SIMULATION-SUPPORTED ROOM ACOUSTICS RETROFIT OF OFFICE SPACES

Similar documents
DIFFUSIVITY AND ITS SIGNIFICANCE TO EFFECTIVE SEAT ABSORPTION IN CONCERT HALLS

SIMPLE APPLICATION OF STI-METHOD IN PREDICTING SPEECH TRANSMISSION IN CLASSROOMS. Jukka Keränen, Petra Larm, Valtteri Hongisto

Acoustic response in non-diffuse rooms

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 7MM TESTED WITH A 20MM AIR GAP IN A REVERBERATION ROOM.

ABOUT UNCERTAINTIES IN SIMULATION MODELS FOR BUILDING SYSTEMS CONTROL

Summary. The basic principles of the simulation technique SERT

Development of a small-scale reverberation room

ODEON APPLICATION NOTE Calibration of Impulse Response Measurements

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 24MM TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM.

Answer - SAQ 1. The intensity, I, is given by: Back

LIMITING ANNOYING NOISE IN OPEN-PLAN OFFICES. Claus Møller Petersen

Sound insulation of planted noise barriers

LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION OF CLASSICTONE 700 ASTM C Type E Mounting. Test Number 2

D. BARD, J. NEGREIRA DIVISION OF ENGINEERING ACOUSTICS, LUND UNIVERSITY

Test Report. RI Acoustic Lab. Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier. 20 Feb. 07

unit 4 acoustics & ultrasonics

Investigations on real-scale experiments for the measurement of the ISO scattering coefficient in the reverberation room

1. Introduction. 2. ISO 3745 and ISO standard comparison

The practical application of G and C 50 in classrooms

LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION COEFFICIENTS OF OSCAR EVO-PANELS

1 BAKER HOUSE DINING: LIGHTING DIAGNOSTIC

Basic Study on a Laboratory Measurement Method of the Normal-Incidence Scattering Coefficient

DELTA Test Report. DANAK TEST Reg. no Measurement of Sound Absorption Coefficient for Kvadrat Soft Cells Wall Panel Type Time

MAC Aura XB Acoustic Test Report

ISO 354 INTERNATIONAL STANDARD. Acoustics Measurement of sound absorption in a reverberation room

Architectural Acoustics Prof. Shankha Pratim Bhattacharya Department of Architecture and Regional Planning Indian Institute of Technology, Kharagpur

Design and Acoustics Brought into Harmony

PROPAGATION, NOISE CRITERIA

Testing Procedure: AS ISO

MEASUREMENTS OF SOUND ABSORPTION TIMBERCRETE

UC Davis - Student Community Center

1. Why do earthquakes happen? 3. What type of mechanical waves are Primary or P waves? 4. What type of mechanical waves are Secondary or S waves?

Last time: small acoustics

ON SOUND POWER MEASUREMENT OF THE ENGINE IN ANECHOIC ROOM WITH IMPERFECTIONS

Modeling Measurement Uncertainty in Room Acoustics P. Dietrich

industry hall : highbay luminaire NJ700 LED Project number : sample system Customer : Processed by : Siteco Light Consulting Date : 07/2013

Ecophon Acoustic Calculator. Accurate values in advance

Technical Report. Project. The Laboratory Determination of The Random Incidence sound Absorption Coefficient of VertiQ Panels.

Part 2: Methods for special reverberation test rooms

Laser scanning vibrometry measurements on a light weight building element

Notes on Absorption and Impedance Measurements

Paseo Recoletos, nº Madrid TEST REPORT

FDTD analysis on the sound insulation performance of wall system with narrow gaps

Chalmers Publication Library

TFI Report Sound Absorption Impact Sound Insulation

Evaluation of standards for transmission loss tests

New techniques in computer aided noise abatement for workplaces next to machinery Wolfgang Probst

Consultancy Report Ref: 9383-R01

(M.K.); (Y.M.) * Correspondence: Tel.

Turbines and turbine sets Measurement of emitted airborne noise Engineering/survey method

DELTA Test Report. Measurement of sound absorption coefficient for 15 mm Fraster felt Plus acoustic panels with mounting depth 45 mm

TFI Report Sound Absorption Impact Sound Insulation

THE ACOUSTIC IMPEDANCE MEASUREMNET SYSTEM USING TWO MICROPHONES

Study of Wenger Audience Seating Chair Absorption. Ron Freiheit

1 Wind Turbine Acoustics. Wind turbines generate sound by both mechanical and aerodynamic

DIFFERENT SOLUTIONS FOR THE ELECTRO ACOUSTIC DIFFUSION SYSTEM IN SAN LORENZO CATHEDRAL IN PERUGIA

ENVIRONMENTAL NOISE IMPACT ASSESSMENT

ACOUSTICS 1.01 Pantone 144 U & Pantone 5405 U

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

Modified wave equation for modelling diffuse sound field

Measurement of sound absorption coefficient for Fraster felt SpaceCover

Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015

Method of Measuring Machinery Sound Within an Equipment Space

Random incidence transmission loss of a metamaterial barrier system

EXPERIMENTAL VERIFICATION OF THE EUROPEAN METHODOLOGY FOR TESTING NOISE BARRIERS IN SITU: SOUND REFLECTION

TFI Report Sound Absorption Impact Sound Insulation

Acoustic Characteristics Analysis of Industrial Premises with Process Equipment

Absorption boundary conditions for geometrical acoustics

Spatial decay rate of speech in open plan offices: the use of D2,S and Lp,A,S,4m as building requirements Wenmaekers, R.H.C.; Hak, C.C.J.M.

Sound power level measurement in diffuse field for not movable sources or emitting prominent discrete tones

Investigations on multi-slope sound energy decays in domed structures

TFI Report Sound Absorption Impact Sound Insulation

Laboratory and In Situ Sound Absorption Measurement under a Synthetized Diffuse Acoustic Field: a Case Study on Five Materials

DELTA Test Report. Measurement of Sound Absorption for AqFlex ON, one Sample as a discrete Object. Performed for Flex Acoustics

HW Set 2 Solutions. Problem 1

New ratings in ISO of plane sound absorbers made for speech communication in classrooms and meeting rooms

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

LABORATORY MEASUREMENTS OF THE REDUCTION OF TRANSMITTED IMPACT NOISE PANETTI OVERLAID BY CONCRETE FLOORING

LABORATORY MEASUREMENT OF SOUND ABSORPTION OF SONOGLASS SPRAY-ON TREATMENT IN THREE CONFIGURATIONS

Absorption modeling with ensemble averaged impedance for wave-based room acoustics simulations

Some issues in measurement of the random-incidence scattering coefficients in a reverberation room

Chapter 17: Waves II. Sound waves are one example of Longitudinal Waves. Sound waves are pressure waves: Oscillations in air pressure and air density

Mapping the sound field of a 400 seat theatre

earthquakes 1. Earthquakes occur when plates grind against one another along cracks called faults.

Laboratory for Acoustics. Determination of the sound absorption (reverberation room method) of Airpanel, manufacturer Texdecor

Geo-identification and pedestrian navigation with geo-mobile applications: how do users proceed?

Measurement of Acoustic Properties of light weight concrete SL-Deck

ISO INTERNATIONAL STANDARD. Acoustics Acoustic insulation for pipes, valves and flanges

Using an ambisonic microphone for measurement of the diffuse state in a reverberant room

Chapter 5 Forward-backward asymmetry: the effect of body position and pointer shapes

Technical Brief 003 Report on the Measurement of Sound Absorption of Planex Linea Storage Units

The Effect of Scenery on the Stage Acoustic Conditions in a Theatre

A suggested method to be used to measure scattering coefficients of full scale samples.

FIFTH INTERNATIONAL CONGRESS ON SOUND AND VIBRATION DECEMBER 15-18, 1997 ADELAIDE, SOUTH AUSTRALIA

Room acoustic modelling techniques: A comparison of a scale model and a computer model for a new opera theatre

A DECOUPLED VIBRO-ACOUSTIC EXTENSION OF NASTRAN

Room Acoustics Experimental Study: Characterization of the Sound Quality in a New Built Church

Contents. Lehman College Department of Physics and Astronomy. Lab manual for PHY 141 Sound, speech and music 1 PENDULUM EXPERIMENT 3

Reciprocity as an Analysing Technique in Building Acoustics

Experimental approach on natural frequency of window vibration induced by low frequency sounds

Transcription:

SIMULATION-SUPPORTED ROOM ACOUSTICS RETROFIT OF OFFICE SPACES Arzu Tugrul, Josef Lechleitner, Matthias Schuß, Ardeshir Mahdavi Department of Building Physics and building Ecology, Vienna University of Technology, Vienna, Austria ABSTRACT This paper addresses the use of performance simulation within the framework of a case study pertaining to room acoustics. The target of the study is an existing office area. The study involves acoustical measurements and simulations, as well as interviews with the occupants before and after acoustical improvement measures. The results of the study contribute to the discussion concerning the effectiveness of acoustical simulation applications and the extent of necessary simulation calibration efforts in modeling the acoustical conditions in existing spaces and prediction of the implications of acoustical retrofit measures. Specifically, they show that simulation model calibration based on preretrofit measurements can substantially improve the quality of simulation's predictions for the post-retrofit conditions. INTRODUCTION The potential benefits of a simulation-aided approach to building design and retrofit have been widely discussed in the past (see, for example, Hensen and Lamberts 2011). The basic idea is to evaluate design intentions a priori using simulation, such that they can be improved and fine-tuned before realization. Currently, the potential of this simulation-aided design support strategy is not being fully exploited. The reasons are multi-faceted. Thereby, usability and reliability concerns with respect to performance simulation applications may play a role. Hence, it would be useful to collect, discuss, and evaluate actual experiences pertaining to the practical cases of simulation deployment in building design, retrofit, and operation. This paper addresses the use of performance simulation within the framework of a case study pertaining to room acoustics. The target of the study was an office area within a university, consisting of closed and open spaces for different functions (workstations, seminar, service spaces). Certain indicators of the room acoustical performance of this office area were obtained based on both measurements and simulations. Subsequently, the simulation models were calibrated using the measurement results. The calibrated simulation models facilitated the prediction of the implication of acoustical retrofit measures. Upon the implementation of on such measure (installation of acoustical absorbers), measurements and simulations were conducted again and the results were compared. Moreover, occupants' subjective evaluation of the acoustical conditions before and after the acoustical retrofit measures were explored as well using appropriate questionnaires. The results of the case study are relevant in view of a number of questions: How effective are acoustical simulation applications in modeling the existing conditions? What are the likely sources of uncertainty in simulation? What is the extent of the calibration needed? Can a calibrated simulation model reliably predict the implications of retrofit measures? The results allow, in addition, the exploration of possible change in the occupants' subjective evaluations of the acoustical conditions as a consequence of the executed retrofit measures. APPROACH The study involved the following steps: i) The existing spaces were documented in view of geometry and material properties. Figure 1 shows a schematic plan of the office area. The study focused on two areas, namely the seminar room (SR) and the open-plan office area (OP). Figures 2 and 3 show the existing conditions in these two areas. ii) Basic acoustical measurements pertaining to reverberation time and sound distribution were conducted to capture the existing acoustical condition. s were conducted with a wireless building acoustic measurement system. For reverberation time measurements in OP, 3 speaker positions and 16 microphone positions were used. For reverberation time measurements in SR, 2 speaker positions and 8 microphone positions were used. For sound distribution measurements in OP, 1 speaker position and 11 microphone positions were used (see Figure 4). For sound distribution measurements in SR, 1 speaker position and 8 microphone positions were used. - 337 -

SR OP Figure 1 Schematic plan of the office area (SR: seminar room; OP: open-plan office area) iii) Occupants were interviewed with respect to their perception of the acoustical conditions. The very small number of interviewed occupants (17) does not allow for a meaningful statistical analysis. Nonetheless, we have included some basic results (tendencies of the expressed opinions and expressions) to provide a general impression of the pre and post retrofit occupancy evaluations. iv) Office spaces were modeled in an advanced room acoustics simulation program (ODEON 2009). Note that a documentation of the acoustical room surface properties (absorption coefficients) did not exist. An in-situ measurement of such properties was also not possible. Thus, assumptions were made based on the surface material types (e.g., plaster, glass, wood) and available general absorption coefficient data in literature (e.g., Fasold and Veres 2003) and the simulation application's database. A summary of these assumptions is given in Table 1. Figure 2 Existing conditions in SR Table 1 Summary of assumptions pertaining to the existing sound absorption properties ( ) of the office area surfaces (included are also the assumed absorption coefficients of the virtual absorbers deployed for model calibration) ELEMENT FREQUENCY [Hz] Floor (wood) 0.04 0.04 0.07 0.06 0.06 0.07 Ceiling (CO) 0.20 0.15 0.10 0.08 0.04 0.02 Ceiling (OP) 0.02 0.02 0.03 0.04 0.05 0.05 Ceiling(SR) 0.02 0.02 0.03 0.04 0.05 0.05 Figure 3 Existing conditions in OP Ex. wall (Brick) Int. wall- (Brick) Int. wall (Gyps. boa.) Window, door(glass) Win. frame (Wood) 0.02 0.02 0.03 0.04 0.05 0.05 0.02 0.02 0.03 0.04 0.05 0.05 0.28 0.14 0.09 0.06 0.05 0.01 0.25 0.15 0.10 0.05 0.03 0.03 0.04 0.04 0.05 0.06 0.06 0.06 Door (wood) 0.20 0.12 0.10 0.07 0.05 0.05 Chairs 0.11 0.35 3 0.63 0.64 7 Virtual absorb. (SR) Virtual absorb. (OP) 0 0.42 0.11 0.15 0.15 0.20 0.68 7 0.24 0.31 0.31 0.32 Figure 4 Speaker and microphone placements for sound distribution measurements - 338 -

v) The simulation model was calibrated using the measurement data. The calibration was based on the comparison of the measured and simulated reverberation times and was realized in terms of virtual surfaces distributed in the office spaces. vi) Existing acoustical conditions were compared with applicable criteria. vii) Acoustical improvement measures in this case, additional absorption were conceived and modeled with the simulation tool. The additional absorption was introduced in the office spaces in terms of panels attached to and suspended from the ceilings, as well as suspended cubical elements. Tables 2 and 3 summarize the sound absorption properties of these elements. ix) Post-retrofit measurements and simulations were performed and compared. x) Occupants were interviewed again in view of the modified acoustical conditions (see also the clarification under point iii above). xi) The results were processed, analyzed, and discussed. viii) The acoustical improvement measures were realized. Figures 5 and 6 show the added absorption elements in the course of the acoustical retrofit. Table 2 Sound absorption ( ) of installed panels ELEMENT FREQUENCY [Hz] Panels 0.29 0.48 7 2 0.86 0.89 Table 3 Equivalent absorption area (in m 2 ) of one cubical element ELEMENT FREQUENCY [Hz] Cub. el. 0.60 1.40 1.80 1.80 0 0 Figure 5 Added absorption elements in SR Figure 6 Added absorption elements in OP RESULTS As noted in the introduction and approach sections, the present research involved data collection pertaining to reverberation times and sound distribution in the office area as well as subjective evaluations by the office users before and after retrofit measures. Figures 7 and 8 show, for SR and OP respectively, the measured values of the reverberation time together with corresponding non-calibrated simulation results. Note that the calibrated simulation results almost exactly match the measurements are thus not explicitly plotted in Figures 7 and 8. As these results show, the existing reverberation times were found to be too long for both SR and OP. Hence, it was concluded that the addition of sound absorbing elements could reduce the reverberation times and improve the room acoustics in the office area. Toward this end, acoustical panels were considered for SR, and a combination of acoustical panels and cubical elements for OP. A reverberation time of around 1.0 s was targeted for the SR (occupied setting). For OP, the targeted reverberation time was around 0.8 s. Figures 9 and 10 show, for SR and OP respectively, the measured and simulated post-retrofit reverberation time values. To illustrate the effect of calibration, these Figures include both non-calibrated and calibrated simulation results. To consider the effect of occupancy in SR, Figure 11 includes calibrated simulation results for the reverberation time under non-occupied and occupied (20 people) conditions. Figures 12 and 13 depict the measured and simulated (non-calibrated and calibrated) sound distribution in OP for pre and post-retrofit cases respectively (nonoccupied conditions). Note that the sound distribution in SR is not shown given the relative small size of the room and homogeneity of sound distribution. Microphone positions were labeled according to their distance to the sound source. Figure 14 shows results of occupants' subjective evaluations with regard to indoor conditions. Figure - 339 -

15 compares pre and post-retrofit percentage of occupants who expressed a specific improvement need. Likewise, Figure 16 documents the pre and post-retrofit degree of expressed annoyance (interference with concentration) due to various noise sources. T60 [s] 125 250 500 1.000 2.000 4.000 Figure 7 Measured and simulated (non-calibrated) reverberation times in SR (non-occupied) Figure 8 Measured and simulated (non-calibrated) reverberation times in OP (non-occupied) Simulation (calibrated) Figure 9 Measured and simulated (non-calibrated and calibrated) post-retrofit reverberation times in SR (non-occupied) Simulation (calibrated) Figure 10 Measured and simulated (non-calibrated and calibrated) post-retrofit reverberation times in OP (non-occupied) Simulation empty Simulation occupied (20 persons) Figure 11 Simulated (calibrated) post-retrofit reverberation times in SR under non-occupied and occupied (20 people) conditions L [db (A)] 96 94 92 90 88 86 84 82 80 Simulation(non-calibrated) Simulation(Calibrated) 1 2 3 4 5 6 7 8 9 10 11 Position Figure 12 Measured and simulated (noncalibrated and calibrated) pre-retrofit sound distribution in OP - 340 -

L [db (A)] 96 94 92 90 88 86 84 82 80 Simulation(non-calibrated) Simulation(calibrated) 1 2 3 4 5 6 7 8 9 10 11 Position Figure 13 Measured and simulated (noncalibrated and calibrated) post-retrofitsound distribution in OP Figure 16 Annoyance levels (negative impact on concentration) due to various noise sources Figure 14 Occupants' subjective evaluations with regard to indoor conditions Better computer/equipment Better furniture Larger office/workplace Better acoustical conditions Better air quality Better lighting conditions Better thermal conditions 0 10 20 30 40 50 Percentage of occupants [%] Pre-retrofit Post-retrofit Figure 15 Percentage of occupants who wished specific improvement measures DISCUSSION AND CONCLUSION The above results warrant a number of observations and conclusions: Simulation results obtained via the noncalibrated simulation model display relatively large errors (see Figures 7 and 8). The errors are most likely due to the uncertainties associated with the assumptions pertaining to the sound absorption coefficients of the room surfaces. As mentioned earlier, a documentation of these coefficients for the existing conditions was not available. Nor was it possible to conduct an insitu measurement of the absorption coefficients. Default assumptions (based on literature, experience, and simulation application's database) may have thus deviated from the "true" surface properties, leading to the aforementioned errors. The calibration process with the virtual absorption elements appears to be quite effective in the trivial sense that, after calibration, simulation results closely match the measurements. The calibration process may be also viewed to be effective in a non-trivial sense: There is a relatively good agreement between simulationbased predictions (based on the calibrated model) and measurement results for postretrofit conditions. This inference is clearly supported by the comparison between the predictions of calibrated and non-calibrated simulation models for the post-retrofit conditions. Predictions based on the noncalibrated model show significantly higher - 341 -

errors than those obtained from the calibrated model (see Figures 9 and 10). With regard to sound distribution, calibrated model predictions and measurement results for pre-retrofit conditions display good agreement (Figure 12). However, for post-retrofit conditions, high deviations are observed at certain positions (Figure 13). The simulation appears to underestimate the occlusion effect (positions 4 and 8) and overestimate direct exposure (positions 5 and 9). As mentioned before, no statistically meaningful inference can be made from the interview results, given the small number of occupants. Nonetheless, the results do seem to suggest a certain improvement regarding the perceived acoustical conditions (see Figure 13). Before retrofit, the acoustical condition was the main occupants' concern when asked about desirable improvements. This circumstance change somewhat after retrofit (see Figure 15). A slight but consistent decrease of expressed noise-induced annoyance levels can be discerned from the results shown in Figure 16. The case study presented thus suggests that the calibration of acoustical simulation models of existing spaces via measurement results can provide an effective way to improve the reliability of the simulation-based assessment of the implications of acoustic retrofit measures in buildings. Specifically, measures necessary to achieve the targeted values of the acoustical performance indicator (in this case, the reverberation times) could be realized and tested virtually using the calibrated simulation model, and implemented subsequently in reality. REFERENCES Fasold, W. and Veres, E. 2003.Schallschutz und Raumakustik In der Praxis. Huss-Medien GmbH Verlag Bauwesen. Berlin, Deutschland. ISBN 3-345-00801-7. Hensen JLM and Lamberts R (editors) 2011. Building performance simulation for design and operation. Spon Press. ISBN13: 978-0-415-47414-6. ODEON 2009.Room acoustics software 9.22 combined version. URL: www.odeon.dk - 342 -