Simplified and approximated relations of heat transfer effectiveness for a steam condenser

Similar documents
The concept of a new approximate relation for exchanger heat transfer effectiveness for a cross-flow heat exchanger with unmixed fluids

The black box model of a double tube counter flow heat exchanger

T718. c Dr. Md. Zahurul Haq (BUET) HX: Energy Balance and LMTD ME 307 (2018) 2/ 21 T793

Multiple pass and cross flow heat exchangers

Overall Heat Transfer Coefficient

c Dr. Md. Zahurul Haq (BUET) Heat Exchangers: Rating & Sizing - I ME 307 (2017) 2 / 32 T666

INSTRUCTOR: PM DR MAZLAN ABDUL WAHID

Axial profiles of heat transfer coefficients in a liquid film evaporator

Introduction to Heat and Mass Transfer

Memorial University of Newfoundland Faculty of Engineering and Applied Science

Chapter 11: Heat Exchangers. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

S.E. (Chemical) (Second Semester) EXAMINATION, 2012 HEAT TRANSFER (2008 PATTERN) Time : Three Hours Maximum Marks : 100

Designing Steps for a Heat Exchanger ABSTRACT

Estimating number of shells and determining the log mean temperature difference correction factor of shell and tube heat exchangers

PROBLEM The heat rate, q, can be evaluated from an energy balance on the cold fluid, 225 kg/h J. 3600s/h

OPTIMIZATION OF AN INDUSTRIAL HEAT EXCHANGER BY THE MINIMALIZATION OF ENTROPY SVOČ FST 2017

COOLING TOWER MODEL IN MNR

ME 331 Homework Assignment #6

Thermal Energy Loss in the Steam Valves and its Effects

LAMINAR FORCED CONVECTION HEAT TRANSFER IN HELICAL COILED TUBE HEAT EXCHANGERS

HEAT EXCHANGER. Objectives

INTRODUCTION: Shell and tube heat exchangers are one of the most common equipment found in all plants. How it works?

ME-662 CONVECTIVE HEAT AND MASS TRANSFER

Circle one: School of Mechanical Engineering Purdue University ME315 Heat and Mass Transfer. Exam #2. April 3, 2014

1. Nusselt number and Biot number are computed in a similar manner (=hd/k). What are the differences between them? When and why are each of them used?

TUBE BANKS TEST PROBLEMS

Effect of flow velocity on the process of air-steam condensation in a vertical tube condenser

Heat Exchangers: Rating & Performance Parameters. Maximum Heat Transfer Rate, q max

374 Exergy Analysis. sys (u u 0 ) + P 0 (v v 0 ) T 0 (s s 0 ) where. e sys = u + ν 2 /2 + gz.

6340(Print), ISSN (Online) Volume 3, Issue 3, Sep- Dec (2012) IAEME AND TECHNOLOGY (IJMET)

Ceiling mounted radiant panels calculations of heat output in heating and cooling application

How can we use Fundamental Heat Transfer to understand real devices like heat exchangers?

Phone: , For Educational Use. SOFTbank E-Book Center, Tehran. Fundamentals of Heat Transfer. René Reyes Mazzoco

Transient Heat Transfer Experiment. ME 331 Introduction to Heat Transfer. June 1 st, 2017

Heat Transfer Coefficient Solver for a Triple Concentric-tube Heat Exchanger in Transition Regime

NUMERICAL HEAT TRANSFER ENHANCEMENT IN SQUARE DUCT WITH INTERNAL RIB

Validation of MARS-LMR Code for Heat Transfer Models in the DHRS of the PGSFR

If there is convective heat transfer from outer surface to fluid maintained at T W.

ESRL Module 8. Heat Transfer - Heat Recovery Steam Generator Numerical Analysis

CHAPTER FOUR HEAT TRANSFER

Numerical Investigation on Effect of Operating Parameters on Plate Fin Heat Exchanger

A generic adsorption heat pump model for system simulations in TRNSYS

ECE309 INTRODUCTION TO THERMODYNAMICS & HEAT TRANSFER. 13 June 2007

A concrete heat accumulator for use in solar heating systems a mathematical model and experimental verification

NUMERICAL ANALYSIS OF PARALLEL FLOW HEAT EXCHANGER

Heat Exchanger Design

Analytical solutions of heat transfer for laminar flow in rectangular channels

Exergy Optimisation for Cascaded Thermal Storage

S.E. (Chemical) (Second Semester) EXAMINATION, 2011 HEAT TRANSFER (2008 PATTERN) Time : Three Hours Maximum Marks : 100

Level 7 Post Graduate Diploma in Engineering Heat and mass transfer

23 1 TYPES OF HEAT EXCHANGERS

DESIGN OF A SHELL AND TUBE HEAT EXCHANGER

ENTROPY GENERATION DUE TO EXTERNAL FLUID FLOW AND HEAT TRANSFER FROM A CYLINDER BETWEEN PARALLEL PLANES

arxiv: v1 [physics.app-ph] 25 Mar 2018


Applied Heat Transfer:

CFD Analysis of Forced Convection Flow and Heat Transfer in Semi-Circular Cross-Sectioned Micro-Channel

PLATE & FRAME HEAT EXCHANGER

Design and Temperature Analysis on Heat Exchanger with TEMA Standard Codes

Heat Transfer Co-efficient and Effectiveness for Water Using Spiral Coil Heat Exchanger: A Comprehensive Study

WTS Table of contents. Layout

طراحی مبدل های حرارتی مهدي کریمی ترم بهار HEAT TRANSFER CALCULATIONS

CONCENTRIC EXCHANGER TEST PROBLEMS

Investigations of hot water temperature changes at the pipe outflow

A cryogenic heat exchanger with bypass and throttling and its thermodynamic analysis

Keywords: Spiral plate heat exchanger, Heat transfer, Nusselt number

PHYSICAL MECHANISM OF CONVECTION

ORC Condenser Heat Exchanger Design and Modelling

Analysis and Comparison of the Performance of Concurrent and Countercurrent Flow Heat Exchangers

Natural Convection from a Long Horizontal Cylinder

Study on the improved recuperator design used in the direct helium-turbine power conversion cycle of HTR-10

Principles of Food and Bioprocess Engineering (FS 231) Problems on Heat Transfer

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

Heat processes. Heat exchange

Heat Transfer Performance in Double-Pass Flat-Plate Heat Exchangers with External Recycle

The Effect of Mass Flow Rate on the Effectiveness of Plate Heat Exchanger

EXPERIMENTAL AND NUMERICAL STUDIES OF A SPIRAL PLATE HEAT EXCHANGER

Department of Energy Fundamentals Handbook. THERMODYNAMICS, HEAT TRANSFER, AND FLUID FLOW, Module 3 Fluid Flow

ME 315 Exam 3 8:00-9:00 PM Thursday, April 16, 2009 CIRCLE YOUR DIVISION

Analysis of the occurrence of natural convection in a bed of bars in vertical temperature gradient conditions

Mathematical modelling of heat transfer in liquid flat-plate solar collector tubes

University of Macau Department of Electromechanical Engineering MECH316 Heat Transfer Syllabus 2 nd Semester 2011/2012 Part A Course Outline

SHELL-AND-TUBE TEST PROBLEMS

Numerical simulation of fluid flow in a monolithic exchanger related to high temperature and high pressure operating conditions

HEAT TRANSFER. Mechanisms of Heat Transfer: (1) Conduction

How to chose cooling fluid in finned tubes heat exchanger

Lecture 3 Heat Exchangers

Temperature distribution and heat flow across the combustion chamber wall.

Ben Wolfe 11/3/14. Figure 1: Theoretical diagram showing the each step of heat loss.

A Comparative Second Law Analysis of Microchannel Evaporator with R-134A & R-22 Refrigerants

THERMODYNAMICS, FLUID AND PLANT PROCESSES. The tutorials are drawn from other subjects so the solutions are identified by the appropriate tutorial.

Numerical Simulation of the Shell-and-Tube Heat Exchanger: Influence of the Lower Flows and the Baffles on a Fluid Dynamics

Convection Heat Transfer. Introduction

IJSRD - International Journal for Scientific Research & Development Vol. 1, Issue 8, 2013 ISSN (online):

The Research of Heat Transfer Area for 55/19 Steam Generator

Convection. forced convection when the flow is caused by external means, such as by a fan, a pump, or atmospheric winds.

The average velocity of water in the tube and the Reynolds number are Hot R-134a

Tutorial 1. Where Nu=(hl/k); Reynolds number Re=(Vlρ/µ) and Prandtl number Pr=(µCp/k)

Dipak P. Saksena Assistant Professor, Mechancial Engg. Dept.Institute of Diploma Studies.Nirmaunieversity

NEW FUEL IN MARIA RESEARCH REACTOR, PROVIDING BETTER CONDITIONS FOR IRRADIATION IN THE FAST NEUTRON SPECTRUM.

Transcription:

Open Access Journal Journal of Power Technologies 92 (4) (2012) 258 265 journal homepage:papers.itc.pw.edu.pl Simplified and approximated relations of heat transfer effectiveness for a steam condenser Rafał Laskowski, Janusz Lewandowski Institute of Heat Engineering, Warsaw University of Technology 21/25 Nowowiejska Street, 00-665 Warsaw, Poland Abstract This paper presents two simplified and approximated relations of heat transfer effectiveness for a steam condenser. The proposed relations of heat transfer effectiveness are the function of the measured and reference parameters. The correctness of relations was verified on the basis of data from the characteristics and measured data for the 200 MW steam condenser. A comparison of the outlet cooling water temperature calculated from the proposed relations and Beckman formula was performed. The formula proposed by Beckman for the heat transfer effectiveness of a steam condenser, in a simplified form, is the function of the saturation temperature, mass flow rate of cooling water and the reference parameter. It contains two constant exponents, which must be determined on the basis of the measured data. To assess the accuracy of the relations, the average value and standard deviation were used. The proposed relations have simpler forms but are slightly less accurate than the Beckman relation. Keywords: heat transfer effectiveness, steam condenser, approximated relation 1. Introduction This paper presents two simplified and approximated relations of heat transfer effectiveness for a steam condenser. The proposed relations of heat transfer effectiveness are the function of the measured and reference parameters. The correctness of relations was verified on the basis of data from the characteristics and measured data for the 200 MW steam condenser. A comparison of the outlet cooling water temperature calculated from the proposed relations and Beckman formula was performed. The formula proposed by Beckman for the heat transfer effectiveness of a steam condenser, in a simpli- Corresponding author Email addresses: rlask@itc.pw.edu.pl (Rafał Laskowski ), jlew@itc.pw.edu.pl (Janusz Lewandowski ) fied form, is the function of the saturation temperature, mass flow rate of cooling water and the reference parameter. It contains two constant exponents, which must be determined on the basis of the measured data. To assess the accuracy of the relations, the average value and standard deviation were used. The proposed relations have simpler forms but are slightly less accurate than the Beckman relation. The intensity of heat flux in a heat exchanger in the changed conditions can be represented in the form of heat transfer effectiveness in the function of two dimensionless parameters [1, 2, 3, 4] ε = ( Q Ċmin = f, Q max Ċ max ) UA Ċ min (1) The function contains the heat capacity for both fluids, overall heat transfer coefficient and heat trans-

fer surface area. Heat capacity is the product of the mass flow rate and the specific heat at constant pressure. Journal of Power Technologies 92 (4) (2012) 258 265 Ċ = c p ṁ (2) Ċ min means lower and Ċ max means higher heat capacity between Ċ h, Ċ c. Overall heat transfer coefficient (U) is a function of heat transfer coefficients for both fluids (α 1, α 2 ) and wall thickness (δ) and wall thermal conductivity (λ). Heat transfer coefficients are a function of Nusselt, Reynolds and Prandtl numbers. To accurately determine the overall heat transfer coefficient, the temperatures at the outlets of the heat exchanger must be known, so the process needs to be made by iteration. Diffrent relations for the overall heat transfer for different flow conditions and mathematical relations describing heat transfer effectiveness for different types of heat exchangers can be found in the literature [5, 6]. Another approach to describe the intensity of heat flux for a heat exchanger was suggested by Beckman in the following form [7, 8, 9] ε = C (T h1 ) α 1 (T c1 ) α 2 (ṁ h ) α 3 (ṁ c ) α 4 (3) In this approach it is assumed that heat transfer effectiveness is a function of input parameters to the heat exchanger: mass flow rates and temperatures of both fluids. In relation we have four constant exponents and a constant C. The α 1, α 2, α 3, α 4 coefficients are calculated, based on the measured data. The parameter C can be eliminated by introducing a reference state. The relation then takes the form ( ) α1 ( ) α2 ( ) α3 ( ) α4 ε Th1 Tc1 ṁh ṁc = (4) ε o T h1o T c1o ṁ ho ṁ co In the case of the phase change of one fluid, for the steam condenser the heat capacity of the steam is much greater than the heat capacity of cooling water Ċ max = Ċ h Ċ min = Ċ c. The relation (1) simplifies to the form ( ) Q UA ε = = f (5) Q max Ċ min Beckman showed that for steam condenser α 2, α 3 the exponents are close to zero and can be omitted [7, 8]. Figure 1: Scheme of a 200 MW steam condenser with measured parameters The heat transfer effectiveness for the steam condenser (T h1 = T h2 = T h ) can be written in the form ( ) α1 ( ) α4 ε Th ṁc = (6) ε o T ho ṁ co Even in a simplified approximated form of the heat transfer effectiveness for a steam condenser, there are two constant exponents that must be determined based on measured data. Szapajko and Rusinowski [10, 11] proposed a linear relation of the heat transfer effectiveness for a steam condenser and feed water heat exchanger as a function of the mass flow rate, assuming that the steam pressure is constant ε = D ṁ c + E (7) In this case we also have two coefficients D and E, which are calculated based on the measured data. Linear relations of the heat transfer effectiveness for a feed water heat exchanger and counterflow and crossflow heat exchanger were proposed in the papers [12, 13], too. The purpose of this paper is to propose the approximated relations of heat transfer effectiveness for the steam condenser using measured input parameters to the heat exchanger, parameters in reference state, without additional coefficients that need to be set based on measured data. 2. Mathematical models 2.1. First mathematical model Steam condensers for a 200 MW power plant were analyzed. In Fig. 1 a scheme of the steam condenser with measured parameters is presented. Within the steam condenser the mass flow rate of cooling water, 259

cooling water temperature at the inlet and outlet of the steam condenser and the pressure in the steam condenser were measured. Cooling water outlet temperature can be expressed as a function of the following parameters T c2 T c1 = f (, ṁ c, p h, A, g) (8) Using Buckingham Π theorem, the above relation can be converted to a form in which there is heat transfer effectiveness ε = T c2 T c1 ) (ṁc g b = C (9) After introduction of the two following dimensionless parameters p h A 3 4 Π 1 = T c2 T c1 (10) Π 2 = ṁc p h The relation takes the form g A 3 4 (11) Π 1 = C (Π 2 ) b (12) After applying logarithms of both sides, we obtain the equation ln (Π 1 ) = lnc + b ln (Π 2 ) (13) The function of the logarithm of the x variable can be expanded in a series [14]. lnx = (x 1) (x 1)2 2 + (x 1)3 3... (14) Considering only the first term in the expansion of the logarithm functions we obtain After arranging Π 1 1 = C 1 + b (Π 2 1) (15) Π 1 = C + b Π 2 b (16) When the cooling water mass flow rate is decreased, the outlet temperature of water can be heated to a higher value. Thus, when the cooling water flow rate tends to zero, heat transfer effectiveness tends to one. From this condition we obtain b = C 1 (17) After inserting the above relation and the transformations we obtain Π 1 1 = (C 1) Π 2 (18) For the reference state we can write Π 1o 1 = (C 1) Π 2o (19) Dividing one equation by the second one we get Π 1 1 Π 1o 1 = Π 2 Π 2o (20) After entering the formulae for dimensionless parameters we have ε 1 ε o 1 = ṁc p h p ho ṁ co (21) We received a relation of heat transfer effectiveness depending on the cooling water mass flow rate, the pressure in the steam condenser and the parameters in reference state without additional coefficients or exponents. After the transformation, heat transfer effectiveness for the steam condenser in the changed conditions, can be written as ε = 1 ṁc p h p ho ṁ co (1 ε o ) (22) 2.2. Second mathematical model An example of temperature distribution along the heat transfer surface area for the steam condenser is shown in the Fig. 2. Outlet cooling water temperature can be presented as T c2 = T h T (23) The above relation can be transformed into the following form ε = T c2 T c1 = 1 T (24) 260

Figure 2: Temperature distribution along the heat transfer surface area for the steam condenser Figure 3: Change in water temperature at the outlet of the steam condenser, from characteristics and calculated from the first proposed formula for 25 values Assuming that approximately T is a linear function of cooling water mass flow rate T a ṁ c (25) Heat transfer effectiveness can be written as ε = T c2 T c1 = 1 a ṁ c (26) Having a reference state it can be written as ε = 1 ṁ c T ho T c1o ṁ co (1 ε o ) (27) We determined a relation between heat transfer effectiveness depending on cooling water mass flow rate, the difference between temperature in the steam condenser and inlet outlet cooling temperature and the parameters in the reference state without additional coefficients or exponents. 3. Results 3.1. Results for the first mathematical model The correctness of the first proposed relation was checked for data from the characteristics as well as on the basis of the measured data for a 200 MW power plant steam condenser. Fig. 3 shows a comparison between the outlet water temperature from the characteristics and as calculated from the first proposed relation for 25 values. The comparison of outlet temperatures shows that the change in the calculated outlet temperature from Figure 4: Difference between the temperature from characteristics and the calculated temperature for 25 values, green line temperature calculated from the Beckman formula, black line temperature calculated from the first proposed formula the first proposed relation and from the characteristics has a similar character. In order to investigate the accuracy of the model the difference between the temperature from the characteristics of the steam condenser and the calculated temperature from the first proposed relation was determined. Fig. 4 shows the difference between the measured water temperature at the outlet of the steam condenser and the calculated temperature (the green line determines the difference between the outlet temperature from the characteristics and the temperature from the Beckman relation, the black line determines the difference between the outlet temperature from the characteristics and the temperature from the first proposed relation). The comparison was made for 25 values. To assess the accuracy of two relations the average value and standard deviation were used. For the first proposed relation an average value of -0.54 and 261

Figure 5: Change of water temperature at the outlet of the steam condenser, measured and calculated from the first proposed formula for 67 values Figure 7: Change in water temperature at the outlet of the steam condenser, from characteristics and calculated from the second proposed formula for 25 values Figure 6: Difference between measured and calculated temperature for 67 values, green line temperature calculated from the Beckman formula, black line temperature calculated from teh first proposed formula the standard deviation of 0.6 were obtained. For the Beckman relation an average value of -0.21 and the standard deviation of 0.44 were obtained. The average value for the Beckman relation is closer to zero, and the standard deviation that shows how data are spread from the average value is closer to zero too. On the basis of the obtained data, we can observe that the outlet water temperature which is determined from the Beckman relation is slightly more accurate. The error designation of the cooling water temperature for both relations is in the range ±1.5 C. A similar comparison was made for the measured data. A comparison between measured and calculated from the first proposed relation water temperature at the outlet of the steam condenser is shown in Fig. 5 for 67 values. For the real data, too, the outlet water temperature calculated from the first proposed relation has a simi- lar character of change as the measured temperature. Fig. 6 shows the difference between the measured water temperature at the outlet of the steam condenser and the calculated temperature (the green line determines the difference between the measured outlet temperature and the temperature from Beckman relation, the black line determines the difference between the measured outlet temperature and the temperature from the first proposed relation). The comparison was made for 67 values. Based on measured data obtained for the first proposed relation the average value is -0.10 and the standard deviation is 0.39. For the Beckman relation an average value of 0.09 and the standard deviation of 0.20 were obtained. The average value for the Beckman relation is closer to zero and standard deviation is also closer to zero. For those data the outlet water temperature determined from the Beckman relation is slightly more accurate. The error designation of the cooling outlet water temperature according to the first proposed relation is in the range ±1 C and for the Beckman relation is in the range ±0.5 C. Compared to data from the characteristics, in this case the error of cooling water is smaller for both relations, because the range of changes in input parameters to the steam condenser was smaller. 3.2. Results for the second mathematical model The correctness of the second proposed relation was checked for data from the characteristics as well as on the basis of the measured data for a 200 MW power plant steam condenser. Fig. 7 shows a comparison between the outlet water temperatures from the 262

Figure 8: Difference between temperature from characteristics and calculated temperature for 25 values, green line temperature calculated from the Beckman formula, black line temperature calculated from the second proposed formula Figure 9: Change in water temperature at the outlet of the steam condenser, measured and calculated from the second proposed formula for 67 values characteristics and calculated from the second proposed relation for 25 values. It results from the shown comparison of outlet temperatures that the change in calculated outlet temperature from the second proposed relation and from the characteristics has a similar character. To investigate the accuracy of the model, the difference between the temperature from the characteristics of the steam condenser and the calculated temperature from the second proposed relation was determined. Fig. 8 shows the difference between the measured water temperature at the outlet of the steam condenser and the calculated temperature (the green line determines the difference between the outlet temperature from the characteristics and the temperature from the Beckman relation, the black line determines the difference between the outlet temperature from the characteristics and the temperature from the second proposed relation). The comparison was made for 25 values. To assess the accuracy of two relations the average value and standard deviation were used. For the second proposed relation an average value of -0.6 and the standard deviation of 1.0 were obtained. For the Beckman relation an average value is -0.21 and the standard deviation is 0.44. The average value for the Beckman relation is closer to zero, and standard deviation that shows how data are spread from the average value is closer to zero too. On the basis of the obtained data, we can observe that the outlet water temperature determined from the Beckman relation Figure 10: Difference between measured and calculated temperature for 67 values, green line temperature calculated from Beckman formula, black line temperature calculated from the second proposed formula is slightly more accurate. The error designation of the cooling outlet water temperature according to the second proposed relation is in the range ±2.5 C and for the Beckman relation is in the range ±1.5 C. A similar comparison was made for the measured data. A comparison between water temperature at the outlet of the steam condenser as measured and as calculated from the second proposed relation is shown in Fig. 9 for 67 values. For the real data, too, outlet water temperature calculated from the second proposed relation has a similar character of change as the measured temperature. Fig. 10 shows the difference between the measured water temperature at the outlet of the steam condenser and the calculated temperature (the green line determines the difference between the measured outlet temperature and the temperature from the Beckman relation, the black line determines the differ- 263

ence between the measured outlet temperature and the temperature from the second proposed relation). The comparison was made for 67 values. Based on measured data obtained for the second proposed relation the average value is 0.07 and the standard deviation 0.48. For the Beckman relation obtained the average value is 0.09 and the standard deviation 0.20. The standard deviation for the Beckman relation is closer to zero. For those data, too, the outlet water temperature determined from the Beckman relation is slightly more accurate. The error designation of the cooling outlet water temperature according to the second proposed relation is in the range ±1 C and for the Beckman relation it is in the range ±0.5 C. Compared to data from the characteristics in this case the error regarding cooling water is smaller for both relations, because the range of changes in input parameters to the steam condenser was smaller. 4. Conclusion The paper presents two simplified and approximated relations of heat transfer effectiveness for a steam condenser. The first proposed relation of heat transfer effectiveness is a function of the cooling water mass flow rate, pressure in the steam condenser and reference parameters. The second one is a function of cooling water mass flow rate, the difference between temperature in the steam condenser and inlet outlet cooling temperature and the parameters in the reference state. Compared to the approximated relation of heat transfer effectiveness for the steam condenser, given by Beckman, the two proposed relations have simpler forms, because they do not contain two constant exponents, which must be determined on the basis of the measured data. The correctness of relations was verified on the basis of data from the characteristics of the condenser manufacturer and measured data for the 200 MW steam condenser. A comparison between Beckman and proposed relations was made for data from the characteristics and measured data. In both cases, the heat transfer effectiveness, proposed by Beckman, is slightly more accurate. To assess the accuracy of both relations, the average value and standard deviation was used. The error designation of the outlet cooling water temperature for the two proposed relations is slightly larger than for the Beckman relation: for data from the characteristics it is in the range ±1.5 C for the first model and ±2.5 C range for the second model, and for measured data it is in the range ±1 C for both models, which corresponds to the measured error of temperature. The larger error for the data from the characteristics is the result of a wider change in inlet parameters to the steam condenser. It seems that the obtained accuracy allows the use of the two proposed formulae to be used for determining outlet water cooling temperature in changed conditions. The two proposed models have a similar degree of accuracy. The purpose of this article is to present the relations (22, 27) of heat transfer efficiency for the steam condenser as a function of the measured parameters only inlet to the condenser. From these relations (22, 27) the temperature of the outlet cooling water can be determined and then the mass flow rate of the steam from the energy balance can be calculated. References [1] F. P. Incropera, D. P. Dewitt, Introduction to heat transfer, John Wiley & Sons, 2002. [2] J. P. Holman, Heat transfer, McGraw-Hill, 2010. [3] E. Kostowski, Heat Transfer (in Polish), WPŚ Gliwice, 2000. [4] T. S. Wiśniewski, Heat Transfer (in Polish), WNT Warszawa, 1997. [5] Y. A. Cengel, Heat transfer, McGraw-Hill, 1998. [6] Y. A. Cengel, Heat and mass transfer, McGraw-Hill, 2007. [7] G. Beckman, G. Heil, Mathematische Modelle für die Beurteilung von Kraftwerksprozessen, EKM Mitteillungen 10/1965. [8] P. Bogusz, O. Kopczyński, J. Lewandowski, Simplified model of heat exchanger (in Polish), XVIII th Congress of the Thermodynamics 22 (2002) 129 135. [9] O. Kopczyński, J. Lewandowski, A concept of thermal - flow state diagnostic system for heat exchangers (in Polish), International Conference Research and Development in Power Engineering (2001) 169 178. [10] G. Szapajko, H. Rusinowski, Empirical modelling of heat exchangers in a CHP Plant with bleed-condensing turbine, Archives of Thermodynamics Vol. 29, 2008, No. 4. [11] G. Szapajko, H. Rusinowski, Theoretical-empirical model of the steam-water cycle of the power unit, Acta Montanistica Slovaca 15 (2010) 24 27. 264

[12] R. M. Laskowski, The application of the Buckingham theorem to modeling high-pressure regenerative heat exchangers in changed conditions, Journal of Power Technologies 91 (4) (2011) 198 205. [13] R. M. Laskowski, The concept of a new approximate relation for heat transfer effectiveness for a cross-flow heat exchanger with unmixed fluids, Journal of Power Technologies 91 (2) (2011) 93 101. [14] W. Żakowski, W. Kołodziej, Mathematics (in Polish), WNT Warsaw, 1993. Nomenclature a constant A heat transfer surface area, m 2 Ċ fluid heat capacity, W/K C constant, dimensionless c p specific heat at constant pressure, J/kg/K b constants, dimensionless D, E empirical coefficients g gravity acceleration, m/s 2 ṁ mass flow, kg/s p pressure, Pa U overall heat transfer coefficient, W/(m 2 K) Q heat flow, W Q max maximum heat flow, W α 1, α 2, α 3, α 4 coefficients of power series ε heat transfer effectiveness, dimensionless Π i (i = 1, 2) number of similarities, dimensionless Index c cold fluid h hot fluid o reference state 1 inlet to the heat exchanger 2 outlet of the heat exchanger 265