State Estimation and Power Flow Analysis of Power Systems

Similar documents
Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

CHAPTER 2 LOAD FLOW ANALYSIS FOR RADIAL DISTRIBUTION SYSTEM

Power System Security Analysis. B. Rajanarayan Prusty, Bhagabati Prasad Pattnaik, Prakash Kumar Pandey, A. Sai Santosh

An Equivalent Circuit Formulation of the Power Flow Problem with Current and Voltage State Variables

Enhanced Newton Method Based Radial Distribution System Load Flow Analysis with Extrapolation Techniques

Power Flow Analysis of Radial Distribution System using Backward/Forward Sweep Method

Fine Tuning Of State Estimator Using Phasor Values From Pmu s

State estimation in distribution grids

ELEC4612 Power System Analysis Power Flow Analysis

Understanding Load Flow Studies by using PSAT

Quasi-Newton Power Flow Using Partial Jacobian Updates

A COMPUTER PROGRAM FOR SHORT CIRCUIT ANALYSIS OF ELECTRIC POWER SYSTEMS

Extension of a Probabilistic Load Flow Calculation Based on an Enhanced Convolution Technique

A Novel Technique to Improve the Online Calculation Performance of Nonlinear Problems in DC Power Systems

LINE FLOW ANALYSIS OF IEEE BUS SYSTEM WITH THE LOAD SENSITIVITY FACTOR

KINGS COLLEGE OF ENGINEERING Punalkulam

SECTION 5: POWER FLOW. ESE 470 Energy Distribution Systems

Performance analysis and comparison of load flow methods in a practical distribution system

Two-Layer Network Equivalent for Electromagnetic Transients

Introduction to State Estimation of Power Systems ECG 740

A DC Power Flow Extension

Smart Grid State Estimation by Weighted Least Square Estimation

Fast Decoupled Power Flow for Unbalanced Radial Distribution Systems

EE 581 Power Systems. Admittance Matrix: Development, Direct and Iterative solutions

PowerApps Optimal Power Flow Formulation

= V I = Bus Admittance Matrix. Chapter 6: Power Flow. Constructing Ybus. Example. Network Solution. Triangular factorization. Let

ECE 476. Exam #2. Tuesday, November 15, Minutes

Simulating a Power System

A LOOP BASED LOAD FLOW METHOD FOR WEAKLY MESHED DISTRIBUTION NETWORK

Optimal DG allocation and sizing in a Radial Distribution System using Analytical Approach

Modelling and Simulation of TCPAR for Power System Flow Studies

The Existence of Multiple Power Flow Solutions in Unbalanced Three-Phase Circuits

Weighted Least Squares Topology Error Detection And Identification

A Term Project report on. State Estimation of Power Systems Using Weighted Least Squares Optimization Technique

1 Unified Power Flow Controller (UPFC)

The N k Problem using AC Power Flows

MEASUREMENTS that are telemetered to the control

Farzaneh Ostovar, Mahdi Mozaffari Legha

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

Real Time Voltage Control using Genetic Algorithm

FLEXIBLE ac transmission system (FACTS) devices give

Fault Locating PRESENTED BY ERIK SCHELLENBERG IDAHO POWER

Security Monitoring and Assessment of an Electric Power System

STATE ESTIMATION IN DISTRIBUTION SYSTEMS

Analyzing the Effect of Loadability in the

New criteria for Voltage Stability evaluation in interconnected power system

IN RECENT years, an instability, usually termed a voltage

Cyber Attacks, Detection and Protection in Smart Grid State Estimation

Generalized Injection Shift Factors and Application to Estimation of Power Flow Transients

Optimal Capacitor Placement in Distribution System with Random Variations in Load

DEVELOPING methods and techniques to quantify the

An Novel Continuation Power Flow Method Based on Line Voltage Stability Index

Optimal Performance Enhancement of Capacitor in Radial Distribution System Using Fuzzy and HSA

Real power-system economic dispatch using a variable weights linear programming method

Simultaneous placement of Distributed Generation and D-Statcom in a radial distribution system using Loss Sensitivity Factor

EE5250 TERM PROJECT. Report by: Akarsh Sheilendranath

Appendix A Solving Systems of Nonlinear Equations

The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of Unbalanced Three Phases Electrical Distribution System

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

Comparison of Loss Sensitivity Factor & Index Vector methods in Determining Optimal Capacitor Locations in Agricultural Distribution

A PROPOSED STRATEGY FOR CAPACITOR ALLOCATION IN RADIAL DISTRIBUTION FEEDERS

Role of Synchronized Measurements In Operation of Smart Grids

Branch Outage Simulation for Contingency Studies

Optimal Compensation of Reactive Power in Transmission Networks using PSO, Cultural and Firefly Algorithms

Comparison between Interval and Fuzzy Load Flow Methods Considering Uncertainty

Harmonic Modeling of Networks

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur. Lecture - 21 Power Flow VI

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

NONLINEAR DC ANALYSIS

PROPOSED STRATEGY FOR CAPACITOR ALLOCATION IN RADIAL DISTRIBUTION FEEDERS

Order Reduction of the Dynamic Model of a Linear Weakly Periodic System Part II: Frequency-Dependent Lines

Performance Improvement of the Radial Distribution System by using Switched Capacitor Banks

CHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS

Power Flow Formulation Based on a Mixed-Linear and Nonlinear System of Equations

J. Electrical Systems x-x (2010): x-xx. Regular paper

False Data Injection Attacks Against Nonlinear State Estimation in Smart Power Grids

TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEM USING UPFC AND FEEDBACK LINEARIZATION CONTROL

Estimating Feasible Nodal Power Injections in Distribution Networks

Improving Transient Stability of Multi-Machine AC/DC Systems via Energy-Function Method

An Improved Method for Determining Voltage Collapse Proximity of Radial Distribution Networks

Analytical Study Based Optimal Placement of Energy Storage Devices in Distribution Systems to Support Voltage and Angle Stability

Elevated Neutral to Earth Voltages Due to Harmonics A T&D Update

AC Circuit Analysis and Measurement Lab Assignment 8

An Efficient Decoupled Power Flow Control Method by use of Phase Shifting Transformers

Effect of Various Holomorphic Embeddings on Convergence Rate and Condition Number as Applied to the Power Flow Problem

DISTURBANCE LOAD MODELLING WITH EQUIVALENT VOLTAGE SOURCE METHOD IN GRID HARMONIC ASSESSMENT

Voltage Dividers, Nodal, and Mesh Analysis

Tutorial 2: Modelling Transmission

ECEN 615 Methods of Electric Power Systems Analysis Lecture 18: Least Squares, State Estimation

Optimal Placement of Multi DG Unit in Distribution Systems Using Evolutionary Algorithms

Chapter 2 Voltage-, Current-, and Z-source Converters

WHEN studying distributed simulations of power systems,

Harmonic Domain Periodic Steady State Modeling of Power Electronics Apparatus: SVC and TCSC

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

OPTIMAL POWER FLOW (OPF) is a tool that has been

POWER flow studies are the cornerstone of power system

A NEW STATE TRANSITION MODEL FOR FORECASTING-AIDED STATE ESTIMATION FOR THE GRID OF THE FUTURE

VOLTAGE stability has become a major concern for the

Reactive Power Solutions

Transcription:

JOURNAL OF COMPUTERS, VOL. 7, NO. 3, MARCH 01 685 State Estimation and Power Flow Analysis of Power Systems Jiaxiong Chen University of Kentucky, Lexington, Kentucky 40508 U.S.A. Email: jch@g.uky.edu Yuan Liao University of Kentucky, Lexington, Kentucky 40508 U.S.A. Email: yliao@engr.uky.edu Abstract State estimation and power flow analysis are important tools for analysis, operation and planning of a power system. In this paper, a new state estimation method based on the extended weighted least squares (WLS) method for considering both measurement errors and model inaccuracy is presented. Two bus, three bus, and IEEE 14 bus test cases are employed to evaluate the accuracy of the method. The comparison results show that the extended WLS method may outperform traditional WLS approach when the model is not accurate. In addition, this paper investigates a method based on Z matrix to implement power flow in a transmission system with multiple types of loads (e.g. constant PQ, constant impedance and constant current magnitude loads or mixed loads). The load flow results demonstrate that the method is effective and easy to implement when composite load types exist in the system. Our studies also show that it may be possible that multiple solutions exist for a power flow problem. Index Terms State estimation, Power flow analysis, Weighted least squares method I. INTRODUCTION Weighted least squares (WLS) state estimation (SE) approach has been an important tool for determining the optimal estimate of power system states [1]. The power network model used in the function relating the measurements to the states in WLS SE is implicitly assumed to be exact. However, the real model may contain two types of errors: parametric and nonparametric errors []. Parametric errors are errors that occur in circuit parameters such as the resistance and reactance of the transmission lines. Non-parametric errors could occur when utilizing a DC load flow model instead of a full AC model, or using approximate positive sequence impedance for representing untransposed lines, etc. Various approaches have been proposed to account for inaccuracy in network parameters, for example, by augmenting the state vector with addition of the suspicious parameters and augmenting the Jacobian matrix at the same time, or by utilizing Kalman filtering theory [3]. However, due to limited measurements, these approaches may not always be possible to identify all suspicious parameters or accurately estimate these parameters in order to alleviate non-parametric errors. Various approaches for distinguishing measurement errors from model errors in the context of errors-invariable model are discussed in paper [4]. The author of [5] proposes an approach called extended least squares for estimating parameters of pseudo-linear models. This approach is firstly applied to power system state estimation in paper [] for considering both potential measurement errors and model errors. This paper further investigates its characteristics and evaluates its effectiveness. Both simple power system cases and a larger power system IEEE 14 bus test case are utilized. The power flow study (also known as load-flow study) has been widely applied to power systems for system planning, operating and control. Over the past decades, researchers have made an enormous amount of efforts to develop numerical power flow calculation approaches. The paper in [6] gives a review and comparison of power flow calculation methods, including Y-matrix, Z-matrix, and Newton methods. The authors of [7] develop a method based on Z matrix which converges more reliably than Y-matrix methods. In all the above methods, the type of loads is usually considered as constant PQ load. However, in reality, there are other types of loads, such as constant impedance load, constant current magnitude load, and mixed two and more types of loads. This paper will examine the effectiveness of Z matrix based power flow method to account for multiple types of loads in the transmission system. II. WLS METHODS A. Traditional WLS Method The system measurement equation is as follows [1]: z = h(x) + e (1) where: z is the (m x 1) measurement vector; x is the an (n x 1) state vector to be estimated; h is a vector of nonlinear functions that relate the states to the measurements; and e is an (m x 1) measurement error vector. It is necessary that m n and the Jacobian matrix of h(x) has rank n. doi:10.4304/jcp.7.3.685-691

686 JOURNAL OF COMPUTERS, VOL. 7, NO. 3, MARCH 01 The optimal state estimate vector x may be determined by minimizing the sum of weighted squares of residuals Min F(x) = [z h(x)] T R 1 [z h(x)] () where, R is the measurement covariance matrix. () is linearized using the Taylor series expansion, retaining the first two terms and ignoring higher-order terms. This leads to a linear WLS problem having the solution x = (H T R 1 H) 1 H T R 1 z (3) where, H is the Jacobian matrix of h(x). The iterative approach is applied to obtain the state update until the absolute value of the difference of the states between successive iterations is less than the tolerance value ε, typically, ε is set to 1e-4. The function h(x) can be linear or nonlinear. H is a constant matrix (m n) in the case of linear function, and it needs only one iteration to converge. Alternatively, the solution to () can be obtained as follows: III. CASE STUDIES OF STATE ESTIMATION This section presents case studies for evaluating the state estimation methods presented in Section II. A. Case Study Utilizing a Three-Bus System Based on DC Load Flow Model Figure 1 shows a sample system with branch impedances labeled in per unit. The correct value of R 1 is 0.5j, however, for some reason, the model database shows 0.3j. The reason for this mistake might be the model database was not updated accordingly after the series compensation capacitor on the line was switched off. Table 1 gives the measurement data. All the meter readings are in per unit based on 100 MW base. The bus voltage angle δ 1 at bus 1, δ at bus and line flows at meter locations need to be estimated. x = (H T R 1 H) 1 H T R 1 z (4) B. The New Extended WLS Method Let the new state vector be X new = X, with z being z the true value or best estimate of the measurement z. Hence, equation (1) is expanded as follows []. U z = h(x) z + ε (5) z e where, U is the (m 1) zero vector, m is total number of measurements, ε is the (m 1) model mismatch error vector, and e is the (m 1) measurement error vector. Define z new = U z, F new(x new ) = h(x) z, η z new = ε e. Therefore we obtain z new = F new (X new ) + η new (6) The cost function, consisting of weighting matrix W ε due to model mismatches, and weighting matrix W e due to measurement error, is defined as follows []: f(x) = [z h(x)] T W ε [z h(x)] + [z z ] T W e [z z ] (7) It is note that F new (X new ) = H new X new. where, H new = H I, I is an (m m) identity matrix, O I and O is a (m n) zero matrix. Figure 1. A three-bus sample power system TABLE 1. MEASUREMENT DATA FOR SYSTEM IN FIGURE 1 Quantity measured from bus 1 to from bus 1 to 3 from bus 3 to Metering Error Meter point variance reading M1 0.0001 0.7 M 0.0001 0.09 M3 0.0001 0.65 According to DC state estimation model, power flow equations can be expressed as follows: p 1 = (δ 1 δ )/R 1 (8) p 13 =.5δ 1 (9) p 3 = 5δ (10) where, p 1, p 13 and p 3 represent real power flow from bus 1 to, from bus 1 to 3, and from bus 3 to, respectively. The H new, obtained using 0.5j and 0.3j can be expressed as follows, respectively. 4 4.5 0 H new_0.5 = 0 5 0 0 1 0 0 0 1 0 0 0 1 1 0 0 0 1 0 0 0 1 (11)

JOURNAL OF COMPUTERS, VOL. 7, NO. 3, MARCH 01 687 1/0.3 1/0.3.5 0 H new_0.3 = 0 5 0 0 1 0 0 0 1 0 0 0 1 1 0 0 0 1 0 0 0 1 (1) The error variances for model mismatches are assumed to take the same values in the extended WLS method. Table shows the estimated results by using the correct R 1. The estimated voltage angles are the same for the two methods, while the estimated power flows by the extended WLS method are much closer to the meter readings than the traditional WLS method. The estimated voltage angles and power flows by using the mistaken R 1 are shown in Table 3. The traditional WLS approach results in large errors in the estimate for power flows, while the extended WLS approach achieves more accurate results. TABLE. ESTIMATED VOLTAGE ANGLES AND POWER FLOW USING R 1 = 0.5j δ 1 δ 1 13 3 Traditional WLS 0.0445-0.131 0.7067 0.1113 0.6607 Extended WLS 0.0445-0.131 0.7133 0.1007 0.6553 TABLE 3. ESTIMATED VOLTAGE ANGLES AND POWER FLOW USING R 1 = 0.3j δ 1 δ 1 13 3 Traditional WLS 0.0636-0.1369 0.6683 0.1590 0.6845 Extended WLS 0.0636-0.1369 0.6941 0.145 0.667 B. Case Study Utilizing a Two-Bus System Based on AC Load Flow Model This section presents a case study based on AC load flow measurement Jacobian H A. Figure shows a twobus sample power system, with branch impedances labeled in per unit. The correct value of the line impedance is 0.4j, however somehow, the data model database shows a value of 0.5j. Figure. A Two-bus Sample Power System TABLE 4. MEASUREMENT DATA FOR SYSTEM IN FIGURE Quantity measured Metering point Error variance Meter reading magnitude at bus 1 M1 0.0001 1.0 magnitude at bus M 0.0004 0.93 from bus 1 to M1 0.0001 1.97 received at bus M 0.0004-1.97 from bus 1 Reactive power from bus 1 to M1 0.0009 1.08 The states that need to be estimated are voltage magnitudes at bus 1 and bus and voltage angle at bus. Table 4 gives the measurement data in per unit. Based on Figure and Table 4, the system equations can be expressed as follows: h 1 = V 1 (13) h = V (14) h 3 = V 1 V sinδ/r 1 (15) h 4 = V 1 V sinδ/r 1 (16) h 5 = V 1 /R 1 V 1 V cosδ/r 1 (17) where, R 1 is line impedance between bus 1 and. V 1 is voltage magnitude at bus 1. V is voltage magnitude at bus. δ is the voltage angle at bus. Functions h 1, h, h 3, h 4 and h 5 represent the bus 1 voltage magnitude, bus voltage magnitude, real power from bus 1 to measured at bus 1, real power received at bus from bus 1 measured at bus, and reactive power from bus 1 to measured at bus 1, respectively. Table 5 and 6 show the estimation results obtained by using R 1 = 0.4j and R 1 = 0.5j, respectively. The variances for the model mismatches are set to 1e-6, 1e-6, 1e-1, 1e-1 and 1e-1 corresponding to equations (13), (14), (15), (16) and (17), respectively. The results yielded by the extended WLS are much closer to the meter readings than the traditional approach. Table 7 illustrates the effects of the variances of model mismatches on the estimation results by using the incorrect line impedance for different variances. From the last row of the table, it is seen that when the variances are properly chosen, more accurate estimate can be obtained by the extended WLS approach. Note that if the error variances for model mismatches are set to be small enough in both DC and AC load flow based studies, then both approaches will result in the same results.

688 JOURNAL OF COMPUTERS, VOL. 7, NO. 3, MARCH 01 TABLE 5. ESTIMATED VOLTAGES AND POWER FLOW USING R 1 = 0.4j FOR THE TWO-BUS SYSTEM 1 Angle of bus from bus 1 to received at bus Reactive power form bus 1 to Traditional WLS 1.0175 0.9696-0.936 1.9675-1.9675 1.1011 Extended WLS 1.0196 0.9343-0.86 1.9698-1.9694 1.085 TABLE 6. ESTIMATED VOLTAGES AND POWER FLOW USING R 1 = 0.5j FOR THE TWO-BUS SYSTEM 1 Angle of bus from bus 1 to received at bus Reactive power form bus 1 to Traditional WLS 1.053 1.063-1.1158 1.9583-1.9583 1.144 Extended WLS 1.001 0.934-1.1450 1.9698-1.9691 1.0819 TABLE 7. ESTIMATED VOLTAGES AND POWER FLOW USING R 1 = 0.5j FOR THE TWO-BUS SYSTEM Variances for model mismatches 1 Angle of bus from bus 1 to received at bus Reactive power form bus 1 to 1/[1e6 1e6 1e 1e 1.009 0.966-1.1389 1.968-1.969 1.0950 1e] 1/[1e6 1e6 1e1 1e1 1.001 0.934-1.1450 1.9698-1.9691 1.0819 1e1] 1/[1e6 1e6 1 1 1] 1.000 0.9304-1.1457 1.9700-1.9699 1.080 C. Case Study Utilizing IEEE 14 Bus System Based on AC Load Flow Model The application of both traditional WLS and the extended WLS approaches for the state estimation of the IEEE 14 bus test case will be presented in this section [8]. Figure 3 shows the test case. Newton Raphson load flow method can be applied to obtain load flow results of the system [9]. The measurement data set chosen from load flow results must satisfy network observability [10]. In the state estimation, the chosen measurement data set for the formulation of state-estimation Jacobian H x are voltage magnitudes, real and reactive power injections, real and reactive power flows [11]. The variances of measurement errors for the above three kinds of measurement data are set to 9e-5, 1e-4 and 64e-6. To simplify the calculation, the variances for model mismatches are all set to 1.0. Two tests are implemented: first, all the branch impedances are correct, the results are shown in Table 8. Second, the branch impedance from bus 4 to bus 7 Z 47 is mistakenly changed to 0.3j, the results are shown in table 9. The true values of voltage magnitude and angle are from Newton Raphson load flow results. To compare the state estimate accuracy of both traditional WLS and the extended WLS approaches, mean absolute percentage error (MAPE) is introduced as follows: Figure 3. IEEE 14 Bus Test case [8] where, A t is the actual value and F t is the calculated value. A smaller value of MAPE indicates a more accurate state estimation result. The MAPE values are shown in the last row of both Tables 8 and 9. As can be seen from Tables 8 and 9, the MAPE values of the extended WLS approach are smaller than those of the traditional WLS approach, indicating that the extended WLS approach can obtain more accurate state estimation results. MAPE = 1 n n A t F t t=1 100% (18) A t

JOURNAL OF COMPUTERS, VOL. 7, NO. 3, MARCH 01 689 TABLE 8. FIRST CONDITION: ALL THE BRANCH IMPEDANCES ARE CORRECT. Bus ID True Value Traditional WLS Extended WLS 1 1.060 0 1.041 0 1.045 0 1.045-4.99 1.06-5.166 1.09-5.138 3 1.010-1.75 0.988-13.41 0.99-13.163 4 1.013-10.4 0.994-10.658 0.997-10.591 5 1.017-8.76 0.998-9.1 1.001-9.064 6 1.070-14.45 1.053-15.01 1.055-14.93 7 1.046-13.4 1.07-13.764 1.030-13.680 8 1.080-13.4 1.063-13.763 1.065-13.680 9 1.031-14.8 1.01-15.405 1.015-15.313 10 1.030-15.04 1.01-15.67 1.014-15.534 11 1.046-14.86 1.08-15.440 1.031-15.349 1 1.053-15.30 1.036-15.891 1.038-15.798 13 1.047-15.33 1.09-15.97 1.031-15.833 14 1.019-16.08 1.001-16.699 1.004-16.600 M% 1.78% 3.6% 1.51% 3.05% with n nodes, under specified generating and loading conditions, the network equation is given by the matrix equation [7] YV = I (19) where, Y is n n bus admittance matrix, V is n 1 vector of node voltages, and I is n 1 vector of current injections. Let bus 1 be designated as the slack bus. The above general set of equations includes the equation for the known slack-bus voltage, which is eliminated by modifying Y and I. The matrix Y is modified by removing the row and column corresponding to the slack bus, and the second to the nth row of matrix I is modified by subtracting from any current element I k the product Y k1 V 1, where Y k1 represents the element of the kth row and first column of matrix Y, and V 1 is the constant slack-bus voltage. Denoting the modified bus admittance matrix and current vector as Y and I, respectively. The equations for the above modifications are [7] Y V = I (0) I = I k Y k1 V 1 (1) Bus ID TABLE 9. SECOND CONDITION: Z 47 = 0.3j True Value Traditional WLS Extended WLS where, k ranges from to n. V is voltage vector from bus to bus n. The node voltages from the second to the nth node are obtained by the product Z I V = Z I () 1 1.06 0 1.043 0 1.046 0 1.045-4.99 1.07-5.154 1.030-5.17 3 1.010-1.75 0.989-13.10 0.993-13.133 4 1.013-10.4 0.996-10.63 0.998-10.565 5 1.017-8.76 0.999-9.104 1.00-9.046 6 1.070-14.45 1.055-15.077 1.058-14.999 7 1.046-13.4 1.038-14.669 1.040-14.580 8 1.080-13.4 1.074-14.61 1.076-14.540 9 1.031-14.8 1.03-16.04 1.05-16.099 10 1.030-15.04 1.00-16.46 1.03-16.159 11 1.046-14.86 1.033-15.699 1.035-15.641 1 1.053-15.3 1.038-15.953 1.041-15.871 13 1.047-15.33 1.031-15.988 1.034-15.906 14 1.019-16.08 1.008-17.16 1.010-17.06 M% 1.34% 5.61% 1.08% 5.06% IV. POWER FLOW STUDY IN A SYSTEM WITH MULTIPLE TYPES OF LOADS This section presents a power flow method based on Z matrix to implement power flow in the transmission system with multiple types of loads. For a power system where, bus impedance matrix Z is obtained from matrix Y. Then, an iterative technique can be applied to obtain the node voltages. During each iteration, the current injection is calculated using the most recent voltage vector. In the transmission system, the loads are usually considered as constant PQ loads. However, there are other types of loads, such as constant impedance load, constant current magnitude load and mixed two and more types of loads at a bus. The load modeling for the above loads are expressed as follows: For a constant impedance load, the injection current into the bus is determined as [1] I l = V(P b+jq b ) V b (3) where, P b and Q b are nominal real and reactive power of the load, V is the voltage of the bus. V b is the nominal voltage. For a constant PQ load [1], I l = ( P b+jq b ) (4) V For a constant current magnitude load [1],

690 JOURNAL OF COMPUTERS, VOL. 7, NO. 3, MARCH 01 I l = P b+jq b V V b (5) For the mixed two and more types of loads, i.e. mixed loads have a constant PQ load and a constant impedance load, each load accounts for 50% of total load of the bus, I l = 0.5 ( P b+jq b V ) 0.5 V(P b+jq b ) V b (6) A modified IEEE 14 bus test case is utilized for case study. The loads of bus 4 and 10 are changed to constant impedance load, the load of bus 13 is changed to constant current magnitude load, and the load of bus 9 is changed to mixed loads with 50% constant PQ load and 50% constant impedance load. Table 10 shows the power flow results and the convergence criterion is a tolerance value of 1e-4 for voltage magnitudes. TABLE 10. POWER FLOW RESULTS FOR THE MODIFIED IEEE 14 BUS TEST CASE Bus ID Magnitude (p.u.) Angle (Degree) 1 1.06 0 1.0480-4.9464 3 1.0100-1.5456 4 1.000-10.1148 5 1.03-8.6985 6 1.088-14.3504 7 1.0600-13.044 8 1.0985-13.044 9 1.0461-14.580 10 1.046-14.8050 11 1.0634-14.6886 1 1.0739-15.360 13 1.0689-15.3784 14 1.0381-15.911 Iteration 15 To test the power flow results, Kirchhoff s current law (KCL) is applied to each bus of the modified IEEE 14 bus test case; that is, at any bus, the sum of branch currents injected into that bus should be equal to the load currents flowing out of that bus. Load currents can be calculated from equations (3) (6). Utilizing voltages of each bus of the system as shown in Table 10, the sum of the branch currents injected into the i-th bus can be obtained from the equation: n I i = k=1 Y ik V k (7) The test results show that the power flow results in Table 10 are correct. This method has the following benefits. It is easy to consider all types of loads, since the loads can be readily represented by injection currents. The bus admittance/impedance matrix, once formulated, doesn t need to be changed if the network remains unchanged, which may be convenient for performing studies spanning a horizon where the load changes according to specified load shape modifiers. It is noted that using the LU factorization technique may determine the solution to (0) more efficiently without the need of obtaining the Z matrix. An interesting observation has been found that the power flow problem may have multiple valid solutions. As an example, we have used the traditional Newton Raphson and the Z-matrix methods to solve the original IEEE 14 bus test case. The results obtained by the two methods are shown in Table 11. The convergence criterion is a tolerance of 1e-4 for voltage magnitude. Both solutions are valid since both satisfy the KCL law, but it can be seen that they are slightly different. TABLE 11. POWER FLOW RESULTS OBTAINED BY Z-MATRIX METHOD AND NEWTON RAPHSON METHOD Z-matrix Method Newton Raphson Bus Method ID 1 1.06 0 1.06 0 1.0465-5.0049 1.0450-4.9891 3 1.0100-1.7178 1.0100-1.749 4 1.0159-10.610 1.013-10.40 5 1.0191-8.7804 1.0166-8.7601 6 1.0755-14.41 1.0700-14.4469 7 1.055-13.319 1.0457-13.368 8 1.091-13.318 1.0800-13.368 9 1.0366-14.7975 1.0305-14.801 10 1.0359-15.0099 1.099-15.0360 11 1.0519-14.831 1.0461-14.8581 1 1.0589-15.69 1.0533-15.973 13 1.053-15.974 1.0466-15.3313 14 1.053-16.035 1.0193-16.0717 Iteration 14 7 V. FUTURE RESEARCH In state estimation, the selection of error variances for measurements and model mismatches may have significant effects on the state estimation accuracy. Error variances for the measurements can be chosen according to meter measurement characteristic, which is usually found in meter s manual. However, it is more difficult to find error variances for model mismatches. Thus, one future work is to find suitable methods to determine the error variances for model mismatches for enhanced state estimation accuracy. VI. CONCLUSION This paper presents a new state estimation algorithm based on the extended WLS method for accounting for both model errors and measurement errors. For comparison purposes, both the traditional WLS method

JOURNAL OF COMPUTERS, VOL. 7, NO. 3, MARCH 01 691 and the new method are evaluated by performing case studies. The estimated results evince that the extended WLS method may outperform the traditional approach when the power network model used is not accurate. The extended WLS method is best suited for cases with known variances for model errors. In addition, this paper also examines a power flow method based on Z matrix for transmission systems with multiple types of loads, and the test results demonstrate that the method is effective and correct. The benefit of this method is that it is straightforward to model composite types of loads in the analysis. Studies also show that multiple valid solutions may exist for a power flow problem. REFERENCES [1] A. Monticelli, State Estimation in Electric Power Systems: a Generalized Approach, New York: Kluwer, 1999. [] Y. Liao, State estimation algorithm considering effects of model, SoutheastCon, 007. Proceedings. IEEE. pp. 450-453. [3] P. Zarco and A. Gomez, Power system parameter estimation: A survey, IEEE Transactions on Power systems, vol. 15, no. 1, Feb. 000, pp. 16-. [4] W. A. Fuller, Measurement Error Models. New York: Wiley, 1987. [5] A. Yeredor, The extended least squares criterion: minimization algorithms and applications, IEEE Transactions on signal processing, vol. 49, no. 1, January 001, pp. 74-86. [6] B. Stott, Review of Load-Flow Calculation Methods, IEEE Transactions on Power Delivery, Vol. 6, no. 7, Jul 1974, pp. 916 99. [7] A. Brameller and J. K Denmead, Some improved methods of digital network analysis, Proc. Znst. Elec. Eng., vol. 109A, pp. 109-116, Feb. 196. [8] http://www.ee.washington.edu/research/pstca/, Power System Test Case Archive. [9] W.F. Tinney and C.E. Hart, Power flow solution by Newton s method", IEEE Transactions on Power Apparatus and Systems, Vol PAS-86, No. 11, 1967, pp. 1449 1460. [10] A. Monticelli and F. F. Wu, Network Observability: Theory, IEEE Trans. On Power Apparatus and Systems, vol. PAS-104, no. 5, pp. 104-1048, May 1985. [11] J. Grainger and W. Stevenson, Power System Analysis, New York: McGraw-Hill, 1994. [1] Yuan Liao, Lecture Notes of Smart Grid class, Department of Electrical and Computer Engineering, University of Kentucky, 011. Jiaxiong Chen was born in Fuqing, China, on September 7, 1985. He received his B.S. degree from Department of Electrical Engineering, Hunan University, Changsha, China, in 008. In 010, he received his M.S. degree from Department of Electrical and Computer Engineering, University of Kentucky, Lexington, KY, USA. He is currently pursuing his PH.D. degree in electrical engineering at University of Kentucky. His research field is power system state estimation. Yuan Liao (S 98, M 00, SM 05) is currently an Associate Professor at the department of electrical and computer engineering at the University of Kentucky. From August 000 to August 005, he was with the ABB Corporate Research Center as an R&D Consulting Engineer and then Principal R&D Consulting Engineer. His research interests include protection, power quality analysis, large-scale resource scheduling optimization and EMS/SCADA design.