Effect of Temperature on Condition Assessment of Oil-Paper Insulation using Polarization- Depolarization Current

Similar documents
Excerpt from the Proceedings of the COMSOL Conference 2010 Paris

Diagnosis of Electrical Performance and Aging Behavior of Transformer Dielectrics

Modeling of Polarization in Oil-Paper Insulation Using Recovery Voltage Measurements

Condition assessment of transformer insulation using dielectric frequency response analysis by artificial bee colony algorithm

Comparing Various Moisture Determination Methods for Power Transformers MAIK KOCH*, MICHAEL KRÜGER, STEFAN TENBOHLEN

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 19, NO. 3, JULY Tapan K. Saha, Senior Member, IEEE, and Prithwiraj Purkait, Member, IEEE

OBSERVATION OF DIELECTRIC PARAMETERS AT GENERATOR STATOR WINDINGS UNDER CHANGING ENVIRONMENTAL CONDITIONS

CIGRE SC A2 & D1 JOINT COLLOQUIUM 2011, KYOTO JAPAN. Water Saturation Limits and Moisture Equilibrium Curves of Alternative Insulation Systems

Dielectric Analysis of Solid Insulations

Understanding the Impacts of Moisture and Thermal Ageing on Transformer s Insulation by Dielectric Response and Molecular Weight Measurements

World Academy of Science, Engineering and Technology

Comparative Study on Conductivity Using Polarization and Depolarization Current (PDC) Test

THE EFFECT OF REVERSAL ON CAPACITOR LIFE

HIGH ENERGY DENSITY CAPACITOR CHARACTERIZATION

Garton Effect and Its Influence on High-Voltage Dielectric Loss. Measurement for Capacitive Equipment

Experimental study of dynamic thermal behaviour of an 11 kv distribution transformer

CHECKING OF POLARIZED AND DEPOLARIZED CURRENTS FOR THE ELECTRICAL EQUIPMENTS, IN ORDER TO DETERMINATE THE STATE OF INSULATION AND ITS HUMIDITY CONTENT

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING

Dielectric Analysis of Insulation Liquids

Parameter Influences on HVDC Transformer Insulation and Its Link to Conduction Processes

CHAPTER 2 ESTIMATION OF BREAKDOWN VOLTAGES IN SMALL INSULATION GAPS AN EMPIRICAL APPROACH

Modeling of Degradation Mechanism at the Oil-Pressboard Interface due to Surface Discharge

Metallized PPS Capacitors for extreme capacitance stability. 1 min / 23 C B

By: Jin Huifei Supervisor: Dr.hab. ir.e Gulski (prof. of PUT) Lukasz Chmura, MSc

On-line Monitoring for Bushing of Power Transformer

ENHANCEMENTS TO DIELECTRIC RESPONSE MEASUREMENTS OF OIL-PAPER INSULATION FOR ONLINE AND OFFLINE APPLICATIONS

Electrical Breakdown Properties of Oil-paper Insulation under Pulsating Voltage Influenced by Temperature

The Impact of Metallized Electrodes on High Energy Density Pulse Power Capacitors

Impact of Accelerated Stresses on Power Transformer Insulation

Capacitors. Typical electrical characteristics of metallized polyester capacitors KEU. Type KEU Metallized polyester capacitors

Studies on hyper scaling dielectric loss of grading capacitors of 500kv breakers

JWG A2/D1.41 HVDC transformer insulation: Oil conductivity 1

СРЕДСТВА ИЗМЕРЕНИЙ MEASUREMENT STAND FOR STUDY PROPERTIES OF ISOLATION MATERIALS USING POLARIZATION METHOD

Requirements to perform accurate dielectric material analysis

On-site Non-destructive Dielectric Response Diagnosis of Rotating Machines

Development of a New Solid Insulation with the use of Phenol Formaldehyde Resin Material for a Liquid-Immersed Transformer

NUMERICAL AND EXPERIMENTAL INVESTIGATION OF THE TEMPERATURE DISTRIBUTION INSIDE OIL-COOLED TRANSFORMER WINDINGS

Insulation Resistance and Polarization of Rotating Machines

Bridge Measurement 2.1 INTRODUCTION Advantages of Bridge Circuit

Metallized Polypropylene Film Capacitor Related Document: IEC

Finite Element Analysis of Disc Insulator Type and Corona Ring Effect on Electric Field Distribution over 230-kV Insulator Strings

High Frequency Dielectric Strength Tests

THREE PHASE CAPACITOR For WIND TURBINES

T. K. Saha and P. Purkait School of Information Technology and Electrical Engineering University of Queensland St. Lucia, Qld Australia

Electric Filed Simulation and Structure Optimization for 40.5kV GIS Based on Finite Element Method

PMLCAP. Polymer Multi Layer Capacitor Specification Sheet RUBYCON CORPORATION PML DIVISION. PMLCAP ST series RPR Rubycon PART No. Drawing No.

Research on Transformer Condition-based Maintenance System using the Method of Fuzzy Comprehensive Evaluation

Code No: RR Set No. 1

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits

JOURNAL OF INTERNATIONAL ACADEMIC RESEARCH FOR MULTIDISCIPLINARY Impact Factor 2.417, ISSN: , Volume 3, Issue 12, January 2016

Evaluation of Capacitance in Motor Circuit Analysis Findings. Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN

Study on Acoustically Transparent Test Section of Aeroacoustic Wind Tunnel

TD-102. HAEFELY HIPOTRONICS Technical Document

Modern Electrical Diagnostics for Metal Oxide Surge Arresters

Fatima Michael College of Engineering & Technology

Short-Term Dielectric Performance Assessment of BOPP Capacitor Films: A Baseline Study

PERMITTIVITY VARIATIONS ON MARBLE BEAMS SUBJECTED TO VARIOUS LOADING LEVELS

OR Explain thermal breakdown in solid dielectrics. How this mechanism is

COMPARATIVE EVALUATION OF BREAKDOWN STRENGTH OF NATURAL ESTERS AND MINERAL OIL

Metallized Polypropylene Film Capacitor Related Document: IEC

Modeling Electric Fields in High Voltage Submersible Changeover Switch

Construction and Characteristics of

Temperature and Field Dependence of Field Grading Tubes for Medium Voltage XLPE Cable Joints

Strength Study of Spiral Flexure Spring of Stirling Cryocooler

Research Article Effect of Asymmetrical Edge Disconnection on Equivalent Series Resistance of Metalized Polypropylene Capacitors

Conductivity of Pressboard for HVDC Insulation Systems

and cables for offshore wind connection

Capacity calculation of the electrotechnical scheme of discharge gap replacement of the ozonizer in the СOMSOL environment

Elizabethtown College Department of Physics and Engineering PHY104

A simple model based control of self excited induction generators over a wide speed range

Jinzhou Power Supply Company, Liaoning Electric Power Company Limited, State Grid, China

Reliability of Flexible Termination Ceramic Capacitors in Temperature-Humidity-Bias Conditions. Michael H. Azarian, Ph.D

1439. Numerical simulation of the magnetic field and electromagnetic vibration analysis of the AC permanent-magnet synchronous motor

Simulation of Partial Discharge in Solid Dielectric Material

Research and Development of Parylene Thin-Film Deposition and Application for Water-Proofing

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM

PARTICLE TRAJECTORIES IN A THREE PHASE COMMON ENCLOSURE GAS INSULATED BUSDUCT WITH MONTE CARLO TECHNIQUE

Metallized Polyester Film Capacitors (MKT-S)

Comparison of Radial Movement of Metallic Particles in a Single Phase Gas Insulated Busduct

Homework Assignment 11


Multilayer Ceramic Chip Capacitors

Formation of white-eye pattern with microdischarge in an air. dielectric barrier discharge system

BREAKDOWN STUDY OF WATER WITH DIFFERENT CONDUCTIVITIES

PRACTICAL APPLICATION OF ELECTRICAL CIRCUITS IN MEASUREMENT. Terry Jackson, Master Electrician. RT Technical Solutions, LLC.

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

ALUMINUM ELECTROLYTIC CAPACITORS Capacitor Life

Reliability Enhancement of Line Insulator of a Transmission System using Artificial Neural Network Sumit Mathur #1, G.K. Joshi* 2

Research Article Finite Element Analysis of Flat Spiral Spring on Mechanical Elastic Energy Storage Technology

STUDIES ON LIGHTNING CHARACTERISTICS

On Designing of a High Voltage Standard Capacitor Using a Semi-Analytical Field Computation Method

Accurate Location of Transformer Hottest Spot by FEM and Thermal Models

MME 467: Ceramics for Advanced Applications

Lecture 20. Measuring Pressure and Temperature (Chapter 9) Measuring Pressure Measuring Temperature MECH 373. Instrumentation and Measurements

BIHAR STATE POWER TRANSMISSION COMPANY LIMITED. Manufacturing Quality Plan Current Transformers (Upto 132 kv)

MKP.g. 1.0 Rated Values and Operational Data

Guide for the Frequency Domain Spectroscopy Measurement for transformer bushing CSG:Deng Jun

Measurement of the organic saturation and organic porosity in. shale

A 2-Dimensional Finite-Element Method for Transient Magnetic Field Computation Taking Into Account Parasitic Capacitive Effects W. N. Fu and S. L.

Critical parameters of

Transcription:

Effect of Temperature on Condition Assessment of Oil- Insulation using Polarization- Depolarization Current Saurabh Indian Institute of Technology (Indian School of Mines) Dhanbad, India M. Mukherjee Jadavpur University Kolkata, India A. K. Pradhan Jalpaiguri Govt. Engg. College Jalpaiguri, India A. Baral Indian Institute of Technology (Indian School of Mines) Dhanbad, India S. Chakravorti Electrical Engineering Jadavpur University Kolkata, India Abstract Polarization Depolarization Current method of dielectric testing is popularly used by the utilities for condition assessment of the insulation of power transformers. Test temperature is an important factor that affects the polarization depolarization current data measured. In this work the effect of test temperature in condition assessment of cellulosic part of oilpaper insulation using polarization depolarization current method has been investigated. Polarization and depolarization current of experimental samples, emulating oil-paper insulation of power transformers, at different test temperatures were measured. The cellulosic moisture content was estimated for the samples at different temperatures using the farthest zero of the transfer function of the Maxwell s model derived from the polarization depolarization current data. The error in the calculated paper moisture content is determined from comparison with the moisture content calculated from the minimum tan delta of the frequency domain spectroscopy data of the test samples maintained at different test temperature. Results obtained clearly show that the error in the moisture content calculated from the polarization depolarization current data increases with the increase in temperature. Keywords Polarization depolarization current; oil-paper insulation system; cellulosic moisture content; frequency domain spectroscopy; minimum tanδ. I. INTRODUCTION Condition assessment and monitoring of transformer insulation has been an area of growing interest in recent years. The main reason for this is that the transformers are one of the most costliest and critical equipments of the power system responsible for maintaining reliable and quality power supply. Faults in transformers are caused mainly due to the failure of its insulation. The insulation system of power transformers mainly comprises of processed transformer oil and cellulose in the form of kraft paper and pressboard. During the lifetime of operation of a transformer its insulation degrades under the influence of electrical, chemical, mechanical and thermal stresses [-3]. The degradation of the insulation results in aging along with the increase in the overall moisture content. The moisture content of cellulosic insulation increases continuously throughout the lifetime of a transformer. Such increase in moisture content is mainly due to diffusive ingress of moisture from the environment and due to gradual degradation of cellulosic materials. The increase in the overall cellulosic moisture content over 4% may decreases the breakdown strength of the insulation sufficiently to cause catastrophic failures. The main focus of modern day researchers is on the development of non-invasive method for condition assessment of power transformers. Dielectric spectroscopy is one of such non invasive method which is widely used [4-5]. Dielectric Spectroscopy includes return voltage measurement (RVM) [6], polarization and depolarization current (PDC) [7-8] and frequency domain spectroscopy (FDS) [9]. RVM is not used for practical applications as it cannot differentiate the effect of the oil and cellulose from the spectroscopy of the characteristic composite insulation [0]. FDS is one the most popularly used methods for condition monitoring of transformer insulation and is more suitable than PDC because it is independent of insulation geometry, more accurate and low noise sensitivity. The only problem of the conventional frequency domain spectroscopy for field testing is that the time of completion of a complete measurement is too long [0]. Polarization and depolarization current measurement on the other hand has a relatively shorter duration of measurement and more age sensitive information can be extracted from the PDC data. PDC method is popularly used for condition assessment of oil-paper insulation for its non-invasiveness, short duration of measurement and for ability to extract more age sensitive information of the oil-paper insulation. The temperature of the measurement is one of the most important factors that affect the dielectric response [-2]. Hence different PDC measurements will be the obtained for the same transformer unit at different temperatures which may result in inaccurate estimation of the condition of the cellulosic part of transformer insulation. It is reported in [3] that the polarizationdepolarization current and dc conductivity increases with the increase in temperature. The study has not reported the direct 978--4799-54-3/4/$3.00 206 IEEE

effect of temperature in the condition assessment of cellulosic part of oil-paper insulation using PDC method. This work mainly focuses on the determining the direct effect on temperature in estimating the moisture content of cellulosic insulation using PDC method. The PDC data are recorded for laboratory samples at different test temperatures and moisture content of cellulosic insulation is estimated from suitable curve fitting technique and zero method reported in [4]. The moisture content estimated from PDC data is then compared with the moisture content determined from the FDS data and the corresponding error obtained is calculated. II. ESTIMATION OF MOISTURE CONTENT OF CELLULOSIC INSULATION USING DIELECTRIC SPECTROSCOPY A. Estimation of moisture content of cellulosic insulation from Polarization - Depolarization Current The branch parameters of the Maxwell s model obtained from suitable curve fitting of the PDC data contains age sensitive information that can be used for condition assessment of cellulosic insulation. Each branch represents a particular group of dipoles having a particular relaxation time [5]. Hence the branch parameters i.e. the resistance (R i ) and the capacitance (C i ) of each branch represent the condition of a particular group of dipoles of the composite oil-paper insulation system of a transformer. However the PDC data is sensitive to the insulation geometry. Hence research has been conducted to determine age sensitive parameter which is less dependent on the insulation geometry. It is reported in [4] that such an age-sensitive parameter can be determined from the transfer function of the Maxwell s Model. The parameter is the farthest zero of the transfer function located in the left half of the s-plane (z ). It is shown mathematically and experimentally that the parameter z can be used to estimate the cellulosic moisture content with satisfactory accuracy. The empirical relationship between the paper moisture content (% pm) and z is given in equation () [4]. ( ) % pm =.78 + 0.48*ln Z () The moisture content of cellulosic insulation of the experimental samples at different test temperatures are determined from the PDC data using equation (). The results obtained are compared with the moisture content obtained from the FDS data in order to determine the direct effect of test temperature in the condition assessment of transformer insulation using PDC data. B. Estimation of moisture content of cellulosic insulation from Frequency Domain Spectroscopy The Frequency domain spectroscopy (FDS) is the most widely used non invasive techniques for condition assessment of oil-paper insulation. The moisture present in the cellulosic insulation significantly affects tanδ value because of its awkwardly shaped molecules []. The minimum tanδ in FDS represents the minimum frictional loss due to rotating dipoles. Hence the minimum tanδ is used for more accurate estimation of moisture content of cellulosic insulation as it represent the intrinsic condition of the insulation. The relationship widely used to determine the paper moisture content (% pm) from minimum tanδ (tanδ min ) established by W. S. Zaengl is represented by equation (2) [5]. pm = 5.297 + 2.53267*ln(tanδ ) (2) % min moisture content of the test samples at different temperatures are also determined from the minimum tanδ obtained from the FDS data. This paper moisture content is used to determine the error in the paper moisture content calculated from the PDC data. III. PREPARATION OF TEST SAMPLES AND EXPERIMENTAL PROCEDURE Laboratory samples are constructed for experimental purpose that emulates the composite oil-paper insulation of power transformer as reported in [, 7]. The procedures used in preparing the test samples are similar to the steps those were reported in [7]. The cross sectional views of the test samples along with the dimensions have been shown in Figure (a). The preparation of test samples begin with the construction of core, A. Over A, a pressboard cylinder, B is placed and a blanket of un-impregnated kraft paper, C, is wrapped over B. The insulation between LV (D) and HV (H) winding is modeled by arranging the layers of copper strips (D)- un-impregnated kraft paper (E) - pressboard strips (F) un-impregnated kraft paper (G) - copper foil (H) in parallel. The photograph of the test samples have been shown in Figure (b). (a) Fig.. Test sample fabricated in the laboratory. (a) Sectional drawing and (b) actual photograph [, 7]. The test samples are heated continuously at 90 C inside a sealed chamber maintained at low pressure for sufficient time to remove residual moisture that might have been absorbed by the test sample from the atmosphere during preparation. The moisture content of the test samples are set using the dry weight test method using the procedure described in [, 7]. In this technique, the weights of the cellulosic part of the insulation (W b ) of the test samples are determined using a balance after heating the sample in a sealed chamber for a sufficient amount of time. The specimen are then kept in open air and kept some times for moisture to ingress. After achieving sufficient moisture, the cellulosic part of the test samples are weighed (W a ). From W b and W a, the moisture content of each sample is calculated using equation (3). Moisture content of the samples at a definite temperature (b)

W W W a b = 00% b In the present work, specific samples re developed for experimental purpose. Value of paper moistures present in each of the test samples at 30 C is given in 3.2%. After absorbing requisite amount of moisture, the test samples are placed inside a specially designed oil-filled glass chamber (as shown in Figure 2) and kept for some days for oilimpregnation. It is worthwhile to mention that the volume of oil within the glass chamber is kept equal for each test sample. The temperature within the glass chamber is kept fixed using the heating bath (marked 2 in Figure 2). Besides temperature, the pressure within the chamber is kept fixed with a vacuum pump (marked as 3 in Figure 2). The arrangement makes sure that the oil used here for impregnation purpose does not moisture from atmosphere and remains fresh. (3) Fig. 3. Environmental chamber for heating the test samples. Fig. 2. Setup for oil impregnation. () Glass chamber, (2) Heating bath, (3) Vacuum pump, (4) Pressure gauge Now the test samples are heated for several days continuously at different temperatures namely; 30 C to 80 C in steps of 0 C using the environmental chamber as shown in Figure 3. After heating each sample at the predefined temperature the dielectric response (frequency domain) is measured from mhz to khz. Also the polarization depolarization currents are measured for the test samples at different temperatures using an instrument designed and fabricated at Jadavpur University as shown in figure 4. An in built real-time non linear de-noising routine ensures noise free measurement of polarization depolarization current of the test sample [8]. Fig. 4. Equipment used to measure the polarization current IV. EXPERIMENTAL RESULTS Polarization depolarization current and tanδ data are measured for the test samples at different temperatures (30 C 80 C). Figure 5 and Figure 6 show depolarization current data and the measured tanδ data of the test samples at different temperatures respectively. It is worth mentioning here that the relaxation (polarization and depolarization) current from the laboratory sample are recorded until it settles down to a constant value. For the laboratory sample constructed it is observed that this time is in the range of 000s.

Polarization Current (A) e-4 e-5 e-6 e-7 e-8 e-9 0. 0 00 000 0000 Time (s) 30 deg C 40 deg C 50 deg C 60 deg C 70 deg C 80 deg C Fig. 5. Measured polarization currents of the test samples at different temperatures tan-delta (%) 000 00 0 0. 0.0 0.00 0.000 0.00 0.0 0. 0 00 000 0000 Frequency (Hz) 30 deg C 40 deg C 50 deg C 60 deg C 70 deg C 80 deg C Fig. 6. Measured tanδ data of the test samples at different temperatures It is clear from the figure 5 that the depolarization current increases with the increase in temperature. The branch parameters of the Modified Maxwell model are determined using suitable curve fitting technique. The transfer function is then formed using the branch parameters equation (4). ( sr0c TF = R 0 0 + ) + no br i= 0 s + s Ri R C Where R i and C i are the respective branch resistance and capacitances, R 0 and C 0 are the insulation resistance and capacitance respectively and no-br represents the number of branches (group of dipoles). The transfer function can also be written as equation (5) in order to express its dependency on z [4]. i i (4) ( s + z ) N( s) TF = (5) D( s) Where, N(s) and D(s) are the modified numerator and modified denominator polynomial of the transfer function of the Maxwell s model respectively. The paper moisture content of the test samples heated at different temperatures are determine from z using equation () and are shown in Table I. TABLE I. PAPER MOISTURE CONTENT AT DIFFERENT TEMPERATURES CALCULATED FROM Z Temperature of the Test Sample Moisture calculated from z (%) 30 C 3.838 40 C 3.485 50 C 3.7702 60 C 4.456 70 C 4.852 80 C 5.053 It is clear from Table I that with the increase in temperature the paper moisture content increases which is in good correlation with the results reported in [9]. The cellulosic moisture content of the test samples at different temperature are calculated from the minimum tanδ obtained from the FDS data as shown in equation (2) in order to determine the accuracy of the cellulosic moisture content determined from the PDC data,. Table II shows a comparison of the moisture content estimated from PDC and FDS method and the error obtained by using PDC data at different temperature. It is clear from Table II that with the increase in temperature the error in the moisture content determined from the PDC data corresponding to the moisture content determined from the FDS data increases with the increase in the temperature. TABLE II. COMPARISON OF THE PAPER MOISTURE CONTENT AT DIFFERENT TEMPERATURES CALCULATED FROM PDC AND TAN-DELTA Temperature of the Test Sample Moisture calculated from z (%) Moisture from measured tanδmin (%) Deviation of the calculated Moisture 30 C 3.838 3.22 0.8832 40 C 3.485 3.675 5.2656 50 C 3.7702 4.2089 0.4242 60 C 4.456 4.6435 0.7242 70 C 4.852 5.808 7.0059 80 C 5.053 6.8064 24.9933 The main reason for this is that the parameter z, from which moisture content is estimated, changes with the change in R 0, R i and C i. It is reported that with the change in temperature the branch resistances changes according to the activation energy of the test samples. The branch resistances (R i ) of insulation at two definite temperatures T and T2 should follow the activation energy relationship as given by equation (6) [20]. W k T2 T R = R e (6) 2

Where, W is the activation energy, k is the ideal gas constant (8.345 J/mol K), R 2 and R are the resistances at temperatures T 2 and T respectively. The branch parameters obtained from the PDC data at different temperatures using curve fitting technique does not follow the relationship given by equation (6). Hence it cannot be ensured that the moisture content obtained from z, which in turn is dependent on the branch parameters, is accurate at every temperature. With the increase in temperature the error will not remain constant. The error will rather increase with the increase in temperature as shown in Table II as the difference increases. At present, the authors of the paper are T T2 engaged in studying the influence of important factors (like variation in aging time and initial paper moisture content of sample ) on paper moisture (column 2 of Table II) evaluated at different temperatures. V. CONCLUSIONS In this work PDC data of transformer samples were measured at different temperatures and the paper moisture content was determined using the farthest zero method. The cellulosic moisture content determined from the PDC data is validated using the cellulosic moisture content determined from the minimum tanδ of the FDS data of the same transformer samples. Experimental results clearly show that the test temperature greatly affects the PDC data. The error in the moisture content determined from z of the PDC data increases with the increase in temperature. Hence the deviation in the paper moisture content determined using PDC and FDS is fixed at a particular temperature and increases with the increase in temperature. REFERENCES [] A. K. Pradhan, B. Chatterjee and S. Chakravorti, Estimation of Moisture Content based on Dielectric Dissipation Factor of Oil-paper Insulation under Non-sinusoidal Excitations, IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 22, No. 2, pp. 822-830, 205. [2] S. Q. Wang, G. J. Zhang, J. L. Wei, Experimental Study of the Aged States Effects on Pressboard PDC Characteristics, Proceedings of the CSEE, Vol. 3, No. 34, pp. 77-83, 20. [3] R. J. Liao, L. J. Yang, H. B. Zheng, Reviews on Oil-paper Insulation Thermal Aging in Power Transformers, Transactions of China Electrotechnical Society, Vol. 27, No. 5, pp. -2, 202. [4] T. K. Saha, "Review of Modern Diagnostic Techniques for Assessing Insulation Condition in Aged Transformers", IEEE Transactions on Dielectric and Electrical Insulation, Vol. 0, No. 5, pp. 903-97, 2003. [5] M. C. Lessard, L. Van Nifterik, M. Masse, J.F.Penneau and R. Grob, Thermal Aging Study of Insulating used in Power Transformer, IEEE Conference on Electrical Insulation and Dielectric Phenomena, San Francisco, USA, Vol. 2, pp. 854 859, 996. [6] Y. C. Kuang, G. Chen, P. Jarmm, Recovery Voltage Measurement on Oil-paper Insulation with Simple Geometry and Controlled Environment, IEEE International Conference on Solid Dielectrics, Toulouse, France, pp. 739-742, 2004. [7] T. K. Saha, P. Purkait, Investigation of Polarization and Depolarization Current Measurements for the Assessment of Oil-paper Insulation of Aged Transformers, IEEE Transactions on Dielectrics and Electrical Insulation, Vol., No., pp. 44-54, 2004. [8] T. K. Saha, P. Purkait, Effects of Temperature on Time-domain Dielectric Diagnostics of Transformers, Australian Journal of Electrical and Electronics Engineering, Vol., No. 3, pp. 57-62, 2004. [9] S. M. Gubanski, P. Boss, G. Csepes, Dielectric Response Methods for Diagnostics of Power Transformers, IEEE Electrical Insulation Magazine, Vol. 9, No. 3, pp. 2-8, 2003. [0] X. Liu, R. Liao, Y. Lv, J. Liu, J. Gao and J. Hao, "Study on Influences and Elimination of Test Temperature on PDC Characteristic Spectroscopy of Oil- Insulation System", Journal of Electrical Technology, 0(), pp. 30-40, 205. [] V. D. Houhanessian, W. S. Zaengl, Application of Relaxation Current Measurements to On-site Diagnosis of Power Transformers, IEEE Conference on Electrical Insulation and Dielectric Phenomena, Minneapolis, America, pp. 45-5, 997. [2] A. Setayeshmehr, I. Fofana, A. Akbari, Effect of Temperature, Water Content and Aging on the Dielectric Response of Oil-impregnated, IEEE International Conference on Dielectric Liquids, Futuroscope-Chasseneuil, France, pp. -4, 2008. [3] T. K. Saha, P. Purkait, Investigations of Temperature Effects on the Dielectric Response Measurements of Transformer Oil-paper Insulation System, IEEE Transactions on Power Delivery, Vol. 23, No., pp. 252-260, 2008. [4] A. Baral and S. Chakravorti, Condition Assessment of Cellulosic Part in Power Transformer Insulation using Transfer Function Zero of Modified Debye Model, IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 2, No. 5, pp. 2028-2036, 204. [5] A. Baral and S. Chakravorti, A Modified Maxwell Model for Characterization of Relaxation Processes within Insulation System having Non-uniform Aging due to Temperature Gradient, IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 20, No. 2, pp. 524 to 534, 203. [6] W. S. Zaengl, Applications of dielectric spectroscopy in time and frequency domain for HV power equipment, IEEE Electrical Insulation Magazine, Vol. 9, No. 6, pp. 9-22, 2003. [7] A. K. Pradhan, B. Chatterjee and S. Chakravorti, Effect of Temperature on Frequency Dependent Dielectric Parameters of Oilpaper Insulation under Non-sinusoidal Excitation, IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 2, No. 2, pp. 653-66, 204. [8] D. Dey, B. Chatterjee, S. Chakravorti and S. Munshi, A Hybrid Filtering Scheme for Proper Denoising of Real-Time Data in Dielectric Spectroscopy, IEEE Transactions on Dielectrics and Electrical Insulation, Vol.4, No.5, pp.323-33, 2007. [9] J. Gao, Y. Wang, R. Liao, C. Qi, J. Liu, "Effect of Temperature Change Mode on Condition Assessment of Oil-paper Insulation Using Frequency Domain Spectroscopy", proceeedings of International Conference on High Voltage Engineering and Application (ICHVE), Poznan, 204. [20] E. I. Koufakis, C. D. Halevidis, A. D. Polykrati, and P. T. Tsarabaris, "Calculation of the Activation Energy of Oil- Insulation in a Distribution Transformer", IEEE Electrical Insulation Magazine, Vol. 28, No. 2, pp. 52-58, 2003.