Three-phase AC Circuits. Measurement of Power in a Three-phase Circuit

Similar documents
Module 4. Single-phase AC circuits. Version 2 EE IIT, Kharagpur

mywbut.com Lesson 16 Solution of Current in AC Parallel and Seriesparallel

Three Phase Systems 295

Power and Energy Measurement

Module 4. Single-phase AC Circuits

VTU E-LEARNING NOTES ON:

Power and Energy Measurement

LO 1: Three Phase Circuits

Module 4. Single-phase AC Circuits. Version 2 EE IIT, Kharagpur 1

Three Phase Circuits

Work, Energy and Power

BASIC PRINCIPLES. Power In Single-Phase AC Circuit

Week No. 6 Chapter Six: Power Factor Improvement

Refresher course on Electrical fundamentals (Basics of A.C. Circuits) by B.M.Vyas

Power Factor Improvement

Electric Circuits II Power Measurement. Dr. Firas Obeidat

Sinusoidal Response of RLC Circuits

FACULTY OF ENGINEERING LAB SHEET

Total No. of Questions :09] [Total No. of Pages : 03

Lecture 11 - AC Power

EEE3405 ELECTRICAL ENGINEERING PRINCIPLES 2 - TEST

Work, Energy and Power

Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations

Unit-3. Question Bank

UNIT- I Phase Sequence:

Conventional Paper-I Part A. 1. (a) Define intrinsic wave impedance for a medium and derive the equation for intrinsic vy

EE 3120 Electric Energy Systems Study Guide for Prerequisite Test Wednesday, Jan 18, pm, Room TBA

THREE-PHASE CIRCUITS

Single Phase Parallel AC Circuits

AC Power Analysis. Chapter Objectives:

THREE-PHASE CIRCUITS. Historical Profiles

Electrical Machines-I Prof. D. Kastha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Basics of Electric Circuits

Sinusoidal Steady State Analysis (AC Analysis) Part II

11. AC Circuit Power Analysis

Power Systems - Basic Concepts and Applications - Part I

ENE 104 Electric Circuit Theory

PARALLEL A.C. CIRCUITS

Module 7. Transformer. Version 2 EE IIT, Kharagpur

Chapter 32A AC Circuits. A PowerPoint Presentation by Paul E. Tippens, Professor of Physics Southern Polytechnic State University

Fault Analysis Power System Representation

Hours / 100 Marks Seat No.

ECE 476 Power System Analysis Fall 2014 Exam #1, Thursday, October 2, :30AM - 10:50AM

EE221 - Practice for the Midterm Exam

ECE 420. Review of Three Phase Circuits. Copyright by Chanan Singh, Panida Jirutitijaroen, and Hangtian Lei, For educational use only-not for sale.

coil of the circuit. [8+8]

MYcsvtu Notes

ECE 421/521 Electric Energy Systems Power Systems Analysis I 2 Basic Principles. Instructor: Kai Sun Fall 2013

Power Systems - Basic Concepts and Applications - Part I

Introduction to Synchronous. Machines. Kevin Gaughan

Chapter 1W Basic Electromagnetic Concepts

Brief Steady of Power Factor Improvement

Generation, transmission and distribution, as well as power supplied to industrial and commercial customers uses a 3 phase system.

BASIC NETWORK ANALYSIS

Electrical Circuits Lab Series RC Circuit Phasor Diagram

EE313 Fall 2013 Exam #1 (100 pts) Thursday, September 26, 2013 Name. 1) [6 pts] Convert the following time-domain circuit to the RMS Phasor Domain.

CHAPTER 22 ELECTROMAGNETIC INDUCTION

ECEN 460 Exam 1 Fall 2018

Chapter 5 Steady-State Sinusoidal Analysis

Revised October 6, EEL , Henry Zmuda. 2. Three-Phase Circuits 1

Analysis of AC Power RMS and Phasors Power Factor. Power Factor. Eduardo Campero Littlewood

ANDERSON S BRIDGE & SCHERING S BRIDGE

SHREE DATTA SHETKARI SAHAKARI KARKHANA LTD. CHARITABLE TRUST SHREE DATTA POLYTECHNIC COLLEGE, DATTANAGAR CLASS TEST-01

In the previous chapter, attention was confined

THREE PHASE SYSTEMS Part 1

Lecture 05 Power in AC circuit

Physics-272 Lecture 20. AC Power Resonant Circuits Phasors (2-dim vectors, amplitude and phase)

Balanced three-phase systems and operation

REACTANCE. By: Enzo Paterno Date: 03/2013

Power system conductor volume calculation

04-Electric Power. ECEGR 452 Renewable Energy Systems

Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Synchronous Machines

12. Introduction and Chapter Objectives

Consider Figure What is the horizontal axis grid increment?

Alternating Current Circuits

6. Three-Phase Systems. Department of Electrical, Electronic, and Information Engineering (DEI) - University of Bologna

UNIVERSITY OF BOLTON SCHOOL OF ENGINEERING BENG (HONS) ELECTRICAL & ELECTRONICS ENGINEERING EXAMINATION SEMESTER /2018

Transmission Line Input Impedance

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

Chapter 2-3 Transformers

EXP. NO. 3 Power on (resistive inductive & capacitive) load Series connection

ALTERNATING CURRENT

Chapter 4. Synchronous Generators. Basic Topology

PHASOR DIAGRAM OF TRANSFORMER. Prepared By ELECTRICALBABA.COM

Energy saving in electromechanical equipment with power coefficient correction. Dimitris Al. Katsaprakakis Aeolian Land S.A.

ALTERNATING CURRENT. with X C = 0.34 A. SET UP: The specified value is the root-mean-square current; I. EXECUTE: (a) V = (0.34 A) = 0.12 A.

EDEXCEL NATIONAL CERTIFICATE UNIT 28 FURTHER MATHEMATICS FOR TECHNICIANS OUTCOME 2- ALGEBRAIC TECHNIQUES TUTORIAL 2 - COMPLEX NUMBERS

INVESTIGATION OF THREE PHASE SYSTEM

Review of DC Electric Circuit. DC Electric Circuits Examples (source:

Boise State University Department of Electrical and Computer Engineering ECE 212L Circuit Analysis and Design Lab

Physics 142 AC Circuits Page 1. AC Circuits. I ve had a perfectly lovely evening but this wasn t it. Groucho Marx

Module 4. Single-phase AC Circuits

Capacitor of capacitance C; Their schematic representations are shown in Figure below.

Assessment Schedule 2015 Physics: Demonstrate understanding of electrical systems (91526)

EE 212 PASSIVE AC CIRCUITS

ELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS

Prince Sattam bin Abdulaziz University College of Engineering. Electrical Engineering Department EE 3360 Electrical Machines (II)

Transformer. Transformer comprises two or more windings coupled by a common magnetic circuit (M.C.).

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

Transcription:

Three-phase AC Circuits Lesson Measurement of Power in a Three-phase Circuit In the previous lesson, the phase and line currents for balanced delta-connected load fed from a three-phase supply, along with the expression for total power, are presented. In this lesson, the measurement of total power in a three-phase circuit, both balanced and unbalanced, is discussed. The connection diagram for two-wattmeter method, along with the relevant phasor diagram for balanced load, is described. Keywords: power measurement, two-wattmeter method, balanced and unbalanced loads, star- and delta-connections. After going through this lesson, the students will be able to answer the following questions:. How to connect the two-wattmeter to measure the total power in a three-phase circuit both balanced and unbalanced? 2. Also how to find the power factor for the case of the above balanced load, from the reading of the two-wattmeter, for the two types of connections star and delta?

Two-wattmeter Method of Power Measurement in a Threephase Circuit W I N a VY L a Y I YN c L c L b b B W 2 I BN Fig. 20. Connection diagram for two-wattmeter method of power measurement in a three-phase balanced system with star-connected load The connection diagram for the measurement of power in a three-phase circuit using two wattmeters, is given in Fig. 20.. This is irrespective of the circuit connection star or delta. The circuit may be taken as unbalanced one, balanced type being only a special case. Please note the connection of the two wattmeters. The current coils of the wattmeters, & 2, are in series with the two phases, & B, with the pressure or voltage. coils being connected across Y and B Y respectively. Y is the third phase, in which no current coil is connected. If star -connected circuit is taken as an example, the total instantaneous power consumed in the circuit is, W= i N v N +i YN v YN + i v BN BN Each of the terms in the above expression is the instantaneous power consumed for the phases. From the connection diagram, the current in, and the voltage across the respective (current, and pressure or voltage) coils in the wattmeter, W are i N and v Y = v N v YN. So, the instantaneous power measured by the wattmeter, W is, W =i N v Y =i N ( v N v YN ) Similarly, the instantaneous power measured by the wattmeter, W 2 is, W 2 =i BN v BY =i BN ( v BN v YN ) The sum of the two readings as given above is, W + W = i v v 2 N ( N YN ) + i ( v v BN BN YN ) i =( i + i YN N BN ) Since, i N + i YN + i BN = 0 or, Substituting the above expression for i YN in the earlier one, W + W 2 =i N v N +i BN v BN +i YN v YN = i v + i v v i + i N N BN BN YN ( N BN )

If this expression is compared with the earlier expression for the total instantaneous power consumed in the circuit, they are found to be the same. So, it can be concluded that the sum of the two wattmeter readings is the total power consumed in the three -phase circuit, assumed here as a star-connected one. This may also be easily proved for deltaconnected circuit. As no other condition is imposed, the circuit can be taken as an unbalanced one, the balanced type being only a special case, as stated earlier Phasor diagram for a three-phase balanced star-connected circuit VBY VBN - IBN VY VN IYN + IN VYN VYB Fig. 20.2 Phasor diagram for two -wattmeter method of power measurement in a three-phase system with balanced star-connected load The phasor diagram using the two-wattmeter method, for a three-phase balanced starconnected circuit is shown in Fig. 20.2. Please refer to the phasor diagrams shown in the figures 8.4 &8.6b. As given in lesson No. 8, the phase currents lags the respective phase voltages by φ = φ p, the angle of the load impedance per phase. The angle, φ is taken as positive for inductive load. Also the neutral point on the load ( N ) is same as the neutral point on the source ( N ), if it is assumed to be connected in star. The voltage at that point is zero (0). The reading of the first wattmeter is, W = V Y I N cos (V Y, I N ) = V Y I N cos ( + ϕ ) = 3 V p I p cos ( + ϕ ) The reading of the second wattmeter is, W 2 = V BY I BN cos (V BY, I BN ) = V BY I BN cos ( ϕ ) = 3 V p I p cos ( ϕ ) The line voltage, V Y leads the respective phase voltage, V N by, and the phase voltage, V N leads the phase current, I N by φ. So, the phase difference between V Y & I

N is ( + φ ). Similarly, the phase difference between V BY & I BN in the second case, can be found and also checked from the phasor diagram. The sum of the two wattmeter readings is, W + W 2 = 3 V p I p [cos ( + ϕ ) + cos ( ϕ )] = 3 V p I p 2 cos cosφ = 3 V p I p cosφ = 3 V L I L cosφ So, (W + W 2 ) is equal to the total power consumed by the balanced load. This method is also valid for balanced delta-connected load, and can be easily obtained. The phasor diagram for this case is shown in the example No. 20.2. Determination of power factor for the balanced load The difference of the two wattmeter readings is, W 2 W = 3 V p I p [cos ( ϕ ) cos ( + ϕ )] = 3 V p I p 2 sin sin φ = 3 V p I p sin φ If the two sides is multiplied by 3, we get 3 (W 2 W ) = 3 V p I p sin φ = 3 V L I L sin φ From the two expressions, we get, W 2 W W W 2 = tanφ or, φ = tan 3 W 2 + W 3 W + W 2 The power factor, cosφ of the balanced load can be obtained as given here, using two wattmeter readings. cosφ = ( + tan 2 φ ) = 2 = 2 y + 3 W2 W + 3 W 2 + W W where, y = W 2 The two relations, cosφ and sin φ can also be found as, cosφ = W + W 2 = W + W 2 and sinφ = W2 + y W = W 2 W 3 V L I L 3 V p I p V L I L 3 V p I p Comments on Two Wattmeter eadings When the balanced load is only resistive (φ = 0 ), i.e. power factor ( cosφ =.0 ), the readings of the two wattmeters (W = W 2 cos = 0.866(+ve) ), are equal and positive. Before taking the case of purely reactive (inductive/capacitive) load, let us take first lagging power factor as ( cosφ = 0.5 ), i.e. φ = +60. Under this condition, W = 0.0, as W cos ( + 60 ) = cos 90 = 0.0, and W 2 cos( 60 ) = cos = 0.866(+ve) is positive.

It may be noted that the magnitudes of the phase or line voltage and also phase current are assumed to be constant, which means that the magnitude of the load impedance (inductive) is constant, but the angle, φ varies as stated. As the lagging power factor decreases from.0 to 0.5, with φ increasing from 0 to + 60, the reading of the first wattmeter, W decreases from a certain positive value to zero (0). But the reading of the second wattmeter, W 2 increases from a certain positive value to positive maximum, as the lagging power factor is decreased from.0 to 0.866 (= cos ), with φ increasing from 0 to +. As the lagging power factor decreases from 0.866 to 0.5, with φ increasing from + to + 60, the reading of the second wattmeter, W 2 decreases from positive maximum to a certain positive value. It may be noted that, in all these cases, W 2 > W, with both the readings being positive. If the lagging power factor is 0.0 (φ = +90 ), the circuit being purely inductive, the readings of the two wattmeters (W = W 2 cos( + 90 ) = cos20 = 0.5 ) are equal and opposite, i.e., W is negative and W 2 is positive. The total power consumed is zero, being the sum of the two wattmeter readings, as the circuit is purely inductive. This means that, as the lagging power decreases from 0.5 to 0.0, with φ increasing from + 60 to + 90, the reading of the first wattmeter, W decreases from zero (0) to a certain negative value, while the reading

of the second wattmeter, W 2 decreases from a certain positive value to lower positive one. It may be noted that W 2 > W, which means that the total power consumed, i.e., (W + W 2 ) is positive, with only W being negative. The variation of two wattmeter readings as stated earlier, with change in power factor (or phase angle) is now summarized in Table 20.. The power factor [pf] ( = cosφ ) is taken as lagging, the phase current lagging the phase voltage by the angle, φ (taken as positive (+ve)), as shown for balanced star-connected load in Fig. 20.2. The circuit is shown in Fig. 20.. All these are also valid for balanced delta-connected load. Sl. Power factor [pf] Wattmeter emarks No. (Phase angle) readings (W) W W 2. pf = unity [.0] +ve +ve W = W 2 (φ = 0 ) 2. 0.5 < pf <.0 +ve +ve W > W 2 ( 60 >φ > 0 ) 3. pf = 0.5 +ve zero Total power = W (φ = 60 ) (0.0) 4. 0.0 < pf < 0.5 +ve -ve W >W 2 (Total ( 90 >φ > 6 0 ) power = +ve) 5. pf = zero [0.0] +ve -ve W =W 2 (Total (φ = 90 ) power = zero (0.0)) Table 20. Variation of two wattmeter readings with change in power factor of the load current It may be noted that, if the power factor is leading (φ = negative (-ve)), the circuit being capacitive, the readings of the two wattmeters change with the readings interchanging, i.e.,w taking the value of W 2, and vice versa. All the points as stated earlier, remain valid, with the comments as given earlier. The first one (#) in Table 20. is a special case, neither lagging, nor leading, with pf =.0. But in second one (#2), both readings remain +ve, with W < W 2. Same is the case in fourth one (#4), where W is ve and W 2 is +ve, with W < W 2, total power being positive (+ve). For third case (#3), W = 0.0 and W 2 is +ve, with

total power = W 2. For last (fifth) case (#5), W is ve and W 2 is +ve, with W = W 2, total power being zero (0.0). Power measurement using one wattmeter only for a balanced load W I N L Y N (N) L Y L B Fig. 20.4 Connection diagram for power measurement using only one wattmeter in a three-phase system with balanced star-connected load IY IY W L

B Fig. 20.5 Connection diagram for power measurement using only one wattmeter in a three-phase system with balanced deltaconnected load The circuit diagram for measuring power for a balanced three-phase load is shown in Fig. 20.3. The only assumption made is that, either the neutral point on the load or source side is available. The wattmeter measures the power consumed for one phase only, and the reading is W = V p I p cos φ. The total power is three times the above reading, as the circuit is balanced. So, the load must be star -connected and of course balanced one, with the load neutral point being available. The load may also be delta-connected balanced one, if the neutral pinpoint on the source side is available. Otherwise for measuring total power for delta- connected balanced load using one wattmeter only, the connection diagram is given in Fig. 20.4. The wattmeter as stated earlier, measures power for one phase only, with the total power consumed may be obtained by multiplying it by three. L L Example 20. Calculate the readings of the two wattmeters (W & W 2 ) connected to measure the total power for a balanced star-connected load shown in Fig. 20.6a, fed from a three-phase, 400 V balanced supply with phase sequence as -Y-B. The load impedance per phase is (20 + j5) Ω. Also find the line and phase currents, power factor, total power, total reactive VA and total VA.

W Y Zp = 20 Ω jx L = j5 Ω N Zp L L Zp B W 2 (a) VBY VB VBN - VY IBN IYN + =36.8 IN VN VYN VYB (b) Fig. 20.6 (a) Circuit diagram for a three-phase system with balanced starconnected load (Example 20.) (b) Phasor diagram

Solution V L = 400 V Z N = Z p = 20 + j5 = 25 + 36.87 Ω As the star-connected load is balanced, the magnitude of the phase voltage is, V p = V L 3 = 400 3 = 23 V Taking the phase voltage, V N as reference, the phase voltages are, V N = 23 0 ; V YN = 23 20 ; V BN = 23 + 20 The phasor diagram is shown in Fig. 20.6b. It has been shown that the line voltage, V Y leads the corresponding phase voltage, V N by. So, the line voltages are, V Y = 400 + ; V YB = 400 90 ; V B = 400 +50 For a star-connected load, the phase and the line currents are same. The current in -phase is, I N = I = V N / Z p = (23.0 0 ) (25.0 + 36.87 ) = 9.24 36.87 A = (7.39 j 5.54) A Two other phase and line currents are, I YN = I Y = 9.24 56.87 A ; I BN = I B = 9.24 + 83.3 A The power factor of the load is cos φ = cos 36.87 = 0.8 lagging, with φ = +36.87, as the load is inductive. Total VA = 3 V p I p = 3 23.0 9.24 = 6.403 kva This can be taken as 3 V L I l = 3 400 9.24 = 6.403 kva Total power = 3 V p I p cos φ = 3 23.0 9.24 0.8 = 5.23 kw Total reactive VA = 3 V p I p sin φ = 3 23.0 9.24 sin 36.87 = 3.842 kva The readings of the two wattmeters are, W = V Y I cos ( + φ ) = 400 9.24 cos 66.87 =.45 kw The phase angle between V Y and I is 66.87, obtained using two phasors. W 2 = V BY I B cos ( φ ) = 400 9.24 cos 6.87 = 3.67 kw The phase angle between V BY and I B is 6.87, obtained using two phasors, where V BY = 400 + 90. The sum of two readings is (.45 + 3.67) = 5.2 kw, which is same as the total power computed earlier Example 20.2 Calculate the readings of the wattmeter (W) connected as shown in Fig. 20.7a. The load is the same, as in Fig. 20.7a (Ex. 20.), i.e., balanced star-connected one, with impedance of (20 + j5) Ω per phase, fed from a three-phase, 400 V, balanced supply, with the phase sequence as -Y-B.

W I Balanced starconnected Y load as in B Fig. 20.6(a) (a) VY 90 - IN VN VYB (b) Solution Fig. 20.7 (a) Circuit diagram (Example 20.2) (b) Phasor diagram The steps are not repeated here, but taken from previous example (20.). The phasor diagram is shown in Fig. 20.7b.

The phase voltage, V N is taken as reference as in Ex. 20.. The phase current, I N is I N = 9.24 36.87 A The phase angle, φ of the load impedance is φ = +36.87 The line voltage, V Y is V Y = 400 + V The line voltage, V YB is V YB = 400 90 V The reading of the wattmeter (W) is, W = V YB I N cos (V YB, I N ) == V L I p cos (90 + ϕ ) = 3 V p I p sinφ = 400 9.24 sin 36.87 = 2.28 kw The value is negative, as the load is inductive. The reading (W) is / 3 = 0.577 times the total reactive power as, 3 V p I p sinφ = 3 V L I L sinφ, or 3 times the reactive power per phase. Example 20.3 Calculate the readings of the two wattmeters (W & W 2 ) connected to measure the total power for a balanced delta-connected load shown in Fig. 20.8a, fed from a threephase, 200 V balanced supply with phase sequence as -Y-B. The load impedance per phase is (4 j4) Ω. Also find the line and phase currents, power factor, total power, total reactive VA and total VA. I Y X C = 4 Ω / = 4 Ω I Y IY Z IB IY Z Z IYB Z B W 2 I B (a)

VB VBY I B IB (+) 60 IY I (-) VY IYB VYB I Y (b) Fig. 20.8 (a) Circuit diagram for a three-phase system with balanced deltaconnected load (Example 20.3) (b) Phasor diagram Solution Z Y = Z p = 4 j4 = 9.8 45 Ω For delta-connected load, V L Taking the line or phase voltage V Y =V p = 200 V as reference, the line or phase voltages are, V Y = 200 0 ; V YB = 200 20 ; V B = 200 + 20 The phasor diagram is shown in Fig. 20.8b. The phase current, I Y is, I Y = V Y / Z p = (200.0 0 )/ (9.8 45 ) = 0. + 45 = (7.42 + j 7.42) A The other two phase currents are, I YN = 0. 75 A ; I B = 0. + 65 A The power factor of the load is cos φ = cos 45 = 0.707 leading, with φ = 45, as the load is capacitive. As the phase currents are balanced, the magnitude of the line current is 3 times the magnitude of the phase current, and the value is I = 3 I Y = 3 0. = 7.5 A It has been shown that the line current, I lags the corresponding phase current, I Y by. So, the line currents are, I = I Y I B = 0. + 45 0. + 65 = 7.5 + 5 A I Y = I YB I Y = 7.5 05 A ; I B = I B I YB = 7.5 + 35 A

The procedure is only presented, with the steps given in brief. Total VA = 3 V p I p = 3 200.0 0. = 6.06 kva This can be taken as 3 V L I l = 3 200 7.5 = 6.06 kva Total power = 3 V p I p cos φ = 3 200.0 0. 0.707 = 4.285 kw Total reactive VA = 3 V p I p sin φ = 3 200.0 0. sin 45. = 4.285 kva The readings of the two wattmeters are, W = V Y I cos ( + φ ) = 200 7.5 cos( 5 ) = 3.38 kw The phase angle between V Y and I is 5, obtained using two phasors. W 2 = V BY I B cos ( φ ) = 200 7.5 cos75 = 0.906 kw The phase angle between V BY and I B is 75, obtained using two phasors, where V BY = 200 + 60. The sum of two readings is (3.38 + 0.906) = 4.286 kw, which is same as the total power computed earlier Alternatively, the phase current, I Y can be taken as reference, with the corresponding phase voltage, V Y leading the current by the angle of the load impedance, φ = 45. So, the phase current and voltage are, I Y = 0. 0 A ; V Y = I Y 0 Z p φ = (0. 9.8) 45 = 200 45 V Two other phase currents and voltages are, I YB = 0. 20 ; I B = 0. + 20 V YB = 200 75 ; V B = 200 + 65 The line current, I is, I = I Y I B = 0. 0 0. + 20 = 7.5 + A Two other line currents are, I Y = 7.5 90 ; I B = 7.5 + 50 The other steps are not shown here. The readers are requested to study the previous lesson (No. 9) in this module. The measurement of power using two wattmeters for load (unbalanced or balanced), fed from a balanced three-phase supply, is discussed in this lesson. Also presented are the readings of the two wattmeters for balanced load, along with the determination of the load power factor from the two readings, and some comments on the way, the two readings vary with change in power factor of the load, with the magnitude of the load impedance remaining constant. Some examples are also described here. This is the last lesson in this module (No.5). In the next module (No.6) consisting of two lessons (no. 2-22) only, the discussion on magnetic circuits will be taken up. 20. Calculate the reading of the two wattmeter s (W, and W 2 ) connected to measure the power for a balanced three-phase load as given in the following. The supply voltage is 200V and the phase.

i. The connections of the wattmeter, W current coil is in phase, and the voltage coil is across and Y ii. The connections of the wattmeter, W 2 current coil is in phase B, and the voltage coil is across B and Y Draw the phasor diagram a. star- connected balanced load with (9-j5) Ω per phase b. delta-connected balanced load with (4+j4) Ω per phase. 20.2 The two wattmeter reading for a balanced three-phase load, are 300W and 00W respectively with the watt meter as given in Prob 20.. Calculate the total power, the line current, the power factor, and also the reactive VA. 20.3 A balanced delta-connected load with 50Ω per phase (Fig. 20.9), is fed from a three-phase 200V supply. Find the reading of the wattmeter. Y W 50 Ω M 50 Ω V 50 Ω B Fig. 20.9

List of Figures Fig. 20. Connection diagram for two-wattmeter method of power measurement in a three-phase balanced system with star-connected load Fig. 20.2 Phasor diagram for two-wattmeter method of power measurement in a threephase system with balanced star-connected load Fig. 20.3 Variation of the readings of two wattmeters (W & W 2 ) with power factor for a balanced load for the circuit of Fig. 20. Fig. 20.4 Connection diagram for power measurement using only one wattmeter in a three-phase system with balanced star-connected load Fig. 20.5 Connection diagram for power measurement using only one wattmeter in a three-phase system with balanced delta-connected load Fig. 20.6 (a) Circuit diagram for a three-phase system with balanced star-connected load (Example 20.) (b) Phasor diagram Fig. 20.7 (a) Circuit diagram (Example 20.2) (b) Phasor diagram Fig. 20.8 (a) Circuit diagram for a three-phase system with balanced delta-connected load (Example 20.3) (b) Phasor diagram