Q-V droop control using fuzzy logic and reciprocal characteristic

Similar documents
Centralized Supplementary Controller to Stabilize an Islanded AC Microgrid

Secondary Frequency Control of Microgrids In Islanded Operation Mode and Its Optimum Regulation Based on the Particle Swarm Optimization Algorithm

A Study on Performance of Fuzzy And Fuzyy Model Reference Learning Pss In Presence of Interaction Between Lfc and avr Loops

MICROGRID is a future trend of integrating renewable

Participation in the Frequency Regulation Control of a Resilient Microgrid for a Distribution Network

Reactive power control strategies for UNIFLEX-PM Converter

Modeling and Stability Analysis of a DC Microgrid Employing Distributed Control Algorithm

Chapter 2 Voltage-, Current-, and Z-source Converters

ENHANCEMENT MAXIMUM POWER POINT TRACKING OF PV SYSTEMS USING DIFFERENT ALGORITHMS

Advanced Control of a PMSG Wind Turbine

Power Grid Partitioning: Static and Dynamic Approaches

Available online at ScienceDirect. Procedia Technology 25 (2016 )

Optimal Placement & sizing of Distributed Generator (DG)

Cell-Like Fuzzy P System and Its Application of Coordination Control in Micro-grid

Fuzzy PID Control System In Industrial Environment

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 5, MAY Xiaolong Chen and Yongli Li

World Academy of Science, Engineering and Technology International Journal of Computer and Systems Engineering Vol:7, No:12, 2013

Reduced Size Rule Set Based Fuzzy Logic Dual Input Power System Stabilizer

A NEW STRUCTURE FOR THE FUZZY LOGIC CONTROL IN DC TO DC CONVERTERS

Performance Of Power System Stabilizerusing Fuzzy Logic Controller

Modeling and Simulation of DIGSILENT-based Micro-grid System

Optimal Tap Settings for Voltage Regulation Transformers in Distribution Networks

Performance analysis and comparison of load flow methods in a practical distribution system

FUZZY LOGIC CONTROL of SRM 1 KIRAN SRIVASTAVA, 2 B.K.SINGH 1 RajKumar Goel Institute of Technology, Ghaziabad 2 B.T.K.I.T.

Control Strategies for Microgrids

EXCITATION CONTROL OF SYNCHRONOUS GENERATOR USING A FUZZY LOGIC BASED BACKSTEPPING APPROACH

COMPARISON OF DAMPING PERFORMANCE OF CONVENTIONAL AND NEURO FUZZY BASED POWER SYSTEM STABILIZERS APPLIED IN MULTI MACHINE POWER SYSTEMS

SoC Balancing of Different Energy Storage Systems in DC Microgrids Using Modified Droop Control

Analytical Study Based Optimal Placement of Energy Storage Devices in Distribution Systems to Support Voltage and Angle Stability

Application of Virtual Synchronous Generator in Solar Power Generation

FUZZY CONTROL CONVENTIONAL CONTROL CONVENTIONAL CONTROL CONVENTIONAL CONTROL CONVENTIONAL CONTROL CONVENTIONAL CONTROL

Locating Distributed Generation. Units in Radial Systems

Adaptive Perturb & Observe MPPT Algorithm of PV Array Based on Hysteresis Comparison

Sunita.Ch 1, M.V.Srikanth 2 1, 2 Department of Electrical and Electronics, Shri Vishnu engineering college for women, India

A Review and Modeling of Different Droop Control Based Methods for Battery State of the Charge Balancing in DC Microgrids

REAL TIME CONTROL OF DOUBLY FED INDUCTION GENERATOR. Benmeziane Meriem, Zebirate Soraya, Chaker Abelkader Laboratory SCAMRE, ENPO, Oran, Algeria

RamchandraBhosale, Bindu R (Electrical Department, Fr.CRIT,Navi Mumbai,India)

Architectures and Algorithms for Distributed Generation Control of Inertia-Less AC Microgrids

Evaluation of Maximum Power Point Controllers in Photovoltaic System

Fuzzy Control Systems Process of Fuzzy Control

Enhanced Fuzzy Model Reference Learning Control for Conical tank process

Design of Decentralized Fuzzy Controllers for Quadruple tank Process

An improved deadbeat predictive current control for permanent magnet linear synchronous motor

EE5250 TERM PROJECT. Report by: Akarsh Sheilendranath

STATE ESTIMATION IN DISTRIBUTION SYSTEMS

Mitigating Subsynchronous resonance torques using dynamic braking resistor S. Helmy and Amged S. El-Wakeel M. Abdel Rahman and M. A. L.

Open Access Permanent Magnet Synchronous Motor Vector Control Based on Weighted Integral Gain of Sliding Mode Variable Structure

Fuzzy Logic Control for Half Car Suspension System Using Matlab

Type-2 Fuzzy Logic Control of Continuous Stirred Tank Reactor

Analysis on the Operating Characteristic of UHVDC New Hierarchical Connection Mode to AC System

Intelligent Control of a SPM System Design with Parameter Variations

General-Purpose Fuzzy Controller for DC/DC Converters

DQ-axis Current-based Droop Controller

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Optimal Placement of Multi DG Unit in Distribution Systems Using Evolutionary Algorithms

c 2014 Olaoluwapo Ajala

Deregulated Electricity Market for Smart Grid: A Network Economic Approach

SYNCHRONOUS GENERATOR s ROTOR INVESTIGATION OF A HYBRID POWER SYSTEM INCLUDING A.G.

ISSN Vol.05,Issue.10, October-2017, Pages:

Single-Phase Synchronverter for DC Microgrid Interface with AC Grid

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

Optimal Control for the Voltage Regulation of a Power Line Including an Interconnection with a Wind Park and FACTS

DESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE

Voltage Stability of Multiple Distributed Generators in Distribution Networks

Appearance of multiple stable load flow solutions under power flow reversal conditions

Nonlinear dynamic simulation model of switched reluctance linear machine

Control of Sampled Switched Systems using Invariance Analysis

An Equivalent Circuit Formulation of the Power Flow Problem with Current and Voltage State Variables

CHAPTER 7 MODELING AND CONTROL OF SPHERICAL TANK LEVEL PROCESS 7.1 INTRODUCTION

Impact of Increased Penetration of Solar PV on Small Signal Stability of Power System

CHAPTER 5 FREQUENCY STABILIZATION USING SUPERVISORY EXPERT FUZZY CONTROLLER

HOW TO DEAL WITH ELECTROMAGNETIC DISTURBANCES CAUSED BY NEW INVERTER TECHNOLOGIES CONNECTED TO PUBLIC NETWORK

Copyright Warning & Restrictions

NEW CONTROL STRATEGY FOR LOAD FREQUENCY PROBLEM OF A SINGLE AREA POWER SYSTEM USING FUZZY LOGIC CONTROL

Estimating Feasible Nodal Power Injections in Distribution Networks

FUZZY LOGIC CONTROL Vs. CONVENTIONAL PID CONTROL OF AN INVERTED PENDULUM ROBOT

Key words: insulator, the equivalent diameter, natural icing, icing thickness, icing degree, characterization method

AN EFFICIENT APPROACH FOR ANALYSIS OF ISOLATED SELF EXCITED INDUCTION GENERATOR

Analysis of Coupling Dynamics for Power Systems with Iterative Discrete Decision Making Architectures

CHAPTER 3 ANALYSIS OF THREE PHASE AND SINGLE PHASE SELF-EXCITED INDUCTION GENERATORS

Design On-Line Tunable Gain Artificial Nonlinear Controller

A DER based Voltage Control Strategy for Microgrids

FU REASONING INFERENCE ASSOCIATED WIT GENETIC ALGORIT M APPLIED TO A TWO-W EELED SELF-BALANCING ROBOT OF LEGO MINDSTORMS NXT

Speed Control of PMSM by Fuzzy PI Controller with MPAC Algorithm

Energy Flow in Electrical Grids

Fuzzy Control for Shunt Capacitors Applied in Distribution Feeders

FUZZY-ARITHMETIC-BASED LYAPUNOV FUNCTION FOR DESIGN OF FUZZY CONTROLLERS Changjiu Zhou

Research Article Finite Element Analysis of Flat Spiral Spring on Mechanical Elastic Energy Storage Technology

Real Time Control of Electrical Distribution Grids

Fuzzy Applications 10/2/2001. Feedback Control Systems FLC. Engine-Boiler FLC. Engine-Boiler FLC. Engine-Boiler FLC. Page 1

Geometry of power flows and convex-relaxed power flows in distribution networks with high penetration of renewables

Cascading Outages in Power Systems. Rui Yao

Fuzzy Control of a Multivariable Nonlinear Process

Impact of Photovoltaic Generation On The Power System Stability

International Conference on Advances in Energy and Environmental Science (ICAEES 2015)

Fault Diagnosis in Distribution Networks with Distributed Generation

POWER SYSTEM STABILITY

Distributed Generators.

DIRECT TORQUE CONTROL OF THREE PHASE INDUCTION MOTOR USING FUZZY LOGIC

FAST DEFUZZIFICATION METHOD BASED ON CENTROID ESTIMATION

Transcription:

International Journal of Smart Grid and Clean Energy Q-V droop control using fuzzy logic and reciprocal characteristic Lu Wang a*, Yanting Hu a, Zhe Chen b a School of Engineering and Applied Physics, Glyndwr University, Wrexham, LL11 2AW, UK b Dept. of Energy and Technology, Aalborg University, Aalborg, DK 9100, Denmark Abstract Today, the conventional power system is facing some global environmental problems, which is leading to a new trend of power grid by using green and clear energy sources. As the platform of smart grid technology, the microgrid associated with distributed energy resources (DERs) may provide electric power at distributed voltage level, which not only is an autonomous system, but also can be connected to the main grid. To improve the stability and controllability of the power grid, this paper presents an improved Q-V droop control strategy using fuzzy logic controller and reciprocal characteristic. Matlab/Simulink is used for analysing the performance of system. The feasibility of the improved droop control strategy has been verified and discussed. The results demonstrate the improved Q-V droop control strategy could have good effects in grid-connected and islanded mode, and during operation mode transitions. Keywords: Microgrid, reactive power, voltage, droop control, fuzzy logic, reciprocal characteristic 1. Introduction Today s world, the conventional power system is facing three main problems, including gradual depletion of fossil fuel resources, environmental pollution and poor energy efficiency. These problems have led to a new trend of power grid by using green and clear energy sources. Therefore, as the conglomerate of distributed generations (DGs), the microgrid technology has gained increasing attention. However, the output power of DGs is randomness, intermittent and difficult to control due to the weather condition and seasonal change, which can easily cause power quality, grid security and stability issues. Therefore, some control strategies and techniques have been studied in the last decades. Among them, droop control strategy has been a hot topic. Droop control method usually respectively regulates the frequency and voltage amplitude to balance the active power and reactive power outputted from the inverter, or simply P-f and Q-V droop control for short. The advantage of droop control is to make the microgrid operated in the autonomous mode and easily add/shed the additional DGs at any point to act as plug-and-play feature. However, the cost of traditional droop control strategy is to neglect regulation accuracy, which cannot guarantee the quality of the grid s frequency and the voltage. Therefore, some droop control strategies based on the improved droop coefficient were studied in the literatures [1]-[5]. In this paper, Q-V droop control using fuzzy logic and reciprocal characteristic are proposed. The traditional and proposed methods are discussed respectively. Finally, the performances of the proposed droop control strategies are compared and analysed based on the results produced with Matlab/Simulink. 2. System Configuration The example system is a three-phase voltage-source-inverter-based radial microgrid in Fig. 1. Feeder A, B and C consist of DERs interfaced by the power electronic inverters and critical loads. In the system, * Manuscript received July 10, 2013; revised July 31, 2013. Corresponding author Tel.:+44-1978-293153; E-mail address: walleva1126@hotmail.com.

Lu Wang et al.: Q-V droop control using fuzzy logic and reciprocal characteristic 89 feeder D only includes non-critical load, DG 1 and 2 are assumed as DC power source to simulate solar photovoltaic (PV) or fuel cell, DG 3 can supply the AC power to the load like wind farm or diesel. Through the point of common coupling, microgrid can be connected to or disconnected from the main power grid as per grid code. All DGs act with plug-to-play feature and independently control to maintain the stability and reliability of the power grid, in response to any disturbance and change maintain the stability and reliability of the power grid, in response to any disturbance and change. Fig. 1. The system structure. Fig. 2. Fuzzy control block. 3. The Conventional Q-V Droop Control The inverter of DG controls the magnitude and phase angle of output voltage and supply the power to the grid through an inductor of reactance X. Normally, the phase shift δ, so approximately having cosδ=1. Ignoring the resistance of transmission line, then Z=X, the reactive power equation can be represented as follows: Q = 3V 1 V (V 1 V)/2X (1) From (1), we can find the reactive power flow could be controlled by the voltage magnitude V. Therefore, the reactive power versus voltage droop characteristics can be expressed as: V ref V = k q (Q ref Q) (2) where V ref indicates the reference voltage; V is the actual voltage; k q stands for the Q-V droop characteristic coefficient. When the loads changed, the reactive power sharing can be done based on k q, the system s voltage can be regulated, then reach to a new steady-state level. Conventionally, the simple droop coefficient is set to be a constant [6]-[9]. As the reactive output power changing, the voltage magnitude of the grid can be changed correspondingly and have a quick response to keep stable. However, the output power of DG may not be constant affected by the weather condition, seasonal change and regional conditions. If k q is set to a big value, a small reactive power change will lead to a greater voltage deviation, which may exceed the allowed fluctuation range referred to IEEE 1547 Standard. Therefore, in order to cope with the power variation, the variable droop coefficient would have more advantages. 4. The Proposed Q-V Droop Control 4.1. Fuzzy logic The fuzzy logic control design is composed of three sections: fuzzification, inference engine and defuzzification. In this case, the error of reactive output power from DGs (inputs 1) and the change rate of error (inputs 2) are used as inputs to the fuzzy reasoning. The fuzzy output is the adjustment of Q-V droop coefficient in Fig. 2. Membership function of the input 1 and output are assigned to seven fuzzy subsets: negative big (NB), negative medium (NM), negative small (NS), zero (ZO), positive small (PS), positive medium (PM), and positive big (PB). Membership function of input 2 is designed to five fuzzy subsets: NB, NS, ZO, PS and PB. The shape of membership function adapts the triangular. The value of the two inputs and output are normalized by the scaling factor. The input and output scaling has designed between 0 and 1.

90 International Journal of Smart Grid and Clean Energy, vol. 3, no. 1, January 2014 Table 1. Rule of fuzzy reasoning Output Input 1 PB PM PS ZO NS NM NB PB PB PM PM PS ZO NS NB PS PB PM PS ZO ZO NS NB Input2 ZO PB PM PS ZO NS NM NB NS PB PS ZO ZO NS NM NB NB PB PS ZO NS NM NM NB The fuzzy reasoning is described by a set of if-then rule. Based on the levels of the two input signals, the adjustment of droop coefficient will be obtained. The rules of fuzzy reasoning are described in Table 1. The adjustment value of droop coefficient can be calculated with defuzzificaion using the centroid method. This method can fully consider the information of fuzzy reasoning, which is described by the area surrounded by the membership function curve and the horizontal axis. When the output variables of the membership function is a set of discrete points, then: m x x k x i N i i 1 m i 1 N i where k is the output variable; m is the number of rule; μ N is the grade of membership; x i is defined as a discrete universal set. By this way, the output of k can be calculated to a precise value with defuzzificaion. Therefore, the actual droop coefficient k q is equal to: k q_actual = k q k q (4) 4.2. Reciprocal characteristic The representation of the reciprocal curve is selected as (5), in which m and A should be positive constants; otherwise the function becomes divergence with slope being positive as shown in Fig. 3. y = A / (x m +1), (m>0 and A>0) (5) (3) Fig. 3. The curves y = A/(x m +1) and x= n μ Fig. 4. The relationship between Q and μ It can be noticed there are five features on (5): 1) the slope of curve keeps negative at any point; 2) with the increment of x, the function y decreases and tends to 0; 3) the range of function y is determined by the numerator A; 4) when the value of A determined, the function y always meets at x=1; 5) the variable n is bigger, y reduces faster around x=1. When in the grid-connected mode, the system voltage is supported by the main power grid. All DGs work at the reference value. Based on the feature 4), the reference value will be set up at x=1 point. Similar as the principle of Bode diagram, transfer the value of

Lu Wang et al.: Q-V droop control using fuzzy logic and reciprocal characteristic 91 horizontal axis into the form of power function. The power is defined as μ and has a relationship with the reactive power, see Fig. 4: x=n μ,(n>1) ; μ = (Q Q ref ) / Q ref (6) where n is constant, greater than 1. Furthermore, the deviation of voltage must satisfy the demand of grid code to keep the whole power system reliable and stable in grid-connected mode, islanded mode and during the transition. As per grid code, the deviation is assumed as 3V, so the value of y fluctuates within the range of 6. Therefore, the expression (5) can be rewritten as: y = 6 / (x m +1) (7) in which the medial value of y is equal to 3. To achieve the value of y to 311 at x=1, y is offset by (311-3) units. Therefore, a new reciprocal curve expression is as follows: y (311-3) = 6 / (x m +1), (m>0) (8) Synthesizing the equation (6), (7) and (8), the reactive output power versus frequency droop coefficient based on reciprocal characteristic is described as: Q (311 A/2) = A / (x m +1), (m > 0 and A>0); x=n μ, (n > 1); μ = (Q Q ref ) / Q ref (9) where Q stands for the actual voltage; A is the range of deviation. Fig. 5 and Fig. 6 describe different Q-V droop coefficients using reciprocal characteristic. In pictures, the fluctuation of voltage magnitude is from 308 V to 314 V. With the increment of m and n, the reciprocal curve has a faster trend to close to the boundary. The slope of crossing point becomes greater as well. As the same reactive power changing, the variables m and n are set bigger, the deviation of system voltage magnitude will be larger. The dynamic response of system also becomes quicker. Therefore, when the reactive power output is smaller, we can choose a big m and n to improve the system s operation. If the output power is large, the small values of m and n can be chosen to reduce the deviation of system s frequency. Fig. 5. Droop coefficients with m increasing. Fig. 6. Droop characteristics with n in turn.

92 International Journal of Smart Grid and Clean Energy, vol. 3, no. 1, January 2014 5. Simulation and Analysis In further discussions of droop control, the peer-to-peer method is adopted. All DGs may take part in droop control based on pre-set control mode. Considering different changes of system s structure, the feasibility of the droop control strategies proposed in previous section will be tested. 5.1. Case 1 The target of Case 1 was to verify the superiority of fuzzy logic droop control. In this model, DG3 was isolated. DG1 respectively applied with fuzzy logic and traditional droop control. To make the same initial condition, the traditional droop coefficient of DG1 was set to 2 10-4. DG2 was operated by the traditional droop characteristic, k q = 1.5 10-4. Based on the same reactive output power changing, we could find the voltage magnitude controlled by fuzzy logic was more stable than that of traditional one during the whole process. The deviation of voltage was only ± 2.5 V. At 0.5 s, the peak value dropped from 316.5 V to 312.5 V, see Fig. 7. 5.2. Case 2 For testing the feasibility of the proposed control strategy, both DG1 and DG2 were applied the fuzzy logic droop control with different regulations. The system structure was same as Case 1. Based on the same initial droop coefficients, the range of regulation of DG1 was 0~1.5 10-4 ; that of DG2 was 0~1.2 10-4. Table 2 outlined the change of reactive power among DG1, DG2 and non-sensitive load. When the microgrid worked in islanded mode, the reactive power of the non-sensitive load was 2190Var. At 1s and 2s, the load was removed and then added. The inverters of DGs had a quick response to reach a new balance point and share the change of reactive power by different fuzzy logic droop characteristics. The voltage magnitude still maintained within the allowed fluctuation ±3V, depict in Fig. 8. The whole system kept stable and reliable to achieve the safe connection. Table 2. Rule of fuzzy reasoning 0.5s~1s 1s~2s Change DG 1-2900Var -1870Var 1030Var DG 2-1400Var -4620Var -3220Var Load 2190Var 0Var -2190Var Fig. 7. DG1 s voltage using different droop control. Fig. 8. Voltage magnitude of DGs in Case 2.

Lu Wang et al.: Q-V droop control using fuzzy logic and reciprocal characteristic 93 Fig. 9. Voltage magnitude of DG1 in Case 3. Fig. 10. Reactive output powers and voltage magnitudes of DGs in Case 4. Fig. 11. The system voltage on the main bus in Case 4. 5.3. Case 3 In this case, the droop control using reciprocal characteristic was discussed. Similar as Case 1, the DG1 respectively was operated by reciprocal characteristic and traditional droop control. The advantage of reciprocal characteristic is the deviation of voltage magnitude can be predetermined by the exporter. Based on the aforementioned definition, the parameters were set as A=4, m=1 and n=1.5. The simulation result was outlined in Fig. 9. In comparison of conventional method, when the range of deviation is fixed, however the reactive output power of DG1 changed, the system voltage would be floating from 310.5V to 313V, which was not exceeded the pre-set limitation, see Fig.9. 5.4. Case 4 To test the feasibility and reliability of droop control using reciprocal characteristic, three DGs need to take participate in Case 4. The pre-set deviations of DG1 and 2 were ±2V, smaller than that of DG2 ±3V. During the whole operating period, the non-critical load and DG2 were shed respectively and switched on again. In Fig. 10, the system transferred to the islanded operation mode at 0.5s. The overshoot of DG2 s reactive power changing was same as than that of DG3, but the fluctuation of voltage was not exceeded the desired limitation. At 3.5s, the load and DG2 added. Based on the different predetermined parameters, the regulation of DG3 s voltage was greater than that of DG1. Fig. 11 demonstrated the system voltage on the main bus. The result verified that the improved droop control strategy had a significant ability to maintain the system stability in grid-connected and islanded mode, and during operation mode transitions.

94 International Journal of Smart Grid and Clean Energy, vol. 3, no. 1, January 2014 5.5. Case 5 In Case 5, the range of voltage deviation was set to ±3V. DG1 was controlled by different reciprocal droop characteristic, whose value of m and n increased in turn. The system structure and operating set were same as Case 3. When the system reached a new voltage point to balance the power sharing, the fluctuation of DG s voltage magnitude becomes bigger due to the large m and n. Therefore, based on the same conditions of DGs, the small m and n could improve the stability and reliability of the power grid, this effect could be seen in Fig. 12. Fig. 12. Voltage magnitude of DG1 with variable m and n. 6. Conclusion In this paper, the three-phase radial microgrid model using fuzzy logic and reciprocal droop control has been discussed. For traditional droop, the small Q-V droop coefficient would lead to the small system frequency deviation and a quick system dynamic response. The system could maintain stable and reliable to share the power during the mode transition and load changing. In comparison of fixed droop coefficient, the fuzzy logic droop control could achieve the droop coefficient has a dynamic change. Due to the changes of DG s reactive output power, the fuzzy controller can calculate the suitable adjustment to modify the droop coefficient. By this way, the deviation of system voltage could be guaranteed. The stability of grid would have a significant improvement. For the reciprocal droop control, the simulation result verified the range of system s voltage floating deviation could be pre-set by the operator. With the increment of variable m and n, the regulation of system voltage is greater with the same change of reactive output power from DGs. The dynamic response of system also became faster. Finally, the feasibility and effectiveness of different control methods and the synthesized operation models were tested. The results demonstrated that the improved droop control strategy performs well in grid-connected and islanded mode, and during operation mode transitions. References [1] Oshiro M, Uchida K, Senjyu T, Yona A. Voltage control in distribution systems considered reactive power output sharing in smart grid. In: Proc. of 2010 International Conference on Electrical Machines and Systems (ICEMS), 2010:458 463. [2] Li P, Wang W, Yang X, Wang S, Cui H, Gao C. A droop control method of microsources based on divided self-adjusting slope coefficient. In: Proc. of 2010 International Conference on Power System Technology (POWERCON), 2010:1 6.

Lu Wang et al.: Q-V droop control using fuzzy logic and reciprocal characteristic 95 [3] Sun G, Zha X. Research on parallel operation of distributed inverter based on variable droop coefficient. In: Proc. of 2011 International Conference on Electric Information and Control Engineering (ICEICE), 2010:4411 4414. [4] Zhu J, Li P, Wang Y, Chen C. Microgrid power control method based on improved droop characteristics. Power System and Clean Energy, 2012; 28(6):29-33 (in Chinese). [5] Chaudhuri NR, Chaudhuri B. Adaptive droop control for effective power sharing in multi-terminal DC (MTDC) grids. IEEE Transactions on Power Systems, 2013; 28(1):21 29. [6] Barklund E, Pogaku N, Prodanovic M, Hernandez-Aramburo C, Green TC. Energy management in autonomous microgrid using stability-constrained droop control of inverters. IEEE Transactions on Power Electronics, 2008; 23(5):2346 2352. [7] Su L, Li G, Jin Z. Modeling, control and testing of a voltage-source-inverter-based microgrid. In: Proc. of the 4th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2011:724 729. [8] Zhi N, Zhang H, Liu J. Overview of microgrid management and control. In: Proc. of International Conference on Electrical and Control Engineering (ICECE), 2011:4598 4601. [9] Alotibe MS, Chandrasena R, Rajakaruna S. Simplified voltage and frequency controller based on droop control for the dynamic analysis of a Microgrid. In: Proc. of the 22nd Australasian Universities Power Engineering Conference (AUPEC), 2012:1 8. [10] Chen Z, Hu Y. Control of power electronic converters for distributed generation units. In: Proc. of the 31st Annual Conference of the IEEE Industrial Electronics Society, 2005:1317 1322. [11] Hu Y, Chen Z, McKenzie H. Voltage source converters in distributed generation systems. Presented at: The Third International Conference on Electric Utility Deregulation and Restructuring and Power Technologies, 2008. [12] Chen Z, Hu Y, McKenzie H. Effects of line parameters on performance of voltage source converters in distributed generation systems. Presented at: The 43rd International Universities Power Engineering Conference UPEC 2008.