Effect of Atmospheric Pressure on Wet Bulb Depression

Similar documents
Non-Reacting Gas Mixtures. Introduction. P-V-T Relationships for Ideal Gas Mixtures. Amagat Model (law of additive volumes)

Principles of Food and Bioprocess Engineering (FS 231) Solutions to Example Problems on Psychrometrics

Lab 8. Lab-tray dryer

Greenhouse Steady State Energy Balance Model

Introduction. Lecture 6: Water in Atmosphere. How Much Heat Is Brought Upward By Water Vapor?

Subject: Principles of Refrigeration and Air Conditioning Lecturer: Assistant Professor Dr. Waheed Shaty Mohammed

R13 SET - 1 '' ''' '' ' '''' Code No RT21033

Applied Thermodynamics for Marine Systems Prof. P. K. Das Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Preparation of psychrometric charts for water vapour in Martian atmosphere

Measuring State Parameters of the Atmosphere

7. The weather instrument below can be used to determine relative humidity.

Soil Water Content & Soil Water Potential

Section 2 of 6 Applied Psychrometrics

Evapotranspiration. Rabi H. Mohtar ABE 325

Water-Temperature-Dependent Wet Bulb Temperature Calculation

Radiation, Sensible Heat Flux and Evapotranspiration

The calibration of Hygrometer (LectureandTraining )

Measuring State Parameters of the Atmosphere

Many short reports are inadequate and need more work

ln P s T and P s T where R 22,105, D A 27, E B 97.

Lecture Ch. 6. Condensed (Liquid) Water. Cloud in a Jar Demonstration. How does saturation occur? Saturation of Moist Air. Saturation of Moist Air

CAE 331/513 Building Science Fall 2015

Thermodynamics Introduction and Basic Concepts

MAHALAKSHMI ENGINEERING COLLEGE

ME6301- ENGINEERING THERMODYNAMICS UNIT I BASIC CONCEPT AND FIRST LAW PART-A

V i = component volume of component i. T282. c Dr. Md. Zahurul Haq (BUET) Gas Mixture ME 203 (2017) 6 / 22. Moist Air T284

R13. II B. Tech I Semester Regular Examinations, Jan THERMODYNAMICS (Com. to ME, AE, AME) PART- A

DEPARTMENT OF MECHANICAL ENGINEERING ME6301-ENGINEERING THERMODYNAMICS

MARIA COLLEGE OF ENGINEERING AND TECHNOLOGY

Preparation of Psychrometric Charts for Alcohol Vapours in Nitrogen

WATER IN THE ATMOSPHERE

PNEUMATIC ENTHALPY COMPARATOR

UBMCC11 - THERMODYNAMICS. B.E (Marine Engineering) B 16 BASIC CONCEPTS AND FIRST LAW PART- A

International Standard

1/2/2016 WEATHER DEFINITION

Welcome. Vaisala Industrial Measure Webinar Series - Humidity Theory, Terms & Definitions. Yumi Alanoly Vaisala Application Engineer

Temp 54 Dew Point 41 Relative Humidity 63%

Atmospheric Composition הרכב האטמוספירה

of Nebraska - Lincoln. Follow this and additional works at:

Exam 1 (Chaps. 1-6 of the notes)

CAE 331/513 Building Science Fall 2017

ME 2202 ENGINEERING THERMODYNAMICS TWO MARKS QUESTIONS AND ANSWERS UNIT I BASIC CONCEPTS AND FIRST LAW

Vantage Pro Technical Reference

Weather is the state or condition of the atmosphere at a given location for a brief time period.

Theory. Humidity h of an air-vapor mixture is defined as the mass ratio of water vapor and dry air,

Measurement of selected microclimatic factors

D501 and D501-RS. Microscanner D-Series IR Thermometers. no effect. no effect. no effect. no effect no effect

Simultaneous heat and mass transfer studies in drying ammonium chloride in a batch-fluidized bed dryer

Module 11: Meteorology Topic 3 Content: Weather Instruments Notes

Psychrometer construction for performance testing in. temperature and humidity chambers, and the precision

Weather, Atmosphere and Meteorology

2.0 KEY EQUATIONS. Evaporator Net Refrigeration Effect. Compressor Work. Net Condenser Effect

Measurement of selected microclimatic factors

Review: Saturation vapor pressure

Topic 1 The Atmosphere and Atmospheric Variables

Level 7 Post Graduate Diploma in Engineering Heat and mass transfer

Dew Point and Cloud Formation

Chapter 4 Water Vapor

4 WATER VAPOR. Contents 4.1. VAPOR PRESSURE AT SATURATION

1. Water Vapor in Air

TM360 TEMP-SEEKER PRECISION THERMO-PSYCHROMETER OPERATION MANUAL

Reference data. CIBSE Guide C

10 minutes reading time is allowed for this paper.

Chapter 1 Introduction and Basic Concepts

SEM-2017(03HI MECHANICAL ENGINEERING. Paper II. Please read each of the following instructions carefully before attempting questions.

Relative Humidity and Dew Point Lab

Module 2. Measurement Systems. Version 2 EE IIT, Kharagpur 1

1. Base your answer to the following question on the weather map below, which shows a weather system that is affecting part of the United States.

How to use the MMU-EGS Meteorological field instruments

8.3 DESIGN OF A SINGLE-EFFECT EVAPORATOR

REALIZATION OF HUMIDITY STANDARD FACILITY USING TWO-PRESSURE HUMIDITY GENERATOR AND HUMIDITY CHAMBER

New Methods for Measuring Water Desorption and Vapour Permeation Rates in Membranes

AE 205 Materials and Energy Balances Asst. Prof. Dr. Tippabust Eksangsri. Chapter 6 Energy Balances on Chemical Processes

GEF2200 atmospheric physics 2018

Thermal Energy Final Exam Fall 2002

Content. Climate Parameters used for the measurement and recording of weather phenomena The Psychrometric Chart

Business. Business. Multiphase Systems Ch. 6. P vs T Diagram: Water (pure component) P vs T Diagram: CO 2 LYNN ORR

Chapter 5 - Atmospheric Moisture

Water in the Atmosphere

Simulation of Heat and Mass Transfer in the Corrugated Packing of the Counter Flow Cooling Tower

Observing Weather: Making the Invisible Visible. Dr. Michael J. Passow

MICHELL TECHNOLOGIES FOR MOISTURE. Calibration. General Principles & Theory, Equipment Considerations

III A-PROPATH: Moist Air

Name Class Date. 3. In what part of the water cycle do clouds form? a. precipitation b. evaporation c. condensation d. runoff

Understanding uncertainties associated with the 5128A RHapid-Cal Humidity Generator

Cold and freeze protection of blueberries in Florida. Dr. Dorota Z. Haman Agricultural and Biological Dept. University of Florida

Lecture 3: DESIGN CONSIDERATION OF DRIERS

HydroUmcal Interactions Between Atmosphere, Soil and Vernation (Proceedings of the Vienna Symposium, August 1991). IAHS Publ. no. 204,1991.

WEATHER. Review Note Cards

Solar Flat Plate Thermal Collector

COOLING TOWER MODEL IN MNR

This paper was presented at PACE 2007 in Dallas. It compares a traditional sling psychrometer with electronic gauges.

Understanding the uncertainties associated with using the 5128A RHapid Cal portable humidity generator

Evaluation of Vaisala HMP45D Humidity Probes

A comparison of globe, wet and dry temperature and humidity measuring devices available for heat stress assessment

UNIT 12: THE HYDROLOGIC CYCLE

Measuring soil respiration in the field different chamber designs

THM80X Series Feature Application. Temperature & Humidity / Flow Measuring Specialist

CHEMISTRY Topic #2: Thermochemistry and Electrochemistry What Makes Reactions Go? Fall 2018 Dr. Susan Findlay See Exercises in Topic 8

EVAPORATION GEOG 405. Tom Giambelluca

Transcription:

Effect of Atmospheric Pressure on Wet Bulb Depression Raymond M. Wheeler, Michael A. Stasiak, Jamie Lawson, Cara Ann P. Wehkamp, and Michael A. Dixon NASA Biological Sciences Office Kennedy Space Center, Florida, USA Department of Environmental Biology University of Guelph Guelph, Ontario, Canada

Reduced Pressures for Space Missions? Reduced gas leakage and hence reduced resupply costs Reduced structural mass Increased potential for finding transparent materials for space greenhouses Rapid egress for EVAs (spacewalks) without prolonged prebreathing and acclimation ------------------- How do environmental sensors perform at reduced pressures?

Effect of Pressure on Saturation Vapour Pressure (Rygalov et al., 2004, NASA Ken Space Center, FL) Saturation Pressure (kpa) 5 4 3 2 1 0 30 C 25 C 15 C 0 20 40 60 80 100 120 Total Pressure (kpa) Steam table values for e s : 30ºC = 4.24 kpa; 25ºC = 3.17 kpa; 15ºC = 1.70 kpa (Kennan, Keyes, et al., 1978)

Different Equations for Calculating Saturation Water Vapour Pressures Goff-Gratch (1946) / and Smithsonian Tables (1984) Log 10 p w = -7.90298 (373.16/T-1) + 5.02808 Log 10 (373.16/T) - 1.3816 10-7 (10 11.344 (1-T/373.16) -1) + 8.1328 10-3 (10-3.49149 (373.16/T-1) -1) + Log 10 (1013.246) with T in [K] and p w in [hpa] Hyland and Wexler (1983) Log p w = -0.58002206 10 4 / T + 0.13914993 10 1-0.48640239 10-1 T + 0.41764768 10-4 T 2-0.14452093 10-7 T 3 + 0.65459673 10 1 Log(T) with T in [K] and p w in [Pa] Magnus Teten (Murray, 1967) Log10 p w = 7.5 t / (t+237.3) + 0.7858 with t in [ C] and p w in [hpa] Buck (1981, 1996) p w = 6.1121 e(18.678 - t / 234.5) t / (257.14 + t) [1996] p w = 6.1121 e17.502 t / (240.97 + t) [1981] with t in [ C] and p w in [hpa] Sonntag (1994) Log p w = -6096.9385 / T + 16.635794-2.711193 10-2 * T + 1.673952 10-5 * T 2 + 2.433502 * Log(T) with T in [K] and p w in [hpa]

All of these equations are related to saturation pressure of pure water vapour, but water vapour in air does not behave as a completely ideal gas and a corrections are required. Buck (1981) Equation: e s =( f ) 6.1121 exp 17.502 T 240.97 + T Where f = the enhancement factor for calculating vapor pressure of moist air instead of pure water vapor. Buck (1981) J. Appl. Meteorol. 20:1527-1532.

... I. 25 1. 2...... '.. 1 0 kpa -''I...... I. t5 I.. 05 I.. 0 o... 20.kP,., '"., ~ ~ 50.kPa ~ -, -- - i., " ~ "' I t- I _ ~ _ "I... I 10 kp:::i. -_..,-_ --._.,.....,... N..... _-. - L_,........ _L. t.-.. -r---.... Effect of temperature and pressure on enhancement factor for correcting moist air properties to that of pure water vapor. From: D.C. Shallcross. 2005. Intl. J. Heat and Mass Transfer 48:1785-1796.

Effects of Pressure on Evaporation Rates (Rygalov et al., 2004) Evaporation Rate (L m -2 d -1 ) 16 14 12 10 8 6 4 2 0 Relative Humidity 0 25 50 75 100 95% 65% 50% Pressure (kpa) Related to increased gas diffusion rates at reduced pressures

Diffusion Coefficient (D v ) of Water Vapour at 25ºC 600 Diffusion Coefficient D v (mm -2 s -1 ) 500 400 300 200 100 Fick's Law for Molecular Diffusion: J B = -C D v [d(c B /C)/dy] where D v is the mass diffusivity or the diffusion coefficient and D v = (0.926/P)[T 2.5 /(T+245)] 0 0 20 40 60 80 100 120 Pressure (kpa)

If evaporation rates increase at reduced pressures.. then wet-bulb (WB) depression should also increase.

Psychrometric Equation using Wet Bulb Temperature e s = e + γ (T db T wb ) γ = the psychrometric constant where γ = p A with p = pressure and A 6.53 x 10-4 K -1 for average size thermometers and aspiration rate of 4 m s -1 But e s is saturation vapour pressure at the wet bulb temperature! Thus this equation can t be used the to solve directly for T wb.

WATER- ~1ARTIAN ATMOSPHERE SYSTEM 50.0 kpo. p ~SSUJt\ En l!:ullpy dabjm : liq u.id wnl:er 0.00 -C..6 11 kpd. dry Martian tloosph.@r@ 0.00 "C. 1 U kpd. Martian t1lmosp b@~ composition : C'O:l 95.49 mol % ~ HO m l. L 60 mol 13 mol > co are mol, To OOtalD lru_o:> entb.:il Pl' ijdd. entb.:11 p}' de,, jilua n Lo entbil'lp)' lilt I ~ U L.i tiod. 160 HO 1 BO A. I'/:j If i V... ~ :'V I f, / I ".' : il..' k.."%, : y.. I. T v., y, :, I ~).OBO.osa.O~.054.052.O ~).048.049 ;;; '".0oU.c <>..042 g.04).oaa ~ ".038.f!.OM ~.032 2:-.O~) 'C.2'.OM 9.01l3 o 10 I 80 '. '. ' " ". ". '", 40.024 ~.022 'iii E.O ~) ::J.c.018 J!.018 ]'".014..:.012:.010.oos.008.004 Dry tolb tempera:lure ("C) Psychometric chart for water vapor in Martian atmosphere brought to 50 kpa pressure. From: D.C. Shallcross. 2005. Intl. J. Heat and Mass Transfer 48:1785-1796.

Themodynamic Wet Bulb Temperature vs. Pressure (at 25ºC Dry Bulb in Air and Martian Atmosphere) 25.0 70% RH 20.0 50% RH Temperature (ºC) 15.0 10.0 Open Symbols -- Air ( 78% N 2 21% O 2 ) (MW = 28.96) 30% RH 5.0 Solid Symbols -- Martian Atmosphere (95% CO 2 ) ( MW = 43.23) (from Shallcross 1997; 2005) 0.0 0 50 100 150 200 Pressure (kpa)

Psychrometric Chart for Pressure using Composite Thermodynamic Properties 4.5 "::]-.N:-:.!?"""" 2!J ~;;g;~~~~2~ 27 35 ~ 2 ~ 24 23 +~~~ 22 ~~~~~2 1 ~ m.d GI 0......, C:i: ;: 3 25-2 1.5 1 1~ ~ 1!I!lIiIl!!I!!!I!!!I!II!i!!i1I!!llIlIiillilllillili ~~~~ 11 ~~~~~ l e ~ ~ 1~ 0) '~~~~~~~l 14 ~ 13 12 11 -.l'><""l'" 10 ~~~~~~~~~7 9 6 ~~~~~~t~~~ 4 o ~ -10-8 -6-4 - ~ 0 2 01 0; B 10 1 ~ 14 1~ 1 8 <0 22 2-" 2:0; 26 30 32 ~ 3& 3D ~ O ~l dd "6 46 SO ~ o C H.-S. Ren. 2004. Construction of a generalized psychrometric chart for different pressures. J. Mech. Eng. Ed. 32(3):212-222.

Composite Psychrometric Chart Nomograph p, ~ Pro kp ~,IP, baf l I~ r~ D. Il I~ IlP 01 I, OHo I ~ O~! o L~,. OJ Q, 01- O! 12 ~.1 011! H.-S. Ren. 2004. Construction of a generalized psychrometric chart for different pressures. J. Mech. Eng. Ed. 32(3):212-222.

Thermodynamic Wet Bulb Temperature vs. Pressure (at Dry Bulb of 25ºC) 25 Relative Humidity 90% Temperature (ºC) 20 15 70% 50% 30% Data estimated from "Composite Psychrometric Charts Ren (2004) 10 40 50 60 70 80 90 100 110 Pressure (kpa)

Our objective was to directly measure wet bulb depression at different pressures and compare our results published psychrometric models for pressure effects.

Experimental Approach Measure wet bulb temperatures five different pressures and three different relative humidities: Pressures: 10, 20, 50, 80, and 100 kpa Relative Humidities: 30, 50, and 70% Each combination allowed to equilibrate for at least 90 minutes, then a 30-min segment of data was averaged for WB, DB, Dew Point, Chamber Air Temperature, Chamber RH, and Water Temperature

Hypobaric Test Chamber University of Guelph, CESF

Environmental Monitoring and Control: Wet Bulb / Dry Bulb Enercorp Model HT-WD-A Psychrometer Two matched platinum RTD temperature probes Constant aspiration -- 3 m s -1 Humidity Control Honeywell Model HIH-3602-A Capacitance Sensors (2) Temperature Control Argus TN 21 Thermisters (2) Dew Point Measurements General Eastern Model 1100DP (1) Humidity Calibration / Comparison (at 100 kpa) Vaisala HMP42 Handheld RH/Temp Probe Pressure Monitoring / Control MKS Barotron Capacitance Manometer Water temperature for the psychrometer reservoir

Wet / Dry Psychrometer Enercorp Inst. Ltd. (Model HT-WD-A) Signal Transmitter Exhaust Fan Air Inlet Tube with Cotton Wick RTD Temp Probe Water Reservoir

Wet Bulb Measurements versus Atmospheric Pressure 25 Dry Bulb Temp. = 25 C y = 0.826 Ln(x) + 16.64 R 2 = 0.722 20 70% RH y = 1.593 Ln(x) + 10.23 Temperature (ºC) 15 10 50% RH R 2 = 0.976 y = 3.002 Ln(x) + 1.349 R 2 = 0.993 5 30% RH Filled symbols represent our Wet Bulb measurements; Open symbols are adiabatic saturation temperatures from Shallcross (1997, 2005) and Ren (2004) (red triangles). 0 0 20 40 60 80 100 120 Pressure (kpa)

Conclusions Our measurements of wet bulb depression at different pressures matched the modeled adiabatic saturation temps reasonably well. At a dry bulb temp of 25 C, the normal wet bulb temp for 30% RH and 100 kpa is ~15 C, but this dropped to ~8 C at 10 kpa. The results suggest that psychrometers need direct calibration at the target pressures or that pressure corrected charts are required. For a given vapour pressure deficit, any moist surfaces, including transpiring plant leaves, will be cooler at lower pressures due to the increased evaporation rates.

Thanks to the CESRF Team at University of Guelph Mike Stasiak Jamie Lawson

Questions? Welcome to Florida!

Wet Bulb Temperature vs. Adiabatic Saturation Temperature Wet Bulb Temperature: The temperature of a sensor covered with pure water that is evaporating freely into the ambient air stream. Typically taken with a matched dry bulb (DB) reading under constant aspiration (3-5 m s -1 ) and shielded from radiation. But WB readings can be affected by the aspiration rate, mass of the sensor, water temperature, properties of the wick, and water purity. Adiabatic Saturation Temperature (also called Thermodynamic Wet Bulb Temperature): The thermodynamic state resulting from adiabatic saturation, where there is no heat or mass transfer involved, and is independent of the measurement technique.

The Psychrometric Chart

Averaged* Chart of Dynamic WB Temperature vs. Pressure 25.0 y = 0.897 Ln (x) + 16.88 ; R 2 = 0.976 70% RH 20.0 y = 1.844 Ln (x) + 9.445 ; R 2 = 0.980 Temperature (ºC) 15.0 10.0 50% RH y = 3.245 Ln (x) - 0.410 ; R 2 = 0.992 5.0 30% RH 0.0 0 50 100 150 200 250 Pressure (kpa) Data for 12 and 20 kpa for CO 2 (95%) atmosphere; 80, 140, and 200 kpa for air; 50 and 100 averaged for CO 2 and air (Shallcross, 1997).