REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 24MM TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM.

Similar documents
REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 7MM TESTED WITH A 20MM AIR GAP IN A REVERBERATION ROOM.

Testing Procedure: AS ISO

MEASUREMENTS OF SOUND ABSORPTION TIMBERCRETE

DELTA Test Report. DANAK TEST Reg. no Measurement of Sound Absorption Coefficient for Kvadrat Soft Cells Wall Panel Type Time

Test Report. RI Acoustic Lab. Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier. 20 Feb. 07

DELTA Test Report. Measurement of sound absorption coefficient for 15 mm Fraster felt Plus acoustic panels with mounting depth 45 mm

LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION COEFFICIENTS OF OSCAR EVO-PANELS

LABORATORY MEASUREMENT OF SOUND ABSORPTION OF SONOGLASS SPRAY-ON TREATMENT IN THREE CONFIGURATIONS

Consultancy Report Ref: 9383-R01

A L I O N Technical Center. Test Report

RIVERBANK ACOUSTICAL LABORATORIES

Measurement of sound absorption coefficient for Fraster felt SpaceCover

Measurement of Acoustic Properties of light weight concrete SL-Deck

LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION OF CLASSICTONE 700 ASTM C Type E Mounting. Test Number 2

DELTA Test Report. Measurement of Sound Absorption for AqFlex ON, one Sample as a discrete Object. Performed for Flex Acoustics

A L I O N Technical Center. Test Report. Port Coquitlam, British Columbia, Canada

RIVERBANK ACOUSTICAL LABORATORIES

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6712/ARL-SA6713 Revision 0 ARL

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6266/ARL-SA6274 Revision 0 ARL

Development of a small-scale reverberation room

Fabric Dazzle 6086 Manufacturer Carnegie Fabrics

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6986/ARL-SA6987 Revision 0 ARL

ISO 354 INTERNATIONAL STANDARD. Acoustics Measurement of sound absorption in a reverberation room

Technical Report. Project. The Laboratory Determination of The Random Incidence sound Absorption Coefficient of VertiQ Panels.

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT

Paseo Recoletos, nº Madrid TEST REPORT

Curtain fabric type Ace Manufacturer Kvadrat A/S

Renolit stretch ceilings

Page 1 of 10 pages Appendix, 5 pages Report no.: P Glostrup, October 12th 2012 Project: Claimant:

REPORT. Client. Test object. Date of testt. Results. Rönnåsgatan 5B Ulricehamn. (7 appendices) content of the

Fabric STREAMER pro. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M111250/04

Fabric VELOS STRATO. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/10

TFI Report Sound Absorption Impact Sound Insulation

Fabric XPRESS + PU-foam Manufacturer Gabriel A/S

Laboratory for Acoustics

Fabric REFLECTACOUSTIC

Fabric TWIST MELANGE Manufacturer Gabriel A/S

Fabric Medley Manufacturer Gabriel A/S

Fabric ALEX. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/09

Determination of sound absorption coefficient in impedance tubes according to ISO (2 appendices)

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6956 Revision 1 ARL

Fabric Sport. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/02

LABORATORY MEASUREMENTS OF THE REDUCTION OF TRANSMITTED IMPACT NOISE PANETTI OVERLAID BY CONCRETE FLOORING

TFI Report Sound Absorption Impact Sound Insulation

stylegreen Iceland Moss / Reindeer Moss of the company FlowerArt

Fabric UDINE. Measurement of sound absorption according to EN ISO 354. Test Report No. M102794/32

Fabric Zetacoustic. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/07

Roller blind fabric PRIMACOUSTIC R

Fabric Corsica. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M111250/16

TFI Report Sound Absorption Impact Sound Insulation

Fabric Umbria III R. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/13

Using an ambisonic microphone for measurement of the diffuse state in a reverberant room

ISO INTERNATIONAL STANDARD

Part 2: Methods for special reverberation test rooms

Technical Note. Measurement of Sound Absorption for Flex Acoustics AqTube. Performed for Flex Acoustics. TC Project no.: T Page 1 of 7

Laboratory for Acoustics. Determination of the sound absorption (reverberation room method) of curtains, manufacturer Vescom BV

Calcul des coefficients d'absorption alpha sabine

TFI Report Sound Absorption Impact Sound Insulation

Laboratory for Acoustics

Laboratory for Acoustics. Determination of the sound absorption (reverberation room method) of Airpanel, manufacturer Texdecor

Report. P.O. Box 70 NL 5700 AB Deurne The Netherlands Report number: A E-RA Date: 12 februari 2014 TS/TS/JW/A E-RA

Technical Brief 003 Report on the Measurement of Sound Absorption of Planex Linea Storage Units

Report. Laboratory for Acoustics

REPORT N CR

The effect of an edge on the measured scattering coefficients in a reverberation chamber based on ISO

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

Evaluation of standards for transmission loss tests

Yalıtım Kontrol Koruma. Insulation Control Protection

THE ACOUSTIC IMPEDANCE MEASUREMNET SYSTEM USING TWO MICROPHONES

Sound Absorption Test Intertek. kraft paper softwall + softblock modular system. m o l o d e s i g n, l t d

Laboratory for Acoustics. Determination of the sound insulation of sliding door constructions, manufactured by Metaflex

ON SOUND POWER MEASUREMENT OF THE ENGINE IN ANECHOIC ROOM WITH IMPERFECTIONS

ISO INTERNATIONAL STANDARD

Acoustic response in non-diffuse rooms

Report. Laboratory for Acoustics Determination of the sound absorption (reverberation room method) of different wired mats, manufacturer Rockwool

Investigations on real-scale experiments for the measurement of the ISO scattering coefficient in the reverberation room

Study of Wenger Audience Seating Chair Absorption. Ron Freiheit

Report. Laboratory for Acoustics

Certificate of Calibration Sound Level Calibrator

Basic Study on a Laboratory Measurement Method of the Normal-Incidence Scattering Coefficient

R & D AKUSTIKA * SIA. Test Report of laboratory Sound Insulation measurements Nr. 569 / 2011 AL 8.4. CUSTOMER: AEROC AS (Estonia)

Summary. The basic principles of the simulation technique SERT

INVESTIGATIONS INTO THE PERFORMANCE OF THE REVERBERATION CHAMBER OF THE INTEGRATED ACOUSTICS LABORATORY. A Thesis Presented to The Academic Faculty

Laboratory and In Situ Sound Absorption Measurement under a Synthetized Diffuse Acoustic Field: a Case Study on Five Materials

MAC Aura XB Acoustic Test Report

Design and Acoustics Brought into Harmony

ISO 3741 INTERNATIONAL STANDARD

Some issues in measurement of the random-incidence scattering coefficients in a reverberation room

Turbines and turbine sets Measurement of emitted airborne noise Engineering/survey method

CERTIFICATE OF CALIBRATION

ISO INTERNATIONAL STANDARD. Test code for machine tools Part 5: Determination of the noise emission

The practical application of G and C 50 in classrooms

Standard ECMA-108 3rd Edition - December Measurement of High-frequency Noise emitted by Information Technology and Telecommunications Equipment

Ecophon Acoustic Calculator. Accurate values in advance

1. Introduction. 2. ISO 3745 and ISO standard comparison

SIMPLE APPLICATION OF STI-METHOD IN PREDICTING SPEECH TRANSMISSION IN CLASSROOMS. Jukka Keränen, Petra Larm, Valtteri Hongisto

The diagram below. to the by the. outlet into. calculation. Since TRANSMISSION VIA STRUCTURE. Vibration Via Supports Duct Breakout

ECMA Measurement of airborne noise emitted and structure-borne vibration induced by small air-moving devices Part 1: Airborne noise measurement

A suggested method to be used to measure scattering coefficients of full scale samples.

Report. Draft. Laboratory for Acoustics

Transcription:

RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 24MM TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM. Testing Procedure: AS ISO 354-2006 Testing Laboratory: Client: Applied Acoustics Laboratory RMIT University, School of Electrical and Computer Engineering Melbourne, Victoria 3000, Australia NATA Accreditation Number 1421 Woven Image Pty. Limited 37-39 Chard Road Brookvale, N.S.W. 2100 Australia Date of Test: 7 th October 2013 Date of Report: 9 th October 2013 Report Number: Testing Officer: 13-119/PD,JW Peter Dale Peter Dale Approved NATA Signatory Accredited for compliance with ISO/IEC 17025 Page 1 of 6

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 24MM TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM. 1. INTRODUCTION The tests described in this report were carried out at the request of Woven Image Pty. Limited to determine the sound absorption coefficients of a sample of Echo Panel 24mm tested with no air gap. The tests were carried out using the Reverberation Room of the School of Electrical and Computer Engineering, The Royal Melbourne Institute of Technology Limited. Testing has been carried out in accordance with AS ISO 354 2006 Acoustics: Measurement of sound absorption in a reverberation room with the exception that the surface area of the sample was 12.32m 2 instead of the maximum sample surface area of 12.00m 2 specified in the AS ISO 354 2006 standard. This was due to the pre-cut size of the panels. At the request of the client the weighted sound absorption coefficient w has been determined in accordance with AS ISO 11654-1997 Acoustics: Sound Absorbers for Use in Buildings - Rating of sound absorption. The equipment used to perform these tests has been calibrated at an accredited laboratory and is in current calibration. 2. TEST FACILITIES AND PROCEDURES 2.1 Facilities: The Reverberation Room is of pentagonal plan with the ceiling inclined with respect to the floor. No two room dimensions are equal or in the ratio of small whole numbers. The volume of the room is 200.0 cubic metres. A sufficiently diffuse sound field is established by the inclusion of 17 stationary diffusing boards of panelboard, each of onesided area approximately one square metre and suspended with random orientation. The total two-sided area of the diffusing elements is 0.16 of the total boundary surface area of the room. Previous tests carried out in the room have established that diffusivity of the room sound field is acceptable. The total surface area of the room boundaries and diffusing elements is 235.6 square metres. 2.2 Generation of Sound-field: The test signals is random noise, band limited to a frequency range of 40Hz to 6300Hz. Three individual loudspeaker positions are used to excite the sound field in the reverberation chamber. The signal is fed to each loudspeaker in turn. 2.3 Receipt of Signals: Four microphones each mounted in statistically independent locations in the Reverberation Room are used to measure the sound field decays in the room. Ten sound decays are obtained at each of the twelve loudspeaker/microphone combinations, thus representing 120 decays for each frequency band. The microphone signal is relayed via a microphone amplifier, to a Bruel & Kjaer 3560 Pulse Multi Analyser System. The Pulse analyser is interfaced to a personal computer. A program running on the personal computer allows the determination of the reverberation time from the sound decays in accordance with the standard. The measuring equipment has been calibrated by an external laboratory, and is in current calibration. Page 2 of 6

3. SAMPLE FOR TESTING 3.1 Description: Woven - Image Echo Panel 24mm tested with no air gap: Woven Image Echo Panel 24mm - As provided by Client Product name: Echo Panel 24mm Material: 100% Pet (60% recycled) Thickness: 24mm Surface Density: 2800gsm Panel Size: 2200mm x 1200mm Primary Use: Workstation panel/divider Air Gap: None Sample Mount Details: The sample tested comprised of a 2 x 2 array of the panels (individual panel dimensions of 2200mm x 1200mm x 24mm) arranged to form a 2803mm x 4395mm rectangle. The panels were placed directly on the floor of the chamber with no air gap. Figure 1 shows the surface detail of the sample and Figure 2 shows the sample installed in the chamber for testing. The sample was tested with the perimeter edges enclosed by metal edges in accordance with the recommendations contained in AS ISO 354. The total surface area of the sample was 12.32m 2 instead of the maximum sample surface area of 12.00m 2 specified in the AS ISO 354 2006 standard. This was due to the pre-cut size of the panels under test. Figure 1: Surface detail of the Echo Panel 24mm. Page 3 of 6

Figure 2: Echo Panel 24mm tested with no air gap installed in Reverberation Chamber 3.2 Location Of Sample In The Reverberation Room Reverberation Chamber (Not to scale): X and Y co-ordinates of the sample location in the Reverberation Room Corner Ref. Number X co-ordinate (metres) Y co-ordinate (metres) 1-0.82 1.73 2-1.85 6.00 3-4.57 5.35 4-3.54 1.07 Descriptor Diagram Reference Length (m) Sample Length 1 to 2 Diagram Ref. A 4.395 Sample Length 1 to 4 Diagram Ref. B 2.803 Page 4 of 6

4. RESULTS The mean reverberation times at each frequency for the empty room, T60 e, the room with the sample installed, T60 e+s, the sound absorption coefficient and the 95% confidence interval are provided in Table 1. The results are rounded to 0.01. The 95% confidence interval for each frequency is determined from the standard deviation of the reverberation times of the empty room and the room with the sample. The k factor used to determine the 95% Confidence interval is 2.201. The results for the sample are detailed in Table 1, Table 2 and Graph 1 of this report. Test conditions: Room Empty Air temperature 21.8 o C Relative Humidity 40% Barometric Pressure 0.7616 metre of mercury Room with Sample Air temperature 22.0 o C Relative Humidity 39% Barometric Pressure 0.7611 metre of mercury Table 1: Reverberation times and Sound Absorption Coefficients for Echo Panel 24mm tested with no air gap. Octave Centre Frequency Bands, Hz Average RT s for empty room. T60 e Average RT s for room. with sample T60 e+s Sound Absorption Coefficient s 95% Confidence Interval for s 100 8.120 7.921 0.01 0.04 125 8.433 7.347 0.05 0.04 160 9.454 7.664 0.06 0.04 200 10.161 7.339 0.10 0.03 250 8.740 5.773 0.15 0.03 315 8.480 4.643 0.25 0.02 400 8.314 3.773 0.38 0.03 500 7.348 2.920 0.54 0.04 630 7.129 2.466 0.69 0.02 800 6.619 2.252 0.76 0.03 1000 6.041 2.009 0.87 0.03 1250 5.256 1.836 0.92 0.04 1600 4.597 1.711 0.96 0.03 2000 3.999 1.619 0.96 0.03 2500 3.386 1.506 0.96 0.03 3150 2.759 1.376 0.95 0.04 4000 2.141 1.190 0.96 0.03 5000 1.797 1.070 0.97 0.04 Page 5 of 6

The weighted sound absorption coefficient w of the sample determined in accordance with AS ISO 11654-1997 Acoustics: Sound Absorbers for Use in Buildings - Rating of sound absorption is: w = 0.45(MH) The Practical Sound Absorption Coefficients are detailed below in Table 2. These values have been determined in accordance with AS ISO 11654-1997 Acoustics: Sound Absorbers for Use in Buildings - Rating of sound absorption. Table 2: Practical Sound Absorption Coefficients for the Sample Frequency (Hz) 125 250 500 1000 2000 4000 Practical Sound Absorption Coefficient, α p 0.05 0.15 0.55 0.85 0.95 0.95 NRC of the sample calculated in accordance with ASTM C423-90A is: 0.65 Graph 1: Sound Absorption Coefficients of Echo Panel 24mm tested with no air gap. Page 6 of 6