A study of action point correction factor for L type flanges of wind turbine towers

Similar documents
NUMERICAL SIMULATION OF FLANGE-BOLT INTERACTION IN WIND TUBRINE TOWER CONNECTIONS

PLASTIC RESISTANCE OF L-STUBS JOINTS SUBJECTED TO TENSILE FORCES

SIMPLE MODEL FOR PRYING FORCES IN T-HANGER CONNECTIONS WITH SNUG TIGHTENED BOLTS

Special edition paper

INFLUENCE OF FLANGE STIFFNESS ON DUCTILITY BEHAVIOUR OF PLATE GIRDER

A CONNECTION ELEMENT FOR MODELLING END-PLATE CONNECTIONS IN FIRE

LOAD CARRYING BEHAVIOR OF PRESTRESSED BOLTED STEEL FLANGES CONSIDERING RANDOM GEOMETRICAL IMPERFECTIONS

STEEL JOINTS - COMPONENT METHOD APPLICATION

On analysis and redesign of bolted L-flanged connections

The Seat Angle Role on Moment-Rotation Response of Bolted Angle Connections

2012 MECHANICS OF SOLIDS

Optimization of contact stress distribution in interference fit

CONNECTIONS WITH FOUR BOLTS PER HORIZONTAL ROW Application of Eurocode 3

NUMERICAL EVALUATION OF THE ROTATIONAL CAPACITY OF STEEL BEAMS AT ELEVATED TEMPERATURES

PREDICTION OF THE CYCLIC BEHAVIOR OF MOMENT RESISTANT BEAM-TO-COLUMN JOINTS OF COMPOSITE STRUCTURAL ELEMENTS

An Increase in Elastic Buckling Strength of Plate Girder by the Influence of Transverse Stiffeners

Modeling of welded angle connections in fire

A numerical parametric study on the plate inclination angle of steel plate shear walls

FINITE ELEMENT ANALYSIS OF TAPERED COMPOSITE PLATE GIRDER WITH A NON-LINEAR VARYING WEB DEPTH

Behavior of bolted angle connections subjected to combined shear force and moment

MODELLING OF BOUNDARY CONDITIONS FOR CYLINDRICAL STEEL STRUCTURES IN NATURAL WIND

Experimental Study and Numerical Simulation on Steel Plate Girders With Deep Section

Fatigue Crack Analysis on the Bracket of Sanding Nozzle of CRH5 EMU Bogie

five Mechanics of Materials 1 ARCHITECTURAL STRUCTURES: FORM, BEHAVIOR, AND DESIGN DR. ANNE NICHOLS SUMMER 2017 lecture

Research Collection. Numerical analysis on the fire behaviour of steel plate girders. Conference Paper. ETH Library

BEHAVIOR OF BOLTED TOP-SEAT ANGLE CONNECTIONS UNDER COMBINED AXIAL TENSION AND MOMENT LOADING

Table of Contents. Preface...xvii. Part 1. Level

FE-Analysis of Stringer-to-floor-beam Connections in Riveted Railway Bridges

Junya Yazawa 1 Seiya Shimada 2 and Takumi Ito 3 ABSTRACT 1. INTRODUCTION

FURTHER RESEARCH ON CHORD LENGTH AND BOUNDARY CONDITIONS OF CHS T- AND X-JOINTS

FINITE ELEMENT ANALYSIS OF THE ROTATION CAPACITY OF BEAM-TO-COLUMN END-PLATE BOLTED JOINT

The Effects of Convolution Geometry and Boundary Condition on the Failure of Bellows

EMA 3702 Mechanics & Materials Science (Mechanics of Materials) Chapter 3 Torsion

Seismic Response Analysis of Structure Supported by Piles Subjected to Very Large Earthquake Based on 3D-FEM

Principles of Finite Element for Design Engineers and Analysts. Ayman Shama, Ph.D., P.E., F.ASCE

A METHOD OF LOAD INCREMENTS FOR THE DETERMINATION OF SECOND-ORDER LIMIT LOAD AND COLLAPSE SAFETY OF REINFORCED CONCRETE FRAMED STRUCTURES

FLEXIBILITY METHOD FOR INDETERMINATE FRAMES

Analysis of the behaviour of the CLIC SiD iron return yoke during a seismic event

INFLUENCE OF WEB THICKNESS REDUCTION IN THE SHEAR RESISTANCE OF NON-PRISMATIC TAPERED PLATE GIRDERS

Use Hooke s Law (as it applies in the uniaxial direction),

3-D Finite Element Analysis of Bolted Flange Joint of Pressure Vessel

Finite-Element Analysis of Parts Stress State of Tight Joint Assembled by Press Fitting

Ph.D. Preliminary Examination Analysis

46th AIAA/ASME/ASCE/AHS/ASC Structures, Structural Dynamics, and Materials Conference April 2005 Austin, Texas

THE EFFECT OF GEOMETRY ON FATIGUE LIFE FOR BELLOWS

Fatigue Failure Accident of Wind Turbine Tower in Taikoyama Wind Farm

TORSION INCLUDING WARPING OF OPEN SECTIONS (I, C, Z, T AND L SHAPES)

Structural Steelwork Eurocodes Development of A Trans-national Approach

Structural Steelwork Eurocodes Development of A Trans-national Approach

Structural Steelwork Eurocodes Development of a Trans-National Approach

Two Tier projects for students in ME 160 class

MECHANICAL TESTING METHODS CONCERNING THE STRESS ANALYSIS FOR A VEHICLE WHEEL RIM

Wind tunnel test on mean wind forces and peak pressures acting on wind turbine nacelles

Influence of residual stresses in the structural behavior of. tubular columns and arches. Nuno Rocha Cima Gomes

AMPLIFICATION OF GROUND STRAIN IN IRREGULAR SURFACE LAYERS DURING STRONG GROUND MOTION

University of Sheffield The development of finite elements for 3D structural analysis in fire

Dynamic Stability and Design of Cantilever Bridge Columns

2014 MECHANICS OF MATERIALS

TABLE OF CONTENTS SECTION TITLE PAGE 2 PRINCIPLES OF SEISMIC ISOLATION OF BRIDGES 3

my!wind Ltd 5 kw wind turbine Static Stability Specification

Supplementary Information to the article entitled: Internally Architectured Materials with Directionally Asymmetric Friction

Finite Element Analysis Prof. Dr. B. N. Rao Department of Civil Engineering Indian Institute of Technology, Madras. Module - 01 Lecture - 13

Mechanical Design in Optical Engineering. For a prismatic bar of length L in tension by axial forces P we have determined:

ASIAN JOURNAL OF CIVIL ENGINEERING (BUILDING AND HOUSING) VOL. 10, NO. 5 (2009) PAGES **-**

COURSE TITLE : APPLIED MECHANICS & STRENGTH OF MATERIALS COURSE CODE : 4017 COURSE CATEGORY : A PERIODS/WEEK : 6 PERIODS/ SEMESTER : 108 CREDITS : 5

Equivalent Uniform Moment Factor for Lateral Torsional Buckling of Steel Beams

Sensitivity and Reliability Analysis of Nonlinear Frame Structures

Static and Modal Analysis of Telescope Frame in Satellite

Effect of Angular movement of Lifting Arm on Natural Frequency of Container Lifting Mechanism using Finite Element Modal Analysis

PLATE GIRDERS II. Load. Web plate Welds A Longitudinal elevation. Fig. 1 A typical Plate Girder

two structural analysis (statics & mechanics) APPLIED ACHITECTURAL STRUCTURES: DR. ANNE NICHOLS SPRING 2017 lecture STRUCTURAL ANALYSIS AND SYSTEMS

A Study on the Tube of Integral Propeller Shaft for the Rear-wheel Drive Automobile Using Carbon Composite Fiber

Finite Element Analysis Lecture 1. Dr./ Ahmed Nagib

Mechanics of Solids. Mechanics Of Solids. Suraj kr. Ray Department of Civil Engineering

D : SOLID MECHANICS. Q. 1 Q. 9 carry one mark each. Q.1 Find the force (in kn) in the member BH of the truss shown.

Boundary Nonlinear Dynamic Analysis

Analysis of a portal steel frame subject to fire by use of a truss model

Design Optimization of Stress Relief Grooves in Lever Guide of Pressure Vessel for Food Processing

Behaviour of Continuous Beam to Column Connections in Post Earthquake Fire

Structural Steelwork Eurocodes Development of A Trans-national Approach

my!wind Ltd 5 kw wind turbine Static Stability Specification

Equivalent T-stubs (Component Method) as per DIN EN

ON THE DESIGN OF A STEEL END-PLATE BEAM-TO-COLUMN BOLTED JOINT ACCORDING TO PN-EN

Mechanics of Materials Primer

A peak factor for non-gaussian response analysis of wind turbine tower

Finite element prediction of the ultimate axial load capacity of V-section band clamps

[5] Stress and Strain

Effective stress analysis of pile foundations in liquefiable soil

A HIGHER-ORDER BEAM THEORY FOR COMPOSITE BOX BEAMS

EQUIVALENT FRACTURE ENERGY CONCEPT FOR DYNAMIC RESPONSE ANALYSIS OF PROTOTYPE RC GIRDERS

Effect of Specimen Dimensions on Flexural Modulus in a 3-Point Bending Test

A Finite Element Study of Elastic-Plastic Hemispherical Contact Behavior against a Rigid Flat under Varying Modulus of Elasticity and Sphere Radius

Parameter Design of High Speed Coupling for 6 MW Wind Turbine Considering Torsional Vibration

Contact pressure distribution in joints formed by V-band clamps Simon M Barrans 1,a, Goodarz Khodabakhshi 1,b and Qiang Xu 1,c

: APPLIED MECHANICS & STRENGTH OF MATERIALS COURSE CODE : 4021 COURSE CATEGORY : A PERIODS/ WEEK : 5 PERIODS/ SEMESTER : 75 CREDIT : 5 TIME SCHEDULE

Dynamic analysis of a reinforced concrete shear wall with strain rate effect. Synopsis. Introduction

Numerical simulation the bottom structures. grounding test by LS-DYNA

Experiment Two (2) Torsional testing of Circular Shafts

7.6 Stress in symmetrical elastic beam transmitting both shear force and bending moment

Loading capacity of yielding connections used in steel arch roadway supports

Transcription:

Received: 16 November 2017 Revised: 10 January 2018 Accepted: 22 February 2018 DOI: 10.1002/we.2193 SHORT COMMUNICATION A study of action point correction factor for L type flanges of wind turbine towers Ikuo Tobinaga 1 Takeshi Ishihara 2 1 Wind Turbine Generator Systems Development 1st Group, Wind Turbine Generator Systems Dept. Hitachi, Ltd. Power Business Unit, Power Production Management Division, 1 1, Kokubu cho 1 chome, Hitachishi ibaraki ken 316 8501, Japan 2 Department of Civil Engineering, School of Engineering, The University of Tokyo, 7 3 1, hongou, bunkyo ku, Tokyo 113 8656, Japan Correspondence Ikuo Tobinaga, Wind Turbine Generator Systems Development 1st Group, Wind Turbine Generator Systems Dept. Hitachi, Ltd. Power Business Unit, Power Production Management Division, 1 1, Kokubu cho 1 chome, Hitachi shi ibaraki ken 316 8501, Japan. Email: ikuo.tobinaga.wa@hitachi.com Abstract A correction factor accounting for the effect of elastic deformation of flange is proposed for the ultimate strength analysis of L type flanges used for wind turbine towers. It is derived based on systematic analyses and explicitly expressed as a function of flange dimensions. The proposed factor is simple and suitable for the engineering applications, comparing with the conventional formula for the ultimate strength analysis of flange connections. KEYWORDS action point, bolt, flange, lever ratio, tower, wind turbine 1 INTRODUCTION An accurate prediction of the ultimate strength of L type flanges used for wind turbine towers is crucial in typhoon and earthquake active areas, because the high strength is required at the flange connection of wind turbine towers. Typical tower flange connections use the L type flanges located inside the tower for the maintenance. Two typical formulas are used for the design of flange connection of wind turbine towers. One is used for the ultimate strength analysis of flange connection. The other is used for the fatigue strength analysis of bolt. Some formulas for the ultimate strength analysis of flange connection have been proposed, 1-4 and FE modellings for L type flanges have been investigated. 5-8 Eurocode 1 provided a formula for the T type flange, which cannot be used for the L type flange. Petersen 2 proposed a formula for the L type flange based on the elastoplastic theory. The resistance obtained from the formula is determined by 3 destruction modes, that is determined by combination of acceptable pulling force acting on bolts and plastic bending resistance of shells and flanges. This formula underestimates the pulling force acting on the bolt when the flange stiffness is low. Seidel 3 proposed a formula which has 2 additional destruction modes and a geometrical limitation. However, this formula needs many steps of calculation to define the geometrical limitation. RISO/DNV 4 shows a formula to evaluate the ultimate strength of bolt for the L type flange connection, but it has the same problem as the formula proposed by Petersen 2 because it did not consider the bolt pretension and the elasticity of flange. In this study, an action point correction factor for the ultimate strength analysis of a L type flange connection is proposed. The formula for the pull force acting on a bolt and the definition of the action point correction factor are described in Section 2. Systematic FE analyses for various flange dimensions are then performed, and the action point correction factor is proposed to explicitly estimate the equivalent acting point of flange reaction force considering the effect of flanges deform in Section 3. Finally, conclusions are summarized in Section 4. 2 ULTIMATE STRENGTH ANALYSIS FOR A L TYPE FLANGE CONNECTION The formula for the pull force acting on a bolt is shown in Section 2.1, and the action point correction factor is then described in Section 2.2. In this study, it is assumed that the pull force acting on the bolt reaches an acceptable limit first before the plastic failure of flange connection occurs. Wind Energy. 2018;1 6. wileyonlinelibrary.com/journal/we Copyright 2018 John Wiley & Sons, Ltd. 1

2 TOBINAGA AND ISHIHARA 2.1 Formula for the pull force acting on a bolt In this study, the strength evaluation of the flange is evaluated by a model for 1 bolt, and the force acting on the tower section is expressed by the T S as shown in Figure 1. As shown in Figure 1, a couple of forces by the shell tension force T S and the bolt reaction force F A is supported by the flange reaction force F R at the inside corner of the flange. On the bolt, pull force acting on bolt T A has an equivalent value of F A but acts in the opposite direction by the law of action and reaction. The flange connection surface separates when the pull force acting on the bolt is higher than the pretension force of bolt. Regarding the flange in the radial direction as a beam, the pull force acting on the bolt T A is a function of shell tension force T S as represented in Equation 1 and derived from the moment balance. T A ¼ F A ¼ A T S ; A ¼ 1 þ g λe ; T S ¼ M N Z t A t At n (1) where A represents an amplification factor of the shell tension force to the pull force acting on the bolt and is known as the lever ratio, λ expresses an action point correction factor and is 1 when the flange is assumed as a rigid body, n is the total number of bolts for a tower section, M and N are the bending moment and the axial force acting on the section, and Z t and A t are the section modulus and the area of section, respectively. For the same shell tension force, A decreases and the flange resistance increases when e increases. However, excessive extension of e causes a flange elastic deformation, and the action point of flange reaction force moves to e ' as shown in Figure 1. This is why the formulas by Petersen 2 and RISO/DNV 4 may underestimate the pull force acting on the bolt. Eurocode 1 limits the flange geometry to e 1.25g, and the flange is regarded as a rigid body. 2.2 Definition of the action point correction factor The action point correction factor shown in Equation 2 is a ratio of an equivalent action point e ' to an ideal action point of flange reaction force e. λ ¼ e =e (2) In order to identify λ, FE analysis is used to evaluate e '. For a flange with an extended length e longer than 1.25g, the limit shell tension force T S,lim can be obtained from a FE analysis when the bolt tension reaches the acceptable pull force acting on the bolt T A, lim and e ' can be calculated from Equations 1 and 2 as follows: e g ¼ : (3) T A; lim 1 T S; lim In this study, the acceptable pull force acting on the bolt T A,lim shown in Ishihara 9 is used as: T A; lim ¼ 0:80 σ y A S (4) where σ y is the 0.2% proof stress and A S is the stress area of bolt. FIGURE 1 Dimension and acting forces on a L type flange

TOBINAGA AND ISHIHARA 3 3 PROPOSAL OF AN ACTION POINT CORRECTION FACTOR FOR A L TYPE FLANGE Systematic finite element analyses are performed in Section 3.1, and a formula for an action point correction factor for a L type flange is then proposed in Section 3.2. 3.1 Finite element analysis and validation In this study, 672 cases of FE analysis using ANSYS 10 are performed, and parameters are listed in Table 1 to cover the variation of flanges for wind turbine towers. Some cases are excluded because the shell of tower exceeds the elastic limit before the bolt achieves to the acceptable pull force. A model of L type flange used in FE analyses is a segment model as shown in Figure 2, which is connected to the shell with an enough length. The segments are modeled by the solid elements with 20 nodes, and the number of elements comprised between 2500 and 6500 depending on the flange model size. Contact condition with a friction coefficient of 0.176 based on examinations is applied for the contact area between each flange but is not applied for the seat area of bolt and nut in order to improve analysis convergence because those contact areas do not open normally and do not affect the results even if they slide slightly. Symmetry condition is applied for the flange axial plane. The lower end of shell is fixed, and a displacement is applied at the upper end of shell. According to Ishihara, 9 an initial pre tension is applied to the bolt, which is 70% of the 0.2% proof stress of bolt. Convergence is checked by comparing the square root sum of the squares of force and moment imbalance. Material properties shown in Figure 3 are used to consider elastic and plastic behavior of steel, which are typically used for flanges, bolts, and tower shells. The FE model used in this study is validated and compared with experimental data by Seidel. 5 The flange model used in the experiment and the FE model used for the validation are shown in Figure 4, respectively. The comparisons between predicted and measured bolt tension and bending moment are shown in Figure 5. Predicted bolt tension and bending moment show good agreement with the experimental data and the results of FE analyses by Seidel. 5 TABLE 1 Summary of parameters used in FE analyses Parameter Value Bolt diameter d B [mm] 36, 48 56, 64 Tower diameter D[m] 3, 4, 5 4, 5, 6 Shell thickness t S [mm] 20, 30, 40 30, 40, 50, 60 Bolt interval p[mm] (2.25, 2.50) d B Flange thickness t F [mm] 75,100,125 100,125,150 Length g[mm] 1.3 d B Length e[mm] (1.25, 1.5, 1.75, 2, 2.25) g FIGURE 2 analyses A model of flange used in FE

4 TOBINAGA AND ISHIHARA FIGURE 3 Material property used in FE analyses FIGURE 4 A flange model used for the validation FIGURE 5 Comparison between predicted and measured bolt tension and bending moment

TOBINAGA AND ISHIHARA 5 FIGURE 6 FE results for 2 typical flanges [Colour figure can be viewed at wileyonlinelibrary.com] FIGURE 7 Variation of the action point correction factor with the aspect ratio a Figure 6 shows the von Mises stress distribution of flange connection and the surface pressure distribution of contact area for 2 typical flanges with e = 1.25 g and e = 2.25 g, when the bolt tensions reach the acceptable pull force acting on the bolt. In the flange with e = 1.25g, maximum surface pressure is appeared at the corner of flange. Therefore, the flange with e = 1.25g is regarded as a rigid body. On the other hand, the flange with e = 2.25g shows the maximum surface pressure at the location near e = 1.0 g. The equivalent action point of flange reaction force e ' calculated by Equation 3 is approximately 0.7e. 3.2 Formula for the action point correction factors The action point correction factors for L type flanges obtained by FE analyses are shown in Figure 7. A formula for the action point correction factors λ is proposed by fitting FE results and expressed by Equation 5.

6 TOBINAGA AND ISHIHARA ( 5 1 1 ab 1:25 e=g 2:25 λ ¼ 1 e=g 1:25 (5) where a ¼ t F = ðe þ gþ 0:12ðe=gÞþ0:55 a 1 b ¼ ðe=g 1:25Þ 0:32 þ 0:45 1:25 e=g 2:25 It is a function of aspect ratio of flange only, and the parameters d B, D, t S, and p as shown in Table 1 are not included in Equation 5 because the effect of these parameters is negligible from the FE analyses. The proposed formula can be applied to the ultimate strength analysis of flange connection when the bolt first reaches an acceptable limit. It provides a conservative, lower bound estimate of the true position of the action point when the plastic limit state is reached because the further inside movement of the action point appears in this situation. 4 CONCLUSIONS In this study, systematic FE analyses on various flange dimensions are performed. An action point correction factor and its geometrical limitation are proposed. The following conclusions are obtained. 1. An action point correction factor of flange reaction force for L type flange of wind turbine tower is proposed based on systematic FE analyses and explicitly expressed as a function of flange dimensions. 2. The proposed factor is simple and suitable for the engineering applications, comparing with the conventional formula for the ultimate strength analysis of flange connections. ORCID Ikuo Tobinaga http://orcid.org/0000-0001-9379-8282 REFERENCES 1. ENV 1993 1 1,Eurocode 3,Design and construction of steel structures. Part 1.1: General design rules, design rules for building construction April, 1992 (in German) 2. Petersen C. Steel Construction. 3rd. ed. Braunschweig: Vieweg Verlag; 1997 (in German). 3. Seidel, Zur Bemessung geschraubter Ringflanschverbindungen von Windenergieanlagen, 127 134, 2001 (in German) 4. DNV/RISO. Guidelines for Design of Wind Turbines. 2nd. ed. ; 2002. 5. Seidel, M., Schaumann, P., Measuring fatigue loads of bolts in ring flange connections, EWEC2001, 2001. 6. Pedersen NL, Pedersen P. On prestress stiffness analysis of bolt plate contact assemblies. Archive of Applied Mechanics. 2008;78(2):75 88. 7. Pedersen NL, Pedersen P. Bolt plate contact assemblies with prestress and external loads: solved with super element technique. Computers and Structures. 2009;87(21 22):1374 1383. 8. Pedersen NL. On analysis and redesign of bolted L flanged connections. Wind Energy. 2017;20(6):1069 1082. 9. Ishihara T. Guidelines for Design of Wind Turbine Support Structures and Foundations. Structural Engineering Series. 20 Japan Society of Civil Engineers; 2010:260 273 (In Japanese). 10. ANSYS, version 14.0, ANSYS, Inc. 2011. How to cite this article: Tobinaga I, Ishihara T. A study of action point correction factor for L type flanges of wind turbine towers. Wind Energy. 2018;1 6. https://doi.org/10.1002/we.2193