NEW DESIGN OF GROUND FAULT PROTECTION

Similar documents
Symmetrical Components. References

Reactive Power Solutions

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications

TECHNICAL BULLETIN 006 Symmetrical Components Overview. Introduction. I a g I b g I c

Distance Elements: Linking Theory With Testing

Figure 1-44: 4-Wire Wye PT Configurations

Identifying the Proper Impedance Plane and Fault Trajectories in Distance Protection Analysis

Analysis of a Relay Operation for an Intercircuit Fault

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

Performance Comparison Between Mho Elements and Incremental Quantity-Based Distance Elements

Effect of core balance current transformer errors on sensitive earth-fault protection in compensated MV networks

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA.

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

Traveling Wave Relays. Fault Location

Determination of Fault Location in Shunt Capacitor Bank through Compensated Neutral Current

Cahier Technique N 11 Guide de réglage de la protection de Distance. Distance Protection (F21) Setting Guide

Impedance relay and protection assemblies

ECEN 460 Exam 1 Fall 2018

Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs

Fault Location in Distribution Feeders with Distributed Generation using Positive Sequence Apparent Impedance

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 8: Unsymmetrical Faults

DISTANCE RELAY SETTINGS

Three Phase Circuits

PHASOR DIAGRAM OF TRANSFORMER. Prepared By ELECTRICALBABA.COM

Study of Time Correlation Between Lightning Data Recorded by LLS and Relay Protection

Selecting the current rating for equipment

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

CHAPTER 2 LOAD FLOW ANALYSIS FOR RADIAL DISTRIBUTION SYSTEM

T-PRO Application in Reactor Protection Using Neutral Differential and Timed Over-Current Back-up Protection

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

Module 3 : Sequence Components and Fault Analysis

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

Fault Analysis Power System Representation

Electrical Circuits Lab Series RC Circuit Phasor Diagram

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

Current protection I 2 t long-time protection

ALPS. Advanced Line Protection System

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

Calculations of Capacitance for Transposed Bundled Conductor Transmission Lines

KINGS COLLEGE OF ENGINEERING Punalkulam

A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

Faults on Electrical System. A Research

In the previous chapter, attention was confined

3VT4 Molded Case Circuit Breakers up to 1000 A

ECE 476 Power System Analysis Fall 2014 Exam #1, Thursday, October 2, :30AM - 10:50AM

Correlation between Lightning Impacts and Outages of Transmission Lines. H-D. BETZ Nowcast GmbH Munich Germany

Module 3 : Sequence Components and Fault Analysis

Single Phase Parallel AC Circuits

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers

Study of Transient Behaviour of the Capacitor Voltage Transformer

EE221 - Practice for the Midterm Exam

The Influence of Abnormal Data on Relay Protection

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Physics 1502: Lecture 25 Today s Agenda

LO 1: Three Phase Circuits

Fault Locating PRESENTED BY ERIK SCHELLENBERG IDAHO POWER

7. Transient stability

EEE3405 ELECTRICAL ENGINEERING PRINCIPLES 2 - TEST

THREE-PHASE CIRCUITS

A New Novel of transverse differential protection Scheme

Electromagnetic Oscillations and Alternating Current. 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3.

BVES Annual Reliability Public Presentation 2016 Performance

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

ECE 585 Power System Stability

Securing Sequence-Current Differential Elements

Adaptive Distance Relaying Scheme for Power Swing Tripping Prevention

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

POWER SWING AND OUT-OF-STEP CONSIDERATIONS ON TRANSMISSION LINES

BASIC PRINCIPLES. Power In Single-Phase AC Circuit

Electrical Power and Energy Systems

Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

CHAPTER 3 CONVENTIONAL DESIGN SOLUTIONS

PMU-Based Power System Real-Time Stability Monitoring. Chen-Ching Liu Boeing Distinguished Professor Director, ESI Center

THREE PHASE SYSTEMS Part 1

To order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle

Lesson 17: Synchronous Machines

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

Electrical Machines-I Prof. D. Kastha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling

Chapter 4. Synchronous Generators. Basic Topology

The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of Unbalanced Three Phases Electrical Distribution System

Secured Busbar Differential Protection Using A Computationally Efficient Dot Product Technique

EE Branch GATE Paper 2010

ECE 476. Exam #2. Tuesday, November 15, Minutes

Module 4. Single-phase AC Circuits

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

GATE 2008 Electrical Engineering

Studies on hyper scaling dielectric loss of grading capacitors of 500kv breakers

0-2 Operations with Complex Numbers

Micro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015

Power Factor Improvement

CIGRE US National Committee 2015 Grid of the Future Symposium. Setting-less Protection: Laboratory Experiments and Field Trials

LCR Series Circuits. AC Theory. Introduction to LCR Series Circuits. Module. What you'll learn in Module 9. Module 9 Introduction

RLC Circuit (3) We can then write the differential equation for charge on the capacitor. The solution of this differential equation is

Preventing Voltage Collapse with Protection Systems that Incorporate Optimal Reactive Power Control

Symmetrical Fault Current Calculations Unlv

High Voltage DC Transmission Prof. Dr. S.N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur

Transcription:

NEW DESIGN OF GROUND FAULT PROTECTION The 71st Annual Conference for Protective Relay Engineers Siemens AG 2018 All rights reserved. siemens.com/energy-management

Why do we need ground fault protection? widely used to protect transmission and distribution lines in case of ground faults can detect and isolate even high resistive ground faults which are not seen by distance protection often combined with a directional element and used in a teleprotection scheme equipped with phase selection also suitable for single pole tripping Page 2

Basic principle of ground fault protection Threshold T - Delay 3I 0 T 0 67N Trip 67N Pickup Ground fault protection is based on zero sequence current 3I = I + I + I 0 A B C Ground fault protection picks up if magnitude of zero sequence current exceeds threshold: 0 3I > threshold Page 3

Directional ground fault protection Threshold T - Delay 3I 0 AND T 0 67N Trip 3U 0 Directional element 67N Pickup directional element based on the angle between zero sequence current and zero sequence voltage Page 4

Directional ground fault protection Threshold T - Delay 3I 0 AND T 0 67N Trip 3I 2 3U 2 Directional element 67N Pickup directional element based on the angle between negative sequence current and negative sequence voltage Page 5

Directional ground fault protection, suited for single pole tripping Threshold T - Delay 67N Pickup 3I 0 AND T 0 3U 2 3I 2 Directional element Phase selector 67N Trip Phase A 67N Trip Phase B 67N Trip Phase C phase selection using the angle of zero sequence current compared to the angle of negative sequence current Page 6

Case 1: Wrong trip using zero sequence polarization wrong trip of directional ground fault protection Malaysia: 147 km line, 132 kv Figure left shows the impedance trajectories in the complex plane BG fault, far away from the polygons of distance protection in reverse direction Page 7

Case 1: Wrong trip using zero sequence polarization Ground current ie exceeds the sensitive threshold of 50A primary which leads to a pickup of the ground fault protection Current of phase B is raising most which is consistent with the pickup of phase B Changes of voltages after fault inception are not very big but leaving enough quantity of zero sequence voltage and negative sequence voltage for the directional element Page 8

Case 1: Wrong trip using zero sequence polarization Figure left is showing zero sequence quantities and negative sequence quantities in the phasor diagram zero sequence current is leading zero sequence voltage by approximately 100 forward fault negative sequence current is lagging negative sequence voltage by approximately 60 reverse fault zero sequence quantities are chosen because they are a little larger than negative sequence quantities. Page 9

Case 2: Wrong polarization due to an error of voltage transformer Figure left shows the impedance trajectories in the complex plane It can be seen that the fault AG appears in reverse direction (green marked trajectory) Page 10

Case 2: Wrong polarization due to an error of voltage transformer significant decrease in the voltage VA is a clear indication for a fault AG voltage VB shows an asymmetry due to a voltage transformer error Wrong reading of VB has a major impact on the wrong direction determination using negative sequence Current IA is raising most which leads to a pickup of ground fault protection indicated by the signal 67G2 Signal FSA indicates that the relay detects the faulted phase A but unfortunately the wrong direction indicated by the signal 32QF Page 11

Case 2: Wrong polarization due to an error of voltage transformer Figure left shows the zero sequence quantities and negative sequence quantities in the phasor diagram negative sequence current is leading negative sequence voltage by approximately 160 forward fault Zero sequence current is lagging zero sequence voltage by approximately 100 reverse fault negative sequence quantities were chosen by setting to detect the direction to fault This leads to the wrong trip of the directional ground fault protection Page 12

Case 3: Wrong phase selection single phase high resistive fault BG close to Amarilis substation At this time the line L-1120 was out of service Due to this Amarilis was a weak infeed side with a transformer with a delta winding on its 10 kv side Page 13

Case 3: Wrong phase selection Figure left shows the impedance trajectories in the complex plane fault BG appears on the real axis of the complex plane in forward direction (red marked trajectory) Page 14

Case 3: Wrong phase selection Due to the transformer on the weak side all three phase currents are nearly in phase, producing a ground current which is much bigger than each single phase current Ground current causes a pickup indicated by the signal 67N Pickup significant decrease in VB but the faulted phase was not detected Instead of a single pole trip command for phase B a three pole trip was issued indicated by the signal Trip 3-pole Page 15

Case 3: Wrong phase selection I2 = a*i0 reason for unselective trip was method applied to detect the faulted phase L2-E L3-E L1-E I 0 I2 = I0 Method is based on the relation between angle of negative sequence current and angle of zero sequence current Zero sequence current should lead negative sequence current by approximately 120 for a fault BG I2 = a 2* I0 I 2 But zero sequence current is leading negative sequence current by approximately 60 only no clear indication for any type of fault Magnitude of the negative sequence current is very small compared to the magnitude of the zero sequence current Page 16

New design of directional ground fault protection Threshold T - Delay 67N Pickup 3I 0 AND T 0 U A U B U C I A I B I C Directional element Phase selector AND AND AND 67N Trip Phase A 67N Trip Phase B 67N Trip Phase C use all available information to detect faulted phase and direction to fault Page 17

Multi criteria phase selection Criteria 1 quality weight 1 Criteria for phase selection Criteria 2 Criteria n quality quality weight 2 weight n Σ A B C quality phase A quality phase B quality phase C Symmetrical components Impedance Phase current Delta current Current sample Current phasor Phase voltage Delta voltage Voltage sample Voltage phasor Page 18

Voltage magnitude criteria The lower the voltage, the higher the quality of the result. 1.00 quality U L1-E/ V 0.90-50 0.14 0.15 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 t/s 0.75 U L1-E/ V 0 0.50 0-50 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 0.25 0.26 t/s 0.25 0.25 0.50 0.75 1.00 ULx [U N ] Page 19

Current magnitude criteria The higher the current, the higher the quality of the result. 1.00 0.90 quality I L1/ A 0.75 2 0-2 -4 0.15 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 t/s 0.50 I L1/ A 0.2 0.25 0.15-0.0-0.2-0.4 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 0.25 0.26 t/s 1 2 3 4 ILx [I N ] Page 20

Impedance ratio criteria The lower the ratio between the measured X and the parameterized X, the higher the quality of the related loop. 1.00 0.90 0.75 X quality Z1 0.50 R 0.25 0.25 0.50 0.75 1.00 XLx / Par(X) Page 21

Multi criteria directional element Criteria 1 Criteria 2 Criteria n quality quality quality weight 1 weight 2 weight n Σ quality forward quality reverse Criteria for directional element Zero sequence Negative sequence Self polarization Memory polarization Cross polarization Memory cross polarization Polarization using delta quantities of faulted phase Polarization using delta quantities of symmetrical components Page 22

Multi-criteria directional element applied to case 2 The binaries show that 7 criteria determine the fault in reverse direction Quality of reverse direction: >75% Quality of forward direction: <25% Multi-criteria directional element can detect the right direction even if some criteria fail Page 23

Conclusion It was shown that the reach of the classical impedance calculation method is significantly influenced by resistive faults on heavy loaded lines. Using the reactance method this reach error can be eliminated. Additionally a new method of loop selection was presented which is optimized for all network topologies. The same philosophy is applied for directional element where different algorithm are weighted dependent on network topology. Page 24

Thank you for your attention! Jörg Blumschein Principal Key Expert Protection EM DG PRO LM&D PPM Wernerwerkdamm 5 13629 Berlin Phone: +49 (30) 386 20135 Fax: +49 (30) 386 25158 E-mail: joerg.blumschein@siemens.com siemens.com/answers Page 25