Power Theory with Non-sinusoidal Waveforms

Similar documents
On Some Properties of Instantaneous Active and Reactive Powers

Fizyczne przyczyny redukcji współczynnika mocy

Interpretation of power phenomena in three phase systems with neutral using instantaneous reactive power p-q theory

Constraints of instantaneous reactive power p q theory

Three- phase four-wire circuits interpretation by means of different power theories

12. Introduction and Chapter Objectives

Selection of Voltage Referential from the Power Quality and Apparent Power Points of View

Meta-theory of electric powers and present state of power theory of circuits with periodic voltages and currents

Chapter 15 Power And Harmonics in Nonsinusoidal Systems

Enhanced Active Power Filter Control for Nonlinear Non- Stationary Reactive Power Compensation

Sinusoidal Steady State Analysis (AC Analysis) Part II

Optimizing Power Flows in Lossy Polyphase Systems: Effects of Source Impedance

Selected paper. Consistent circuit technique for zero-sequence currents evaluation in interconnected single/three-phase power networks

Refresher course on Electrical fundamentals (Basics of A.C. Circuits) by B.M.Vyas

P-Q THEORY AND APPARENT T POWER CALCULATION FOR ACTIVE FILTERING

Quantitative Analysis of Reactive Power Calculations for Small Non-linear Loads

Review of Basic Electrical and Magnetic Circuit Concepts EE

Sinusoidal Response of RLC Circuits

On electrical power evaluation in dq coordinates under sinusoidal unbalanced conditions

Conservative Functions: An Approach in Nonlinear and Switched Network Analysis

Analysis of Wind Generator Operations under Unbalanced Voltage Dips in the Light of the Spanish Grid Code

Adaptive Fuzzy Logic Power Filter for Nonlinear Systems

Lecture 11 - AC Power

Comparative analysis of influence of the type line supplying nonlinear load on deformation of voltage and current in the power system

04-Electric Power. ECEGR 452 Renewable Energy Systems

Module 4. Single-phase AC Circuits

11. AC Circuit Power Analysis

Power Quality. Guide for electrical design engineers. Power Quality. Mitigation of voltage unbalance

THREE-PHASE POSITIVE AND NEGATIVE SEQUENCES ESTIMATOR TO GENERATE CURRENT REFERENCE FOR SELECTIVE ACTIVE FILTERS

Power Factor Improvement

Modeling of Power System Components During Electromagnetic Transients

Working Active Power Concept in a Three Phase System

ELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS

AC Power Analysis. Chapter Objectives:

BASIC NETWORK ANALYSIS

Three Phase Circuits

Lecture 10: Grid Faults and Disturbances

BASIC PRINCIPLES. Power In Single-Phase AC Circuit

Working active power, reflected active power, and detrimental active power in the power system

Electronic Power Conversion

Lecture 05 Power in AC circuit

Power System Analysis Using Space Vector Transformation

(Refer Slide Time: 00:55) Friends, today we shall continue to study about the modelling of synchronous machine. (Refer Slide Time: 01:09)

EXP. NO. 3 Power on (resistive inductive & capacitive) load Series connection

2 Simulation exercise 2

Modified algorithms of direct power control of AC/DC converter co-operating with the grid

Pre-Lab. Introduction

AC Circuits. The Capacitor

10.1 COMPLEX POWER IN CIRCUITS WITH AC SIGNALS

Work, Energy and Power

Chapter 2 Voltage-, Current-, and Z-source Converters

EN Power Electronics and Machines

Consider a simple RC circuit. We might like to know how much power is being supplied by the source. We probably need to find the current.

Power and Energy Measurement

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Project Components. MC34063 or equivalent. Bread Board. Energy Systems Research Laboratory, FIU

Fourier series. XE31EO2 - Pavel Máša. Electrical Circuits 2 Lecture1. XE31EO2 - Pavel Máša - Fourier Series

Work, Energy and Power

Energy Conversion and Management

An Innovative Simple Test Circuit for Single-Phase Short Circuit Making Test of High-Voltage Switching Devices

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

(Refer Slide Time: 01:30)

Sinusoidal Steady-State Analysis

VTU E-LEARNING NOTES ON:

A Novel Time-Domain Perspective of the CPC Power Theory: Single-Phase Systems

Reactive Power Flow Control of a Dual Unified Power Quality Conditioner

CONTROL OF SINGLE-PHASE POWER ACTIVE FILTERS

15-884/484 Electric Power Systems 1: DC and AC Circuits

Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs

Power Systems - Basic Concepts and Applications - Part I

Currents Physical Components (CPC) in systems with semi-periodic voltages and currents

LO 1: Three Phase Circuits

Handout 11: AC circuit. AC generator

Why the formula P = VI COS φ is wrong.

Analysis of AC Power RMS and Phasors Power Factor. Power Factor. Eduardo Campero Littlewood

Notes on Electric Circuits (Dr. Ramakant Srivastava)

Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines)

The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of Unbalanced Three Phases Electrical Distribution System

DYNAMIC ANALYSIS OF ORTHOGONAL APPARENT POWER COMPONENTS IN POLYPHASE UNBALANCED NETWORKS. By Afsaneh Ghanavati

Circuit Analysis-II. Circuit Analysis-II Lecture # 5 Monday 23 rd April, 18

True Power vs. Apparent Power: Understanding the Difference Nicholas Piotrowski, Associated Power Technologies

RLC Circuit (3) We can then write the differential equation for charge on the capacitor. The solution of this differential equation is

The Effect of Harmonic Distortion on a Three phase Transformer Losses

Power and Energy Measurement

ECE 420. Review of Three Phase Circuits. Copyright by Chanan Singh, Panida Jirutitijaroen, and Hangtian Lei, For educational use only-not for sale.

Balanced three-phase systems and operation

Voltage-Vector in Three-Dimensional Space Vector Modulation based on αβr- Coordinate for Four-Leg Active Filter

Comparative Analysis of Speed Control of Induction Motor by DTC over Scalar Control Technique

Ingeniería y Competitividad ISSN: Universidad del Valle Colombia

The simulation analysis of the bridge rectifier continuous operation in AC circuit

Electrical and Magnetic Modelling of a Power Transformer: A Bond Graph Approach

ECE 421/521 Electric Energy Systems Power Systems Analysis I 2 Basic Principles. Instructor: Kai Sun Fall 2013

6.334 Power Electronics Spring 2007

Transient Behavior of

1 Phasors and Alternating Currents

HOW TO DEAL WITH ELECTROMAGNETIC DISTURBANCES CAUSED BY NEW INVERTER TECHNOLOGIES CONNECTED TO PUBLIC NETWORK

Revision of Basic A.C. Theory

Figure 5.2 Instantaneous Power, Voltage & Current in a Resistor

Research of Hybrid Three-phase equilibrium Technology

KINGS COLLEGE OF ENGINEERING Punalkulam

Transcription:

Annex 3 Power Theory with Non-sinusoidal Waveforms Andrzej Firlit The power theory 1 of electric circuits in its present form is the result of research of a few generations of scientists and electrical engineers. The term power theory is often used in phrases such as Fryze s power theory, the p q power theory or the power theory based on the current s physical components theory, etc. In this context it means the suggested interpretation of power phenomena taking place in electric circuits, the definition of quantities related to them and the mathematical relations. The term power theory of electric circuits can also be understood as the general state of knowledge about their properties. In this case it would be the collection of real statements and interpretations, definitions and formulas describing these properties. The power theory is developing for two main reasons. The first reason is cognitive. In relation to electric circuits the power theory is searching for an answer to the question: why does an electrical load usually require the apparent power of the supply source to be bigger than the active power? This question is strongly connected with the need for an interpretation of power phenomena in electric circuits. The second reason is practical. The power theory is trying to answer the question: how can the apparent power of the supply source be reduced without decreasing the active power of an electrical load? These two deceptively simple questions turn out to be exceptionally difficult. In spite 1 In this case the term power theory means the state of knowledge about the power properties of electric circuits. The power theory understood in that way is a collective result of the intellectual work of those who contribute to explaining the power properties of electric circuits [16],[24]. Handbook of Power Quality Edited by Angelo Baggini 2008 John Wiley & Sons, Ltd

28 of the fact that it has been over a hundred years since the first power theory questions were asked, some answers are still controversial [16],[24]. A3.1 CONVENTIONAL CONCEPTS OF THE POWER PROPERTIES OF ELECTRIC CIRCUITS This annex presents a basic review of the simplest cases from the point of view of power properties (power phenomena) which are considered in single-phase and three-phase electric circuits. This will remind us about the way in which the commonly used quantities in electrotechnics were defined, such as the instantaneous power p t, the active power P, the reactive power Q, the apparent power S, the distortion (harmonic) power H, the deformation power D, power factors DPF and PF, etc. This kind of description of power properties (power phenomena) of electric circuits is defined as conventional and is valid for the steady-state analysis. A3.1.1 Single-Phase Circuits A3.1.1.1 Sinusoidal Waveform of Supply Voltage and Linear Load Figure A3.1 shows the sinusoidal waveforms of supply voltage u t and load current i t in a single-phase electric circuit with linear (resistance inductive) load under steady-state operation. 350 300 250 200 [V, A, W] p(t)/10 150 100 u(t) 50 0 i(t) 50 100 ϕ [s] 150 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 Figure A3.1 Waveforms of: supply voltage u t, load current i t and instantaneous power p t for an a.c. circuit with a linear (resistance inductive) load under steady-state operation

29 If the linear load is supplied by sinusoidal voltage u t with the angular frequency : u t = 2U sin t (A3.1) then load current i t can be expressed by the following relation (Figure A3.1): i t = 2I sin t (A3.2) where U is the r.m.s. value of supply voltage u t ; I is the r.m.s. value of load current i t ; and is the phase angle between voltage u t and current i t ( = U I ). The instantaneous power p t is defined as the rate of electric energy flow w t from the supply source to the load and it is equal to the product of u t and i t, which is p t = dw t = u t i t = 2UI sin t sin t (A3.3) dt Relation (A3.3) can be transformed into the following: p t = UI cos UI cos 2 t p t = UI cos 1 cos 2 t UI sin sin 2 t (A3.4) (A3.5) Figure A3.1 shows the waveform of instantaneous power p t. It is a periodic waveform of period T/2, where T is the common period of signals u t and i t. In relations (A3.4) and (A3.5) are components with constant value for given, components with double angular frequency 2 t, components which always take the value greater than or equal to 0 and components of which the average value always equals zero. On the basis of (A3.4) and (A3.5) the following quantities, commonly known and used in electrotechnics to describe the power properties of electric circuits, are defined: P = UI cos active power (A3.6) Q = UI sin reactive power (A3.7) S = UI apparent power (A3.8) Using (A3.4) (A3.8) the instantaneous power p t can be shown to be p t = S cos S cos 2 t = P p osc t (A3.9) p t = S cos 1 cos 2 t S sin sin 2 t (A3.10) = P 1 cos 2 t Q sin 2 t = p a t p b t The waveforms of separated components of instantaneous power p t are shown in Figure A3.2. According to the definition, the active power P equals the average value over one period T of the instantaneous power p t (see Equation (A3.11)). It is also equal to the d.c. component of the waveform of p t (see Equations (A3.4), (A3.6) and (A3.9)): P = 1 T t 0 +T t 0 p t dt = UI cos (A3.11)

30 4000 3000 [W, VA] p(t) = P p osc (t) p(t) p(t) p osc (t) p 2000 S 1000 0 P (a) 1000 P osc (t ) [s] 2000 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 4000 3000 [W, VA, VAr] p(t) = p a (t) p b (t) p(t ) p(t) p a (t) p b (t) 2000 P a (t ) Q 1000 (b) 0 1000 P b (t ) 2000 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 [s] Figure A3.2 Waveforms of separated components of instantaneous power p t

31 In both theory and practice the active power is quite significant because it is reliable enough to define electric energy provided from the source to the load and transformed into other forms in it, such as heat energy, mechanical energy, light energy, etc., so it is an important parameter for the productive processes its dimension is watt, W. The reactive power Q is an amplitude of the component p b t from the relations in Equations (A3.5), (A3.7) and (A3.10) its dimension is volt-ampere reactive, VAr. If the voltage of the supply source U is known, the reactive power Q and the active power P define the r.m.s. value of the load current I (see Equation (A3.12)). Compensation of reactive power to the value Q = 0VAr reduces the r.m.s. value of load current I to its minimal value and eliminates the component p b t (it eliminates the power oscillation): I = ( ) P 2 + U ( ) Q 2 (A3.12) U Besides the active power P and the reactive power Q there is also the term of apparent power S its dimension is volt-ampere, VA. It is the amplitude of the component p osc t of the instantaneous power p t (see Equations (A3.4), (A3.8) and (A3.9)). It gives information on the biggest value of the active power that can be obtained from the supply source with the given supply voltage U and the load current I. In the above case the power equation (A3.13) is fulfilled: S 2 = P 2 + Q 2 (A3.13) In Figure A3.3 a so-called power triangle is shown, whereas Equation (A3.14) shows the relation for the complex power S. The magnitude of the complex power S is equal to the apparent power S: S = U I = Ue j (Ie j ) = Se j = Se j = S cos ( ) + js sin ( ) = P + jq (A3.14) where a bar and a bar with an asterisk denote respectively a complex number and a conjugate complex number. The parameter cos, called the power factor, is defined as cos = P S = DPF (A3.15) Figure A3.3 Graphical representation of power components power triangle

32 It gives information on the extent to which the apparent power S is used, e.g. cos = 0 5 means that only half of the apparent power S is used as the active power P. The parameter cos is also called a displacement power factor (DPF) or the power factor in the first-harmonic domain. A3.1.1.2 Sinusoidal Waveform of the Supply Voltage and Non-linear Load The following consideration assumes that the voltage of the supply source is sinusoidal, while the current waveform will be non-sinusoidal (distorted) because of the non-linear character of the load (Figure A3.4). Therefore, the equation of load current is as follows: i t = 2I n sin n t n n=1 (A3.16) where n is the harmonic order; I n is the r.m.s. value of the nth harmonic of current i t ; and n is the phase angle between the nth voltage u t and current i t harmonics, n = U n I n. The r.m.s. value of the distorted load current i t can be expressed as I = I 2 1 + I 2 2 + I 2 3 + I 2 4 + = I 2 1 + I 2 n = 1 T n=2 T 0 i 2 t dt (A3.17) 250 200 [V, A, W] p(t)/10 150 100 u(t ) 50 0 i(t) 50 100 [s] 150 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 Figure A3.4 Waveforms of: voltage u t, current i t and instantaneous power p t for an a.c. circuit with a non-linear load under steady-state operation

In that case the equation of instantaneous power p t is as follows: 33 p t = UI 1 cos 1 1 cos 2 t UI 1 sin 1 sin 2 t + 2UI n sin t sin n t n n=2 (A3.18) In relations (A3.17) and (A3.18) the component of the first harmonic (the fundamental frequency) denoted by subscript (1) was separated. The definitions of active power P (Equation (A3.6)), reactive power Q (Equation (A3.7)) were specified in the first-harmonic domain and do not change, therefore P 1 = UI 1 cos 1 = P active power (A3.19) Q 1 = UI 1 sin 1 = Q reactive power (A3.20) However, the equation of apparent power S changes, as follows: S = UI = U I 2 1 + I 2 n apparent power (A3.21) n=2 Therefore the power equation takes the form of S 2 = U 2 I 2 = U 2 I 2 1 + U 2 n=2 I 2 n = S2 1 + H 2 = P 2 1 + Q2 1 + H 2 = P 2 1 + D2 (A3.22) In this way in Equation (A3.22) the apparent power in the first-harmonic domain S 1, the distortion (harmonic) power H and the deformation power D were separated. Figure A3.5 shows the so-called power tetrahedron. Therefore on the basis of Equations (A3.17), (A3.21) and (A3.22) the following was obtained: S 1 = UI 1 apparent power in the first harmonic domain A3 8 (A3.23) H = U I n distortion (harmonic) power (A3.24) D = n=2 Q 2 1 + H 2 deformation power (A3.25) Figure A3.5 Graphical representation of power components power tetrahedron

34 In this case of non-linear load the power factor, denoted as PF = cos, was defined as PF = P 1 S = P 1 S 2 1 + H 2 = = cos = cos 1 cos P 1 P 2 1 + Q2 1 + H 2 (A3.26) whereas the equation of the DPF (Equation (A3.15)) does not change and is associated only with the first harmonic domain: DPF = cos 1 = P 1 S 1 (A3.27) Between the factors PF and DPF the following relation exists: where PF = P 1 S = = UI 1 cos 1 UI I 1 I 2 1 + n lim I 2 n n=2 = I 1 I cos 1 = cos 1 1 + 1 n lim I n 2 n=2 I 1 2 cos 1 = 1 1 + THD 2 i DPF (A3.28) is the total harmonic distortion of i t. THD i = nlim I 2 n n=2 I 1 A3.1.2 Three-phase circuits Consider the three-phase, three-wire electric circuit shown in Figure A3.6. Phase voltages and currents are expressed in the form of column vectors: u = u t = u R u S u T T and i = i t = i R i S i T T (A3.29) u i R i Supply Source u R u S i S i T Load u T Figure A3.6 Phase voltages and currents at the cross-section R S T

35 Figure A3.7 shows the sinusoidal symmetrical waveforms of supply voltage u(t) and load current i(t) in the three-phase electric circuit with linear load. Therefore the simplest case from the point of view of power phenomena which take place in three-phase electric circuits is considered. 200 [V, A, W] p 3 f /20 150 100 u 50 0 i (a) 50 100 150 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 [s] 4000 3500 [W] p R p S p T p 3 f 3000 2500 2000 1500 1000 500 0 500 i (b) 1000 [s] 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 Figure A3.7 Waveforms of: supply voltage u(t, load current i(t and phase instantaneous powers p R t, p S t, p T t and instantaneous power p 3f t

36 Referring to the definitions which were given in Section A3.1.1.1, the equation of instantaneous power p 3f t of the three-phase circuit can take the form p 3f t = p R t + p S t + p T t = u R t i R t + u S t i S t + u T t i T t (A3.30) In this case the waveform of instantaneous power p 3f t is constant, in contrast to the single-phase circuit (Figure A3.1, Figure A3.2): p 3f t = 3P = P 3f (A3.31) The relations of powers of the three-phase circuit take the form P R = U R I R cos = P S = P T = P P 3f = 3P Q R = U R I R sin = Q S = Q T = Q P 3f = 3P S R = S R 1 = U R I R = S S = S T = S S 3f = S 3f 1 = 3S (A3.32) (A3.33) (A3.34) and power factors PF 3f and DPF 3f take the form PF 3f = DPF 3f = P 3f S 3f (A3.35) In the above-mentioned case the interpretation, definitions and equations describing these properties for single-phase circuits (Section A3.1.1.1) with sinusoidal supply voltage and current were applied. However, in three-phase circuits a phenomenon occurs which is not present in single-phase circuits, namely the asymmetry of waveforms of supply voltages u(t) and/or load currents i(t). Considering only the asymmetry of load currents of resistive load causes the occurrence of a phase shift between the voltages and currents in three-phase, three-wire electric circuits (despite the lack of passive elements!). Therefore, the displacement power factor DPF 3f equals a value less than 1, DPF 3f < 1. Figure A3.8 shows the waveforms of voltages u(t) and currents i(t) in three-phase, three-wire electric circuits with balanced (Figure A3.8a) and unbalanced (Figure A3.8 b) resistive load. Note in Figure A3.8(b) that the instantaneous power p 3f t is no longer constant. In this situation the interpretation, definitions and formulas for single-phase circuits proposed in Section A3.1.1.1 do not apply. Figure A3.9 shows the sinusoidal symmetrical waveforms of supply voltages u(t) and load current i(t) in a three-phase electric circuit with symmetrical non-linear load. The presence of distorted phase load currents results in the fact that instantaneous power p 3f t is no longer constant. However, in this case it is possible to use the interpretation, definitions and formulas for single-phase circuits proposed in Section A3.1.1.2. Then the quantities in Equations (A3.19) (A3.21) and (A3.23) (A3.25) must be multiplied by 3, similar to Equations (A3.32) (A3.34). This would not be possible if the waveforms of supply voltages u(t) and/or load currents i(t) were asymmetrical. These presented considerations showed the lack of a conventional approach to the interpretation, definitions and formulas of power properties of electric circuits. This was

37 500 [V, A, W] 400 p 3 f /100 300 u 200 100 i 0 (a) 100 200 300 400 0.06 0.07 0.08 0.09 [s] 0.1 600 [V, A, W] p 3 f /100 400 u 200 i 0 (b) 200 400 600 0.06 0.065 0.07 0.075 0.08 0.085 0.09 0.095 [s] 0.1 Figure A3.8 Waveforms of: supply voltage u(t, load current i(t and instantaneous power p 3f t in the three-phase, three-wire electric circuit with balanced (a) and unbalanced (b) resistive load

38 [V, A, W] 250 200 p 3 f /20 150 100 u 50 0 i (a) 50 100 150 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 [s] 5000 [W] p 3 f 4000 3000 2000 (b) 1000 0 p R p S p T [s] 1000 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 Figure A3.9 Waveforms of: supply voltage u(t, load current i(t, phase instantaneous powers p R t, p S t, p T t and instantaneous power p 3f t especially apparent in the case of three-phase circuits with asymmetrical waveforms of voltages and/or currents. Moreover, it should be emphasized that this kind of approach does not take into consideration the distorted supply voltage and is valid only for steady-state analysis.

39 A3.1.2.1 Apparent Power in Three-phase Circuits It is worth noting that in electrotechnics three definitions are used to calculate the apparent power of three-phase electric circuits, namely S A = U R I R + U S I S + U T I T S G = P3f 2 + Q2 3f S B = UR 2 + US 2 + U T 2 IR 2 + IS 2 + I T 2 arithmetic apparent power PF A = P S A geometric apparent power PF G = P S G Buchholz s apparent power PF B = P S B (A3.36) (A3.37) (A3.38) where P = P R + P S + P T total active power, Q = Q R + Q S + Q T total reactive power. The first two, the arithmetic apparent power S A and the geometric apparent power S G, are most often used in three-phase electric circuits. Buchholz s definition of apparent power S B is rather unknown among the electrical engineering community. As long as the supply voltage is sinusoidal and symmetrical, and the load is balanced, these relations give the same correct result. If one of the above-mentioned conditions is not met the obtained results will differ. The consequence of this will be that we get different values of power factors for the same electric circuit. Therefore, the value of power factor depends on the choice of the apparent power definitions. For obvious reasons such a situation is neither desired nor admissible. In [25] it has been proved that in such a case only Buchholz s definition of apparent power S B allows for the correct calculation of apparent power, and therefore of the power factor value. Thus, the arithmetic apparent power S A and the geometric apparent power S G do not properly characterize the power phenomena in the case of asymmetrical waveforms of supply voltage and/or load currents in unbalanced electric circuits. Moreover, it can be proven that Buchholz s apparent power can be extended to circuits with non-sinusoidal voltages and currents [25]. A3.2 MODERN (SELECTED) CONCEPTS OF THE POWER PROPERTIES OF ELECTRIC CIRCUITS The first propositions of the power theory appeared in the 1920s and 1930s. Two basic trends of power theory development came into being at that time. The first makes use of Fourier series to describe the power properties of electric circuits. This trend treats the electrical waveforms as the sum of components with different frequencies and that is why the power properties of an electric circuit are defined in the frequency domain. Almost at the same time that the frequency trend came into being, a trend stressing the direct definition of power quantities in electric circuits, without using Fourier series, appeared. They are defined as the functional of the waveforms of current and voltage that is in the time domain. The problem of a lack of a universally accepted power theory describing the power properties of an electric circuit with non-sinusoidal waveforms of voltages and currents and valid for steady and transient states has taken on greater and greater significance since the discovery of the semiconductor and the development of power electronics. Besides the undeniable advantages of power converters, they are also a source of negative phenomena.

40 The growth in the number of power converters (non-linear devices) has caused a significant increase in the level of harmonics and has revealed their negative influence on the power system. For this reason, since the 1970s the interest in describing the power properties of such devices and the interest in methods of improving power factor have significantly increased [44]. There are many methods for the description of power phenomena occurring in electric circuits under non-sinusoidal conditions, which, de facto, are proposals of the power theory. The extension of the reactive power to non-sinusoidal and asymmetrical waveforms is now a subject of controversy. Many new power theories have been proposed and they are not accepted by all researchers around the world. The suggested definitions of this topic are still confusing and it is difficult to find a general and unified interpretation of power phenomena and the definitions of power properties under non-sinusoidal conditions, particularly when three-phase unbalanced circuits are analyzed. The most popular power theory has been proposed by Akagi and co-authors, which is known as the p q power theory [2],[3]. In many researchers opinion and also in the author s opinion the most correct interpretation of power phenomena and description of power properties was presented by Czarnecki, which is known as the power theory based on the current s physical components theory [19],[20]. Both theories are of particular importance for the development of power theory. A3.2.1 The p q Power Theory Proposed by Akagi et al. H. Akagi, A. Nabae and Y. Kanazawa proposed in 1983 the generalized theory of the instantaneous reactive power [2],[3], also known as the p q power theory. This theory has been developed in the time domain. It is valid for steady and transient states and for three-phase, three-wire or four-wire circuits. Its definitions are formulated on the basis of the transformation of a three-phase system in natural R S T coordinates, to the orthogonal (or 0) coordinates (the Clarke transformation). The transformation allows for the time-domain analysis of the power properties of three-phase circuits, as well as the physical interpretation of the defined quantities. But the suggested interpretation is still controversial. The instantaneous imaginary power proposed by Akagi and co-authors does not have a clear physical meaning. The present analysis will be focused on three-wire circuits (Figure A3.6). Therefore, zero-sequence voltage or current components are not present. The p q power theory (in its original form) transforms instantaneous voltage u and current i (see Equation (A3.29)) measurements by the following matrix equations: [ e e ] = [ 2 1 1 3 1 2 2 0 3 3 2 2 ] u R u S u T and [ ] [ i 2 1 1 = i 3 1 2 2 0 3 3 2 2 ] i R is i T (A3.39) where e = e + e, i = i + i, e = e, e = e, i = i, i = i are space vectors of voltage and current in coordinates and their amplitudes (the arrow denotes a space vector).

41 The instantaneous active power p and the instantaneous imaginary power q were defined as p = e i + e i q = e i + e i (A3.40) (A3.41) where: p q is the real power in the three-phase circuit equal to the conventional equation of the instantaneous power p 3f t (Equation (A3.30)). This power represents the total energy flow per unit time in the three-wire, three-phase circuit, in terms of components (its dimension is W). is the imaginary power (the imaginary axis vector is perpendicular to the real plan in coordinates), has a non-traditional physical meaning and gives the measure of the quantity of current or power that flows in each phase without transporting energy at any instant. Akagi and co-authors introduced the instantaneous imaginary power space vector q in order to define the instantaneous reactive power. This means that q could not be dimensioned in W, VA or VAr, so its dimension is imaginary volt-amperes, IVA. Therefore, on the basis of Equations (A3.40) and (A3.41) the following was obtained: [ ] [ ] [ ] p e e = i (A3.42) q e e i where q is the amplitude of space vector q ( q = q). To calculate the currents i, i in coordinates the expression (A3.42) is changed into the following: [ ] [ ] 1 [ ] i e e = p = 1 [ ] [ ] e e p i e e q e 2 + (A3.43) e2 e e q In general, when the load is non-linear and unbalanced the real and imaginary powers can be divided into average and oscillating components, as follows: p = p + p = p + p h + p 2f 1 q = q + q = q + q h + q 2f 1 (A3.44) (A3.45) where p, q are the average components, p h, q h oscillating components (h stands for harmonic) and p 2f 1, q 2f 1 oscillating components (2f 1 refers to double the fundamental component frequency). From these power components it is possible to calculate the current components in coordinates. Then, by using the Clarke inverse transformation, it is possible to calculate the currents in the natural R S T coordinates. Finally, according to the p q power theory, the three-phase unbalanced non-linear load is expressed in four components i = i p + i q + i h + i 2f 1 (A3.46)

42 where i p is associated with p, i.e. with the active power P defined in the traditional way, p = P R + P S + P T = P ; i q is associated with q, i.e. with the reactive power Q (in the case of a symmetrical sinusoidal supply voltage and balanced linear load, q is equal to the reactive power Q 3f defined in the traditional way in the fundamental harmonic domain, q = q = Q 3f (Equation (A3.33)); i h is associated with p h and q h, i.e. with the presence of harmonics in voltage and current waveforms; and i 2f 1 is associated with p 2f 1 and q 2f 1, i.e. the unbalance load currents. Figure A3.10 shows a graphical representation of defined power components in the three-phase circuit. The p q power theory turned out to be a very useful tool for building and developing the control algorithms of active power filters. This power theory has been the basis of many other proposals of power theory. Among them the most interesting is the power theory proposed by Peng [48], [50]. A3.2.2 The Power Theory Based on the Current s Physical Components Theory Proposed by Czarnecki The power theory based on the current s physical components theory proposed by L. S. Czarnecki has been developed in the frequency domain. This theory is a proposal for the physical interpretation of power phenomena occurring in electric circuits under unbalanced conditions and in the presence of non-sinusoidal waveforms. The complete Czarnecki theory for three-phase unbalanced circuits with periodic non-sinusoidal source voltage was presented in 1994 [20]. The theory deals comprehensively with all situations in circuits with periodic waveforms, from the interpretation in physical terms to methods for power factor improvement in single-phase and three-phase circuits. For the purpose of the present analysis the power theory for three-phase, three-wire electric circuits (Figure A3.6) has been applied under the assumption that the voltage unbalance at the cross-section R S T is negligibly small; it has therefore been neglected in the analysis. Figure A3.10 The p q power theory a graphical representation of defined power components in a three-phase circuit

43 Phase voltages are expressed in terms of Fourier series and presented in the form of the vector u (see Equation (A3.29)): u R u = u S = u n = u n R u n S = 2Re U n R U n S e jn 1 t u n N n N T u n N n T U n T (A3.47) = 2Re U n e jn 1 t n N where U n = U n R U n S U n T T is the vector of voltage complex r.m.s. values. N denotes the set of voltage harmonics observed at the cross-section R S T. The supply source is assumed to have internal impedance, therefore the same harmonics occur in both the voltages and currents. Phase currents are presented, analogously to the voltages, by means of the vector i (see Equation (A3.29)): i = i R is i T = i n = n N n N = 2Re I n e jn 1t n N i n R i n S i n T = 2Re n N I n R e jn 1t I n S I n T (A3.48) where I n = I n R I n S I n T T is the vector of current complex r.m.s. values. The complex power S n of the nth-order harmonic is S n = U T n I n = P n + jq n (A3.49) where P n and Q n are the nth-order harmonic active and reactive power of a load. If the load is passive, linear and time invariant, then the harmonic active power P n is transmitted from the source to the load, i.e. P n 0. If any of the above conditions is not satisfied the current harmonics can be generated in the load. The energy at the generated harmonic frequencies can be transmitted from the load to the source, i.e. P n 0. Hence the set of all orders of harmonics N has been divided into two subsets N A and N B : if P n 0 then n N A if P n < 0 then n N B (A3.50) Thus the voltages u, currents i and active power P observed at the cross-section R S T (Figure A3.6) have been decomposed into the following components: i = i n = i n + i n = i A + i B n N n N A n N B u = u n = u n u n = u A u B n N n N A n N B P = P n = P n P n = P A P B n N n N A n N B (A3.51) (A3.52) (A3.53)

44 According to the current s physical components theory, the current of the three-phase, unbalanced, non-linear load has been decomposed into five components: i = i a + i s + i r + i u + i B (A3.54) The components are defined by the following relations: i a = 2Re G e U A n e jn 1 t active current (A3.55) n N i s = 2Re (G e n G e )U A n e jn 1 t scattered current (A3.56) n N A i r = 2Re jb e n U A n e jn 1 t reactive current (A3.57) n N A i u = i u n = 2Re A n U A n e jn 1 t unbalanced current (A3.58) n N A n N A i B = i n load-generated current (A3.59) n N B where G e is the equivalent conductance; Y e n = G e n +jb e n the equivalent admittance and A n the unbalanced admittance. Appropriate relationships, which enable the determination of G e, Y e n, A n, and powers P A, D s, Q r, Q u, S B, S F, S are given in [19],[20]. Each component is associated with a different power phenomenon and is orthogonal with respect to the others. Thus the current decomposition (A3.54) reveals five different physical phenomena, which determine the load current value, namely active energy transmission to the load, i a ; change of the load conductance G e n with frequency, i s ; reciprocating flow of energy, i r ; load current unbalance, i u ; active energy transmission back to the source, i B. If harmonic currents are generated by the supply source, due to the distorted voltage, then the current components i a, i s, i r, i u may also contain, besides the fundamental, also high-order harmonics of orders already present in the voltage. 2 Thus, each of the components i a, i s, i r, i u can be additionally decomposed into the fundamental and high-order harmonics, e.g. i a = i a 1 + i a h (A3.60) where the subscript (h) means harmonics without the first harmonic. The subscript (1) means the first harmonic. The equivalent electric circuits for harmonics of order n N A and n N B are shown in Figure A3.11 and Figure A3.12, respectively. 2 This is decided by the sign of the active power calculated for the given harmonic [19],[20].

45 Figure A3.11 The equivalent electric circuit for harmonics of order n N A Figure A3.12 The equivalent electric circuit for harmonics of order n N B (where Z e n is the impedance of the supply source for harmonics of order n N B Due to the orthogonality of the current s physical components, their r.m.s. values satisfy the relation i 2 = i a 2 + i s 2 + i r 2 + i u 2 + i B 2 (A3.61) where i is the r.m.s value of i (see Equation (A3.29)) and i = i T n i n = i T n i n = n M n M n M I 2 n R + I 2 n S + I 2 n T = i R 2 + i S 2 + i T 2 where M denotes respectively the set N A or N B. Multiplying Equation (A3.61) by the square of the supply voltage r.m.s. value u, we obtain the equation of powers for an unbalanced three-phase circuit with non-sinusoidal waveforms: S 2 = P 2 A + D2 s + Q2 r + Q2 u + S2 B + S2 F (A3.62)

46 where S = u i = SA 2 + S2 B + SF 2 apparent power (A3.63) S A = u A i A = PA 2 + D2 s + Q2 r + Q2 u supply-originated apparent power (A3.64) S B = u B i B load-generated apparent power (A3.65) S F = u A 2 i B 2 + u B 2 i A 2 forced apparent power (A3.66) P A = P n active power for harmonics n N A of order n N A A3 53 (A3.67) D s = u A i s scattered power (A3.68) Q r = u A i r reactive power (A3.69) Q u = u A i u unbalanced power (A3.70) The last component of the apparent power, S F, occurs even in an ideal circuit, when the supply voltage source is connected with a current source of harmonic orders different than the supply voltage harmonics. In the case of unidirectional flow of energy from the supply source to the load, some power components are equal to zero (S B = S F = 0), and then S A = S and for all orders of harmonics P n 0 (the subset N B is empty). The power factor PF CPC has been determined by means of the components of the apparent power S, and also by means of the current s physical components: PF cpc = P S = P A P B P 2 A + D 2 s + Q2 r + Q2 u + S2 B + S 2 F = i a i i = a i a 2 + i s 2 + i r 2 + i u 2 + i B 2 (A3.71) In this way the decomposition (A3.54) reveals the influence on the source power factor PF CPC of all physical phenomena in three-phase unbalanced circuits with periodic distorted waveforms. This theory provides the basis for developing control algorithms, among others, for reactive power compensators, balancing compensators, hybrid filters and active power filters. A3.2.3 Other Proposed Power Theories As was mentioned above, many proposals of power theory and many suggested definitions of power properties (power phenomena) exist in the scientific literature. Table A3.1 shows a list of proposals of power theories. This list is limited due to the large number of attempts to define them. Due to the fact that the list is a summary of the different concepts, only their general characteristics are presented: the domain in which the power theory was defined, the date of its publication, the type of electric circuits (single-, three-, multi-phase), and the kind of quantities that were used in the definitions (average, r.m.s, instantaneous) [54].

Table A3.1 Comparison of the proposed power theories and suggested definitions of power properties (power phenomena) 47 Author(s) of The Power Theory Date of publication Number of phases of the circuit Value of the quantities Single Three Multiple Average and/or r.m.s. values Instantaneous value Defined in time domain Fryze (Fryze s power theory) orthogonal currents Kusters and Moore inductive and capacitive current Depenbrock the first harmonic of voltage and current Akagi, Nabae, Kanazawa the p q power theory Ferrero, Superti-Furga the Park power theory Willems generalized Akagi s and Ferrero s p q power theories Depenbrock the FDB (Fryze Buchholz Depenbrock) power theory Rossetto and Tenti instantaneous orthogonal currents Nabae and Tanaka instantaneous space vector with polar coordinates Peng generalized instantaneous reactive power theory Peng generalized non-active power theory 1931 1979 1979 1983 1991 1992 1993 1994 1996 1996 2000

48 Table A3.1 (Continued) Author(s) of The Power Theory Date of publication Number of phases of the circuit Value of the quantities Single Three Multiple Average and/or r.m.s. values Instantaneous value Defined in frequency domain Budeanu s power theory 1927 Shepherd and Zakikhani 1972 optimum capacity Czarnecki 1983 Harmonic the current s physical components theory 1994 analysis Optimization approach Pasko, Siwczyński, Walczak 1985 BIBLIOGRAPHY [1] Akagi H., Nabae A., The p-q theory in three-phase systems under non-sinusoidal conditions. European Transactions on Electrical Power, vol. 3, no. 1, pp. 27 31, 1993. [2] Akagi H., Kanazawa Y., Nabae A., Generalized theory of the instantaneous reactive power in three-phase circuits. Proceedings of the International Power Electronics Conference, (JIEE IPEC), pp. 1375 1386, Tokyo/Japan, 1983. [3] Akagi H., Kanazawa Y., Nabae A., Instantaneous reactive power compensators comprising switching devices without energy storage components. IEEE Transactions on Industry Applications, vol. IA-20, no. 3, pp. 625 631, 1984. [4] Akagi H., Nabae A., Atoh S., Compensation characteristics of active power filter using multiseries voltage source PWM converters. Electrical Engineering in Japan, vol. 106, no. 5, 1986. [5] Akagi H., Nabae A., Atoh S., Control strategy of active power filters using multiple voltage-source PWM converters. IEEE Transactions on Industry Applications, vol. IA-22, no. 3, pp. 460 4658, 1986. [6] Akagi H., Kim H., Ogasawara S., The theory of instantaneous power in three-phase four-wire systems: a comprehensive approach. IEEE IAS Annual Meeting 1999 Conference Record, Vol. 1, pp. 431 439, 1999. [7] Akagi H., Watanabe E. H., Aredes M., The p-q theory for active filter control: some problems and solutions. Sba Controle & Automação, vol. 15, no. 1, pp. 78 84, 2004. [8] Aredes M., Watanabe E. H., Stephan R. M., New concepts of instantaneous active and reactive powers in electrical systems with generic loads. IEEE Transaction on Power Delivery, vol. 8, no. 2, pp. 697 703, 1993.

49 [9] Buchholz F., Das Begriffsystem Rechtleistung, Wirkleistung, Totale Blindleistung, Selbstverlag, Munich, 1950. [10] Budeanu C. I., Puissances reactives et fictives, Inst. Romain de l Energie, Bucharest, 1927. [11] Cichowlas M., Prostownik sterowany metoda modulacji szerokosci impulsów z filtracja aktywna (PWM rectifier with active filtering). Rozprawa Doktorska, Politechnika Warszawska, 2004. [12] Czarnecki L. S., Ortogononalne składniki pradu odbiornika liniowego zasilanego napięciem odkształconym. Zeszyty Naukowe Politechniki Ślaskiej, seria Elektryka, nr 86, str. 5 17, 1983. [13] Czarnecki L. S., Considerations on the reactive power in nonsinusoidal situations. IEEE Transactions on Instrumentation and Measurement, vol. IM-34, pp. 399 404, 1984. [14] Czarnecki L. S., What is wrong with the Budeanu concept of reactive and distortion power and why it should be abandoned. IEEE Transactions on Instrumentation and Measurement, vol. 36, pp. 834-837, 1987. [15] Czarnecki L. S., Orthogonal decomposition of the current in a three-phase nonlinear asymmetrical circuit with nonsinusoidal voltage. IEEE Transactions on Instrumentation and Measurement, vol. IM-37, no. 1, pp. 30 34, 1988. [16] Czarnecki L. S., Reactive and unbalanced current compensation in three-phase asymmetrical circuits under nonsinusoidal conditions. IEEE Transactions on Instrumentation and Measurement, vol. IM-38, no. 3, pp. 754 759, 1989. [17] Czarnecki L. S., A time-domain approach to reactive current minimization in nonsinusoidal situations. IEEE Transactions on Instrumentation and Measurement, vol. 39, pp. 698 703, 1990. [18] Czarnecki L. S., Scattered and reactive current, voltage and power in circuits with nonsinusoidal waveforms and their compensation. IEEE Transactions on Instrumentation and Measurement, vol. 40, no. 3, pp. 563 567, 1991. [19] Czarnecki L. S., Current and power equations at bidirectional flow of harmonic active power in circuits with rotating machines. European Transactions on Electrical Power, vol. 3, no. 1, pp. 45 52, 1993. [20] Czarnecki L. S., Dynamic, power quality oriented approach to theory and compensation of asymmetrical systems under nonsinusoidal conditions. European Transactions on Electrical Power, vol. 5, pp. 347 358, 1994. [21] Czarnecki L. S., Power theory of electric circuits: common data base of power related phenomena and properties. European Transactions on Electrical Power, vol. 4, no. 6, pp. 491 494, 1994. [22] Czarnecki L. S., Supply and loading quality improvement in sinusoidal power systems with unbalanced loads supplied with asymmetrical voltage. Archiv für Elektrotechnik, vol. 77, pp. 169 177, 1994. [23] Czarnecki L. S., Power related phenomena in three-phase unbalanced systems. IEEE Transactions on Power Delivery, vol. 10, no. 3, pp. 1168 1176, 1995. [24] Czarnecki L. S., Powers and compensation in circuits with periodic voltage and currents. Part 2 Outline of the history of power theory development. JUEE, vol. III-2, pp. 37 46, 1997 (in Polish). [25] Czarnecki L. S., Energy flow and power phenomena in electrical circuits: illusions and reality. Electrical Engineering, vol. 82, pp. 119 126, Springer-Verlag, 2000. [26] Czarnecki L. S., Harmonics and power phenomena. Wiley Encyclopedia of Electrical and Electronics Engineering, Supplement 1, pp. 195 218, John Wiley & Sons, Inc., New York, 2000. [27] Czarnecki L. S., Moce i kompensacja w obwodach z okresowymi przebiegami pradu i napięcia. Część 7Waściwości energetyczne liniowych, trójprzewodowych obwodów trójfazowych. JUEE, Tom VI, Zeszyt 1, str. 21 28, 2001. [28] Czarnecki L. S., Comparison of instantaneous reactive power p-q theory with theory of the current s physical components. Archiv für Elektrotechnik, vol. 85, no. 1, pp. 21 28, 2003.

50 [29] Czarnecki L. S., Power properties of three-phase electric circuits and their misinterpretations by the instantaneous reactive power p-q theory. Przeglad Elektrotechniczny, nr 59, str. 23 40, 2003. [30] Czarnecki L. S., Moce i kompensacja w obwodach z okresowymi przebiegami pradu i napięcia. Część 9 Defekty teorii chwilowej mocy biernej p-q Nabae a i Akagi ego. JUEE, Tom 9, Zeszyt 2, 5, 2004. [31] Depenbrock M., Wirk- und Blindleistung, ETG-Fachtagung Blindleistung, Aachen, October 1979. [32] Depenbrock M., Some remarks to active and fictitious power in polyphase and single-phase systems. European Transactions on Electrical Power, vol. 3, pp. 15 19, 1993. [33] Depenbrock M., The FBD method, a generally applicable tool for analyzing power relations. IEEE Transactions on Power Systems, vol. 8, pp. 381 387, 1993. [34] Depenbrock M., Staudt V., Wrede H., A theoretical investigation of original and modified instantaneous power theory applied to four-wire systems. IEEE Transactions on Industry Applications, vol. 39, no. 4, pp. 1160 1168, 2003. [35] Ferrero A., Superti-Furga G., A new approach to the definition of power components in three-phase systems under nonsinusoidal conditions. IEEE Transactions on Instrumentation and Measurement, vol. 40, pp. 568 577, 1991. [36] Fryze S., Moc rzeczywista, urojona i pozorna w obwodach elektrycznych o przebiegach odkształconych pradu i napięcia. Przeglad Elektrotechniczny, nr 7, str. 193 203, 1931; nr 8, str. 225 234, 1931; nr 22, str. 673 676, 1932. [37] Kusters N. L., Moore W. J. M., On the definition of reactive power under non-sinusoidal conditions. IEEE Transactions on Power Apparatus and Systems, vol. PAS-99, no. 5, pp. 1845 1854, 1980. [38] Nabae A., Tanaka T., A new definition of instantaneous active-reactive current and power based on instantaneous space vectors on polar coordinates in three-phase circuits. Conference Record IEEE/PES 1996 Winter Meeting, Baltimore, MD, 1996. [39] Nabae A., Togasawa S., Murase T., Nakano H., Reactive power compensation based on a novel cross-vector theory. IEEE Transactions on Industry Applications, vol. 114, no. 3, pp. 340 341, 1994. [40] Nabae A., Nakano H., Togasawa S., An instantaneous distortion current compensator without any coordinate transformation. Proceedings of the IEEE International Power Electronics Conference 1995, pp. 1651 1655, 1995. [41] Pasko M., Dobór kompensatorów optymalizujacych warunki pracy źródeł napięć jednofazowych i wielofazowych z przebiegami okresowymi odkształconymi. Zeszyty Naukowe Politechniki Ś askiej, seria Elektryka, z. 135, monografia habilitacyjna, Gliwice, 1994. [42] Pasko M., Opis właciwoci energetycznych, energetyczno-jakociowych obwodów elektrycznych z przebiegami niesinusoidalnymi okresowymi. Przeglad Elektrotechniczny, nr 59, str. 23 40, 2002. [43] Pasko M., Maciażek M., Aktywna kompensacja równoległa w układach trójfazowych czteroprzewodowych. Przeglad Elektrotechniczny, R.80, str. 544 548, 6/2004. [44] Pasko M., Maciażek M., Wkład elektrotechniki teoretycznej w poprawę jakości energii elektrycznej. IC-SPETO 2004, Tom I, ss. 5a 5k (referat monograficzny) lub Wiadomości Elektrotechniczne, Nr 7 8, str. 37 46, 2004. [45] Pasko M., Walczak J., Optymalizacja energetyczno-jakościowych właciwości obwodów elektrycznych z przebiegami okresowymi niesinusoidalnymi, Zeszyty Naukowe Politechniki Ślaskiej, seria Elektryka, z. 150, monografia, Gliwice, 1996. [46] Pasko M., Maciażek M., Dębowski K., Kompensacja wpływu odbiorników nieliniowych na sieć zasilajac a niskiego napięcia. Przeglad Elektrotechniczny, R.80, str. 807 812, 9/2004.

51 [47] Peng F. Z., Harmonic sources and filtering approaches. IEEE Industry Applications Magazine, July/August, pp. 18 25, 2001. [48] Peng F. Z., Lai J. S., Generalized instantaneous reactive power theory for three-phase power systems. IEEE Transactions on Instrumentation and Measurement, vol. 45, no. 1, pp. 293 297, 1996. [49] Peng F. Z., Tolbert L. M., Compensation of nonactive current in power systems definitions from a compensation standpoint. IEEE Power Engineering Society Summer Meeting, Seattle, WA, pp. 983 987, 15 20 July 2000. [50] Peng F. Z., Ott G. W. Jr, Adams D. J., Harmonic and reactive power compensation based on the generalized reactive power theory for three-phase four-wire systems. IEEE Transactions on Power Electronics, vol. 13, no. 6, pp. 1174 1181, 1998. [51] Rashid M., Dixon J., Moran L., Active filters. Power electronics handbook, Chapter 33, Academic Press, New York, 2001. [52] Rossetto L., Tenti P., Evaluation of instantaneous power terms in multi-phase systems: techniques and applications to power-conditioning equipment, European Transactions on Electrical Power, vol. 4, pp. 469 475, 1994. [53] Shepherd W., Zakikhani P., Suggested definition of reactive power for nonsinusoidal systems. Proceedings of the IEE, vol. 119, no. 9, pp. 1361 1362, 1972. [54] Tolbert L. M., Habetler T. G., Comparison of time-based non-active power definitions for active filtering. IEEE International Power Electronics Congress, Acapulco, Mexico, pp. 73 79, 15 19 October 2000. [55] Willems J. L., A new interpretation of the Akagi Nabae power components for nonsinusoidal three-phase situations. IEEE Transactions on Instrumentation and Measurement, vol. 41, pp. 523 527, 1992.