BV SERIES VERTICAL BLOWER COIL UNITS Nominal Sizes 2 thru 10 Ton MAGIC AIRE BV SERIES FAN COILS ARE ETL LISTED TO U.S. AND CANADIAN SAFETY STANDARDS AND ARE ASSEMBLED TO ORDER FOR COMPETITIVE DELIVERY. UNITED ELECTRIC COMPANY, L.P. 1 Galveston St. Wichita Falls, Texas 76301 9-397-2100 Fax 860-998-1520 BVE 1.0 6/12/2008 www. magicaire.com
HVAC Guide Specifications Fan Coil Unit Vertical Cabinet Model, Ducted HVAC Guide Specifications Size Range: 800 to 00 Nominal CFM MagicAire Model Number: BV Part 1 General 1.01 SYSTEM DESCRIPTION Vertical, 2-pipe or 4-pipe, belt-driven fan coil unit. External parts are to be made with polyurethane based powder coated galvanealed, while internal parts are to be built from heavy gauge galvanized steel casing model fan coil unit for ducted installation above the ceiling, with full access to internal components. 1.02 QUALITY ASSURANCE Each coil shall be factory tested for leakage at minimum of 0 psig air pressure with coil submerged in water. Insulation and adhesive shall meet NFPA-90A requirements for flame spread and smoke generation. 1.03 DELIVERY, STORAGE AND HANDLING Unit shall be handled and stored in accordance with the manufacturer s instructions. Part 2 Products 2.01 EQUIPMENT A. General: Factory-assembled, vertical, draw-thru type fan coil unit is suitable for ducted installation. Unit shall be complete with water, DX or steam coil(s); fan(s); motor; belt drive; drain pan; and filters. B. Casing: Construction shall be heavy gauge galvanealed steel, painted with baked on polyurethane based powder coating, colored beige, lined with one-in. thick fiberglass Exact-O-Kote thermal/acoustical insulation. Supply and return duct connections shall be approx. one inch long. Removable front panel shall be provided for access to the fan/motor assembly. A molded plastic double-sloped IAQ drain pan shall extend under the full length and width of the coil(s) with a 3/4-in FPT connection for sizes BV 08-20, and BV 30 & standard drain pans are galvanized. (Optional) Stainless steel drain pan for sizes BV 30 &. C. Fans: Belt-driven, double-width fan wheels shall have forward-curved blades and be statically and dynamically balanced. Fan drive shall consist of variable-pitch motor pulley, fixed-pitch fan pulley and V-belt. Fans and scrolls shall be of galvanized steel. D. Coils: Unit shall be equipped with a standard capacity (3) or (4)-row CW/HW, or (3) or (4)-row DX A-coil for installation in a 2-pipe system. Additional coils shall be provided for installation in a 4-pipe system. Water coils shall have 3/8-in. (sizes 08-30) and 1/2-in. (sizes ) copper tubes with aluminum fins bonded to the tubes by mechanical expansion. Water coil(s) shall have manual air vent(s). DX coils shall have 3/8-in. copper tubes with aluminum fins bonded to the tubes by mechanical expansion. Coil(s) shall have a minimum working pressure of 0 psig at 200 F. Each coil shall have sweat connections for copper tubes. E. Operating Characteristics: A single-circuit coil unit installed in a 2-pipe CW/HW system shall be capable of providing heating or cooling. DX coils are suitable for R-22 or R-410A cooling only or R-22 or R-410A heat pump operation. A two coil unit installed in a 4-pipe system shall be capable of providing sequenced heating and cooling as determined by the controls provided by others. F. Motor(s): Fan motors shall be open, drip-proof, single-speed, 60 Hz, 17 rpm single or 3-phase, suitable for continuous duty at 104-deg F ( C) in 115, 208, 230, or 277 volts (60 Hz). Three-phase motors are available in 208, 230, or 460 volts (60 Hz). Single-phase motors shall be provided with resilient mount and automatic reset thermal overload protection. Three-phase 575 volt motors are by others. G. Electric Heat: a. The electric discharge heater shall be constructed of high-grade resistance wire supported by ceramic insulators on plated steel brackets. The electric heaters are to be field mounted to the unit or duct mounted downstream from the fan outlet. High limit thermal cutouts and non adjustable air proving switch shall protect the heat elements in the event of an air failure. Electric heaters are factory pre-wired for field mounting and electrical power connection. b. (Optional) Single point line connection includes fan contactor/ relay. c. (Optional) Disconnect for combined heater and motor amperage. H. Filters: a. 2 throwaway filter(s) shall be installed in the unit. b. (Optional) 2 pleated filter(s), MERV-7, shall be installed as indicated on the equipment schedule. I. Insulation: a. Units shall be equipped with 1-in. thick, 1.5-lbs/ft 3, Exact-O-Kote insulation. b. (Optional) 7/8 closed cell insulation c. (Optional) 1 double wall construction shall consist of 1 Exact-O-Kote insulation with min. 22-gauge galvanized steel liner with no fiberglass insulation exposed to the airstream. J. Coil Options: a. Unit shall be equipped with a coil for installation in a 2-pipe system. b. For installation in a 4-pipe CW/HW system, unit shall be equipped with a (3) or (4) row cooling/2-row hot water heating coils (heating coils located in either preheat or reheat position). c. Unit shall be equipped with a standard capacity (3) or (4) row DX (direct expansion) cooling coil (or optional dual circuit face split) DX cooling coil as required. d. For installation in a 4-pipe system the unit shall be equipped with either a (3) or (4) row DX cooling/2-row heating coil. Note: Hot water coil re-heat installation requires the use of a heating coil low-limit on units with DX cooling. Optional Accessories: a. Discharge or Return air plenum shall be constructed of heavy gauge galvanealed steel, painted with baked on polyurethane based powder coating, colored beige, lined with one-in. thick fiberglass Exact-O-Kote thermal/acoustical insulation. b. Units to be provided with ETL listed motor start stop station (MSS) with 24v transformer, terminal strip and disconnect switch. Motors without thermal overload will have motor starters with overload protection. MSS is not available with 2-speed motors or electric heat see electric heat option. BVE 1.0 Page 2 6/12/2008
BV Series Standard Features Controls (i.e. contactor, starter, or transformer/fan relay) not included in standard product. Chilled water (optional hot water or steam) coil stubouts, electrical and drain connections are standard left hand looking at front of unit. BV-08-20 are one-piece units. BV-30- are three-piece units and each section is individually cartoned. Stocked Optional Accessories: 2 Row Hot Water Heating Coil Specify preheat or reheat for 2-5 Ton units Discharge Plenum (Grilles field supplied and installed) Return Plenum (Grille, if required, field supplied and installed) 2 Pleated Filters (MERV-7) Motor Start/Stop Station (24V transformer, motor relay, contactor, or starter, terminal strip, and disconnect included) Non-Stock Options: Special Insulation Steam Coils Electric Heat BV-08 with panels removed. BV-30 with panels removed. BVE 1.0 Page 3 6/12/2008
BV Nomenclature Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Example B V E 0 8 A A A A A A A A 0 0 A A A A A A A M Unit Type/Size CFM (See page 5 for Ranges) BV -- Vertical Belt 0 -- None - No Motor Supplied* 8 -- CFM Range 8 Drive Unit 1 -- CFM Range 1 9 -- CFM Range 9 2 -- CFM Range 2 A -- CFM Range 10 Generation/Series 3 -- CFM Range 3 B -- CFM Range 11 E -- Product Generation 4 -- CFM Range 4 C -- CFM Range 12 5 -- CFM Range 5 D -- CFM Range 13 Unit Type/Size 6 -- CFM Range 6 E -- CFM Range 14 08 -- 800 CFM 2 Nom. Tons 7 -- CFM Range 7 F -- CFM Range 15 12 -- 1200 CFM 3 Nom. Tons 16 -- 1600 CFM 4 Nom. Tons Notes: 20 -- 2000 CFM 5 Nom. Tons *1. Drive kit (blower sheave, motor sheave and belts) to be 30 -- -- 3000 CFM 00 CFM 7.5 Nom. Tons 10 Nom. Tons supplied and installed by field. Power Supply Future Use A -- N/A A-- Future Use B -- 115/1 D -- 208/2/1 Cooling Coil E -- 277/1 A -- None G -- 208/2/3 B -- Chilled Water No Face Split H -- 460/3 H -- DX / R22 No Face Split Notes: J -- DX / R22 Dual Face Split S -- DX / R410A No Face Split T -- DX / R410A Dual Face Split COIL CONFIGURATION Heat Pos Connection Hand Future Use A -- Preheat Left-Hand (Cooling & Heating Coil) or N/A A -- Future Use R -- Reheat Left-Hand (Cooling & Heating Coil) Notes: Future Use 1. Water Heating Coil cannot be in reheat when cooling coil is DX. A -- Future Use 2. Left-Hand and Right-Hand defined as looking at the front panels. HEATING COIL AA -- NONE - USE FOR 2-PIPE UNIT OR NO COIL H2 -- Hot Water Std Cap SS -- STEAM Std Cap SH -- STEAM High Cap 1. Unit shall be wired for 2V at factory. Field must switch transformer tap (if provided) to 208V. Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Example B V E 0 8 A A A A A A A A 0 0 A A A A A A A M TSP (See page 5 for Ranges) Always M 0 -- None - No Motor Supplied D -- TSP Range 13 1 -- TSP Range 1 E -- TSP Range 14 Future Use 2 -- TSP Range 2 F -- TSP Range 15 A -- Future Use 3 -- TSP Range 3 G -- TSP Range 16 4 -- TSP Range 4 H -- TSP Range 17 Drain Pan 5 -- TSP Range 5 J -- TSP Range 18 A -- Plastic (Std for 08-20) 6 -- TSP Range 6 K -- TSP Range 19 B -- Stainless Steel (Opt for 30-) 7 -- TSP Range 7 L -- TSP Range 20 C -- Galvanized (Std for 30-) 8 -- TSP Range 8 M -- TSP Range 21 9 -- TSP Range 9 N -- TSP Range 22 Controls A -- TSP Range 10 P -- TSP Range 23 A -- Junction Box Only B -- TSP Range 11 R -- TSP Range 24 B -- Motor Start/Stop Station* C -- TSP Range 12 S -- TSP Range 25 Notes: *1. Motor Start/Stop station shall include a terminal strip, Motor 24V Class 2 Transformer (75VA), motor relay, (see page 5) contactor, or starter and interlocking disconnect. *2. Motor Start/Stop station is not available with Electric Heat Insulation (opt - field installed) or 2-speed motors. A -- Standard - Fiberglass IAQ C -- Closed Cell D -- Double Wall Filter Options A -- 2" Throwaway Filter B -- 2" Pleated Filter (MERV 7) BVE 1.0 Page 4 6/12/2008
BV Nomenclature Detail CFM Options - Position 14 Selection Description CFM PER UNIT SIZE 08 12 16 20 30 0 None - No Motor Supplied* STD 1 CFM Range 1 600 900 1200 10 22 3000 2 CFM Range 2 6 9 1280 1600 20 31 3 CFM Range 3 700 960 1360 1700 25 3200 4 CFM Range 4 7 1000 14 1800 2700 3300 5 CFM Range 5 800 1020 20 1900 28 30 6 CFM Range 6 8 1080 1600 2000 3000 30 7 CFM Range 7 900 11 1680 2100 31 3600 8 CFM Range 8 9 1200 1760 2200 3200 37 9 CFM Range 9 960 1260 18 2300 3300 3800 A CFM Range 10 1000 1320 1920 20 30 00 B CFM Range 11 1380 2000 20 30 4200 C CFM Range 12 14 3600 40 D CFM Range 13 10 37 4600 E CFM Range 14 4800 F CFM Range 15 00 TSP Options - Position 15 TSP Schedule Description Selection 08 12 16 20 30 0 None - No Motor Supplied X X X X X X 1 TSP Range 1 0.20-0.30 X X X X X X 2 TSP Range 2 0.31-0. X X X X X X 3 TSP Range 3 0.41-0. X X X X X X 4 TSP Range 4 0.51-0.60 X X X X X X 5 TSP Range 5 0.61-0.70 X X X X X X 6 TSP Range 6 0.71-0.80 X X X X X X 7 TSP Range 7 0.81-0.90 X X X X X X 8 TSP Range 8 0.91-1.00 X X X X X X 9 TSP Range 9 1.01-1.10 X X X X X X A TSP Range 10 1.11-1.20 X X X X X X B TSP Range 11 1.21-1.30 X X X X X X C TSP Range 12 1.31-1. X X X X X X D TSP Range 13 1.41-1. X X X X X X E TSP Range 14 1.51-1.60 X X X X X X F TSP Range 15 1.61-1.70 X X X X X X G TSP Range 16 1.71-1.80 X X X X X X H TSP Range 17 1.81-1.90 X X X X X X J TSP Range 18 1.91-2.00 X X X X X X K TSP Range 19 2.01-2.10 X X X X X L TSP Range 20 2.11-2.20 X X M TSP Range 21 2.21-2.30 X X N TSP Range 22 2.31-2. X X P TSP Range 23 2.41-2. X X R TSP Range 24 2.51-2.60 X X S TSP Range 25 2.61-2.70 X X Motor Options - Position 16 & 17 Selection 16-17 Voltage Description Type, Encl HP AA No Motor* B1 0.25 B2 0.33 B3 0. B4 115/208-230/1 ODP 0.75 B5 1.00 B6 1. B7 2.00 C1 0. 115/230/1 C2 ODP, HE 0.75 only C3 1.00 E1 0. E2 115/1 ODP, 2SP 0.75 E3 1.00 F1 0. 230/1 F2 ODP, 2SP 0.75 only F3 1.00 G1 0.25 G2 0.33 G3 0. G4 277/1 ODP 0.75 G5 1.00 G6 1. G7 2.00 Selection 16-17 Voltage Description Type, Encl HP H1 0. H2 0.75 H3 1.00 208-230/460/3 ODP H4 1. H5 2.00 H6 3.00 J1 0. J2 0.75 J3 1.00 J5 2.00 208-230/460/3 ODP, HE J6 3.00 J7 5.00 J8 7. J9 10.00 K1 0. K2 0.75 K3 208-230/460/3 ODP, 2SP 1.00 K4 1. K5 2.00 Min/Max HP Motors Model 08 12 16 20 30 BV MIN HP 1/4 1/4 1/2 1/2 3/4 3/4 MAX HP 1 1/2 1 1/2 1 1/2 1 1/2 5 5 BVE 1.0 Page 5 6/12/2008
BV Physical Data Model BVE 08 12 16 20 30 Nominal Capacity ( tons ) 2 3 4 5 7.5 10 Nominal CFM 800 1200 1600 2000 3000 00 Fan Nominal Cfm 800 1200 1600 2000 3000 00 Fan Size 100-6R 100-6R 120-6R 120-9R 1-9R 1-9R Filter Quantity 1 1 1 2 4 4 Nominal Size 20 x 20 20 x 20 22.5 x 22.5 16 x 25 20 x 25 20 x 25 Coils Face Area - DX (sqft) 3.00 3.00 4.00 5.00 7.33 9.17 FPI - DX 10 10 10 10 10 10 No of Rows 3 4 4 4 4 4 Face Area - Chilled Water (sqft) 3.00 3.00 4.00 5.00 7.33 9.17 FPI - Chilled Water 10 10 10 10 10 10 Tube Dia (OD) 3/8 3/8 3/8 3/8 3/8 1/2 No of Rows - Chilled Water 3 4 4 4 4 4 Face Area - Hot Water (sqft) 2.01 2.01 2.41 3.19 5.73 7.81 FPI - Hot Water 10.00 10.00 10.00 10.00 10.00 10.00 Coil Connections Chilled Water - Supply-Return (Swt-OD) 3/4-3/4 3/4-3/4 7/8-7/8 1 1/8-1 1/8 1 1/8-1 1/8 1 3/8-1 3/8 Hot Water - Supply-Return (Swt-OD) 7/8-7/8 7/8-7/8 7/8-7/8 1 1/8-1 1/8 1 1/8-1 1/8 1 1/8-1 1/8 DX - Liquid - Suction (Swt-OD) 3/8-3/4 3/8-3/4 1/2-7/8 1/2-1 1/8 5/8-1 1/8 1/2-7/8 (2 ea) Steam - Supply-Condensate (MPT) 1 1/2-1 1 1/2-1 1 1/2-1 1 1/2-1 2-1 1/2 2-1 1/2 Condensate Drain Line Primary Secondary Approximate Weight (lb) 3/4" FPT 3/4" FPT 7/8" OD N/A Cooling Only - Electric Heat 164 170 200 253 364 462 Cooling and Hydronic Heating 178 184 217 274 4 564 Unit Dimensions (in) Height.0.0 56.5 59.5 84.4 84.4 Width 22.3 22.3 25.1 29.5 54.0 54.0 Depth 24.0 24.0 24.3 26.0 31.0 31.0 BVE 1.0 Page 6 6/12/2008
BV 08-20 Preheat Unit BVE 1.0 Page 7 6/12/2008
BV 08-20 Reheat Unit BVE 1.0 Page 8 6/12/2008
BV 30 Preheat Unit BVE 1.0 Page 9 6/12/2008
BV 30 Reheat Unit BVE 1.0 Page 10 6/12/2008
BV Preheat Unit BVE 1.0 Page 11 6/12/2008
BV Reheat Unit BVE 1.0 Page 12 6/12/2008
BV Steam Capacity BVE Size 08 12 16 20 30 SCFM 600 800 1000 900 1200 10 1200 1600 2000 10 2000 20 22 3000 37 3000 00 00 Heating Capacity - High Capacity Steam Coils Entering Air Temp - EDB -20-10 0 10 20 30 60 TC 84.30 80.90 77. 74.10 70.70 67.30 63.90 60. 57.00 LDB 109.0 113.8 118.6 123.4 128.2 132.9 137.7 142.5 147.3 TC 99.00 95.00 91.00 87.00 83.00 79.00 75.00 71.00 67.00 LDB 93.6 99.0 104.4 109.8 115.2 120.6 126.0 131.4 136.9 TC 111.00 106. 102.10 97.60 93.10 88.60 84.10 79.60 75.10 LDB 82.0 87.8 93.7 99.6 105.5 111.3 117.2 123.1 129.0 TC 105.30 101.00 96.70 92. 88.20 84.00 79.70 75. 71.20 LDB 87.4 93.1 98.7 104.4 110.0 115.7 121.3 127.0 132.7 TC 121.30 116. 111. 106.60 101.70 96.80 91.90 87.00 82.10 LDB 72.8 79.1 85.3 91.6 97.8 104.0 110.3 116.5 122.8 TC 134.20 128.80 123.30 117.90 112. 107.10 101.60 96.20 90.80 LDB 62.2 68.8 75.5 82.2 88.9 95.6 102.2 108.9 115.6 TC 127. 122.30 117.20 112.00 106.90 101.70 96.60 91. 86.30 LDB 77.5 83.6 89.7 95.7 101.8 107.8 113.9 119.9 126.0 TC 1.60 139.70 133.90 128.00 122.10 116.20 110.30 104. 98. LDB 63.6 70.2 76.8 83.4 90.1 96.7 103.3 109.9 116.6 TC 160.10 153.60 147.20 1.70 134.20 127.80 121.30 114.80 108.30 LDB 53.5 60.5 67.6 74.6 81.6 88.7 95.7 102.7 109.7 TC 192.30 184. 176.70 169.00 161.20 153. 1.70 137.90 130.10 LDB 97.7 103.0 108.2 113.4 118.7 123.9 129.2 134.4 139.7 TC 223. 214. 205. 196. 187. 178. 169.30 160.30 151.30 LDB 82.6 88.5 94.3 100.2 106.0 111.9 117.7 123.6 129.4 TC 249.00 238.90 228.90 218.80 208.70 198.70 188.60 178. 168. LDB 71.5 77.8 84.1 90.4 96.7 103.0 109.3 115.6 121.9 TC 277.70 266. 255.30 244.00 232.80 221.60 210. 199.10 187.90 LDB 93.3 98.8 104.2 109.6 115.0 120.4 125.9 131.3 136.7 TC 321.60 308.60 295.60 282.60 269.60 256.60 243.60 230.60 217.60 LDB 78.5 84.5 90.5 96.5 102.5 108.6 114.6 120.6 126.6 TC 7.20 342.80 328. 313.90 299. 285.00 270.60 256.20 241.70 LDB 67.5 73.9 80.4 86.9 93.3 99.8 106.3 112.7 119.2 TC 378.70 363. 348.10 332.80 317. 302.20 286.90 271.60 256.30 LDB 95.9 101.2 106.6 111.9 117.2 122.5 127.8 133.1 138.4 TC 439.60 421.80 4.10 386.30 368. 3.80 333.00 315.20 297. LDB 80.9 86.8 92.8 98.7 104.6 110.5 116.4 122.4 128.3 TC 489.10 469.30 449.60 429.80 410.00 390.30 370. 3.70 331.00 LDB 69.8 76.2 82.6 88.9 95.3 101.7 108.0 114.4 120.8 NOTES: 1. Steam coil rating based on 5 psig steam pressure. EDB - Entering Dry-Bulb 2. Reference steam capacity multiplier table for other steam pressures. LDB - Leaving Dry-Bulb TC - Total Capacity (MBH) BVE 1.0 Page 13 6/12/2008
BV Electric Heat Field Installed Dimensional Data BVE 1.0 Page 14 6/12/2008
BV Field Installed Electric Heat List (Table BVE-300T) Unit Size BVE-08/12 BVE-16 BVE-20 BVE-30/ Rated Control Box Plenum Volts KW C D E G H I 2-1 5 3.5 8 11.5 8.8 12.1 14 2-1 10 3.5 8 11.5 8.8 12.1 14 208-1 5 3.5 8 11.5 8.8 12.1 14 208-1 10 3.5 8 11.5 8.8 12.1 14 2-3 10 3.5 8 11.5 8.8 12.1 14 208-3 10 3.5 8 11.5 8.8 12.1 14 480-3 10 3.5 8 11.5 8.8 12.1 14 120-1 5 3.5 8 11.5 8.8 12.1 14 277-1 5 3.5 8 11.5 8.8 12.1 14 277-1 10 3.5 8 11.5 8.8 12.1 14 2-1 6 3.5 12 12 9.6 14.1 14 2-1 10 3.5 12 12 9.6 14.1 14 2-1 12 5.5 14 12 9.6 14.1 20 2-3 10 3.5 12 12 9.6 14.1 14 2-3 15 3.5 12 12 9.6 14.1 14 208-1 5 3.5 12 12 9.6 14.1 14 208-1 10 3.5 12 12 9.6 14.1 14 208-1 15 5.5 14 18 9.6 14.1 20 208-3 7.5 3.5 12 12 9.6 14.1 14 208-3 17 3.5 12 12 9.6 14.1 14 120-1 4.8 3.5 12 12 9.6 14.1 14 480-3 15 3.5 12 12 9.6 14.1 14 480-1 15 3.5 12 12 9.6 14.1 14 2-1 5 3.5 12 11.5 14.4 13.1 14 2-1 10 3.5 12 11.5 14.4 13.1 14 2-1 15 5.5 14 18 14.4 13.1 20 2-1 19 5.5 14 18 14.4 13.1 20 208-1 5 3.5 12 11.5 14.4 13.1 14 208-1 10 3.5 12 11.5 14.4 13.1 14 208-1 15 5.5 14 18 14.4 13.1 20 208-1 19 5.5 14 18 14.4 13.1 20 208-3 5 3.5 12 11.5 14.4 13.1 14 208-3 10 3.5 12 11.5 14.4 13.1 14 208-3 15 3.5 12 11.5 14.4 13.1 14 208-3 19 3.5 12 11.5 14.4 13.1 14 2-3 5 3.5 12 11.5 14.4 13.1 14 2-3 10 3.5 12 11.5 14.4 13.1 14 2-3 15 3.5 12 11.5 14.4 13.1 14 2-3 19 3.5 12 11.5 14.4 13.1 14 480-1 5 3.5 12 11.5 14.4 13.1 14 480-1 19 3.5 12 11.5 14.4 13.1 14 480-3 5 3.5 12 11.5 14.4 13.1 14 480-3 19 3.5 12 11.5 14.4 13.1 14 2-1 5 3.5 14 11.5 13.4 16.9 14 2-1 10 3.5 14 11.5 13.4 16.9 14 2-1 15 5.5 16 18 13.4 16.9 20 2-1 21 5.5 16 18 13.4 16.9 20 208-1 5 3.5 14 11.5 13.4 16.9 14 208-1 10 3.5 14 11.5 13.4 16.9 14 208-1 15 5.5 16 18 13.4 16.9 20 208-1 21 5.5 16 18 13.4 16.9 20 2-3 5 3.5 14 11.5 13.4 16.9 14 2-3 10 3.5 14 11.5 13.4 16.9 14 2-3 15 3.5 14 11.5 13.4 16.9 14 2-3 21 5.5 16 18 13.4 16.9 20 208-3 5 3.5 14 11.5 13.4 16.9 14 208-3 10 3.5 14 11.5 13.4 16.9 14 208-3 15 3.5 14 11.5 13.4 16.9 14 208-3 21 5.5 16 18 13.4 16.9 20 480-3 5 3.5 14 11.5 13.4 16.9 14 480-3 10 3.5 14 11.5 13.4 16.9 14 480-3 15 3.5 14 11.5 13.4 16.9 14 480-3 21 3.5 14 11.5 13.4 16.9 14 480-1 5 3.5 14 11.5 13.4 16.9 14 480-1 10 3.5 14 11.5 13.4 16.9 14 480-1 15 3.5 14 11.5 13.4 16.9 14 480-1 21 3.5 14 11.5 13.4 16.9 14 BVE 1.0 Page 15 6/12/2008
BV Component Air Pressure Drop Model BVE-08 BVE-12 BVE-16 BVE-20 BVE-30 BVE- Blower Size 10 X 6 10 X 6 12 X 6 12 X 9 15 X 9 15 X 9 Chilled Water Hot Water DX Steam Filter CFM Std Cap Std Cap Std Cap Std Cap High Cap T/A Pleated 600 0.06 0.08 0.12 0.07 0.13 0.09 0.09 6 0.07 0.10 0.13 0.08 0.15 0.11 0.10 700 0.08 0.11 0.14 0.09 0.17 0.12 0.11 7 0.09 0.12 0.15 0.10 0.19 0.13 0.13 800 0.10 0.13 0.17 0.11 0.21 0.14 0.14 8 0.12 0.15 0.18 0.13 0.23 0.16 0.15 900 0.13 0.16 0.20 0.14 0.25 0.17 0.16 9 0.14 0.17 0.21 0.16 0.28 0.19 0.17 1000 0.16 0.19 0.22 0.17 0.30 0.20 0.18 900 0.13 0.16 0.22 0.14 0.25 0.17 0.16 960 0.15 0.18 0.24 0.16 0.28 0.19 0.17 1020 0.17 0.19 0.27 0.18 0.31 0.21 0.18 1080 0.19 0.21 0.29 0.20 0.34 0.22 0.19 11 0.21 0.23 0.32 0.22 0.38 0.24 0.21 1200 0.23 0.24 0.34 0.24 0.41 0.26 0.22 1260 0.25 0.26 0.37 0.26 0. 0.28 0.23 1320 0.28 0.28 0.39 0.28 0.48 0.30 0.24 1380 0.31 0.30 0.42 0.31 0.52 0.32 0.25 14 0.34 0.32 0. 0.33 0.56 0.34 0.26 10 0.37 0.34 0.48 0.36 0.60 0.36 0.28 1200 0.13 0.19 0.22 0.20 0. 0.07 0.06 1280 0.15 0.21 0.24 0.22 0.39 0.07 0.07 1360 0.17 0.22 0.27 0.25 0.43 0.08 0.08 14 0.19 0.24 0.29 0.28 0.48 0.09 0.09 1520 0.21 0.27 0.32 0.31 0.52 0.09 0.09 1600 0.23 0.29 0.34 0.34 0.57 0.10 0.10 1680 0.25 0.31 0.37 0.37 0.62 0.11 0.11 1760 0.28 0.33 0.39 0. 0.68 0.12 0.11 18 0.31 0. 0.42 0.44 0.73 0.12 0.12 1920 0.34 0.37 0. 0.47 0.79 0.13 0.13 2000 0.37 0. 0.48 0.51 0.84 0.14 0.13 10 0.13 0.17 0.22 0.10 0.18 0.13 0.13 1600 0.15 0.19 0.24 0.11 0.20 0.14 0.14 1700 0.17 0.21 0.27 0.12 0.23 0.16 0.15 1800 0.19 0.22 0.29 0.14 0.25 0.17 0.16 1900 0.21 0.24 0.32 0.15 0.27 0.19 0.17 2000 0.23 0.26 0.34 0.17 0.30 0.20 0.18 2100 0.25 0.28 0.37 0.18 0.32 0.21 0.19 2200 0.28 0.30 0.39 0.20 0. 0.23 0.20 2300 0.31 0.32 0.42 0.21 0.37 0.25 0.21 20 0.34 0.34 0. 0.23 0. 0.26 0.22 20 0.37 0.37 0.48 0.25 0.43 0.28 0.23 22 0.14 0.13 0.23 0.11 0.21 0.06 0.06 20 0.15 0.14 0.25 0.13 0.23 0.07 0.07 25 0.17 0.16 0.28 0.14 0.26 0.07 0.07 2700 0.19 0.17 0.30 0.16 0.28 0.08 0.08 28 0.22 0.19 0.33 0.18 0.31 0.09 0.09 3000 0.24 0.20 0. 0.19 0.34 0.09 0.09 31 0.27 0.22 0.38 0.21 0.37 0.10 0.10 3300 0.29 0.23 0.41 0.23 0. 0.11 0.11 30 0.32 0.25 0.44 0.25 0.43 0.12 0.11 3600 0. 0.26 0.47 0.27 0.46 0.12 0.12 37 0.38 0.28 0. 0.29 0. 0.13 0.13 3000 0.15 0.13 0.25 0.10 0.19 0.09 0.09 3200 0.18 0.14 0.28 0.12 0.22 0.10 0.10 30 0.20 0.15 0.30 0.13 0.24 0.11 0.11 3600 0.22 0.17 0.33 0.15 0.26 0.12 0.12 3800 0.25 0.18 0.36 0.16 0.29 0.13 0.13 00 0.28 0.19 0.39 0.18 0.31 0.14 0.14 4200 0.30 0.21 0.42 0.19 0.34 0.15 0.14 40 0.34 0.22 0. 0.21 0.37 0.17 0.15 4600 0.37 0.24 0.48 0.23 0. 0.18 0.16 4800 0. 0.26 0.52 0.25 0.43 0.19 0.17 00 0.44 0.27 0.55 0.26 0.46 0.20 0.18 NOTES: 1. All values are in inches wc. 2. Pressure drop includes standard fiberglass filters. 3. All pressure drops are with dry coil. BVE 1.0 Page 16 6/12/2008
BV08-12 Fan Performance BVE-08/12 Fan Performance Total Static Pressure (in. wg) 0.20 0.30 0. 0. 0.60 0.70 0.80 0.90 1.00 1.10 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 600 522 0.06 612 0.08 693 0.10 766 0.12 834 0.14 899 0.16 961 0.18 ---- ---- ---- ---- ---- ---- 6 533 0.07 621 0.09 700 0.11 772 0.13 838 0.15 901 0.18 961 0.20 ---- ---- ---- ---- ---- ---- 700 546 0.08 631 0.10 708 0.12 778 0.14 844 0.17 905 0.19 964 0.22 1020 0.24 1074 ---- ---- ---- 7 560 0.09 642 0.12 717 0.14 786 0.16 8 0.18 911 0.21 968 0.23 1023 0.26 1076 0.29 1127 0.32 800 575 0.11 654 0.13 727 0.15 795 0.18 858 0.20 917 0.23 973 0.25 1027 0.28 1079 0.31 1129 0.34 8 590 0.12 667 0.15 738 0.17 804 0.20 866 0.22 924 0.25 980 0.27 1033 0.30 1083 0.33 1133 0.36 900 607 0.14 680 0.17 7 0.19 814 0.22 875 0.24 932 0.27 987 0.30 1039 0.33 1089 0.36 1137 0.39 9 624 0.16 695 0.19 762 0.21 825 0.24 885 0.27 941 0.30 995 0.32 1046 0. 1095 0.38 1143 0.42 960 627 0.16 698 0.19 764 0.22 827 0.25 887 0.27 943 0.30 996 0.33 1047 0.36 1097 0.39 1144 0.42 1000 642 0.18 710 0.21 775 0.24 837 0.27 895 0.29 9 0.32 1003 0. 1054 0.38 1102 0.41 1149 0. 1020 649 0.18 716 0.22 780 0.25 841 0.28 899 0.31 954 0.34 1007 0.36 1057 0. 1105 0.43 1152 0.46 1080 672 0.21 736 0.24 797 0.28 856 0.31 913 0.34 967 0.37 1018 0. 1067 0.43 1115 0.47 1161 0. 11 695 0.24 756 0.27 815 0.31 872 0.34 927 0.38 980 0.41 1030 0.44 1079 0.48 1125 0.51 1171 0.54 1200 719 0.27 777 0.31 834 0. 889 0.38 942 0.42 994 0. 1043 0.49 1091 0.52 1137 0.56 1181 0.59 1260 743 0.31 799 0.34 854 0.38 907 0.42 959 0.46 1009 0. 1057 0.53 1104 0.57 1149 0.61 1192 0.64 1320 768 0.34 821 0.38 874 0.42 925 0.47 976 0.51 1024 0.55 1071 0.59 1117 0.62 1162 0.66 1205 0.70 1380 793 0.39 8 0.43 895 0.47 9 0.51 993 0.56 1041 0.60 1087 0.64 1132 0.68 1175 0.72 1217 0.76 14 819 0.43 868 0.47 917 0.52 965 0.56 1012 0.61 1058 0.65 1103 0.70 1147 0.74 1189 0.78 1231 0.82 10 8 0.48 892 0.52 939 0.57 986 0.62 1031 0.66 1076 0.71 1120 0.75 1162 0.80 1204 0.84 12 0.89 BVE-08/12 Fan Performance Total Static Pressure (in. wg) 1.20 1.30 1. 1. 1.60 1.70 1.80 1.90 2.00 2.10 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 600 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 6 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 700 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 7 1177 0. 1225 0.37 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 800 1178 0.37 1225 0. ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 8 1180 0.39 1226 0.42 1271 0.46 1316 0.49 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 900 1184 0.42 1229 0. 1274 0.48 1317 0.52 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 9 1189 0. 1233 0.48 1277 0.51 1319 0.55 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 960 1190 0. 1234 0.49 1278 0.52 1320 0.55 1361 0.59 12 0.63 1442 0.66 ---- ---- ---- ---- ---- ---- 1000 1194 0.48 1239 0.51 1281 0.55 1323 0.58 1364 0.62 14 0.65 1443 0.69 ---- ---- ---- ---- ---- ---- 1020 1197 0.49 1241 0.52 1283 0.56 1325 0.59 1365 0.63 15 0.67 1444 0.71 1482 0.74 1520 0.78 1557 0.82 1080 1205 0.53 1248 0.57 1290 0.60 1331 0.64 1371 0.68 1410 0.71 1448 0.75 1486 0.79 1522 0.83 1559 0.87 11 1214 0.58 1257 0.61 1298 0.65 1338 0.69 1377 0.72 1416 0.76 14 0.80 1490 0.84 1527 0.88 1562 0.92 1200 1224 0.63 1266 0.66 1307 0.70 1346 0.74 1385 0.78 1423 0.81 1460 0.85 1496 0.90 1532 0.94 1567 0.98 1260 12 0.68 1276 0.72 1316 0.75 15 0.79 1394 0.83 1431 0.87 1467 0.91 13 0.95 1538 1.00 1573 1.04 1320 1246 0.74 1287 0.78 1326 0.81 1365 0.85 13 0.89 14 0.93 1476 0.98 1511 1.02 1546 1.06 1580 1.10 1380 1258 0.80 1298 0.84 1337 0.88 1375 0.92 1413 0.96 1449 1.00 1485 1.04 1520 1.08 1554 1.13 1587 1.17 14 1271 0.86 1310 0.90 1349 0.95 1386 0.99 1423 1.03 19 1.07 1494 1.11 1529 1.16 1563 1.20 1596 1.25 10 1284 0.93 1323 0.97 1361 1.02 1398 1.06 1434 1.10 1470 1.15 15 1.19 1539 1.24 1572 1.28 1605 1.33 BVE-08/12 Fan Performance Total Static Pressure (in. wg) 2.20 2.30 2. 2. 2.60 2.70 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 600 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 6 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 700 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 7 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 800 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 8 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 900 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 9 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 960 1594 0.81 ---- ---- ---- ---- ---- ---- 1000 1626 0.88 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1020 1593 0.86 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1080 1594 0.91 1629 0.95 1664 0.99 ---- ---- ---- ---- ---- ---- 11 1597 0.96 1632 1.01 1666 1.05 1699 1.09 1732 1.14 ---- ---- 1200 1601 1.02 16 1.06 1669 1.11 1702 1.15 1734 1.20 ---- ---- 1260 1607 1.08 16 1.13 1673 1.17 1706 1.22 1738 1.26 1769 1.31 1320 1613 1.15 1646 1.19 1679 1.24 1711 1.28 1742 1.33 1773 1.38 1380 1620 1.22 1653 1.26 1685 1.31 1717 1.36 1748 1. 1778 1. 14 1629 1.29 1661 1.34 1692 1.39 1724 1.43 1754 1.48 ---- ---- 10 1637 1.37 1669 1.42 1700 1.47 ---- ---- ---- ---- ---- ---- BVE 1.0 Page 17 6/12/2008
BV-16 Fan Performance BVE-16 Fan Performance Total Static Pressure (in. wg) 988 1.01 1022 1.07 1056 1.13 1089 1.19 1121 1.25 1152 1.31 BVE-16 Fan Performance Total Static Pressure (in. wg) 1.20 1.30 1. 1. 1.60 1.70 1.80 1.90 2.00 2.10 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1200 1041 0.60 1078 0.64 1114 0.68 1149 0.73 1184 0.77 1218 0.81 1251 0.86 1284 0.91 1316 0.95 1347 1.00 1280 10 0.66 1087 0.70 1122 0.74 1157 0.79 1191 0.83 1224 0.88 1256 0.92 1288 0.97 1319 1.02 13 1.07 1360 1062 0.72 1097 0.76 1132 0.81 1166 0.85 1199 0.90 1231 0.95 1263 1.00 1294 1.04 1325 1.09 15 1.14 14 1074 0.78 1109 0.83 1142 0.88 1176 0.93 1208 0.97 12 1.02 1271 1.07 1302 1.12 1332 1.17 1362 1.22 1520 1087 0.85 1121 0.90 1154 0.95 1187 1.00 1219 1.05 12 1.10 1280 1.15 1311 1.21 13 1.26 1369 1.31 1600 1101 0.93 1134 0.98 1167 1.03 1199 1.08 1230 1.14 1261 1.19 1291 1.24 1320 1.30 1349 1. 1378 1. 1680 1116 1.00 1149 1.06 1181 1.11 1212 1.17 1243 1.22 1273 1.28 1302 1.33 1331 1.39 1360 1. ---- ---- 1760 1132 1.09 1164 1.15 1195 1.20 1226 1.26 1256 1.32 1286 1.38 1315 1.43 1343 1.49 ---- ---- ---- ---- 18 1148 1.18 1180 1.24 1210 1.30 1241 1.36 1270 1.42 1299 1.48 ---- ---- ---- ---- ---- ---- ---- ---- 1920 1165 1.27 1196 1.33 1226 1. 1256 1.46 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 2000 1183 1.37 1213 1.44 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- BVE-16 Fan Performance Total Static Pressure (in. wg) 2.20 2.30 2. 2. CFM RPM BHP RPM BHP RPM BHP RPM BHP 1200 1378 1.05 19 1.10 1439 1.16 1280 1381 1.12 1411 1.17 14 1.22 1469 1.27 1360 1385 1.19 1414 1.24 1443 1.30 1472 1. 14 1391 1.27 1419 1.33 1448 1.38 1476 1.43 1520 1398 1.36 1426 1.42 14 1.47 ---- ---- 1600 16 1.46 ---- ---- ---- ---- ---- ---- 1680 ---- ---- ---- ---- ---- ---- ---- ---- 1760 ---- ---- ---- ---- ---- ---- ---- ---- 18 ---- ---- ---- ---- ---- ---- ---- ---- 1920 ---- ---- ---- ---- ---- ---- ---- ---- 2000 ---- ---- ---- ---- ---- ---- ---- ---- BVE 1.0 Page 18 6/12/2008
BV-20 Fan Performance BVE-20 Fan Performance Total Static Pressure (in. wg) 0.20 0.30 0. 0. 0.60 0.70 0.80 0.90 1.00 1.10 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 10 516 0.21 575 0.25 629 0.29 678 0.33 724 0.37 768 0.41 812 0. 856 0. 901 0.54 948 0.58 1600 534 0.24 592 0.29 644 0.33 692 0.37 737 0.41 779 0.46 821 0. 862 0.55 904 0.59 9 0.64 1700 553 0.28 608 0.33 659 0.37 706 0.41 7 0.46 792 0.51 832 0.55 871 0.60 910 0.65 949 0.70 1800 572 0.32 626 0.37 675 0.42 721 0.46 764 0.51 805 0.56 844 0.61 882 0.66 919 0.71 956 0.76 1900 592 0.37 644 0.42 692 0.47 737 0.52 779 0.57 819 0.62 857 0.67 894 0.72 930 0.77 965 0.83 2000 613 0.42 662 0.47 709 0.52 753 0.57 795 0.63 834 0.68 871 0.73 907 0.79 942 0.84 976 0.90 2100 633 0.47 681 0.53 726 0.58 770 0.64 810 0.69 849 0.75 886 0.80 921 0.86 955 0.92 989 0.97 2200 654 0.53 700 0.59 744 0.65 786 0.70 826 0.76 864 0.82 901 0.88 936 0.94 969 0.99 1002 1.05 2300 676 0.60 720 0.66 763 0.72 804 0.78 843 0.84 880 0.90 916 0.96 9 1.02 983 1.08 1015 1.14 20 698 0.67 7 0.73 781 0.79 821 0.85 860 0.92 896 0.98 932 1.04 966 1.11 998 1.17 1030 1.23 20 720 0.74 761 0.81 801 0.87 839 0.94 877 1.00 913 1.07 948 1.13 981 1.20 1013 1.26 1044 1.33 BVE-20 Fan Performance Total Static Pressure (in. wg) 1.20 1.30 1. 1. 1.60 1.70 1.80 1.90 2.00 2.10 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 10 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1600 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1700 988 0.75 1028 0.80 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1800 992 0.81 1029 0.86 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1900 1000 0.88 10 0.93 1069 0.99 1104 1.04 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 2000 1010 0.95 1043 1.01 1076 1.06 1109 1.12 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 2100 1021 1.03 1053 1.09 1085 1.15 1116 1.21 1147 1.27 1179 1.33 1210 1.39 1242 1. ---- ---- ---- ---- 2200 1033 1.11 1064 1.17 1095 1.24 1125 1.30 1155 1.36 1185 1.42 1215 1.48 12 1.55 1275 1.61 1306 1.67 2300 1047 1.20 1077 1.27 1107 1.33 1136 1.39 1165 1.46 1194 1.52 1222 1.59 1251 1.65 1280 1.72 1309 1.78 20 1060 1.30 1090 1.36 1119 1.43 1148 1.49 1176 1.56 1204 1.63 1232 1.69 1259 1.76 1287 1.83 1314 1.90 20 1074 1. 1104 1.47 1132 1.53 1161 1.60 1188 1.67 1215 1.74 1242 1.81 1269 1.88 1295 1.95 ---- ---- BVE 1.0 Page 19 6/12/2008
BV30- Fan Performance BVE-30/ Fan Performance Total Static Pressure (in. wg) 0.20 0.30 0. 0. 0.60 0.70 0.80 0.90 1.00 1.10 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 22 2 0.31 491 0. 526 0.39 560 0.44 593 0.48 625 0.52 655 0.57 685 0.61 715 0.66 744 0.70 20 472 0.36 9 0.41 543 0. 576 0. 607 0.54 638 0.59 667 0.64 696 0.68 724 0.73 752 0.78 25 492 0.42 527 0.47 561 0.52 592 0.56 623 0.61 652 0.66 680 0.71 708 0.76 7 0.81 762 0.86 2700 512 0.49 546 0.54 579 0.59 609 0.64 639 0.69 667 0.74 694 0.79 721 0.85 748 0.90 773 0.95 28 533 0.56 566 0.62 597 0.67 627 0.72 655 0.77 683 0.83 709 0.88 7 0.94 761 0.99 786 1.05 3000 554 0.65 586 0.70 616 0.76 6 0.81 672 0.87 699 0.92 725 0.98 7 1.04 775 1.10 799 1.16 31 575 0.74 606 0.79 6 0.85 663 0.91 690 0.97 716 1.03 741 1.09 765 1.15 789 1.21 813 1.27 3200 583 0.77 613 0.83 642 0.88 669 0.94 696 1.00 721 1.06 746 1.12 771 1.18 794 1.25 818 1.31 3300 597 0.83 626 0.89 655 0.95 682 1.02 708 1.08 733 1.14 758 1.20 781 1.26 805 1.33 828 1.39 30 612 0.90 6 0.97 668 1.03 694 1.09 720 1.15 7 1.22 769 1.28 792 1. 815 1.41 838 1.48 30 619 0.94 647 1.00 674 1.07 701 1.13 726 1.19 751 1.26 775 1.32 798 1.39 821 1. 843 1.52 3600 641 1.06 668 1.12 695 1.19 720 1.26 7 1.32 769 1.39 792 1.46 815 1.52 837 1.59 859 1.66 3600 641 1.06 668 1.12 695 1.19 720 1.26 7 1.32 769 1.39 792 1.46 815 1.52 837 1.59 859 1.66 37 663 1.18 689 1.25 715 1.32 7 1.39 764 1.46 787 1.53 810 1.60 832 1.67 854 1.74 875 1.81 3800 671 1.23 696 1.30 722 1.37 746 1.44 770 1.51 793 1.58 816 1.65 838 1.72 859 1.79 881 1.86 00 700 1.42 725 1.49 749 1.56 773 1.64 796 1.71 819 1.78 8 1.86 862 1.93 883 2.01 903 2.08 4200 731 1.62 754 1.70 778 1.78 800 1.86 823 1.93 844 2.01 866 2.09 886 2.16 907 2.24 926 2.32 40 761 1.85 784 1.93 806 2.01 828 2.09 849 2.17 870 2.25 891 2.34 911 2.42 931 2. 9 2.58 4600 792 2.10 813 2.18 8 2.27 856 2. 877 2.44 897 2.52 917 2.61 936 2.69 956 2.78 974 2.86 4800 822 2.37 843 2.46 864 2.55 884 2.63 904 2.72 924 2.81 943 2.90 962 2.99 981 3.07 999 3.16 00 853 2.66 873 2.75 893 2.85 913 2.94 932 3.03 951 3.12 970 3.21 988 3.31 1007 3. 1024 3.49 BVE-30/ Fan Performance Total Static Pressure (in. wg) 1.20 1.30 1. 1. 1.60 1.70 1.80 1.90 2.00 2.10 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 22 772 0.75 799 0.80 826 0.84 853 0.89 879 0.94 904 0.99 929 1.05 954 1.10 978 1.16 1001 1.22 20 779 0.83 806 0.88 832 0.93 858 0.98 883 1.03 908 1.08 933 1.13 957 1.19 980 1.24 1003 1.30 25 788 0.91 814 0.97 839 1.02 864 1.07 889 1.12 913 1.18 937 1.23 960 1.28 984 1.34 1006 1. 2700 799 1.01 824 1.06 848 1.11 872 1.17 896 1.22 920 1.28 943 1.34 966 1.39 988 1. 1010 1.51 28 810 1.11 834 1.16 858 1.22 881 1.28 904 1.33 927 1.39 9 1. 972 1.51 994 1.57 1016 1.63 3000 823 1.21 846 1.27 869 1.33 892 1.39 914 1. 936 1.51 958 1.57 980 1.63 1001 1.69 1022 1.76 31 836 1.33 859 1.39 881 1. 903 1.52 925 1.58 946 1.64 967 1.70 988 1.77 1009 1.83 1030 1.89 3200 8 1.37 863 1.43 885 1.49 907 1.56 928 1.62 9 1.68 971 1.75 991 1.81 1012 1.88 1032 1.94 3300 8 1. 872 1.52 894 1.58 915 1.65 936 1.71 957 1.78 978 1.84 998 1.91 1018 1.97 1038 2.04 30 860 1.54 881 1.61 903 1.67 924 1.74 944 1.81 965 1.87 985 1.94 1005 2.01 1025 2.08 10 2.14 30 865 1.59 886 1.65 907 1.72 928 1.79 949 1.85 969 1.92 989 1.99 1009 2.06 1028 2.13 1048 2.20 3600 880 1.73 901 1.80 921 1.87 942 1.94 962 2.01 981 2.08 1001 2.15 1020 2.22 10 2.29 1059 2.36 3600 880 1.73 901 1.80 921 1.87 942 1.94 962 2.01 982 2.08 1001 2.15 1020 2.22 10 2.29 1059 2.36 37 896 1.88 916 1.95 936 2.02 956 2.10 976 2.17 995 2.24 1014 2.32 1033 2.39 1052 2.46 1070 2.54 3800 901 1.93 921 2.01 941 2.08 961 2.15 980 2.23 1000 2.30 1018 2.37 1037 2. 1056 2.52 1074 2.60 00 923 2.16 943 2.23 962 2.31 981 2.39 1000 2.46 1019 2.54 1037 2.62 1055 2.69 1073 2.77 1091 2.85 4200 946 2. 965 2.48 984 2.56 1002 2.64 1021 2.72 1039 2.80 1056 2.88 1074 2.96 1091 3.04 1109 3.12 40 969 2.66 988 2.74 1006 2.83 1024 2.91 1042 2.99 1059 3.08 1077 3.16 1094 3.25 1111 3.33 1128 3.42 4600 993 2.95 1011 3.03 1029 3.12 1046 3.20 1064 3.29 1081 3.38 1098 3.47 1115 3.55 1131 3.64 1147 3.73 4800 1017 3.25 10 3.34 1052 3.43 1069 3.52 1086 3.61 1103 3.70 1120 3.79 1136 3.88 1152 3.97 1168 4.07 00 1042 3.58 1059 3.67 1076 3.77 1093 3.86 1110 3.95 1126 4.05 1142 4.14 1158 4.24 1174 4.33 1189 4.43 BVE-30/ Fan Performance Total Static Pressure (in. wg) 2.20 2.30 2. 2. 2.60 2.70 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 22 1025 1.28 1047 1.34 1069 1.41 1091 1.48 1112 1.55 1133 1.62 20 1026 1.36 1049 1.42 1071 1.49 1092 1.55 1113 1.62 1134 1.69 25 1029 1.46 1051 1.52 1072 1.58 1094 1.64 1115 1.71 11 1.77 2700 1032 1.57 1054 1.63 1075 1.69 1096 1.75 1117 1.82 1137 1.88 28 1037 1.69 1058 1.75 1079 1.81 1099 1.87 1120 1.94 11 2.00 3000 1043 1.82 1063 1.88 1084 1.94 1104 2.01 1124 2.07 1144 2.14 31 10 1.96 1070 2.02 1090 2.09 1110 2.15 1129 2.22 1148 2.29 3200 1052 2.01 1072 2.07 1092 2.14 1112 2.20 1131 2.27 11 2.34 3300 1058 2.11 1078 2.17 1097 2.24 1116 2.31 11 2.38 1154 2. 30 1064 2.21 1083 2.28 1102 2. 1121 2.42 11 2.49 1159 2.56 30 1067 2.27 1086 2.33 1105 2. 1124 2.47 1143 2.54 1161 2.62 3600 1077 2.43 1096 2. 1114 2.58 1133 2.65 1151 2.72 1169 2.79 3600 1077 2.43 1096 2. 1114 2.58 1133 2.65 1151 2.72 1169 2.79 37 1088 2.61 1106 2.69 1124 2.76 1142 2.83 1160 2.91 1178 2.99 3800 1092 2.67 1110 2.75 1128 2.82 1146 2.90 1163 2.97 1181 3.05 00 1108 2.93 1126 3.01 1143 3.09 1160 3.17 1177 3.25 1194 3.33 4200 1126 3.21 1143 3.29 1159 3.37 1176 3. 1193 3.54 1209 3.62 40 1144 3. 1161 3.59 1177 3.67 1193 3.76 1209 3.85 1225 3.93 4600 1163 3.82 1180 3.91 1195 4.00 1211 4.09 1227 4.18 1242 4.27 4800 1184 4.16 1199 4.25 1215 4.34 1230 4.44 12 4.53 1261 4.62 00 1204 4.52 1220 4.62 12 4.71 12 4.81 1265 4.91 ---- ---- BVE 1.0 Page 20 6/12/2008
BV-08 Chilled Water Capacity CFM @ 80 F EDB EWT GPM PD (FT) 600 800 1000 AIR ENTERING TEMPERATURE EWB 57 62 67 72 77 57 62 67 72 77 57 62 67 72 77 TC 15.80 16.26 19.23 24.13 29.51 18.70 18.76 21.44 26.26 32.02 21.03 21.06 23.11 27.68 33.71 SHC 15.80 15.64 14.29 12.94 11.47 18.70 18.76 16.89 14.80 12.69 21.03 21.06 19.17 16. 13.57 3.0 1.5 LDB 55.9 56.3 59.0 61.9 65.2 58.6 58.6 61.3 64.4 67.7 60.7 60.8 62.9 66.1 69.5 LWB 46.7 52.5 57.0 60.9 64.9 48.0 53.9 58.8 63.1 67.4 49.0 54.8 60.0 64.6 69.1 BF 0.43 0.22 0.17 0.17 0.00 0. 0.28 0.20 0.19 0.17 0.55 0. 0.24 0.21 0.19 TC 17.91 19.48 25.22 31.96 39. 21.89 22.92 28.90 36.52 44.83 25.30 26.06 31.64 39.90 48.88 SHC 17.91 17.77 16.99 16.18 15.14 21.89 21.57 20.31 18.90 17.29 25.30 25.00 23.17 21.15 19.01 6.1 6.0 LDB 52.6 53.2 55.2 57.5 60.3 54.9 55.5 57.7 60.2 63.2 56.8 57.3 59.6 62.3 65.3 LWB.2.5 53.5 56.6 60.0 46.3 51.9 55.6 59.2 62.9 47.2 52.9 57.2 61.0 65.0 42 BF 0.36 0.17 0.16 0.19 0.00 0.41 0.21 0.18 0.20 0.00 0.46 0.26 0.20 0.21 0.00 TC 18.65 20.91 27.64.12 43. 23.06 24.94 32.39 41.05.57 26.94 28.25 36.11.68 56.17 SHC 18.64 18.56 18.10 17.55 16.72 23.06 22.86 21.86 20.80 19.46 26.93 26.58 25.11 23.52 21.67 9.2 12.9 LDB 51.5 52.0 53.6 55.5 58.1 53.6 54.1 56.1 58.3 61.0 55.3 55.9 58.0 60.3 63.2 LWB 44.6 49.5 52.0 54.8 57.8.6 51.0 54.1 57.3 60.7 46.5 52.1 55.7 59.1 62.9 BF 0.33 0.16 0.16 0.00 0.00 0.38 0.19 0.18 0.22 0.00 0.42 0.23 0.21 0.22 0.00 TC 19.03 21.73 28.96 36.86.57 23.68 26.12 34.38 43.67 53.88 27.83 29.88 38.74 49.12 60.51 SHC 19.03 19.04 18.73 18.33 17.62 23.68 23.52 22.78 21.94 20.74 27.82 27.57 26.30 24.97 23.30 12.3 22.1 LDB.9 51.3 52.7 54.4 56.8 52.9 53.4 55.1 57.1 59.7 54.5 55.0 57.0 59.1 61.8 LWB 44.4 49.0 51.2 53.7 56.6.3.4 53.2 56.2 59.4 46.1 51.5 54.7 58.0 61.6 BF 0.32 0.15 0.16 0.00 0.00 0.36 0.18 0.18 0.24 0.00 0. 0.21 0.21 0.23 0.00 TC 14.61 14.65 17.30 21.95 27.28 17.30 17.33 19.33 23.84 29.54 19.47 19. 20.88 25.10 31.05 SHC 14.61 14.65 13.42 12.08 10.67 17.30 17.33 15.96 13.88 11.79 19.47 19. 18.12 15.43 12.63 3.0 1.5 LDB 57.7 57.7 60.2 63.1 66.2 60.2 60.2 62.2 65.3 68.6 62.2 62.2 63.8 66.8 70.2 LWB 47.6 53.5 58.1 62.0 66.0 48.7 54.6 59.6 64.0 68.3 49.6 55.3 60.7 65.3 69.8 BF 0.48 0.25 0.17 0.16 0.00 0.54 0.33 0.21 0.19 0.18 0.58 0. 0.25 0.21 0.20 TC 16.53 17.21 22.51 29.19 36. 20.22 20. 25.73 33.27 41.49 23.37 23. 28.17 36.29.16 SHC 16.53 16.48 15.79 15.00 14.05 20.22 20.42 18.95 17.57 16.07 23.37 23. 21.66 19.70 17.68 6.1 6.0 LDB 54.7 55.0 56.9 59.1 61.7 56.8 56.7 59.1 61.6 64.4 58.6 58.6 60.8 63.5 66.3 LWB 46.2 51.9 55.1 58.2 61.5 47.2 53.1 57.0 60.4 64.2 48.0 53.9 58.3 62.1 66.1 BF 0.41 0.19 0.15 0.18 0.00 0.46 0.21 0.18 0.19 0.00 0. 0.28 0.21 0.21 0.00 TC 17.20 18.30 24.74 32.15.32 21.29 22.04 28.92 37. 46.94 24.87 25.12 32.19 41.66 52.04 SHC 17.20 17.26 16.79 16.25 15.52 21.28 21.21 20.33 19.30 18.09 24.86 25.12 23.42 21.85 20.16 9.2 12.9 LDB 53.7 53.9 55.5 57.3 59.7 55.6 55.9 57.7 59.8 62.4 57.2 57.1 59.4 61.7 64.4 LWB.7 51.2 53.8 56.5 59.5 46.6 52.4 55.6 58.8 62.1 47.3 53.3 57.0 60.4 64.1 BF 0.38 0.16 0.15 0.20 0.00 0.43 0.21 0.18 0.20 0.00 0.47 0.23 0.20 0.22 0.00 TC 17.55 19.02 25.95 33.80 42. 21.85 22.89 30.75 39.95.09 25.68 26.48 34.59 44.87 56.16 SHC 17.55 17.67 17. 16.97 16.37 21.85 21.83 21.15 20.33 19.28 25.68 25.61 24.48 23.17 21.67 12.3 22.1 LDB 53.2 53.3 54.7 56.3 58.6 55.0 55.2 56.8 58.8 61.2 56.5 56.7 58.5 60.6 63.2 LWB.4.8 53.1 55.6 58.3 46.3 51.9 54.8 57.7 60.9 47.0 52.8 56.2 59.4 62.9 BF 0.37 0.15 0.15 0.22 0.00 0.41 0.19 0.18 0.21 0.00 0. 0.23 0.20 0.22 0.00 TC 13.42 13.44 15.36 19.71 24.97 15.89 15.92 17.18 21.36 27.00 17.89 17.91 18.80 22.48 28. SHC 13.42 13.44 12.57 11.21 9.86 15.89 15.92 14.97 12.94 10.88 17.89 17.91 16.98 14.43 11.69 3.0 1.5 LDB 59.5 59.6 61.3 64.2 67.3 61.8 61.9 63.2 66.2 69.5 63.6 63.7 64.7 67.6 70.9 LWB 48.4 54.3 59.2 63.1 67.0 49.4 55.2 60.5 64.9 69.1.2 55.9 61.3 66.1 70.5 BF 0.52 0.31 0.18 0.16 0.18 0.57 0.39 0.22 0.19 0.18 0.62 0. 0.27 0.21 0.20 TC 15.15 15.19 19.71 26.32 33.56 18.53 18.57 22.46 29.93 38.06 21.43 21.47 24.85 32.59 41. SHC 15.15 15.19 14.60 13.82 12.95 18.53 18.57 17.52 16.23 14.84 21.43 21.47 20.17 18.25 16.28 6.1 6.0 LDB 56.9 56.9 58.5 60.7 63.2 58.8 58.8 60.6 63.0 65.6 60.4 60.4 62.0 64.6 67.4 LWB 47.2 53.2 56.8 59.7 63.0 48.1 54.0 58.4 61.7 65.4 48.8 54.6 59.4 63.2 67.1 48 BF 0.46 0.22 0.15 0.17 0.00 0. 0.28 0.18 0.19 0.00 0.54 0.34 0.22 0.21 0.23 TC 15.75 15.87 21.71 29.07 37.17 19. 19.54 25.34 33.83 43.17 22.79 22.83 28.08 37.52 47.79 SHC 15.75 15.87 15.47 14.95 14.31 19.49 19.54 18.80 17.79 16.69 22.78 22.83 21.70 20.18 18.63 9.2 12.9 LDB 55.9 55.9 57.3 59.2 61.4 57.7 57.7 59.2 61.4 63.8 59.1 59.2 60.8 63.1 65.6 LWB 46.8 52.8 55.6 58.2 61.1 47.6 53.5 57.2 60.2 63.6 48.2 54.1 58.4 61.7 65.3 BF 0.44 0.19 0.15 0.18 0.00 0.48 0.25 0.18 0.20 0.00 0.51 0.30 0.20 0.21 0.00 TC 16.07 16.31 22.81 30.60 39.20 20.01 20.06 26.97 36.10 46.15 23.52 23.58 30.28.48 51.65 SHC 16.07 16.29 15.97 15.60 15.10 20.01 20.06 19.52 18.72 17.80 23.52 23.58 22.65 21.37 20.02 12.3 22.1 LDB 55.5 55.2 56.6 58.3 60.3 57.1 57.1 58.5 60.4 62.7 58.4 58.5 60.0 62.1 64.5 LWB 46.5 52.5 55.0 57.4 60.1 47.3 53.3 56.5 59.3 62.4 47.9 53.8 57.6 60.8 64.2 BF 0.42 0.16 0.15 0.18 0.00 0.46 0.23 0.18 0.20 0.00 0.49 0.27 0.20 0.22 0.00 NOTES: 1. SHC is based on 80 F EDB of air entering coil. Use the following formulas BF - Bypass Factor to correct SHC based on other EDB. EDB - Entering Dry-Bulb Correction Fabor = 1.10 x (1-BF) x (EDB - 80) EWB - Entering Wet-Bulb SHC (New) = (Correction Factor x CFM/1000) + SHC (MBH) (from Tables above) EWT - Entering Water Temp LDB = EDB - SHC (MBH) /1.10/CFM x 1000 LDB - Leaving Dry-Bulb LWB - Leaving Wet-Bulb 2. Direct interpolation is permissible. Do not extrapolate. PD - Water Pressure Drop (ft) SHC - Sensible Capacity (MBH) TC - Total Capacity (MBH) BVE 1.0 Page 21 6/12/2008
BV-12 Chilled Water Capacity CFM @ 80 F EDB EWT GPM PD (FT) 900 1200 10 AIR ENTERING TEMPERATURE EWB 57 62 67 72 77 57 62 67 72 77 57 62 67 72 77 42 48 3.0 1.1 8.2 7.8 13.4 19.7 18.6 36.6 3.0 1.1 8.2 7.8 13.4 19.7 18.6 36.6 3.0 1.1 8.2 7.8 13.4 19.7 18.6 36.6 TC 21.57 21.85 23.89 28.36 34.53 24.82 24.85 26.34 30.19 36.38 27.23 27.26 28.14 31.55 37.55 SHC 21.57 21.24 19.15 16.39 13.74 24.82 24.85 22.53 18.76 14.94 27.23 27.26 25.34 20.87 15.92 LDB 58.0 58.5 61.1 64.6 68.2 61.0 61.1 63.2 66.7 70.3 63.4 63.4 64.8 68.0 71.7 LWB 47.7 54.1 58.9 63.5 67.9 49.1 54.8 60.3 65.3 70.0.1 55.8 61.3 66.5 71.3 BF 0.49 0.27 0.18 0.16 0.17 0.56 0.37 0.23 0.18 0.16 0.61 0.44 0.28 0.21 0.18 TC 27.29 29.18 36.95 46.67 57.29 33.18 34.36 41.80 52.67 64.49 38.05 38.88.64 56.97 69.62 SHC 27.29 26.66 25.12 23.70 21.98 33.18 32.49 29.90 27.51 24.85 38.05 37.41 34.08 30.67 27.11 LDB 52.2 53.2 55.5 58.0 60.9 54.7 55.4 58.1 60.8 63.9 56.7 57.3 59.9 62.8 66.0 LWB.0.5 53.9 57.1 60.6 46.1 51.9 56.1 59.7 63.6 47.1 53.0 57.6 61.6 65.7 BF 0. 0.16 0.15 0.19 0.00 0.41 0.21 0.17 0.19 0.00 0.46 0.26 0.20 0.20 0.00 TC 28.76 31.87 41.64 52.81 65.08.54 37.92 48.51 61.38 75. 41.32 43.10 53.80 67.89 83.31 SHC 28.75 28.27 27.29 26. 25.04.51 34.74 32.90 31.13 28.96 41.29.51 37.72.08 32.07 LDB.7 51.6 53.5 55.5 58.1 52.9 53.8 56.0 58.3 61.2 54.8 55.5 57.9 60.4 63.4 LWB 44.2 49.3 52.0 54.7 57.8.3.8 54.1 57.3 60.8 46.2 51.9 55.7 59.3 63.1 BF 0.31 0.14 0.15 0.00 0.00 0.37 0.18 0.17 0.22 0.00 0.41 0.21 0.19 0.22 0.00 TC 29.44 33. 44.02 55.93 69.03 36.66.01 52.08 66.02 81.30 42.92.63 58.43 73.94 90.92 SHC 29.44 29.08 28.42 27.74 26.64 36.65 36.00 34.53 33.12 31.22 42.91 42.08 39.81 37.60 34.91 LDB.0.8 52.4 54.2 56.6 52.0 52.8 54.8 56.9 59.6 53.8 54.6 56.7 59.1 61.9 LWB 43.9 48.6 51.0 53.5 56.3 44.9.1 53.0 56.0 59.3.7 51.3 54.6 57.9 61.5 BF 0.30 0.14 0.15 0.00 0.00 0.34 0.17 0.17 0.25 0.00 0.39 0.20 0.19 0.23 0.00 TC 19.98 20.01 21.72 25.77 31.81 22.99 23.02 23.97 27.54 33.47 25.22 25.26 25.86 28.76 34.51 SHC 19.98 20.01 18.14 15.39 12.79 22.99 23.02 21.39 17.74 13.94 25.22 25.25 23.90 19.81 14.90 LDB 59.7 59.7 62.0 65.5 69.0 62.4 62.5 64.0 67.3 71.0 64.6 64.6 65.7 68.6 72.2 LWB 48.5 54.3 59.6 64.3 68.7 49.7 55.5 61.0 65.9 70.6.7 56.3 61.8 67.0 71.7 BF 0.52 0.31 0.19 0.16 0.16 0.59 0.41 0.24 0.19 0.17 0.64 0.48 0.30 0.21 0.18 TC 25.19 25.98 32.94 42.57 53.08 30.64 31.15 37. 47.93 59.61.15.22.95 51.76 64.25 SHC 25.19 24.92 23.38 21.99 20.39 30.64 30.41 27.97 25.60 23.08.15.22 32.04 28.62 25.22 LDB 54.3 54.8 57.1 59.6 62.4 56.6 56.9 59.4 62.1 65.1 58.5 58.6 61.0 63.9 67.0 LWB 46.0 51.8 55.5 58.6 62.1 47.1 53.0 57.3 61.0 64.8 47.9 53.9 58.6 62.6 66.7 BF 0. 0.18 0.15 0.18 0.00 0. 0.24 0.18 0.19 0.00 0. 0.28 0.20 0.20 0.00 TC 26.54 28.05 37.25 48.33 60.49 32.80 33.74 43.29 56.04 69.98 38.15 38.80 47.88 61.88 77.14 SHC 26.53 26.31 25.33 24.41 23.23 32.78 32.48 30.63 28.89 26.89 38.13 37.85.23 32.62 29.81 LDB 53.0 53.5 55.3 57.3 59.8 55.0 55.4 57.6 59.9 62.6 56.7 57.0 59.3 61.8 64.6 LWB.3 51.0 53.8 56.5 59.5 46.3 52.1 55.7 58.8 62.2 47.1 53.0 57.1 60.5 64.3 BF 0.37 0.15 0.15 0.20 0.00 0.41 0.19 0.17 0.20 0.00 0. 0.24 0.19 0.21 0.00 TC 27.16 29.12 39.43 51.26 64.28 33.82.36 46.55 60.38 75.54 39.62.58 52.15 67.52 84.34 SHC 27.15 26.98 26.34 25.68 24.74 33.82 33.56 32.08 30.71 29.01 39.61 39.30 37.09 34.92 32.46 LDB 52.3 52.8 54.4 56.1 58.4 54.2 54.6 56.5 58.6 61.1 55.8 56.2 58.2 60.5 63.2 LWB.0.5 52.9 55.3 58.1.9 51.6 54.7 57.6 60.8 46.7 52.5 56.1 59.3 62.9 BF 0. 0.14 0.15 0.24 0.00 0.39 0.18 0.17 0.21 0.00 0.43 0.22 0.19 0.22 0.00 TC 18.36 18.39 19. 23.20 29.04 21.13 21.16 21.78 24.83 30.51 23.19 23.22 23.56 25.95 31.43 SHC 18.36 18.39 17.13 14.41 11.83 21.13 21.16 20.08 16.71 12.93 23.19 23.22 22.44 18.72 13.86 LDB 61.3 61.4 62.9 66.3 69.8 63.9 63.9 64.9 68.0 71.6 65.8 65.9 66.5 69.1 72.7 LWB 49.2 55.0 60.4 65.1 69.5.3 56.0 61.5 66.5 71.2 51.2 56.8 62.3 67.5 72.2 BF 0.56 0.37 0.20 0.16 0.16 0.62 0.46 0.27 0.19 0.17 0.67 0.52 0.33 0.22 0.18 TC 23.08 23.15 28.83 38.34 48.74 28.09 28.16 33.03 43.07 54.61 32.24 32.30 36.18 46.43 58.77 SHC 23.09 23.15 21.61 20.27 18.78 28.09 28.16 26.09 23.69 21.30 32.24 32.30 29.98 26.54 23.25 LDB 56.5 56.5 58.8 61.1 63.8 58.5 58.6 60.7 63.4 66.3 60.3 60.4 62.2 65.1 68.0 LWB 47.0 53.0 57.0 60.1 63.5 48.0 53.9 58.5 62.2 66.0 48.8 54.6 59.6 63.7 67.7 BF 0. 0.21 0.15 0.17 0.00 0. 0.28 0.18 0.18 0.00 0.54 0.34 0.21 0.20 0.22 TC 24.30 24.46 32.68 43.68 55.74 30.05 30.10 37.86.52 64.32 34.97.02 42.03 55.69 70.79 SHC 24.29 24.46 23. 22.46 21.41 30.04 30.10 28.33 26.65 24.81 34.95.02 32.70 30.16 27.54 LDB 55.3 55.2 57.2 59.1 61.4 57.1 57.1 59.1 61.4 64.0 58.6 58.7 60.7 63.1 65.8 LWB 46.4 52.5 55.6 58.2 61.1 47.3 53.3 57.2 60.3 63.7 48.0 53.9 58.4 61.8 65.5 BF 0.42 0.16 0.14 0.18 0.00 0.46 0.23 0.17 0.19 0.00 0. 0.28 0.19 0.20 0.00 TC 24.86 25.36 34.66 46.41 59.33 30.98 31.06.82 54.54 69.57 36.30 36.37.66 60.89 77.54 SHC 24.86 24.91 24.25 23.62 22.80 30.97 31.06 29.63 28.29 26.76 36.29 36.37 34. 32.23 29.98 LDB 54.7 54.8 56.3 58.1 60.2 56.3 56.4 58.2 60.3 62.6 57.8 57.9 59.8 62.0 64.5 LWB 46.2 52.1 54.8 57.2 59.9 46.9 53.0 56.4 59.2 62.4 47.6 53.6 57.6 60.8 64.2 BF 0.41 0.16 0.14 0.19 0.00 0. 0.20 0.16 0.19 0.00 0.48 0.25 0.18 0.21 0.00 NOTES: 1. SHC is based on 80 F EDB of air entering coil. Use the following formulas BF - Bypass Factor to correct SHC based on other EDB. EDB - Entering Dry-Bulb Correction Fabor = 1.10 x (1-BF) x (EDB - 80) EWB - Entering Wet-Bulb SHC (New) = (Correction Factor x CFM/1000) + SHC (MBH) (from Tables above) EWT - Entering Water Temp LDB = EDB - SHC (MBH) /1.10/CFM x 1000 LDB - Leaving Dry-Bulb LWB - Leaving Wet-Bulb 2. Direct interpolation is permissible. Do not extrapolate. PD - Water Pressure Drop (ft) SHC - Sensible Capacity (MBH) TC - Total Capacity (MBH) BVE 1.0 Page 22 6/12/2008
BV-16 Chilled Water Capacity CFM @ 80 F EDB EWT GPM PD (FT) 1200 1600 2000 AIR ENTERING TEMPERATURE EWB 57 62 67 72 77 57 62 67 72 77 57 62 67 72 77 42 48 4.1 1.7 8.7 7.5 13.4 17.0 18.0 30.0 4.1 1.7 8.7 7.5 13.4 17.0 18.0 30.0 4.1 1.7 8.7 7.5 13.4 17.0 18.0 30.0 TC 28. 28.57 32.09 38.76 47.18 32.94 32.99.38 41.27 49.96 36.29 36.33 37.90 43.13 51.74 SHC 28. 28.58 25.62 22.21 18.79 32.94 32.99 30.07 25.31 20.42 36.28 36.33 33.76 28.02 21.73 LDB 58.2 58.3 61.0 64.4 67.9 61.1 61.2 63.2 66.5 70.1 63.4 63.4 64.8 68.0 71.5 LWB 47.8 53.8 58.8 63.3 67.6 49.1 54.9 60.3 65.1 69.7.1 55.8 61.3 66.3 71.1 BF 0.49 0.27 0.18 0.16 0.14 0.56 0.36 0.24 0.19 0.16 0.61 0.44 0.28 0.22 0.19 TC 34.11.85 44.76 56.58 69.44 41.09 42.09.30 63.16 77.27 46.78 47.00 54.67 67.81 82.77 SHC 34.11 33.60 31.43 29.29 26.80 41.09.52 37.25 33.81 30.14 46.78 47.00 42.31 37.55 32.71 LDB 53.9 54.6 57.0 59.6 62.6 56.5 57.0 59.4 62.3 65.4 58.6 58.6 61.2 64.2 67.3 LWB.8 51.5 55.2 58.7 62.4 47.0 52.8 57.2 61.1 65.2 48.0 53.9 58.6 62.8 67.1 BF 0.39 0.19 0.16 0.17 0.00 0. 0.25 0.19 0.19 0.00 0. 0.28 0.22 0.21 0.17 TC.99 38.89.54 64.06 78.95 44.02 46.10 58.07 73.41 90.22.78 52.08 63.65 80.38 98.57 SHC.98.48 34.02 32. 30.42 44.00 43.38.69 37.99 34.86.75.11 46.43 42.54 38.39 LDB 52.5 53.2 55.2 57.4 60.2 54.8 55.4 57.7 60.1 63.1 56.7 57.2 59.5 62.2 65.1 LWB.1.5 53.5 56.6 59.9 46.2 51.9 55.6 59.1 62.8 47.1 52.9 57.1 60.9 64.9 BF 0.36 0.17 0.16 0.19 0.00 0.41 0.21 0.19 0.20 0.00 0.46 0.25 0.21 0.21 0.00 TC 36.96.89 53.72 68.26 84.27.57 48.58 62.66 79.43 97.83 52.94 55.16 69.57 88.03 108.22 SHC 36.95 36.64.49 34.28 32.51.57 44.90 42.75.51 37.72 52.93 52.25 49.01.67 41.90 LDB 51.8 52.4 54.1 56.1 58.7 53.9 54.5 56.6 58.8 61.6 55.7 56.3 58.5 60.9 63.7 LWB 44.8 49.8 52.5 55.4 58.5.8 51.3 54.6 57.8 61.4 46.7 52.3 56.1 59.7 63.5 BF 0.34 0.16 0.16 0.21 0.00 0.39 0.20 0.18 0.20 0.00 0.43 0.23 0.21 0.22 0.00 TC 26.38 26.43 29.02.18 43.48 30. 30.54 32.17 37.53.97 33.59 33.63 34.63 39.30 47.57 SHC 26.38 26.42 24.19 20.83 17.47 30. 30.54 28.48 23.87 19.03 33.59 33.63 31.90 26.54 20.30 LDB 59.9 59.9 62.0 65.3 68.7 62.5 62.6 64.0 67.2 70.8 64.6 64.7 65.6 68.6 72.1 LWB 48.6 54.4 59.6 64.1 68.4 49.8 55.5 60.9 65.8 70.4.7 56.3 61.8 66.8 71.6 BF 0.53 0.32 0.19 0.16 0.14 0.59 0.41 0.25 0.19 0.17 0.64 0.48 0.31 0.23 0.20 TC 31.49 32.17 39.85 51.54 64.25 37.95 38.05.03 57.39 71.34 43.22 43.29 49.03 61.53 76.30 SHC 31.49 31.34 29.28 27.22 24.88 37.95 38.05 34.92 31. 28.02 43.22 43.29 39.81.08 30.33 LDB 55.9 56.2 58.5 61.0 63.9 58.3 58.3 60.7 63.4 66.4 60.2 60.3 62.3 65.2 68.3 LWB 46.8 52.6 56.6 60.0 63.7 47.8 53.8 58.3 62.2 66.2 48.7 54.6 59.5 63.7 67.9 BF 0.44 0.21 0.16 0.17 0.00 0.49 0.27 0.19 0.19 0.20 0.54 0.33 0.23 0.21 0.19 TC 33.21 34.47.12 58.52 73.26.64 41.37 51.66 66.91 83.53 46.89 47.02 56.73 73.14 91.12 SHC 33.20 33.09 31.62 30.09 28.25.62. 37.94.30 32. 46.86 47.02 43.42 39.62.72 LDB 54.6 54.9 56.8 59.0 61.6 56.7 57.0 59.1 61.5 64.3 58.5 58.6 60.8 63.4 66.2 LWB 46.1 51.9 55.1 58.1 61.4 47.1 53.0 57.0 60.4 64.1 47.9 53.9 58.3 62.0 65.9 BF 0.41 0.18 0.16 0.18 0.00 0.46 0.24 0.18 0.19 0.00 0. 0.28 0.21 0.21 0.00 TC 34.10.94 48.03 62.46 78.34 42.06 43.14 55.90 72.52 90.75 48.87 49.19 61.97 80.24 100.22 SHC 34.09 34.03 32.93 31.75 30.20 42.05 41.86 39.79 37.60.06 48.86 49.19.74 42.46 39.00 LDB 54.0 54.2 55.9 57.9 60.3 55.9 56.2 58.1 60.3 63.0 57.6 57.6 59.8 62.2 64.9 LWB.8 51.4 54.3 57.0 60.1 46.7 52.6 56.1 59.3 62.7 47.5 53.5 57.4 60.9 64.7 BF 0.39 0.17 0.15 0.18 0.00 0.44 0.22 0.18 0.20 0.00 0.48 0.24 0.21 0.22 0.00 TC 24.23 24.27 26.01 31.55 39.71 28.02 28.06 29.03 33.79 41.91 30.87 30.90 31.47.43 43.33 SHC 24.23 24.27 22.76 19.43 16.13 28.02 28.06 26.75 22.43 17.63 30.87 30.90 29.90 25.03 18.87 LDB 61.5 61.6 63.0 66.2 69.6 63.9 64.0 64.9 67.9 71.4 65.9 65.9 66.5 69.1 72.6 LWB 49.3 55.1 60.4 65.0 69.3.4 56.1 61.5 66.4 71.0 51.2 56.8 62.3 67.4 72.1 BF 0.57 0.38 0.21 0.16 0.15 0.62 0.46 0.27 0.20 0.17 0.67 0.52 0.33 0.23 0.20 TC 28.86 28.93.02 46.34 58.89 34.79 34.86 39.74 51. 65.26 39.63 39.70 43. 55.12 69.70 SHC 28.86 28.93 27.18 25.13 22.94 34.79 34.86 32.60 29.20 25.81 39.63 39.70 37.26 32.64 27.93 LDB 58.0 58.0 59.9 62.4 65.2 60.1 60.1 61.8 64.6 67.5 61.8 61.9 63.3 66.2 69.2 LWB 47.7 53.6 58.0 61.4 65.0 48.7 54.5 59.4 63.3 67.2 49.4 55.2 60.4 64.6 68.8 BF 0.48 0.26 0.16 0.16 0.00 0.53 0.33 0.20 0.19 0.18 0.57 0.39 0.24 0.21 0.20 TC 30.42 30.49 39. 52.79 67.37 37.24 37.33.24 60.20 76.64 42.97 43.07 49.96 65.69 83.47 SHC 30.41 30.49 29.20 27.71 26.04 37.22 37.31.17 32.59 29.92 42.95 43.04. 36.67 32.89 LDB 56.8 56.8 58.5 60.7 63.1 58.7 58.7 60.5 62.9 65.5 60.3 60.4 62.0 64.6 67.3 LWB 47.1 53.1 56.7 59.7 62.9 48.0 53.9 58.3 61.7 65.3 48.8 54.6 59.4 63.1 67.0 BF 0.46 0.22 0.15 0.17 0.00 0. 0.28 0.18 0.19 0.00 0.54 0.34 0.22 0.21 0.21 TC 31.22 0.00 42.13 56.44 72.18 38.52 38.61 48.90 65.38 83.42 44.77 44.88 54.20 72.22 91.99 SHC 31.22 0.00 30.37 29.22 27.85 38.52 38.61 36.81 34.67 32.38 44.77 44.87 42.42 39.24 36.03 LDB 56.2 57.7 59.6 61.9 57.9 58.0 59.7 61.8 64.3 59.5 59.5 61.2 63.5 66.1 LWB 46.9 56.0 58.7 61.7 47.7 53.6 57.5 60.7 64.1 48.4 54.3 58.7 62.1 65.8 BF 0.44 0.00 0.15 0.17 0.00 0.48 0.26 0.18 0.19 0.00 0.52 0.31 0.21 0.21 0.00 NOTES: 1. SHC is based on 80 F EDB of air entering coil. Use the following formulas BF - Bypass Factor to correct SHC based on other EDB. EDB - Entering Dry-Bulb Correction Fabor = 1.10 x (1-BF) x (EDB - 80) EWB - Entering Wet-Bulb SHC (New) = (Correction Factor x CFM/1000) + SHC (MBH) (from Tables above) EWT - Entering Water Temp LDB = EDB - SHC (MBH) /1.10/CFM x 1000 LDB - Leaving Dry-Bulb LWB - Leaving Wet-Bulb 2. Direct interpolation is permissible. Do not extrapolate. PD - Water Pressure Drop (ft) SHC - Sensible Capacity (MBH) TC - Total Capacity (MBH) BVE 1.0 Page 23 6/12/2008