Selecting the current rating for equipment

Similar documents
Overhead lines. 110 kv wood tower with guy wires

TeSys circuit-breakers

Fault Calculation Methods

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS. Type PVA10 / PV10 PV14 PV22 Rated current I n up to 32 A up to 63 A up to 125 A Rated voltage U n

Fault Analysis Power System Representation

3VT4 Molded Case Circuit Breakers up to 1000 A

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS

Effect of core balance current transformer errors on sensitive earth-fault protection in compensated MV networks

FAZ tripping characteristics at 30 C: B, C, D to IEC/EN FAZ tripping characteristics at 30 C: R to IEC/EN

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

08/072 PKZ2 Motor-Protective Circuit-Breakers Tripping Characteristics

Power capacitors in general

Issued August DATA SHEET. 3VT3 MCCB up to 630 A

1..LOW VOLTAGE POWER CAPACITORS MKP (CYLINDRICAL) 2 2..PPM / MKP TECHNOLOGY 2 3..OPERATING CONDITION Voltage Ambient temperature

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM

Current protection I 2 t long-time protection

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION

Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs

Three Phase Circuits

OR Explain thermal breakdown in solid dielectrics. How this mechanism is

Sinusoidal Steady State Analysis (AC Analysis) Part II

Damping resistor design consideration

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

MCB NB1-63H Miniature Circuit Breaker

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

ECE 325 Electric Energy System Components 5 Transmission Lines. Instructor: Kai Sun Fall 2015

ECE 476. Exam #2. Tuesday, November 15, Minutes

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

XD1-L Cable Differential Protection Relay

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

EE Branch GATE Paper 2010

Worked Example for the Calculation of Earthing Current and Electric Shock Hazard Potential Difference in a Rod and Grid Earthing System

The Effect of Harmonic Distortion on a Three phase Transformer Losses

CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING

Capacitor Application Issues

Modeling and Simulation of Air Insulated and Gas Insulated Substations

X T O B P 1 6 B C 1 S

Overload Relays. SIRIUS 3RU1 Thermal Overload Relays. 3RU11 for standard applications. 5/46 Siemens LV 1 AO 2011

The development of a Roebel cable based 1 MVA HTS transformer

Sealing possibility Electrical endurance (ops) Mechanical endurance (ops) Overvoltage category Standards

Power and Energy Measurement

Question Bank. Electric Energy, Power and Household Circuits

TYPE. max. working voltage 250 V 350 V 500 V 750 V. max. overload voltage 500 V 700 V 1000 V 1500 V. basic specifications IEC B

FL ballasts Electronic fixed output. PC TC PRO sr 1/2x11 42 W PC PRO compact

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations

Reactive Power Solutions

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

Semiconductor (AC) fuses

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity

90 MCB range Modular circuit breakers for circuit protection

Fatima Michael College of Engineering & Technology

Low Frequency Transients

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

Commissioning testing of a 1 MVA Superconducting transformer featuring 2G HTS Roebel cable

EXEMPLAR NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 ( ) (X-Paper) 09:00 12:00

TRANSIENTS POWER SYSTEM. Theory and Applications TERUO OHNO AKIH1RO AMETANI NAOTO NAGAOKA YOSHIHIRO BABA. CRC Press. Taylor & Francis Croup

Energy saving in electromechanical equipment with power coefficient correction. Dimitris Al. Katsaprakakis Aeolian Land S.A.

FEATURES APPLICATIONS DESCRIPTION QUICK REFERENCE DATA. PILKOR components

Superconducting Fault Current Limiters

Module 3 : Sequence Components and Fault Analysis

Installation Contactors ISU-xxx ISM-xxx

5V/400mA Low Drop Voltage ILE4275 TECHNICAL DATA

To order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle

Thermal-Magnetic Circuit Breaker 2210-T2...

Impedance relay and protection assemblies

Transformer. Transformer comprises two or more windings coupled by a common magnetic circuit (M.C.).

THF / 1SCC330001M THF 1S1 C

Modeling of Transmission Line and Substation for Insulation Coordination Studies

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

Film Capacitors. EMI suppression capacitors. Date: June 2018

Conventional Paper-I-2011 PART-A

Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines)

Power and Energy Measurement

Superconducting Fault Current Limiters

Introduction to AC Circuits (Capacitors and Inductors)

General characteristics, Products

Familiarization, and Ohm's Law

In the previous chapter, attention was confined

Data Bulletin. SEPAM 49RMS Application Note Protection for Motor Applications Class Number SEPAM 49RMS Protection for Motor Applications

Exam 3--PHYS 102--S14

Study of Transient Behaviour of the Capacitor Voltage Transformer

PHYS 1441 Section 001 Lecture #23 Monday, Dec. 4, 2017

Products for Luminaire Protection and Power Adjustment Products

5SP and 5SY Supplementary Protection UL 1077

Apparatus Models: Transformers

Capacitors. Dominik Pieniazek, P.E. VI Engineering, LLC Nicholas A. Losito Jr. Castle Power Solutions, LLC

and cables for offshore wind connection

5SJ4...-.HG Circuit Breakers to IEC and UL 489

Non-Contact Safety Systems CMS

A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2

Part 4: Electromagnetism. 4.1: Induction. A. Faraday's Law. The magnetic flux through a loop of wire is

T h e rm i s t o r s

Cat. No. 140M-F M-D8E-B

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits

Transcription:

Selecting the current rating for equipment 1. Rated current: the maximum continuous load current. Short-time withstand current: thermal withstand current term term is given for 1s or 3s short circuit current duration Equivalent 1s current stress, when and time t are nown: W Þ Þ 1s 1s R 1s t ; t / s energy is the same f the transient components are high, the equation becomes: Þ t 1s '' (m + m the effect of DC-component n the effect of decay in AC-component Std VDE 010 : m 0 0,8 n 0, 1 n) t/s m ~ r/x, t n ~ /, t 3. Pea withstand current: defines the mechanical strength requirements i dyn,5 term» 1,8 Ö term

Mechanical stresses of a short circuit F a m0 p i i a 1 F L i F Example: -phase short circuit, 10 A a 1,0 m ; F/L? i 1 L F L m0 i1 i p a 4p 10 p 5 15 m -7 10 ; -1 i 5 1 m i 10 6,5 Vs A Am æ çva è 5 A 1 m J s VAs m m ö s ø 1 m m ote: in the case of a 3-phase fault, the forces are 15% bigger

Grid short circuit power S 100 MVA, Transformer rating S 16 MVA, and reactance u x 10 %, secondary voltage 0 V, line length is 40 m and resistance and inductance r 0.3 W/m ja l 1.1 mh/m. Compute a) 3-phase short circuit current in A and B, b) the dynamic current rating of busbar A, and c) the equivalent 1s current for line A-B when the fault time is 0.6 second?. 100 V 0 V 40 m One-line diagram: S S u x A l, r X X T A R j X i B B Th? Th? etwor impedances (in 0 V) : X X R T j S u x s r S 0 W 100 40 0,3W 0 0,1 16 0,333 W W 1 W X i pf s l p 40 50 1,1 10-3 W 13,8 W

a) 3-phase short circuit current in points A & B : Thevenin s method : Th 0 3 A : B: Z Þ Z Th Th X Rj + Z + Th Th X T @ j(x,833 W 4,075 A + X T + X j ) 1 + j16,653 Þ Þ Z Th Z Th Th 1 + 16,653 @ 0,56 A @ 0,53 W b) Dynamic rating for busbar A : i dyn,5 term,5 4,075 A @ 10, A c) Thermal rating for line A-B, when t 0,6 s :, max s 4,075 A, max t/s 4,075 0,6 A @ 3,16 A

Switching devices Rated quantities : Rated voltages and insulation level Thermal 1s withstand current () Dynamic withstand current (dyn.5*) Maing capacity of short circuit current highest fault current pea value, that the switch can close Breaing capacity of short circuit current highest fault current, that the switch can interrupt usually given as: - ac-component rms value, and - dc-component %-share

1. Disconnector (isolator) in open-position a reliable open point when closed, can carry load and fault current no breaing or maing capacity. Switch-disconnector a disconnector able to brea load current & mae fault current used e.g. in MV overhead distribution networs Example: n 4 V n 630 A 1s 16 A ma 40 A (maing capacity) Capacity of disconnecting a transformer in no-load 16 A Capacity of disconnecting an OH-line in no-load 4 A Capacity of disconnecting an underground cable 5 A

3. Fuse-switch-disconnector A switch-disconnector equipped with HV fuses Operation of one fuse causes opening of the switch Þ prevents -phase operation 4. Circuit breaer switch able to brea and mae also the short circuit currents wors either automatically or manually controlled in the case of fault, tripped by a protective relay

Operation of a circuit breaer a) melted metal bridge b) stationary power arc c) moving power arc d) the arc voltage ~ time The breaing wor W must be ept small. W t ò 0 u v (t) i v (t) dt n order to help the interruption, the arc is: drawn longer divided into parts cooled down de-ionized (absorbing materials)

Some CB types air CB oil CB minimum oil CB Pressurized air CB SF 6 - CB vacuum CB

Current transformers n s p The current error F 100 % K n transformation ratio s secondary current p primary current i K p - 100 1 c n s T ò - The composite error e (K i i ) dt % Measurement transformers nstrument security current current, for which e c equals 10% F s nim F s nstrument security factor normal value 5 or 10 Protective transformers Accuracy limit factor F T defines the current, when e c 5% or 10% (5P tai 10P) typical values 5,10,15,0 or 30 (times the rated current) Example: 10 P 15 p T o p

The accuracy classes of CT:s Accuracy burden power factor Primary error angle error composite class x S cos f x p ± % ± min error % 0,1 0,5 1 0.8 ind for 0,05 0,4 15 S ³ 5 VA 0, 0, 8 - otherwise 1,0 0,1 5 1 1, 0,1 5 0, 0,05 0,75 30 0, 0,35 15-1,0 0, 10 1, 0, 10 0,5 0,05 1,5 90 0, 0,75 45-1,0 0,5 30 1, 0,5 30 1 0,05 3,0 180 0, 1,5 90-1,0 1,0 60 1, 1,0 60 3 0,5 1 0,5 3 - - 1, 3 5 0,5 1, 5 - - 5 P 1 1 1 60 - n - - 5 10 P 1 3 - - n - - 10 ote n equals to the accuracy limit factor

Equivalent circuit for a CT 1 Z s Z w m 1: L m Z b nternal burden S s Z s Z s impedance of the secondary winding Z w impedance of the secondary wiring Z b impedance of the secondary burden (relays etc.) A CT eeps its accuracy class when Z w + Z b is smaller than the rated burden Z impedance defined by S Z

Example : 100/1 A 10 P 15 current transformer nternal burden Rated burden Secondary cabling 0.5 VA 10 VA W f the burden by relays is 10 VA, what is the effect of cabling impedance to the accuracy limit current? The burden of secondary cabling at rated current: S F w T ' R F T SS + S + S S VA w S + S The burdens are resistive: 0.5 + 10 Þ F T ' 15 1.6 0.5 + + 10 Þ the accuracy limit current F T 1,6 A

Measurement of zero sequence current Sum connection : Large load currents cause measurement errors Short circuit currents and unequal saturation Þ apparent sum current created cable type CT: even 0.5 A currents detected 1 3 A S Sum connection Cable type CT

Voltage transformers (VT) the rated voltage factor maximum operating frequency voltage, that the VT must tolerate for a given time ( rated ) protective transformer (3 P or 6 P) must eep its accuracy up to the voltage rated Rated voltage factors of VT:s rated voltage time Primary connection and system earthing factor 1, continuous in general between the phases and between the star point and earth 1, continuous 1,5 30 s between phase and earth in solid earthed systems 1, continuous between phase and earth in other systems 1,9 30 s if automatic earth fault tripping 1, continuous between phase and earth in unearthed and compensated 1,9 8 h neutral systems, if no earth fault tripping The maximum errors allowed for VT:s in general Additional requirements for protective VT:s class voltage error angle error % min 0,1 0,1 5 0, 0, 10 0,5 0,5 0 1 1,0 40 3 3,0 - class voltage error angle error % min 3 P 3,0 10 6 P 6,0 40

The measurement of zero sequence voltage d L1 + (1+ a 3 0 + a L + ) ( 1 L3 + ) + 3 0 a 1Ð10

Voltage transformer ferroresonance initiated by some switching action is stopped, when more lines are connected phase voltages strongly distorted may cause high overvoltages damping using 50-60 W resistor in open delta

Equivalent circuit for a power transformer R X R 0 X 0 Example: A 16 MVA transformer X R r 0 (S 0 P P S S 0 0 3 1 W 0,0161 0,088 16 1 W 0,005 16 & 0,0055 p.u. P 5,5 W 7,4 W 3 hr ) z R X Þ x r x x S S + r 0,1p.u. z - r 0,09985» 1 0,0055 W 0,15 W 16 1 0,1 16 W,76 W 0,1p.u.

The ampacity of a power transformer

Cellulose fiber Composed of chains of molecules Electrical strength depends on the length of the chain Chains are broen by oxygen water and heat

Temperature distribution At rated load: q a ambient temperature Dq or 55 C Hg r 3 C The rate of life time decay (EC 354) the winding hot-spot temperature the relative rate of life time decay q h V q a ( q + Dq h or -98) /6 é1+ RK ê ë 1+ R ù ú û x + Hg r K y K R / P n n / P 0 y 1,6 x 0,8

Overload capacity (EC 354) ormal cyclic load current 1,5 hot-spot temperature 140 top-oil temperature 105 Long term overload capacity current 1,8 hot-spot temperature 150 top-oil temperature 115 Short term overload capacity current hot-spot temperature * top-oil temperature * 16 14 1 The rate of life time decay ~ load current Life time decay p.u. 10 8 6 4 0 0,9 1 1,05 1,1 1,15 1, Load current p.u.