BRE Client Report. Calculation of summertime solar shading performance for MicroLouvre. Prepared for: Smartlouvre. BRE Watford, Herts WD25 9XX

Similar documents
BRE Client Report. Aging of light pipe materials (4000 hours artificial ageing) Prepared for: James McGowan Monodraught. BRE Watford, Herts WD25 9XX

Double-Skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of Direct Solar Radiation

Thermal Comfort; Operative Temperature in the Sun

Working of a SUNLUX SUNSCREEN

Appendix 5.A11: Derivation of solar gain factors

(Refer Slide Time: 00:01:19 min)

THE AVERAGE TOTAL DAYLIGHT FACTOR

Blockout Déco N203 COLLECTION BLOCK SUNLIGHT BLOCKOUT OF = 0% COPACO BLOCKOUT DÉCO N203

Serge 600 COLLECTION REFLECTS SUNLIGHT OUTDOORS GLASSFIBRE OF = 5%

Natté P CLARITY & COMFORT POLYESTER OF = 1-10% COPACO NATTÉ P

Natté COLLECTION CLARITY & COMFORT GLASSFIBRE OF = 1-10% COPACO NATTÉ

Description of Benchmark Cases for Window and Shading Performance Calculation

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND

Chapter Seven. Solar Energy

Solar reflected glare affecting visual performance

Definitions of U- and g-value in case of double skin facades or vented windows

EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS

The energy performance of an airflow window

LOW E SATINÉ 5500 LOW E

CAE 331/513 Building Science Fall 2016

Solar Radiation 230 BTU s per Hr/SF. Performance Glazing Coatings, Layers & Gases

TREES Training for Renovated Energy Efficient Social housing

Glazing selection for solar design

Design strategy for Low e windows with effective insulation

Effect of Installing a Curved Venetian Blind to the Glass Window on Heat Transmission

Section 1: Overhang. Sizing an Overhang

SIMPLE LOW CONCENTRATING MODULE DESIGN INCRESES SOLAR CELL OUTPUT 25%

Winter Night. Thermos 6mm Outdoors # #

SCREEN LOW E SATINÉ 5500 LOW E

How to evaluate daylight. Initiated by the VELUX Group

SCREEN LOW E SATINÉ 5500 LOW E

ADVANCED ROOF COATINGS: MATERIALS AND THEIR APPLICATIONS

Calculation of Pressure Drop Across Sunray Louvre. Prepared for: David Evans Sunray Engineering Ltd. November Client report number

Orientation of Building

Solar shading for low energy buildings

LOW E SATINÉ 5500 LOW E

EXPERIMENTAL DETERMINATION OF SPECTRAL AND ANGULAR DEPENDENT OPTICAL PROPERTIES OF INSULATING GLASSES

SOLAR GEOMETRY (AND RADIATION)

Customer: Ashton Industrial Sales Ltd. South Road, Harlow Essex CM20 2AR UNITED KINGDOM. Project/Customer: Profilex HM spacer

Daylighting design with climate. Francesco Anselmo

Weathertightness testing of Solar Slate Plate to MCS012. Prepared for: Michael Share. Solar Slate Plate. 24 th June Test report number

Calculation of solar radiation in SAP 2012 (revised version June 2014)

Simplified Collector Performance Model

Chapter 1 Solar Radiation

Model 3024 Albedometer. User s Manual 1165 NATIONAL DRIVE SACRAMENTO, CALIFORNIA WWW. ALLWEATHERINC. COM

1 BAKER HOUSE DINING: LIGHTING DIAGNOSTIC

5.6.2 SHADOW / DAYLIGHT ASSESSMENT

Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha

Performance Assessment of PV/T Air Collector by Using CFD

ASSESSMENT OF WINDOW SYSTEMS CONSIDERING SOLAR AND THERMAL PERFORMANCE

Testing of Lincolnshire Limestone. Prepared for: Phil Kerry Goldholme Stone Ltd. Irnham Grange Irnham Road Corby Glen Grantham Lincolnshire NG 33 4 NE

Sunlight and its Properties II. EE 446/646 Y. Baghzouz

Declarations of equivalence of Verosol sun screens. SilverScreen and EnviroScreen

The influence of solar radiation on the distribution of temperatures in historic masonry

Solar Control in Traditional Architecture, Potentials for Passive Design in Hot and Arid Climate

Report TAG3-UA-1212-E07 Testing of the transmission and the g-value of a polycarbonate multiwall panel AKYVER 16/7 IR Control Grey

Project 2. Introduction: 10/23/2016. Josh Rodriguez and Becca Behrens

ABSTRACT INTRODUCTION OPTICAL CALCULATIONS

Institut national des sciences appliquées de Strasbourg GENIE CLIMATIQUE ET ENERGETIQUE APPENDICES

Solar radiation and architectural design in Barcelona

SENSITIVITY OF THE SOLAR HEAT GAIN COEFFICIENT OF COMPLEX FENESTRATION SYSTEMS TO THE INDOOR CONVECTION COEFFICIENT

PREDICTING OVERHEATING RISK IN HOMES

LESSON PLAN - Optimum Orientation of Solar Panels Using Soltrex Data

IDA ICE CIBSE-Validation Test of IDA Indoor Climate and Energy version 4.0 according to CIBSE TM33, issue 3

CHAPTER 3. The sun and the seasons. Locating the position of the sun

Prototype Heat Island Application

Daylighting Buildings Nexus November 12, 2009

Predicting Natural Light in Atria and Adjacent Spaces using Physical Models

TECHNICAL COMMITTEE of the EU Cool Roofs Council

Photovoltaic Systems Solar Radiation

Performance of Fixed Horizontal Shading Devices in South Facing Residential Buildings in Dhaka

38 B Our Environment. Ederlinda Viñuales Gavín Marco Nicolini. Sun Exposition &

Solar Energy Cooking with the Sun

AN EVALUATIVE METHOD FOR HIGH-PERFORMANCE WINDOW SYSTEM AND WINDOW SIDE RADIATION ENVIRONMENT

ISO INTERNATIONAL STANDARD

Prentice Hall EARTH SCIENCE. Tarbuck Lutgens

Draft for comment (613) Public Works Canada Design & Construction Technology DRAn' 1 July, Computer-Aided Design Centre (CAD) TSS COPY

Chapter 2 Available Solar Radiation

SIMULATION OF FRAME CAVITY HEAT TRANSFER USING BISCO v10w

Period 14 Activity Sheet: Energy in Nature

Chapter 2. Heating Earth's Surface & Atmosphere

MASSACHUSETTS INSTITUTE OF TECHNOLOGY Department of Physics Problem Solving 10: The Greenhouse Effect. Section Table and Group

Testing of Ancaster Limestone. Prepared for: Phil Kerry Goldholme Stone Ltd. Irnham Grange Irnham Road Corby Glen Grantham Lincolnshire NG 33 4 NE

Astron 104 Laboratory #10 Solar Energy and the Habitable Zone

ARCHITECTURE IN THE DAYLIGHT

Solar Time, Angles, and Irradiance Calculator: User Manual

Solar Heat Gain Coefficient of Complex Fenestrations with a. Venetian Blind for Differing Slat Tilt Angles

CZECH TECHNICAL UNIVERSITY IN PRAGUE FACULTY OF MECHANICAL ENGINEERING DEPARTMENT OF ENVIRONMENTAL ENGINEERING

Professor Haig Gulvanessian CBE Civil Engineering and Eurocodes Consultant, Visiting Professor, Imperial College London

Chapter 10 Planetary Atmospheres: Earth and the Other Terrestrial Worlds. What is an atmosphere? About 10 km thick

ME 476 Solar Energy UNIT TWO THERMAL RADIATION

Planetary Atmospheres: Earth and the Other Terrestrial Worlds Pearson Education, Inc.

Solar Flat Plate Thermal Collector

Heat Transfer. Energy from the Sun. Introduction

Chapter 22: Uses of Solar Energy

HEATING THE ATMOSPHERE

INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS

AT350 EXAM #1 September 23, 2003

Lecture 3: Global Energy Cycle

Solar Radiation Protections on Façades: A Case Study in a Hot Semi-Humid Climate

Transcription:

BRE Client Report Calculation of summertime solar shading performance for MicroLouvre Prepared for: Smartlouvre Date: 21 December 2017 Report Number: P111107-1000 Issue: 2 BRE Watford, Herts WD25 9XX Customer Services 0333 321 8811 From outside the UK: T + 44 (0) 1923 664000 F + 44 (0) 1923 664010 E enquiries@bre.co.uk www.bre.co.uk Prepared for: Smartlouvre 18 The Tanneries Brockhampton Lane Havant Hampshire PO9 1JB

Prepared by Name Dr Paul Littlefair Position Associate Director, Environment Date 21 December 2017 Signature Checked by Name Stephanie King Position Senior Consultant Date 21 December 2017 Signature This report is made on behalf of Building Research Establishment Ltd. (BRE) and may only be distributed in its entirety, without amendment, and with attribution to BRE to the extent permitted by the terms and conditions of the contract. BRE s liability in respect of this report and reliance thereupon shall be as per the terms and conditions of contract with the client and BRE shall have no liability to third parties to the extent permitted in law. Page 1 of 9

1 Introduction BRE have been commissioned by Smartlouvre to determine the solar radiation transmittance of their MicroLouvre system. This is a sheet of very small louvres, usually applied to the outside of windows to reduce solar heat gain. The usual way to assess the solar gain performance of a system is to calculate the total solar transmittance. This is the fraction of incoming solar radiation that passes through a window and/or shading system. In Europe it is often called the g value. The total solar transmittance includes both radiation that is transmitted directly through the window, and radiation that is absorbed and then re-radiated, convected or conducted into the room. For most glazings, the total solar transmittance is measured at normal incidence (ie with the sun directly opposite the window). However when the sun hits the window at an oblique angle, less radiation will be transmitted. This is particularly important for a shading device like MicroLouvre, which is designed to block high angle sun. It will transmit much less solar gain when the sun is high in the sky than a simple measure at normal incidence would indicate. The effective g value (refs 1, 2) is a better metric for the performance of angle dependent shading devices such as MicroLouvre. It allows for the effects of radiation coming in from different angles, throughout a sunny day in summer. It is defined as: Effective g value = Solar gain in period of potential overheating through window with shading device Solar gain through unshaded, unglazed aperture for the same period The period from May-August has been chosen as the basis for the calculation of solar protection. The whole day has been taken, but only peak days (the 2.5% centile of radiation availability) are included as solar overheating is most likely to occur on clear days with uninterrupted sun. This means that the effective g value will vary with the orientation of the window. To simplify things slightly, the data have been averaged so that east and west facing windows give the same value; for UK weather conditions this leads to only a very small difference. Page 2 of 9

2 Details of the effective g value calculation The effective g value of a shading system is calculated using the following approach. CIBSE (in their Guide A) have tabulated the radiation available on peak summer days (the 2.5% centile of radiation availability) and these values have been used as the basis for calculation, together with the sun positions for that period and a model of the radiance of the sky (ref 1). This enables data to be calculated to allow for the different amounts of radiation received from different directions. This has been carried out for a series of sky patches at 2 intervals in altitude and 5 in azimuth, a total of 3240 data points. Sun and sky radiation are combined, so if the sun is located in a particular sky patch at any time during the summer period its direct radiation is added on. Since the MicroLouvre is intended to be used with glazing, the data are weighted according to the variation of angular transmittance of a typical window (a double glazed low emissivity window). This means that radiation which comes at a glancing angle to the window is given less weight because most of it would be reflected by the glazing anyway, in the absence of MicroLouvre. The data can then be coupled with the angular transmittance of the shading device to give an overall value of shading performance. For vertical glazing, ground reflected radiation needs to be taken into account. Ground reflected radiation can reduce the effectiveness of devices like MicroLouvre because they do not block it as much as they do sky and sun radiation. Consequently a fairly detailed model of ground reflected radiation has been assumed. A ground albedo of 0.2 has been assumed. The obstruction of the ground by the building itself has been taken into account, assuming that the window is halfway up the façade. The façade is taken to be of infinite width, with an albedo of 0.2. No external obstruction (for example a building opposite) has been included in the calculation. External obstructions would tend to increase the relative effectiveness of the MicroLouvre, because it has a lower transmittance for radiation coming from higher up. For both ground reflected and sky and sun radiation, the data are coupled with the angular transmittance of the shading device and glazing to give the effective g value. A BRE publication The summertime solar performance of windows with shading devices (ref 1) gives full details of the way the calculation is carried out. The Microlouvre is modelled as a series of louvres tilted at a 17 angle to the horizontal. Figure 1, taken from Smartlouvre s product specification, shows its geometry. Page 3 of 9

Figure 1. Geometry of MicroLouvre (based on specification by Smartlouvre) The vertical spacing between adjacent louvres was 1.49mm, and each louvre blade was 1.38mm wide. The thickness of the louvre blade was taken to be 0.32mm. The blades were assumed to be rectangular in cross section. The spacer wire was taken to be straight and an average of 0.257mm wide spaced at 12.7mm intervals. Reflection of radiation between the blades was included. The solar reflectance of the material used to make black MicroLouvre was taken to be between 0.05-0.10 (5-10%). Only the black MicroLouvre has been modelled. Page 4 of 9

3 Results The second column of Table 1 gives the effective g value (solar transmittance) of MicroLouvre alone. This is does not include radiation that is absorbed by the MicroLouvre and then re-radiated, but it does include radiation reflected inwards from the MicroLouvre. The third and fourth columns give the fraction of radiation that is absorbed and reflected back out. Table 1. Effective g value (solar transmittance, absorptance and reflectance of MicroLouvre alone. r=0.05 Effective g value Absorptance Reflectance North 0.29 0.69 0.02 NE/NW 0.23 0.75 0.02 E/W 0.18 0.80 0.02 SE/SW 0.12 0.85 0.02 South 0.12 0.85 0.03 r=0.1 Effective g value Absorptance Reflectance North 0.29 0.67 0.04 NE/NW 0.24 0.72 0.04 E/W 0.19 0.77 0.05 SE/SW 0.13 0.82 0.05 South 0.13 0.82 0.05 The total effective solar energy transmittance g can be determined for a window plus blind combination using the methods given in EN 13363-1 (ref 3). The effective g value gtot for a glazing and external shading combination is given by: Page 5 of 9

gtot = gb. g + αb Λ Λ2 + gb (1-g) Λ Λ1 where g is the effective g value of the glazing, gb is the effective g value of the MicroLouvre alone (second column of table 1), and the absorptivity of the MicroLouvre αb is given in the third column of table 1. Λ = 1 1/ U + 1/ Λ1 + 1/ Λ2 with Λ1= 5 W/m 2 K; Λ2 = 10 W/m 2 K where U is the thermal transmittance of the glazing. (Note: Λ1 and Λ2 are notional parameters which are mathematically fitted). This analysis assumes that the external shading is in thermal contact with the window, and mounted fairly close to it. If the MicroLouvre is mounted some distance from the window, and there is good ventilation of the space in between, gtot = gb. g The total solar energy transmittance gtot for a glazing and an internal shading combination is given by: Λ gtot = g. (1 - g. ρb - αb ) Λ2 Λ = 1 1/ U + 1/ Λ2 with Λ2 = 30 W/m 2 K ρb, the solar reflectance of the MicroLouvre, is given in the fourth column of table 1. The effective g value gtot for shading between two glass s (a mid- shading device) is given by: gtot = gb. g + g. (αb + (1-g) ρb ). Λ Λ3 Λ = 1 1/ U + 1/ Λ3 with Λ3 = 3 W/m 2 K Table 2 gives values for the overall effective g values of MicroLouvre (reflectance 0.05) coupled with four different glazing types. These are the reference glazings in BS EN 14501:2005 (ref 4). 1. Reference glazing A. Single glazing, U=5.8 W/m 2 K, normal incidence transmittance g=0.85. Page 6 of 9

2. Reference glazing B. Double clear glazing, U=2.9 W/m 2 K, normal incidence transmittance g=0.76. 3. Reference glazing C. Double low emissivity glazing, U=1.2 W/m 2 K, normal incidence transmittance 0.59. 4. Reference glazing D. Double soft coat low emissivity glazing, U=1.1 W/m 2 K, normal incidence transmittance 0.32. Table 3 gives the values for MicroLouvre with a material reflectance of 0.1. The values for the two reflectances are very similar. Table 2. Effective g values (solar transmittances) for MicroLouvre/glazing combinations. Slat reflectance 0.05. r=0.05 A. Single glazing B. Double clear glazing C. Double low emissivity glazing D. Double soft coat low emissivity glazing Internal External Internal Mid External Internal Mid External Internal Mid External North 0.62 0.39 0.58 0.39 0.32 0.45 0.23 0.22 0.23 0.11 0.16 NE/NW 0.67 0.36 0.62 0.41 0.30 0.49 0.23 0.20 0.25 0.11 0.15 E/W 0.68 0.33 0.64 0.40 0.27 0.51 0.22 0.18 0.27 0.11 0.14 SE/SW 0.65 0.29 0.62 0.37 0.23 0.49 0.19 0.15 0.25 0.09 0.12 South 0.61 0.28 0.57 0.34 0.22 0.45 0.17 0.14 0.22 0.08 0.11 Table 3. Effective g values (solar transmittances) for MicroLouvre/glazing combinations. Slat reflectance 0.1. r=0.1 A. Single glazing B. Double clear glazing C. Double low emissivity glazing D. Double soft coat low emissivity glazing Internal External Internal Mid External Internal Mid External Internal Mid External North 0.61 0.38 0.57 0.39 0.32 0.45 0.23 0.22 0.23 0.11 0.16 NE/NW 0.66 0.36 0.61 0.40 0.30 0.49 0.23 0.21 0.25 0.12 0.15 E/W 0.67 0.33 0.63 0.40 0.27 0.51 0.22 0.18 0.27 0.11 0.14 SE/SW 0.64 0.29 0.61 0.37 0.23 0.48 0.19 0.15 0.25 0.09 0.12 South 0.60 0.28 0.56 0.34 0.22 0.44 0.17 0.14 0.22 0.08 0.11 Page 7 of 9

For comparison, Table 4 gives the effective solar transmittances of the glazing alone, without MicroLouvre. Table 4. Effective g values for glazing on its own A. Single B. Double clear C. Double low emissivity D. Double soft coat low emissivity North 0.71 0.62 0.47 0.24 NE/NW 0.77 0.68 0.51 0.26 E/W 0.80 0.70 0.53 0.28 SE/SW 0.77 0.68 0.51 0.26 South 0.72 0.63 0.47 0.23 The values in Tables 2 and 3 include heat that is absorbed by the MicroLouvre and then transferred inside the window. For the low transmittance reference glazing D, the equations in EN13363-1 predict higher transmittance with externally mounted Microlouvre than with a mid- installation. This is because the externally mounted Microlouvre will heat up in the sun and the method assumes that some of this heat is conducted or convected indoors. The extent to which this actually happens will depend on the way the Microlouvre is installed, and the amount of ventilation between it and the window. With a mid installation, most of the incoming solar radiation is reflected away by the outer of the reference glazing D, which means that the Microlouvre does not warm up as much and less heat is predicted to enter the room. Overall, the results show that: Mounted externally or mid, MicroLouvre makes a substantial difference to the solar transmittance of the window. This can be seen by comparing the values in Tables 2 and 3 with those in Table 4, which gives the effective solar transmittances of the glazing alone, without MicroLouvre. The performance of the MicroLouvre does vary with orientation, although it has a significant effect for all orientations. Mounted externally, it is best for E/W, SE/SW and South facing windows. When the MicroLouvre is mounted internally, it makes only a relatively small reduction in transmittance compared to an unshaded window. The calculations have been carried out for black MicroLouvre, and nearly all the radiation is either transmitted or absorbed. Most of this absorbed radiation is then trapped in the room if the MicroLouvre is inside, unless there is some form of ventilation such as a trickle vent. White MicroLouvre would be expected to reflect more radiation and therefore to have a bigger impact when mounted internally. Page 8 of 9

4 References 1. Littlefair P J. Summertime solar performance of windows with shading devices. BRE FB 9. Bracknell, IHS Markit, 2005. 2. Chartered Institution of Building Services Engineers (CIBSE). Design for improved solar shading control. London, CIBSE, 2006. 3. BSI. Solar protection devices combined with glazing Calculation of solar and light transmittance Simplified method. BS EN 13363-1:2003 +A1:2007. London, BSI, 2007. 4. BSI. Blinds and shutters - Thermal and visual comfort Performance characteristics and classification. BS EN 14501:2005. London, BSI, 2005. Building Research Establishment Ltd Report Ends Report No. P111107-1000 Page 9 of 9