NUMERICAL MODELLING OF TEMPERATURE AND AIR FLOW DISTRIBUTION IN ENCLOSED ROOM

Similar documents
Air Flow Modeling in a Mechanically Ventilated Room

BSE Public CPD Lecture Numerical Simulation of Thermal Comfort and Contaminant Transport in Rooms with UFAD system on 26 March 2010

Environmental Engineering

DYNAMIC INSULATION APPLIED TO THE RESIDENTIAL BUILDING (PART 2) Numerical Evaluation of Thermal Insulation Effect on Air Supply Window System

Thermal behavior and Energetic Dispersals of the Human Body under Various Indoor Air Temperatures at 50% Relative Humidity

A Discussion of Low Reynolds Number Flow for the Two-Dimensional Benchmark Test Case

Proceedings of CLIMA 2000 World Congress, Brussels, Belgium. Simplified Method for Indoor Airflow Simulation

An Evaluation of Turbulence Models for the Numerical Study of Forced and Natural Convective Flow in Atria

Natural convection heat transfer around a horizontal circular cylinder near an isothermal vertical wall

CFD as a Tool for Thermal Comfort Assessment

ROOM AVERAGE VELOCITY EQUATION A TOOL TO IMPROVE DESIGN OF THERMAL COMFORT CONDITIONS

A Simulation Tool for Radiative Heat Exchangers

Thermal environment in indoor spaces with under-floor air distribution systems: 2. Determination of design parameters (1522-

EXPERIMENT AND SIMULATION OF RADIANT/CONVECTIVE SPLIT FROM PASSENGER IN AIRCRAFT CABINS

Building heat system sizing

If there is convective heat transfer from outer surface to fluid maintained at T W.

Prediction of Thermal Comfort and Ventilation Efficiency for Small and Large Enclosures by Combined Simulations

STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION

Calculating equation coefficients

Entropy 2011, 13, ; doi: /e OPEN ACCESS. Entropy Generation at Natural Convection in an Inclined Rectangular Cavity

MATHEMATICAL MODELING OF A COMBINED HOT-WATER HEATING SYSTEM BY MEANS OF THE FINITE ELEMENT METHOD

Study of air curtains used to restrict infiltration into refrigerated rooms

Effect of Static Magnetic Field Application on the Mass Transfer in Sequence Slab Continuous Casting Process

OPERATIVE TEMPERATURE SIMULATION OF ENCLOSED SPACE WITH INFRARED RADIATION SOURCE AS A SECONDARY HEATER

Modelling conjugate flow and heat transfer in a ventilated room for indoor

TankExampleNov2016. Table of contents. Layout

Increasing Energy Efficiency of HVAC Systems in Buildings Using Phase Change Material

EFFECT OF THE INLET OPENING ON MIXED CONVECTION INSIDE A 3-D VENTILATED CAVITY

INTERNAL FLOW IN A Y-JET ATOMISER ---NUMERICAL MODELLING---

Air Diffusion Designing for Comfort

VALIDATION OF CFD ANALYSIS OF NATURAL CONVECTION CONDITIONS FOR A RESIN DRY-TYPE TRANSFORMER WITH A CABIN.

Natural Convection Heat Loss from A Partly Open Cubic Enclosure Timothy N Anderson 1,a * and Stuart E Norris 2,b

ISO 7730 INTERNATIONAL STANDARD

FINITE ELEMENT ANALYSIS OF MIXED CONVECTION HEAT TRANSFER ENHANCEMENT OF A HEATED SQUARE HOLLOW CYLINDER IN A LID-DRIVEN RECTANGULAR ENCLOSURE

Comparison of two equations closure turbulence models for the prediction of heat and mass transfer in a mechanically ventilated enclosure

EXPERIMENTAL SETUP The experimental test-room was representative of a full-sized office space. This was a natural

THERMAL TRANSMITTANCE EVALUATION OF CONCRETE HOLLOW BLOCKS

CFD MODELLING OF CONVECTIVE HEAT TRANSFER FROM A WINDOW WITH ADJACENT VENETIAN BLINDS

EXPERIMENTAL AND SIMULATION TEMPERATURE EVALUATION WHICH DETERMINE THERMAL COMFORT

CAE 331/513 Building Science Fall 2017

A Numerical Investigation on Active Chilled Beams for Indoor Air Conditioning

NUMERICAL STUDY OF HEAT AND MASS TRANSFER DURING EVAPORATION OF A THIN LIQUID FILM

ENHANCED MODELLING OF INDOOR AIR FLOWS, TEMPERATURES, POLLUTANT EMISSION AND DISPERSION BY NESTING SUB-ZONES WITHIN A MULTIZONE MODEL

Optimization of the Air Gap Spacing In a Solar Water Heater with Double Glass Cover

Iterative calculation of the heat transfer coefficient

DEFINING THE PERFORMANCE OF THE DOUBLE SKIN FAÇADE WITH THE USE OF THE SIMULATION MODEL

THREE-DIMENSIONAL MIXED CONVECTION HEAT TRANSFER IN A PARTIALLY HEATED VENTILATED CAVITY. Corresponding author;

Natural Ventilation. CFD modelling of a double-skin facade. Huw Birch. Supervisor: Abigail Hathway

Development of a Simplified Cooling Load Design Tool for Underfloor Air Distribution (UFAD) Systems

METHODOLOGY (3) where, x o is the heat source separation and α is the. entrainment coefficient α.

NUMERICAL ANALYSIS OF THERMAL COMFORT PARAMETERS IN LIVING QUARTERS

Transient Analysis of the Buoyancy Driven Flow in a Passive Solar System for Indoor Heating

Numerical simulation of human thermal comfort in indoor environment

FORMULA SHEET. General formulas:

Turbulent Natural Convection in an Enclosure with Colliding Boundary Layers

Qasim Hammodi Hassan*, Sabah Tarik Ahmed**, Ala'a Abbas Mahdi***

SELF-SUSTAINED OSCILLATIONS AND BIFURCATIONS OF MIXED CONVECTION IN A MULTIPLE VENTILATED ENCLOSURE

Vector and scalar variables laminar natural convection in 2D geometry arbitrary angle of inclination

INFLUENCE OF THE GEOMETRICAL PARAMETERS OF URBAN CANYONS ON THE CONVECTIVE HEAT TRANSFER COEFFICIENT

Study of the Aeraulic Flows in a Building Including Heating and Air Conditioning Systems

International Journal of Scientific & Engineering Research, Volume 6, Issue 5, May ISSN

Heat Transfer Convection

Convection Workshop. Academic Resource Center

C ONTENTS CHAPTER TWO HEAT CONDUCTION EQUATION 61 CHAPTER ONE BASICS OF HEAT TRANSFER 1 CHAPTER THREE STEADY HEAT CONDUCTION 127

PERIODICALLY FULLY DEVELOPED LAMINAR FLOW AND HEAT TRANSFER IN A 2-D HORIZONTAL CHANNEL WITH STAGGERED FINS

Computer Evaluation of Results by Room Thermal Stability Testing

CFD-SIMULATIONS OF TRANSPARENT COATED AND GAS-FILLED FACADE PANELS

Energy and Buildings

Summary of Dimensionless Numbers of Fluid Mechanics and Heat Transfer

NUMERICAL ANALYSIS OF MIXED CONVECTION CHARACTERISTICS INSIDE A VENTILATED CAVITY INCLUDING THE EFFECTS OF NANOPARTICLE SUSPENSIONS

ELEC9712 High Voltage Systems. 1.2 Heat transfer from electrical equipment

THERMAL COMFORT SIMULATION IN MODERN AIRCRAFT COCKPITS

Numerical studies on natural ventilation flow in an enclosure with both buoyancy and wind effects

The energy performance of an airflow window

True/False. Circle the correct answer. (1pt each, 7pts total) 3. Radiation doesn t occur in materials that are transparent such as gases.

Level 7 Post Graduate Diploma in Engineering Heat and mass transfer

Heat transfer enhancement in natural convection in micropolar nanofluids

THE EFFECTS OF LONGITUDINAL RIBS ON ENTROPY GENERATION FOR LAMINAR FORCED CONVECTION IN A MICROCHANNEL

Computational Modelling of the Impact of Solar Irradiance on Chemical Degradation of Painted Wall Hangings in an Historic Interior

Influence of Heat Transfer Process in Porous Media with Air Cavity- A CFD Analysis

Numerical Study of Free Convection Heat Transfer in a Square Cavity with a Fin Attached to Its Cold Wall

Modelling interfacial heat transfer in a 2-phase flow in a packed bed

COMPUTATIONAL ANALYSIS OF LAMINAR FORCED CONVECTION IN RECTANGULAR ENCLOSURES OF DIFFERENT ASPECT RATIOS

Comparison of STAR-CCM+ and ANSYS Fluent for Simulating Indoor Airflows

Combined Natural Convection and Thermal Radiation in an Inclined Cubical Cavity with a Rectangular Pins Attached to Its Active Wall

Laminar flow heat transfer studies in a twisted square duct for constant wall heat flux boundary condition

Aalborg Universitet. Comparison between Different Air Distribution Systems Nielsen, Peter Vilhelm. Publication date: 2006

NATURAL CONVECTION HEAT TRANSFER IN PARTIALLY OPEN ENCLOSURES CONTAINING AN INTERNAL LOCAL HEAT SOURCE

STUDY OF A PASSIVE SOLAR WINTER HEATING SYSTEM BASED ON TROMBE WALL

il'h:t\.gy ;.\ND flujldjl'jg$ ELSEVIER Energy and Buildings 33 (2000)

Principles and Applications of Building Science Dr. E Rajasekar Department of Civil Engineering Indian Institute of Technology, Roorkee

Chapter 3 NATURAL CONVECTION

NUMERICAL SIMULATION OF FLOW AND HEAT TRANSFER AROUND VERTICAL CYLINDER SUBMERGED IN WATER

Studies on flow through and around a porous permeable sphere: II. Heat Transfer

Atrium assisted natural ventilation of multi storey buildings

TOWARDS A MORE RELIABLE MODELLING OF NIGHT-TIME VENTILATION WITH BUILDING ENERGY SIMULATION MODELS

Available online at ScienceDirect. Energy Procedia 69 (2015 )

CZECH TECHNICAL UNIVERSITY IN PRAGUE FACULTY OF MECHANICAL ENGINEERING DEPARTMENT OF ENVIRONMENTAL ENGINEERING

MODELLING THERMAL COMFORT FOR TROPICS USING FUZZY LOGIC

Effect of Shape and Flow Control Devices on the Fluid Flow Characteristics in Three Different Industrial Six Strand Billet Caster Tundish

Transcription:

NUMERICAL MODELLING OF TEMPERATURE AND AIR FLOW DISTRIBUTION IN ENCLOSED ROOM Igor Bonefacic 1, Bernard Frankovic 2, Ivan Vilicic 3, Vladimir Glazar 4 Faculty of Engineering, Vukovarska 58, Rijeka, Croatia, e-mail: 1 igor.bonefacic@riteh.hr, 2 bernard.frankovic@riteh.hr, 3 ivan.vilicic@riteh.hr, 4 vladimir.glazar@riteh.hr In the paper three-dimensional case of heat transfer and air flow has been presented for enclosed space heating and cooling with unit mounted on the wall. Numerical modelling has been used to analyze effect of space height on temperature and air velocity distribution under standard conditions. Physical processes in two rooms with different heights are modelled using specialized computational fluid dynamics (CFD) software FLUENT. Calculations are carried out in an empty room without any human or mechanical activity and compared with previous experimental measurements. Numerical analysis has shown distinct relationship between room dimensions (height in this case) and state of comfort in the room. Although average values of temperature and air velocity in the room are satisfactory there are local distortions from the standard optimal comfort values. Considerable differences in temperature distribution are observed especially in heating conditions where temperature drop in lower layers of higher room occur due to buoyancy effects. To cancel buoyancy effects it is necessary to increase air inlet velocity from the unit which could lead to local air velocity distortions resulting with disturbed optimal comfort values. 1. Introduction Primary goal during air-condition designing of enclosed working space is to find adequate microclimate for people residing in that room. Basically, it means that state of thermal comfort has to be achieved. That implies thermodynamical balance between human body and the environment during different physical activities. Physical quantities of greatest relevance for microclimate are air temperature in the room, air humidity, local air velocity and surface temperature of surrounding walls, windows and heating surfaces. In recent years, extensive research effort has been made in the development of general fluid flow and heat transfer programs for solving the flow of air in a room. Similar studies had been carried out, Lee et al.(1997) applied the Finite element method to study the characteristics of forced and mixed convection in an air-cooled room for both the laminar and turbulent regimes, Sinha (2001) deals with case of two-dimensional numerical prediction of an airfow configuration in a room (enclosure) with inlet and outlet as applicable to cooling and ventilation. Three-dimensional model of a computer room with regard to thermal comfort was presented by Richtr et al. (2001) using standard k-ε turbulence model for modelling air flow. Rutman et al. (2002) give extensive view on using numerical modelling tools for improving indoor environment quality, component optimisation and complete system optimisation.

Air temperature A general recommendation for design of heating and cooling processes for working offices and enclosed areas, where no major physical activities are carried out, is that the temperature has to be held constant in between 21-23 C. During summertime, when outdoor temperatures are higher, it is advisable to keep air-conditioned offices slightly warmer then in winter periods to minimize the high temperature difference between indoors and outdoors. Recommendation is that difference should not be higher than 7 C. Thermal comfort depends also on vertical temperature distribution in the room. Allowed vertical air temperature difference between 1.1m and 0.1m above the floor (head and ankle respectively of the person in sitting position) or between 1.7m and 0.1m above floor (head and ankle respectively of the person in upright position) is less than 3 C (ISO 7730-1994). ). According to Zukowski (2003), the most comfortable state is that where floor temperature is the same or slightly higher than air temperature in head level. Mean Radiant Temperature State of thermal comfort cannot be determined simply by knowing air temperature in the room. It is known fact that at least 50% of all thermal energy between the environment and a human body exchanges through radiation. A human body is constantly exchanging radiant heat with all objects that surrounds it due to temperature difference between them. Mean Radiant Temperature (MRT) of a space is really the measure of the combined effects of temperatures of surfaces within that space on human body. A scale of seven degrees from 3 to +3 can be used to measure thermal sensation based on the scale of ASHRAE (1992) and Nagano, Morchida (2004). The larger the surface area and the closer one is to it, the more effect the surface temperature has on the individual. MRT thus changes with position in the room and with it corresponding air temperature which provides thermal comfort. In general if MRT drops by 1 C, air temperature has to be raised by 1-1.5 C. Air velocity (draft) Air flow velocity is important factor in determining thermal comfort because increased air velocity can cause discomfort due to increased convective heat transfer from surface of a human body. ISO 7730-1994 limits local air flow velocity in offices and spaces where no major physical activites occur at 0.15 m/s during winter periods (heating) and 0.25 m/s during summer (cooling). Sense of draft is more pronounced with decreased phyisical activity. Also, discomfort caused by draft increases with air temperature drop. Contrary, if air velocity in enclosed space is to low it could couse feeling of stuffiness and bad odour especially in winter (heating) periods. It is, therefore, necessary to assure optimal level of air circulation in the room.

2. Mathematical model The problem is solved using mathematical model of threedimensional turbulent flow of uncompressible fluid which is described using general differential equation: ( ρφ) + ( ρuiφ ) = Γ + Sφ t xi x i x, (1) i where variable φ represents velocity components u, v, w and temperature T. The importance of buoyancy forces in a mixed convection flow can be measured by the ratio of the Grashof and Reynolds numbers: Gr 2 Re Δρgh =, (2) 2 ρv which exceeds unity, showing that strong buoyancy effects in the flow could be expected. Performances of different turbulence models in similar studies were examined in Rouaud, Havet (2002). Turbulence was modeled using realizable k-ε model which consist of transport equation for turbulent kinetic energy k, and its dissipation rate ε. x i x i μ k i σ k b, (3) xi k x j 2 μt ε ε ε ρεui = μ ρc2 + C1 ε C3 ε G x + i σ. (4) ε x j k + νε k t ( ρku ) = μ + + G + G ρε ( ) b In these equations G b represents generation of turbulence kinetic energy due to buoyancy effects. C 2, C 1ε and C 3ε are constants. σ k and σ ε are the turbulent Prandtl numbers for k and ε, respectively (FLUENT Inc., 1998). System of transport equations was solved using CFD software FLUENT based on finite volume method (Patankar, 1980). 3. Boundary conditions 3.1. SUMMER Constant air inlet velocity boundary condition: v in =2,0 m/s, T in =293 K, φ = 0 (Air flow inlet angle).

Picture 1. Simulated enclosed room Heat transfer due to convection and radiation is defined by: 4 4 T TZ q = α V ( TV TZ ) + ε V σ, (5) 100 100 where is: α V - Convection heat transfer coefficient at the external wall surface; T V - External air temperature; T Z - External wall surface temperature; T - External radiation temperature; ε V - External emissivity; σ - Stefan-Boltzmann's constant. 3.2. WINTER Constant air inlet velocity boundary condition: v in =1,7 m/s, T in =300 K, φ = 45 (Air flow inlet angle).

Convective heat transfer is defined by: q = α T T ). (6) V ( V Z 4. Simulation results 4.1. SUMMER Picture 2. Temperature field for rooms with different heights, 2.5m (left) and 3m (right) Picture 3. Vertical temperature distribution in the middle of the room Picture 4. Air velocity field

4.2. WINTER Picture 5. Temperature field for rooms with different heights, 2.5m (left) and 3m (right) Picture 6. Vertical temperature distribution in the middle of the room Picture 7. Air velocity field 5. Conclusion In this work heating and cooling of the enclosed room is simulated (Picture 1). Numerical analysis based on finite volume method is used to solve threedimensional unsteady flow in enclosed space and resulting temperature distribution and air velocity field for two rooms with different height is given. Analysis shows strong influence of a/c unit position and room geometry (room height in this case) on thermal comfort. Despite the fact that mean values of

temperature and air flow velocity are satisfactory there are some deviations in local values. Results of numerical analysis show considerable differences in temperature distribution beetwen rooms with different height especially in winter period (Picture 5). In case of 3m high room the warm air cannot reach lower levels due to buoyancy and as result local air temperature below 1m from the floor is not satisfactory (Picture 6). To compensate for buoyancy effects it is necessary to increase air inlet velocity from the unit which, on the other hand, leads to disturbed thermal comfort because of draft. Conducted numerical analysis can be relatively easy expanded on similar technical problems from the field of heating, ventilation and climatization. It could inlude humidity or calculation of mean radiant temperature (MRT). Also, time dependent boundary conditions could be included which leads to more realistic simulations allowing analysis of system regulation. Major limiting factor for simulating more complex problems is, of course, available CPU power i.e. calculation time. NOMENCLATURE C - constant g - acceleration due to gravity, m/s 2 G - generation of turbulent kinetic energy, kg/ms 3 h - height, m k - turbulence kinetic energy, m 2 /s 2 q - heat flux, W/m 2 S - source term t - time, s T - temperature, K u,v,w - velocity components, m/s x,y,z - Cartesian coordinates, m greek letters α - heat transfer coefficient, W/m 2 K Γ - diffusivity ε - turbulent dissipation rate, m 2 /s 3 ε - emissivity μ - dynamic viscosity, Pa s ν - kinematic viscosity, m 2 /s ρ - density, kg/m 3 σ - Stefan-Boltzmann constant, 5.67 10 8 W/m 2 K 4 σ k - turbulent Prandtl number for k σ ε - turbulent Prandtl number for ε φ - angle, Φ - transported scalar subscripts in - Z - V - inlet wall external

REFERENCES Rutman, E., Fournier, F., Jurkowski, R., Bailly, A., Franković, B., Viličić, I., 2002, Industrial Approach for CFD Modelling Applications for Air-conditioning and Heat Exchanger Systems, Energy and the Environment 2002, Vol. 2, Opatija, Croatia, pp.11-18 Lee, S.C., Cheng, C.Y., Chen, C.K., 1997, Finite elements solutions of laminar and turbulent flows with forced and mixed convection in an air-cooled room, Numerical Heat Transfer, Part A, 31, pp. 529 50. Sinha, S. L., 2001, Behaviour of Inclined Jet on Room Cooling, Building and Environment 36, pp. 569-578. Richtr, J., Katolicky, J., Jicha, M., 2001, Numerical modeling of the influence of angle adjustment of A/C diffuser vanes on thermal comfort in a computer room, Seventh International IBPSA Conference, Rio de Janeiro, Brazil, pp. 1135-1141. Zukowski, M., 2003, A Numerical Analisys of Heat and Mass Transfer in a Room with the Air-Underfloor Heating, 8th International IBPSA Conference, Bialystok Technical University, Poland. ASHRAE ANSI/ASHRAE Standard 55-1992 Thermal environmental conditions for human occupancy, 1992. FLUENT 6.1 User's Guide, FLUENT Inc., 1998. Rouaud, O., Havet, M., 2002, Computation of the Airflow in a Pilot Scale Clean Room Using k-ε Turbulence Models, International Journal of Refrigeration 25, pp. 351-361. Patankar, S.V., 1980, Numerical heat transfer and Fuid Flow, Washington DC, Hemisphere.