REPORT NUMBER: MID-001 ORIGINAL ISSUE DATE: April 22, 2016 REVISED DATE: NA. EVALUATION CENTER Intertek 8431 Murphy Drive Middleton, WI 53562

Similar documents
ASTM C STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLOW METER APPARATUS

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT

TEST REPORT. Test Method : See the attached sheets.

TEST REPORT. Page 1 of 11

Sound Absorption Test Intertek. kraft paper softwall + softblock modular system. m o l o d e s i g n, l t d

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

SHANGHAI MYLCH WINDOWS & DOORS THERMAL PERFORMANCE TEST REPORT

MOLEKULE INC. TEST REPORT

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045

Test Results: Results of the test period on 06/19/16 using the Equivalent CTS Method: Thermal transmittance at test conditions (U s ):

Standard Guide for Determination of the Thermal Resistance of Low-Density Blanket-Type Mineral Fiber Insulation 1

PERFORMANCE TEST REPORT. Rendered to: WORLDWIDE DOOR COMPONENTS, INC. PRODUCTS: PVC and Composite Door Jamb Material

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC. PRODUCT: Fiberglass Door Slab

HFM 100 Series. Thermal Conductivity Meter for measurement of insulation and construction materials.

REPORT NUMBER: GZU-001 ORIGINAL ISSUE DATE:

Order No. G Date: September 8, 2010 REPORT NO CRT-001 TEST OF SMF/PAPI SYSTEM RENDERED TO

Report No: NCTL NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15

Intertek Environmental VOC Emissions

Technical Procedure for General Laboratory Equipment

Vincent Barraud SOPREMA BASICS OF THERMAL INSULATION

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed

Electrical Parameter. Measurement and Test Report for. MaxGreen LED Ltd.

Test Report For: FunderMax GmbH. MAX Resistance 2. SEFA , 2.1 Chemical/Stain Resistances

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC.

REPORT NUMBER: GZU -001 ORIGINAL ISSUE DATE:

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6956 Revision 1 ARL

A L I O N Technical Center. Test Report. Port Coquitlam, British Columbia, Canada

FUNDERMAX GMBH TEST REPORT

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NORTH EAST WINDOWS USA, INC.

PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. PRODUCT: SUN TUNNEL Domes TYPES: Acrylic and Polycarbonate

Report No: NCTL S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15. Test Specimen

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6986/ARL-SA6987 Revision 0 ARL

RIVERBANK ACOUSTICAL LABORATORIES

LaserComp, Inc., DESCRIPTION OF THE INSTRUMENT

TEST REPORT IEC Photobiological safety of lamps and lamp systems

THERMAL PERFORMANCE TEST REPORT

Assessing The Thermal Performance of Building Enclosure Materials Using A Medium-Size Hot Box Chamber Summer Meeting Torkan Fazli

A L I O N Technical Center. Test Report

Standard Test Method for Determination of the Thermal Conductivity of Anode Carbons by the Guarded Heat Flow Meter Technique 1

AIR-INS inc. 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) Fax : (450)

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6712/ARL-SA6713 Revision 0 ARL

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6266/ARL-SA6274 Revision 0 ARL

Reflectec Thermal Fabric & Reflectec Fiberboard

CALIBRATION CERTIFICATE # 503

Standard Test Method for Thermal Conductivity of Refractories 1

E v a l u a t i o n C e r t i f i c a t e

Standard Test Method for Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the Guarded-Hot-Plate Apparatus 1

OPTO Laboratory Test Report IES LM MEASURING LUMEN MAINTENANCE OF LED LIGHT SOURCE. Test Date January 16, 2014 to April 8, 2015.

RIVERBANK ACOUSTICAL LABORATORIES

Use of Phase-Change Materials to Enhance the Thermal Performance of Building Insulations

CONSTRUCTION MATERIALS

Standard Test Method for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Using Hot Box Methods 1

Measurement of heat transfer coefficients for polymer processing simulation

2.1. Accuracy, n- how close the indication of the thermometer is to the true value.

ACCEPTANCE PROCEDURE FOR ROMET ROTARY METER BODIES AND/OR MECHANICAL NON-CONVERTING AND CONVERTING MODULES

Certificate of Accreditation

Simulation Report (Revised) Rendered To: Showcase Custom Vinyl Windows 1002 Olde Towne Drive Irving, TX 75061

IGNITABILITY ANALYSIS USING THE CONE CALORIMETER AND LIFT APPARATUS

Operating Instructions Validation Tool Kit, KT2 For use with USP Apparatus #1 & #2

NFRC SOLAR HEAT GAIN COEFFICIENT TEST REPORT. Rendered to: CLEAR FOCUS IMAGING

Standard Practice for Calculating Thermal Transmission Properties Under Steady- State Conditions 1

NFRC THERMAL TEST SUMMARY REPORT January 27, 1999 Test Specimen

Photobiological safety of lamps and lamp systems

NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06

CERTIFICATE OF CALIBRATION

Morehouse. Edward Lane, Morehouse Instrument Company 1742 Sixth Ave York, PA PH: web: sales:

MEASUREMENT OF THE THERMAL DIFFUSIVITY OF BUILDING MATERIALS

Infrared Thermometer Calibration A Complete Guide

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

Building Envelope Requirements Overview Page 3-4

OCEAN/ESS 410. Class 3. Understanding Conductive Cooling: A Thought Experiment. Write your answers on the exercise sheet

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report

TEST REPORT (Self-Tested Data)

E C t y p e - e x a m i n a t i o n C e r t i f i c a t e

INDIANA DEPARTMENT OF TRANSPORTATION OFFICE OF MATERIALS MANAGEMENT. VERIFYING THERMOMETERS ITM No T

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

Standard Test Method for Evaluating the Resistance to Thermal Transmission of Materials by the Guarded Heat Flow Meter Technique 1

IES LM MEASUREMENT AND TEST REPORT For. IGT LIGHTING INC Lincoln St. Suite B, Riverside, CA Test Model: IGTFL

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

RoHS. Dimming: PWM/VR/0-10V QPL ID # PL21D5Q1B95E. Cat# W LED FlatPanel Slipfitter Mount. EPA Rating 2.

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

TEST METHOD FOR DETERMINING BREAKAWAY FORCE OF A MAGNET

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

Comparison tests of cellular glass insulation for the development of cryogenic insulation standards

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

Akhan Tleoubaev Andrzej Brzezinski

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

QSM 5.1 FAQs. For a test with a recommended maximum holding time measured in hours, the holding time shall be tracked by the hour.

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

LM Test Report. for. Forest Lighting Corporate. LED Tube. Model: FL-T8U BN

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

A Case for Periodic Calibration or Verification of RTDs

Transcription:

REPORT NUMBER: 102550917MID-001 ORIGINAL ISSUE DATE: April 22, 2016 REVISED DATE: NA TEST REPORT EVALUATION CENTER Intertek 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Cali Bamboo 6675 Mesa Ridge Rd Suite 100 San Diego, CA 92121 Ines Way iway@calibamboo.com PRODUCTS EVALUATED: Premium + Cork Underlayment EVALUATION PROPERTY: ASTM C518 Report of Testing SG360 Control for compliance with the applicable requirements of the following criteria: ASTM C518-2010: Standard Test Method for Steady-State Transmission Properties by Means of the Heat Flow Apparatus. "This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program." 1

Report No.: 102550917MID-001 Page 2 of 6 1 Table of Contents 1 TABLE OF CONTENTS... 2 2 INTRODUCTION... 3 3 TEST SAMPLES... 3 3.1. SAMPLE SELECTION... 3 3.2. SAMPLE AND ASSEMBLY DESCRIPTION... 3 4 TESTING AND EVALUATION METHODS... 3 4.1. THERMAL CONDUCTIVITY... 3 TESTING AND EVALUATION RESULTS... 5 4.2. RESULTS AND OBSERVATIONS... 5 4.2.1. DEVIATION TO THE TEST METHOD... 5 4.2.2. STATEMENT OF MEASUREMENT UNCERTAINTY... 5 4.2.3. CALIBRATION OF ASTM C518... 5 5 CONCLUSION... 6 6 REVISION SUMMARY... 6

Report No.: 102550917MID-001 Page 3 of 6 2 Introduction Intertek has conducted testing for Cali Bamboo on Premium + Cork Underlayment to evaluate the thermal transmission properties. Testing was conducted in accordance with ASTM C518-2010: Standard Test Method for Steady-State Transmission Properties by Means of the Heat Flow Apparatus. This evaluation began April 21, 2016 and was completed April 21, 2016. 3 Test Samples 3.1. SAMPLE SELECTION Samples were received directly from the client. Samples were received at the Intertek Middleton Evaluation Center April 7, 2016 in good condition. 3.2. SAMPLE AND ASSEMBLY DESCRIPTION Sample Name: Premium + Cork Underlayment Sample Description: Three cork panels were provided by the client. The recorded dimensions and density are in section 4.2 The samples were then place in 22 C and 50 % R.H. for a period of time until less than a 1 % mass change is observed over a 24-h period 4 Testing and Evaluation Methods 4.1. Conductivity The heat flow meter apparatus establishes steady state unidirectional heat flux through a test specimen between two parallel plates at constant but different temperatures. By appropriate calibration of the heat flux transducer(s) with calibration standards and by measurement of the plate temperatures and plate separation, Fourier s law of heat conduction is used to calculate thermal conductivity, thermal resistance, or resistivity. The accurate use of the test method is limited by the capability of the apparatus to reproduce unidirectional constant heat flux density in the specimens, and by the precision in the measurement of temperature, thickness, EMF produced by the heat flux transducer, etc. The apparatus shall not be used at temperatures, thickness or resistances, other than those within the range of the calibration; unless it can be shown that there is no difference in accuracy. The apparatus must be capable of maintaining at least a 10 C temperature difference across the specimen for the duration of the test, unless a smaller LT is a requirement of a particular test. The specimens tested may also limit the use of the test method and these limitations are outlined in Practice C1045.

Report No.: 102550917MID-001 Page 4 of 6 This evaluation was accomplished using a HFM436/3/1 ER Heat Flow Meter Conductivity Instrument, manufactured by Netzsch. The HFM436/3/1 ER determines thermal conductivity in accordance with ASTM C 518. Heat flow through a solid, results from having a temperature gradient in the material. conductivity is a material property, which determines how much heat flows through a given thickness of the material when there is a temperature difference. The Fourier linear heat flow equation defines thermal conductivity under steady state conditions as: where: l = ø DX DT l = thermal conductivity, ø = heat flux, W m 2 W m K DT = temperature difference across distance LX, K DX = distance between hot and cold plates, m Prior to each series of tests, the HFM436/3/1 ER was calibrated using a sample whose thermal conductivity is known and traceable to national standards. To perform the test, the specimens are placed in the HFM436/3/1 ER instrument; the top (hot) plate is brought downwards creating contact of both plates with the test specimen. The hot and cold plates were then allowed to equilibrate to the required temperatures and their exact temperatures were read from the instrument. The mean temperature for testing is 75 o F with a temperature difference between plates at 40 o F. Density Measurements were taken using standard ASTM D1622.

Report No.: 102550917MID-001 Page 5 of 6 Testing and Evaluation Results 4.2. RESULTS AND OBSERVATIONS Specimen Length (mm) Depth (mm) Depth (in) Weight Density Cork Underlayment Avg. Avg. Avg. kg (kg/m 3 ) (lbs/ft 3 ) 1 307.85 3.06 0.1205 0.04780 164.68 10.28 2 304.06 2.84 0.1116 0.04303 163.71 10.22 3 306.17 2.93 0.1154 0.04553 165.27 10.32 Mean: 164.55 10.27 StdDev: 0.79 0.05 Test Information Conductivity Conductivity per inch per meter Conductance Heat Flux K Value K Value R Value R Value R/in R/m U q Units: Btu-in/hr-ft 2 - ºF W/m-K Hr-ft 2 -ºF/Btu m 2 -K/W Hr-ft 2 - ºF/Btu/in m 2 -K/W/m W/m 2 -K W/m 2 Specimen 1 0.216403 0.03121 0.55682 0.0981 4.62 32.04 10.20 36.20 Specimen 2 0.200598 0.02893 0.55635 0.0980 4.99 34.56 10.21 36.06 Specimen 3 0.206882 0.02984 0.55771 0.0982 4.83 33.51 10.18 36.54 Average 0.207961 0.02999 0.55696 0.0981 4.81 33.37 10.20 36.27 Test Duration of the Measured Measured Delta Delta Mean Mean Information measurement Thickness Thickness Temperature Temperature Temperature Temperature Temperature Gradient Units: min (in) (m) ºF ºC ºF ºC ºF/in ºK/m Specimen 1 0:39:25 0.121 0.003061 38.39 3.55 76.12 24.51 318.53 63.75 Specimen 2 0:39:24 0.112 0.002835 38.36 3.53 75.82 24.34 343.67 64.27 Specimen 3 0:38:23 0.115 0.002931 38.46 3.59 75.81 24.34 333.34 64.06 Average 0:39:04 0.116 0.002942 38.40 3.56 75.92 24.40 331.85 64.03 4.2.1. Deviation to the test method There were no deviations to the standard method. 4.2.2. Statement of Measurement Uncertainty The uncertainty of the Netzsch Conductivity Instrument HFM436/3/1 ER is estimated to be 1-3%. 4.2.3. Calibration of ASTM C518 NIST standard SRM1450c Fibrous Glass board #1450C748 was run before testing began. The calibration testing was within 1% error of the NIST standard value.

Report No.: 102550917MID-001 Page 6 of 6 5 Conclusion Intertek has conducted testing for Cali Bamboo on Premium + Cork Underlayment to evaluate the thermal transmission properties. Testing was conducted in accordance with ASTM C518-2010: Standard Test Method for Steady-State Transmission Properties by Means of the Heat Flow Apparatus. There is no pass fail criterion for ASTM C518. The conclusions of this test report may not be used as part of the requirements for Intertek product certification. Authority to Mark must be issued for a product to become certified. INTERTEK Reported by: Sandy Osborne Lab Technician I, Verification Center Reviewed by: Bryan Bowman Chemist, Verification Center 6 Revision Summary DATE April 22, 2016 SUMMARY Original Issue Date