation of (x) is shown in Fig. 4, where values correspond to the slope of the straight line that best fits all points. Oil exponent values are: case 1 = 0.80 (taken from [3]), case 2 = 0.82 and case 3 = 0.79. 6.4 Winding exponent (y) The winding exponent (y) can be also derived from steady-state conditions by plotting the ratio of the average winding resistance under a load factor (K) and the average winding resistance at rated load factor against the load factor in a log log plot according to the following equation [3]: g = g r K y (3) In the same way, derivation of (y) is shown in Fig. 5, where values correspond to the slope of the straight line that best fits all points. Winding exponent values are: case 1 = 1.6 (taken from [3]), case 2 = 1.4 and case 3 = 1.5. As results of this section, Table 2 summarises all thermal parameters derived from the extended temperature rise tests and proposed in IEC 60076-7 [3] for the three cases proposed in this work. Key parameters such as Δθ or, the hot-spot-to-top-oil gradient at rated current (Δθ hr ) and g r are obtained from the temperature rise tests for both case 2 and case 3. H is taken as the ratio of the Δθ hr to g r for case 3, which is 1.5. While HST measurements are not available for case 1 and case 2, H of 1.1 is used according to IEC 60076-7 [3]. 7 Experimental validation Fig. 3 Fitting top-oil temperature rise from internal fibre optic sensor and oil pocket at 1.0 load factor Thermal parameters derived in this work (Table 2) were validated by comparing the measured HST with the estimated one in a validation test which represents a short period overloading scenario. It is based on a two-step load profile where the transformer was subjected to 160 This is an open access article published by the IET under the Creative Commons

Fig. 5 Derivation of the winding exponent (y) for cases 2 and 3 Fig. 6 Comparison of the estimated HST using parameters from cases 1, 2 and 3 and the measured HST under a two-step overloading profile Table 2 Summary of thermal parameters for three case studies Parameters Case 1 Case 2 Case 3 Δθ or, K 60.0 37.6 42.7 Δθ hr, K 18.0 17.7 20.3 x 0.80 0.82 0.79 y 1.6 1.4 1.5 t o, min 180 216 244 t w, min 4.0 9.6 9.4 g r 16.4 16.1 13.6 H 1.1 1.1 1.5 0.7 pu for 17 h, 1.8 pu for 2 h and 0.7 pu for 4 h. Fig. 6 shows a comparison of three estimated HSTs from the proposed cases and the measured HST using fibre optic sensors. 7.1 Root-mean-square-deviation (rmsd) To quantify the difference between the experimental HST curve and the estimated curve, the calculation of the root-mean-square-deviation (rmsd) was done according to (4), which has been used in previous works [9]. Where n is the number of readings, u HS( estimated) and u HS( experimental) are the estimated HST and the measured HST, respectively 1 n [ ( ) ( )] rmsd = 2 u n HS( estimated) t i uhs( experimental) t i i=1 Values obtained for the three cases are: case 1 = 12.4, case 2 = 6.2 and case 3 = 2.2, which indicates case 3 provides the best estimation of HST. From Fig. 6, it can be noticed that the estimation obtained using thermal parameters from case 1 is far from the experimental data, where the HST reached a peak value of 155.1 C, overestimated by 32.6 C compared to the measured value. On the other hand, although the estimated HST using thermal parameters from case 2 fits better to the measured values than the one from case 1, it is underestimated by 10.3 C. The thermal parameters obtained from case 3 using internal fibre optic sensors provide the best estimation of HST with a maximum difference of 4 C. (4) 8 Conclusion In this work, a 200 kva, 11/0.433 kv distribution transformer with built-in fibre optic sensors has been tested under different load scenarios to study its DTR. Extended temperature rise tests under three constant load profiles have been carried out on the transformer to derive thermal parameters needed to estimate the HST by implementing the IEC thermal model. Based on the data measured from internal and external sensors as well as values taken from the IEC standard, three different cases or scenarios have been proposed to analyse the thermal behaviour of the transformer. The HST was estimated and compared with experimental data obtained from an additional validation test based on a two-step load profile, where the transformer was subjected to a load peak value of 1.8 pu for 2 h. The HST was overestimated when thermal parameters referred to the IEC standard (case 1) were used. Thermal parameters derived from external sensors (case 2) underestimated the HST. The best estimation of the HST was achieved by implementing thermal parameters derived from internal sensors (case 3). Comparing the three sets of thermal parameters, one of the key differences is oil time constant, which could be the major reason causing the different estimation of HST under short term overloading conditions. 9 Acknowledgments This work was funded by the Engineering and Physical Sciences Research Council (EPSRC) through the Innovate UK consortium project Common Application Platform for Low Voltage Network Management, grant number EP/N508421/1. Special thanks to Innovate UK and the industry partners EA Technology and Nortech for their contributions to this project. The authors would also like to thank Winder Power for its valuable input on the construction of the transformer used in this work. 10 References 1 CIGRE Working Group A2.24: Thermal performance of transformers, Technical Brochure 393, vol. 129, 2009 2 IEEE C57.91: Guide for loading mineral-oil-immersed transformers and step-voltage regulators, 2012, pp. 1 123 3 IEC 60076-7: Power transformers Part 7: loading guide for oil-immersed power transformers, 2005 4 Radakovic, Z., Feser, K.: A new method for the calculation of the hot-spot temperature in power transformers with ONAN cooling, IEEE Trans. Power Deliv., 2003, 18, pp. 1284 1292 This is an open access article published by the IET under the Creative Commons 161

5 Susa, D., Nordman, H.: A simple model for calculating transformer hot-spot temperature, IEEE Trans. Power Deliv., 2009, 24, pp. 1257 1265 6 IEC 60076-2: Power transformers Part 2: temperature rise for liquid-immersed transformers, 2011 7 IEC 60076-1: Power transformers Part 1: general, 2011 8 Gao, Y., Wang, Z., Jones, D.: How to make use of transformer heat run test results? Review on thermal parameter derivation methods. Int. Conf. on Condition Monitoring and Diagnosis (CMD), 2014, pp. 383 387 9 Villarroel, R., García, D. F., García, B., et al.: Moisture diffusion coefficients of transformer pressboard insulation impregnated with natural esters, IEEE Trans. Dielectr. Electr. Insul., 2015, 22, pp. 581 589 162 This is an open access article published by the IET under the Creative Commons