Use Coldplate to model a cold plate and heat exchanger circuit

Similar documents
EPAC Software. COLDPLATE Example. Serpentine Example

UNIT CONVERSIONS User Guide & Disclaimer

Radiant Heating Panel Thermal Analysis. Prepared by Tim Fleury Harvard Thermal, Inc. October 7, 2003

Water Circuit Lab. The pressure drop along a straight pipe segment can be calculated using the following set of equations:

Plant Design LECTURE 8: REBOILER CIRCUIT DESIGN. Daniel R. Lewin Department of Chemical Engineering Technion, Haifa, Israel

Development and Validation of Flat-Plate Collector Testing Procedures

Learning Objectives. Lesson 6: Mathematical Models of Fluid Flow Components. ET 438a Automatic Control Systems Technology 8/27/2015

PART II. Fluid Mechanics Pressure. Fluid Mechanics Pressure. Fluid Mechanics Specific Gravity. Some applications of fluid mechanics

SKM DRILLING ENGINEERING. Chapter 3 - Drilling Hydraulics

Mohammed Rashnur Rahman, N.M. Aftabul Alam Bhuiya, and Md. Rasel Miah

NEBB Fundamental Formulas

INTERNATIONAL SYSTEM OF UNITS

Math 308 Exam I Practice Problems

Principles of Food and Bioprocess Engineering (FS 231) Example Problems on Units and Dimensions

MOTOR WIRING DATA From National Electrical Code 3 PHASE SQUIRREL CAGE INDUCTION MOTORS 230 Volt 460 Volt Min. # Max. Rating

Laboratory/Demonstration Experiments in Heat Transfer: Laminar and Turbulent Forced Convection Inside Tubes. Abstract

Circle one: School of Mechanical Engineering Purdue University ME315 Heat and Mass Transfer. Exam #2. April 3, 2014

a right triangle), we see that x 200 or equivalently x = 200 tan θ. The rate at which the ray of light moves along the shore is

CONCEPTS AND DEFINITIONS. Prepared by Engr. John Paul Timola

CHAPTER 3 SHELL AND TUBE HEAT EXCHANGER

Math 308 Exam I Practice Problems

Experiment 1. Measurement of Thermal Conductivity of a Metal (Brass) Bar

Continuous Pasteurization of Egg Yolk with Plate Heat Exchangers: Thermal-Hydraulic Performance and Configuration Optimization

Ohio EPA Formula/Conversion Table for Water Supply and Distribution Exams

Topic 8: Flow in Packed Beds

STRUCTURAL ANALYSIS OF A WESTFALL 2800 MIXER, BETA = 0.8 GFS R1. By Kimbal A. Hall, PE. Submitted to: WESTFALL MANUFACTURING COMPANY

Coolant. Circuits Chip

The online of midterm-tests of Fluid Mechanics 1

LEAKLESS COOLING SYSTEM V.2 PRESSURE DROP CALCULATIONS AND ASSUMPTIONS

Part II Fundamentals of Fluid Mechanics By Munson, Young, and Okiishi

ESTIMATING PRODUCTION AND BOOSTER PUMP LOCATION FOR LONG DISTANCE PUMPING

Section 2.5 Mixing Problems. Key Terms: Tanks Mixing problems Input rate Output rate Volume rates Concentration

4 Mechanics of Fluids (I)

Section 1: Theory of Heat Unit 2: Matter and Energy

PLATE TYPE HEAT EXCHANGER. To determine the overall heat transfer coefficient in a plate type heat exchanger at different hot fluid flow rate

Memorial University of Newfoundland Faculty of Engineering and Applied Science

RIG HYDRAULICS. P 1 = Eρ 0.8 Q 1.8 (PV) 0.2. psi or bar. P 1 ρ. = pressure loss, psi or bar = Density, ppg or kg/l = flow rate, gpm, l/min

ESRL Module 8. Heat Transfer - Heat Recovery Steam Generator Numerical Analysis

Thermal Unit Operation (ChEg3113)

Thermal Analysis of Shell and Tube Heat Ex-Changer Using C and Ansys

Orifice and Venturi Pipe Flow Meters

Ben Wolfe 11/3/14. Figure 1: Theoretical diagram showing the each step of heat loss.

DESIGN AND COST ANALYSIS OF HEAT TRANSFER EQUIPMENTS

If you need more room, use the backs of the pages and indicate that you have done so.

EXPERIMENT NO. 4 CALIBRATION OF AN ORIFICE PLATE FLOWMETER MECHANICAL ENGINEERING DEPARTMENT KING SAUD UNIVERSITY RIYADH

) = slugs/ft 3. ) = lb ft/s. ) = ft/s

Applications of Integration to Physics and Engineering

Northern Lesson 2 Gear Pump Terminology. Gear Pump 101. Lesson 2: Gear Pump Terminology. When your reputation depends on it!

Math Spring 2014 Homework 2 solution

130 CHAP. 4 Systems of ODEs. Phase Plane. Qualitative Methods. Find the eigenvalues and eigenvectors of the matrix

Universität Duisburg-Essen Fakultät für Ingenieurwissenschaften WS 2012 Maschinenbau, IVG, Thermodynamik Dr. M. A. Siddiqi

Open PRAIRIE: Open Public Research Access Institutional Repository and Information Exchange

Fluid Flow Analysis Penn State Chemical Engineering

Solve the set of equations using the decomposition method and AX=B:

طراحی مبدل های حرارتی مهدي کریمی ترم بهار HEAT TRANSFER CALCULATIONS

Custom Search Sponsored Links

TOTAL HEAD, N.P.S.H. AND OTHER CALCULATION EXAMPLES Jacques Chaurette p. eng., June 2003

Ph.D. Qualifying Exam in Fluid Mechanics

Annubar Primary Element Flow Calculations

In this process the temperature difference across the given length of pipe can be described as:

Exam #1. A. Answer any 1 of the following 2 questions. CEE 371 October 8, Please grade the following questions: 1 or 2

EF 152 Exam 1 Fall 2018 Page 1 Copy 165

CHAPTER-4 EVALUATION OF NANOFLUIDS PROPERTIES

Chapter 1 INTRODUCTION

Given Find Water Properties

CHE-201. I n t r o d u c t i o n t o Chemical E n g i n e e r i n g. I N S T R U CTOR: D r. N a b e e l S a l i m A b o - Ghander.

Piping Systems and Flow Analysis (Chapter 3)

Basic Math Concepts for Water and Wastewater Operators. Daniel B. Stephens & Associates, Inc.

EMA 3702 Mechanics & Materials Science (Mechanics of Materials) Chapter 3 Torsion

Rheological and Engineering Properties of Orange Pulp. Elyse Payne Juan Fernando Muñoz José I. Reyes De Corcuera

Fachgesprach 12. HVAC Pumps. For Project Managers

CHAPTER 6 Applications of Integration

Unit Conversions, Important Constants and Relationships

Compute the lateral force per linear foot with sloping backfill and inclined wall. Use Equation No. 51, page 93. Press ENTER.

Atmospheric pressure. 9 ft. 6 ft

MATH Exam 2-3/10/2017

APPENDIX B ABBREVIATIONS, SYMBOLS AND CONVERSION FACTORS Abbreviations

Ex Problem 10 - Countercurrent Packed Tower for Absorption of Ammonia Gas (Pilat)

Orifice and Venturi Pipe Flow Meters

FDE 211 MATERIAL & ENERGY BALANCES. Instructor: Dr. Ilgin Paker Yikici Fall 2015

APPENDIX H CONVERSION FACTORS

7. PROCESS EQUIPMENT DESIGN

Only if handing in. Name: Student No.: Page 2 of 7

DIMENSIONS AND UNITS

True/False. Circle the correct answer. (1pt each, 7pts total) 3. Radiation doesn t occur in materials that are transparent such as gases.

Computational Fluid Dynamics of Parallel Flow Heat Exchanger

1/54 Circulation pump, safety valve, expansion vessel

Lentis Pai/Associate Director/Wiwynn

THE EXPERIMENTAL STUDY OF THE EFFECT OF ADDING HIGH-MOLECULAR POLYMERS ON HEAT TRANSFER CHARACTERISTICS OF NANOFLUIDS

Pressure Measurement. Transmitters for basic requirements SITRANS P MPS (submersible sensor) Transmitter for hydrostatic level 2/27

Simulation of Free Convection with Conjugate Heat Transfer

2.0 KEY EQUATIONS. Evaporator Net Refrigeration Effect. Compressor Work. Net Condenser Effect

Mass Balance MATHEMATICAL MODEL FOR THERMAL CRACKING OF HYDROCARBONS ETHANE CRACKING

STYLE GUIDELINES AND SPECIFICATIONS

Math 2Z03 - Tutorial # 3. Sept. 28th, 29th, 30th, 2015

Given Find Water Properties

Chapter 4: Temperature

Flow in Pipes Simulation Using Successive Substitution Method

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X X X X X X X Adopt Entire Chapter as amended (amended sections listed below)

CHAPTER 12 Turbomachinery

Transcription:

Use Coldplate to model a cold plate and heat exchanger circuit The cold plate and heat exchanger to be modeled are shown below. It is assumed the heat exchanger is a Lytron model 6210 and the cold plate parameters are shown in Figure 1. Figure 2 is the assumed pump curved used to circulate 50% ethylene glycol and water through both the cold plate and heat exchanger. Figure 1: Cold plate and heat exchanger setup

Figure 2: Pump curve used to circulate the ethylene glycol/water fluid through both the cold plate and heat exchanger 20 18 16 1, 17.9 2, 16.5 14 Pressure - PSI 12 10 8 3, 12 6 4 2 0 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 Flow rate - Gal/min

Determine the pressure loss coefficient of the heat exchanger The effective pressure loss coefficient K for the liquid side of the heat exchanger is calculated as follows assuming an ID of.287 inches and 20 degree C. This loss coefficient K along with the pump curve, the 36 inch length of tubing and the internal pressure drop in the cold plate are used to determine the ethylene glycol/water flow rate. Figure 3: Pressure drop versus flow rate curve for the Lytron 6210 heat exchanger Assume the pressure drop, P, through the exchanger is given by: P = 2 KρV KρΨ = 2g 2gA 2 2

Where: ρ = 66.4 lb/ft3, the density of ethylene glycol and water at 20C. V is the velocity. G is the gravity constant. A is the cross sectional area of tube. D is the ID of the tube. Ψ is the volume flow rate in ft3/min. Q is the volume flow rate in gal/min. Solving for K: K = 2 2gA P 2 ρψ = 2 2 2 4 2 2 2 ( ft / sec )( πd / 4) ( in )( P( lb / in ))( 1ft /144in ) 3 3 2 ( 66.4lb / ft )( Ψft / min) ( 1min/ 60sec) 2 2 32.17 K = P 4 2 14.93D / Ψ Convert flow rates: Q 3 3 ( gal / min) = Ψ( ft / min)( 7.48gal / ft ) Ψ = Q / 7.48 Substitute into K: K = 4 2 835.21D P / Q For D =.287 in. and from the Lytron pressure drop curve at Q = 2gal/min, P = 8 lb/in 2 : K = 11.33 And for D =.287 inches, at Q = 3gal/min, P = 18 lb/in 2 : K = 11.33 Since the value of K is the same for both data points, then the assumed equation for calculating K appears to be correct.

Determine the flow rate of the fluid through the cold plate/heat exchanger Figures 4 through 7 lists the inputs to Coldplate necessary to determine the fluid flow rate. Note that the Inlet Fluid Temperature is assumed to be 30C; the pressure drop is a weak function of temperature so in this case using 30C will result in a small error. The model can be easily rerun with an updated temperature. Figure 4: Geometry Input

Figure 5: Fluid Properties Input

Figure 6: Pressure Drop Parameters Figure 7: Pump Impedance Curve

The intersection of the pressure drop and pump curves shows the operating point has a flow rate of approximately 2 gal/min. This value will be used for the rest of analysis. Figure 8: Pump Operating Point

Thermal/fluid circuit and conductor connection values The thermal/fluid circuit for connecting the cold plate to the heat exchanger is shown in Figure 9 and the value of the conductors are calculated below. Figure 9: Thermal/Fluid Circuit The conductor G HX is taken from the Lytron curve for the model 6210 heat exchanger, Figure 10 at 2 gal/min and 180 CFM it is: G HX = 62 W/C G HX can be treated as a conductor from the air inlet temperature (node 5001) to the inlet EGW inlet temperature (node 3998).

Figure 10: Lytron Heat Exchanger Thermal Conductance Curves

The EGW (ethylene glycol and water) fluid flow conductor mcp EGW is calculated as below: ρ = 65.9 lb/ft 3 Cp = 25.52 (W-min)/(lb-C) m = ρ Ψ = (65.9 lb/ ft 3 )(2gal/min)(1ft 3 /7.48gal) = 17.62 lb/min mcp EGW = (17.62 lb/min)( 25.52 (W-min)/(lb-C)) = 449.7W/C The air inlet fluid flow conductor for the heat exchanger is calculated as below: ρ = P/RT ρ = [(14.7 lb/ft 2 )(144in 2 /1ft 2 )]/[(53.34ft/R)(30+273)K(1.8R/1.0K)] ρ =.073 lb/ft 3 Cp = 7.6 (W-min)/(lb-C)) m = ρ Ψ = (.073 lb/ ft 3 )(180ft 3 /min) = 13.14 lb/min mcp Air = [13.14 lb/min][ 7.6 (W-min)/(lb-C)] = 99.9W/C Input the thermal/fluid model into Coldplate The thermal/fluid circuit shown in Figure 9 is inputted to Coldplate as shown in Figures 11 through 14. Note that the connection from the inlet air node (5001) to the first fluid node (242) in the cold plate needs to be disconnected as shown. This is done by over-writing the connection and adding a new connection with a value of 0. For this analysis, assume the cold plate is 12 nodes wide and 20 nodes long. In addition, assume the cold plate has a 4 pass tube configuration. Assume also the power is uniformly distributed.

Figure 11: Define Cold Plate Node Structure and Extra Nodes Used in Figure 9

Figure 12: Define Uniformly Distributed 1200Watts across Cold Plate and Power to the Heat Exchanger

Figure 13: Define the Conductor Connections shown in Figure 9

Figure 14: Define the Cold Plate as a 4 Pass Tube Configuration

Results from running the Coldplate model Figure 15 shows the results from running the model while the calculations below compare the model results with hand (explicit) analysis. T 3998 = 30C + (1200W)/(62W/C) = 49.35C versus 49.37C T 3997 = 49.35C - (1200W)/(449.7W/C) = 46.69C versus 46.70C T 3999 = 30C + (1200W)/(99.9W/C) = 42.01C versus 42C Figure 15: Results from the Coldplate model