EXPERIMENTAL VERIFICATION OF THE EUROPEAN METHODOLOGY FOR TESTING NOISE BARRIERS IN SITU: SOUND REFLECTION

Similar documents
ACOUSTIC INTRINSIC PERFORMANCES OF NOISE BARRIERS: ACCURACY OF IN SITU MEASUREMENT TECHNIQUES

Test Report. RI Acoustic Lab. Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier. 20 Feb. 07

On the declaration of the measurement uncertainty of airborne sound insulation of noise barriers

Progress in sound reflection measurements on noise barriers in situ

DELTA Test Report. DANAK TEST Reg. no Measurement of Sound Absorption Coefficient for Kvadrat Soft Cells Wall Panel Type Time

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

Sound reflection from different noise barriers

Measurement of Acoustic Properties of light weight concrete SL-Deck

Users Manual. Marshall Day Acoustics. Double Panels Contact 33 Details Marshall Day 37.8 Acoustics PO Box

MEASUREMENTS OF SOUND ABSORPTION TIMBERCRETE

DELTA Test Report. Measurement of sound absorption coefficient for 15 mm Fraster felt Plus acoustic panels with mounting depth 45 mm

THE ACOUSTIC IMPEDANCE MEASUREMNET SYSTEM USING TWO MICROPHONES

Measurement of sound absorption coefficient for Fraster felt SpaceCover

Laboratory and In Situ Sound Absorption Measurement under a Synthetized Diffuse Acoustic Field: a Case Study on Five Materials

DELTA Test Report. Measurement of Sound Absorption for AqFlex ON, one Sample as a discrete Object. Performed for Flex Acoustics

Micro-perforated sound absorbers in stretched materials

ON SITE DETERMINATION OF SOUND ABSORPTION COEFFICIENT OF ROAD PAVEMENTS USING MOBILE LABORATORY

Impedance of standard impact sources and their effect on impact sound pressure level of floors

Answer - SAQ 1. The intensity, I, is given by: Back

Calcul des coefficients d'absorption alpha sabine

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

Evaluation of standards for transmission loss tests

ISO 354 INTERNATIONAL STANDARD. Acoustics Measurement of sound absorption in a reverberation room

TFI Report Sound Absorption Impact Sound Insulation

Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015

The façade sound insulation and its classification

Renolit stretch ceilings

INTER-NOISE AUGUST 2007 ISTANBUL, TURKEY

TFI Report Sound Absorption Impact Sound Insulation

Turbines and turbine sets Measurement of emitted airborne noise Engineering/survey method

COMPARISON OF THE METHODS TO CALIBRATE THE DIFFUSE FIELD SENSITIVITY OF LABORATORY STAND- ARD MICROPHONE

A L I O N Technical Center. Test Report

Investigations on real-scale experiments for the measurement of the ISO scattering coefficient in the reverberation room

Laboratory for Acoustics. Determination of the sound insulation of sliding door constructions, manufactured by Metaflex

Laboratory for Acoustics

RIVERBANK ACOUSTICAL LABORATORIES

Fabric Dazzle 6086 Manufacturer Carnegie Fabrics

stylegreen Iceland Moss / Reindeer Moss of the company FlowerArt

Laboratory for Acoustics. Determination of the sound absorption (reverberation room method) of Airpanel, manufacturer Texdecor

A L I O N Technical Center. Test Report. Port Coquitlam, British Columbia, Canada

This document is a preview generated by EVS

TFI Report Sound Absorption Impact Sound Insulation

A simple model for estimating excess attenuation of road traffic noise

Recent topics in acoustic scattering coefficient determination for wall surfaces

Development of a small-scale reverberation room

Fabric REFLECTACOUSTIC

Basic Study on a Laboratory Measurement Method of the Normal-Incidence Scattering Coefficient

ISO INTERNATIONAL STANDARD

CONSOLIDATED GRANULAR MEDIA FOR SOUND INSULATION: PERFORMANCE EVALUATION THROUGH DIFFERENT METHODS

Acoustic response in non-diffuse rooms

Fabric ALEX. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/09

Technical Note. Measurement of Sound Absorption for Flex Acoustics AqTube. Performed for Flex Acoustics. TC Project no.: T Page 1 of 7

SIMPLE APPLICATION OF STI-METHOD IN PREDICTING SPEECH TRANSMISSION IN CLASSROOMS. Jukka Keränen, Petra Larm, Valtteri Hongisto

REPORT N CR

Modeling and simulation of windows with noise mitigation and natural ventilation

Fabric VELOS STRATO. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/10

Fabric Sport. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/02

Laboratory for Acoustics

Curtain fabric type Ace Manufacturer Kvadrat A/S

Laser scanning vibrometry measurements on a light weight building element

CDD/CDR. Single cone ceiling diffusers for supply air. Quick facts. Quick guide CDD/CDR A I R F L O W - S O U N D L E V E L

Benefits of Reduced-size Reverberation Room Testing

Sound radiation and sound insulation

ISO INTERNATIONAL STANDARD

Fabric Zetacoustic. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/07

EFFECTS OF PERMEABILITY ON SOUND ABSORPTION AND SOUND INSULATION PERFORMANCE OF ACOUSTIC CEILING PANELS

Fabric Corsica. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M111250/16

LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION COEFFICIENTS OF OSCAR EVO-PANELS

Witold MIKULSKI. Central Institute for Labour Protection National Research Institute Czerniakowska 16, Warszawa, Poland;

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6266/ARL-SA6274 Revision 0 ARL

Part 2: Methods for special reverberation test rooms

Reflection and absorption coefficients for use in room acoustic simulations

TFI Report Sound Absorption Impact Sound Insulation

Fabric Umbria III R. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/13

LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION OF CLASSICTONE 700 ASTM C Type E Mounting. Test Number 2

CDD/CDR. Circular ceiling diffuser for supply air QUICK FACTS

Report. Laboratory for Acoustics

Paseo Recoletos, nº Madrid TEST REPORT

Effect and minimization of errors in in-situ ground

Method of Testing of Sound Absorption Properties of Materials Intended for Ultrasonic Noise Protection

Fabric STREAMER pro. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M111250/04

UNCERTAINTY OF FAÇADE SOUND INSULATION MEAS- UREMENTS OBTAINED BY A ROUND ROBIN TEST: THE IN- FLUENCE OF THE LOW FREQUENCIES EXTENSION

ISO 3741 INTERNATIONAL STANDARD

45º CONGRESO ESPAÑOL DE ACÚSTICA 8º CONGRESO IBÉRICO DE ACÚSTICA EUROPEAN SYMPOSIUM ON SMART CITIES AND ENVIRONMENTAL ACOUSTICS

DESIGN OF MICRO-PERFORATED ABSORBERS (MPA)

Acoustic design of lightweight cabin walls for cruise ships

Drop towers and fitness flooring assemblies

Fabric TWIST MELANGE Manufacturer Gabriel A/S

Gesellschaft für Akustikforschung Dresden mbh Acoustic Engineering Dresden AED Acoustic Measuring Instruments & Analysis Software

Sound-Absorbing and Insulating Enclosures for Ultrasonic Range

Fabric XPRESS + PU-foam Manufacturer Gabriel A/S

Krantz Components. Twist outlet DD-N... for ceiling installation. Air distribution systems

Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015

Fabric Medley Manufacturer Gabriel A/S

Fabric UDINE. Measurement of sound absorption according to EN ISO 354. Test Report No. M102794/32

LABORATORY MEASUREMENT OF SOUND ABSORPTION OF SONOGLASS SPRAY-ON TREATMENT IN THREE CONFIGURATIONS

DIFFUSIVITY AND ITS SIGNIFICANCE TO EFFECTIVE SEAT ABSORPTION IN CONCERT HALLS

FIFTH INTERNATIONAL CONGRESS ON SOUND AND VIBRATION DECEMBER 15-18, 1997 ADELAIDE, SOUTH AUSTRALIA

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

Chalmers Publication Library

Transcription:

000059.doc/0 EXPERIMENTAL VERIFICATION OF THE EUROPEAN METHODOLOGY FOR TESTING NOISE BARRIERS IN SITU: SOUND REFLECTION M. GARAI, P. GUIDORZI DIENCA, University of Bologna, Viale Risorgimento 2, 40136, Bologna, Italy Tél.: +39-051-2093298 / Fax: +39-051-2093296 / Email: massimo.garai@mail.ing.unibo.it Keywords NOISE BARRIERS - SOUND REFLECTION - IN SITU MEASUREMENT - ADRIENNE ABSTRACT The European project Adrienne (1995-97) produced innovative methods for testing the intrinsic characteristics of noise barriers in situ. These methods are now under consideration at CEN to become European standards. This paper reports the verification of the Adrienne test method for sound reflection over a selection of seventeen noise barriers, tested both outdoors, using the new method, and in laboratory, following the EN 1793-1 standard. The Adrienne method has been found sensitive to the shape and the acoustic impedance of the barriers under test. The comparison between outdoor and laboratory results shows an acceptable correlation, while differences can be explained with the different sound fields and averaging techniques between the outdoor and laboratory tests. It is concluded that the Adrienne method is the most promising one for its intended use. 1. - INTRODUCTION The sound reflection/absorption of seventeen noise barriers, representative of the Italian and European market, was tested both outdoors, using the new Adrienne method [1,2,3], and in laboratory, following the EN 1793-1 standard [4]. In both cases different single number ratings for sound reflection/absorption were calculated [4,5,7]. The work permitted: to test the practicability and the reliability of the new method for different kinds of barriers; to test the sensitivity of the new method to the shape and the acoustic impedance of the barriers under test; to compare the outdoor and laboratory values obtained on the same set of barrier samples and to investigate their correlation, which can be useful for predicting the expected field performance from laboratory data. 2. - THE SAMPLES All samples had the same global size: about 3.0x3.5 m for the laboratory test and 18.0x4.0 m for the outdoor test. In Table 1, the barrier samples are presented with conventional names in order to not disclose the producer names. The barriers submitted to the test can be grouped in six classes: 1. concrete barriers (5 samples): barrier elements are made of a heavy concrete back panels supporting front panels made with lighter concrete and with a non flat shape; the posts are large and strong to support the considerable weight of the structure;

000059.doc/1 2. metallic barriers (7 samples): barrier elements are metallic boxes, perforated on one face and partially filled with a high density rock wool; in two cases a high density synthetic damper was added; in two cases the elements were simple, not perforated, metallic sheets; the posts are metallic beams with a H section; 3. resin barriers (1 sample): the barrier elements are boxes made with polyether resin sheets reinforced using glass fibres; the boxes are perforated on one face and partially filled with a glass fibre blanket; the posts are made using the same polyether resin; 4. acrylic barriers (1 sample): the barrier elements are transparent polymethylmethacrylate (PMMA) sheets, 20 mm thick, supported by a light metallic frame; 5. mixed barriers (1 sample): the half barrier close to the ground is made of metallic panels, like those described above (point 2); the upper half is made of transparent polymethylmethacrylate (PMMA) sheets, 15 mm thick, supported by a light metallic frame; the posts are metallic beams with a H section; 6. wood barriers (1 sample): the barrier is made of four layers i.e., from front to back: wood tiles made of spaced laths; rock wool blanket; fibre-concrete aggregate board; wood board; the posts are metallic beams with a H section. 3. - LABORATORY MEASUREMENTS The laboratory test method specified in EN 1793-1 [4] was applied. It fully conforms to the well-known ISO 354 [6], with some additions relevant for noise barriers. The specimens were mounted in the test opening and assembled in the same manner as the manufactured devices used in practice, with the same connections and seals between component parts. All the reflecting parts exposed on the traffic side (posts, brackets, and other parts) were present on the specimens. Where posts are employed in construction, at least one post was included in the specimen, with panels attached on both sides. The samples were placed directly on the floor of the reverberation room, with the side that would face the traffic noise source facing the inner part of the room. The values of the sound absorption coefficient = S were measured in the onethird octave bands from 100 Hz to 5 khz [4,6]. Two kinds of single number rating of sound absorption were calculated: the rating = w used in building acoustics, as defined in ISO 11654 [7]; the traffic noise rating DL =, as defined in EN 1793-1 [4], using the normalized A-weighted sound pressure level of traffic noise defined in EN 1793-3 [5]. All values of the ratings = w and DL = are reported in Table 1. The DL = values were calculated both on the full frequency range 100 Hz to 5 khz, in one-third octave frequency bands, and in the restricted frequency range 250 Hz to 5 khz; the latter calculation was made in view of the comparison with the single number rating values resulting from the outdoor measurements (see Section 4). 4. - OUTDOOR MEASUREMENTS The Adrienne test method was already presented in several publications, e.g. [1,2,3], and will not be detailed here. It is only worth recalling that the final value of the sound reflection index RI is the arithmetic average of the values measured at several points in front of the barrier. The analysis window must be the new Adrienne window, uniquely defined in shape, length and position [1,2,3]. Valid sound insulation index measurements, for 4 m tall barriers, are acknowledged to start from the 250 Hz one-third octave band [1,2,3]. In the following the outdoor measured values are therefore considered in the frequency range from 250 Hz to 5 khz, in one-third octave bands. The measurement system was similar to that described in [2,3]. The test signal was a MLS sequence of order 16; 64 averages were performed for each impulse response acquisition. The test site is a flat, grass covered ground. The grass was cut before the beginning of the tests. All

000059.doc/2 samples were built in the same place and removed after the test, one after the other. Measurements were taken in good meteorological conditions, with no rain or strong wind (wind speed always < 4 m/s). Background noise didn t influence the measurements. The single number rating for the reflection index was computed using a formula analogous to that for DL = [4] and was named DL RI ; due to the above mentioned low frequency limit, the calculations were performed in the one-third frequency bands from 250 Hz to 5 khz. The results are reported in Table 1. Sample Type = w [db] lab. 100 to DL = [db] lab. 100 to DL = [db] lab. 250 to DL RI [db] outdoors 250 to CON1 Concrete 0.75 9 10 6 CON2 Concrete 0.65 6 7 4 CON3 Concrete 0.90 10 12 4 CON4 Concrete 0.65 5 6 3 CON5 Concrete 0.50 5 5 2 CON6 Concrete 0.20 1 1 0 MET1 Metal 1.00 20 20 5 MET2 Metal 1.00 18 20 5 MET3 Metal 0.95 16 20 5 MET4 Metal 0.15 0 0 0 MET5 Metal 0.95 8 9 4 MET6 Metal 0.95 19 20 6 MET7 Metal 0.95 13 20 5 RES1 Resin 0.80 8 9 4 ACR1 Acrylic 0.10 0 0 0 MIX1 Met./Acr. 0.60 4 4 3 WOOD Wood 0.65 8 8 4 Table 1. Single number ratings of sound absorption/reflection 5. - COMPARISON BETWEEN LABORATORY AND OUTDOOR DATA In the laboratory a conventional sound absorption coefficient is measured (Sabine s coefficient = S ); outdoors the new sound reflection index, RI, is measured; in order to compare them on the same graph, the sound absorption coefficient were converted to conventional sound reflection values using the formula: r 1 = (1) S S It is well-known that the Sabine s coefficient is overestimated and can also get values over 1, outside the range of validity of its own definition; in this case, the value of r S in Eq. (1) was set to zero. The new sound reflection index RI is defined so as it can get values over 1, for reflecting and non flat surfaces [1,2,3]. In any case, differences between the values of r S and RI were expected, because: 1. the sound field in front of the test specimen is a diffuse field in laboratory and a frontal free-field outdoors.

000059.doc/3 2. The sampling and averaging of the sound field is very different between the laboratory and outdoor procedures; 3. The steady state signal recorded in the laboratory is very different from the impulse response recorded outdoors. Fig. 1 shows the results for the sample CON4, constituted by back concrete panels supporting light clay aggregate blocks, 120 mm thick. The blocks contain cavities connected to front holes on the exposed face and are intended to act as resonators to improve the sound absorption. The two curves are similar down to 250 Hz, where the outdoor measurements have they low frequency limit. On the other hand, laboratory results seem to overestimate the sound absorption (underestimate the sound reflection). This is confirmed looking at Fig. 2, that shows the results for the sample MET2, a metallic barrier with a curved shape and made of metallic boxes having the side that would face the traffic noise source perforated in order to expose the inner rock wool. For this sample, the = S values are so overestimated that the reflection coefficient r S is no more useful from the 500 Hz one-third octave band on. The application of standard statistical theory to data of Table 1 permitted to obtain various correlation laws between the single number ratings. The linear correlation between the two single number ratings = w and DL = obtained from laboratory measurements, calculated over the frequency range 100 Hz to 5 khz, is: DL= 18.71= w 4.10 ( r 0.875) (2) The value of the correlation coefficient is quite low, considering that the two ratings were calculated on the same data set: it is clear that the two ratings are not fully comparable, being based on different procedures and bounded to conventional maximum values (1 for = w [7] and 20 db for DL = [4]). Therefore, for noise barriers the usage of = w should be avoided. The linear correlation law between the single number ratings DL =, obtained from laboratory data, and DL RI, obtained from outdoor data (all calculated over the frequency range 250 Hz to 5 khz), is: DL RI 0.26DL = 1.26 ( r 0.84) (3) The value of the correlation coefficient is strongly influenced by the anomalous result of the sample CON1, which got an unusually great value of the outdoor rating; excluding this sample the linear correlation law becomes: DL RI 0.26DL = 1.11 ( r 0.89) (4) Now the value of the correlation coefficient is quite acceptable and its value is high enough to support the conclusion that Eq. (4) can be useful for predicting the expected field performance from laboratory data measured according to EN 1793-1. Work is in progress to obtain a better value of the lowest reliable frequency for outdoor measurements; it is hoped that this can also improve the strength of the correlation between outdoor and laboratory data. 6. - CONCLUSIONS The new Adrienne method proved to be easy to use and reliable for all kinds of barriers. It has been found sensitive the shape and the acoustic impedance of the barriers under test. The

000059.doc/4 comparison between outdoor and laboratory results shows a quite acceptable correlation, while existing differences can be explained with the different sound fields and averaging techniques between the outdoor and laboratory tests. In other words, results obtained using the Adrienne test method [1,2,3] are fairly consistent with laboratory results obtained using EN 1793-1 [4]. While work is in progress to obtain a better value of the lowest reliable frequency for outdoor measurements, the correlation laws resulting from the present work can already be useful for predicting the sound reflection performance of noise barriers in the field from laboratory data. It can be concluded that the Adrienne method is the most promising one for its intended use. ACKNOWLEDGEMENTS The measurements reported in this work have been done in 1999 by the authors for Italferr. The laboratory tests were performed in the facilities of Istituto Giordano (Bellaria, Italy), in the frame of a contract with DIENCA. In particular, the authors would like to thank Andrea Bruschi for his invaluable help during laboratory measurements. This work was partially supported by CNR (National Research Council of Italy) under the grant 99.01938.CT07. REFERENCES [1] Adrienne Research Team, Test methods for the acoustic performance of road traffic noise reducing devices - Final report, European Commission - DGXII - SMT Project MAT1-CT94049, 1998 [2] J.-P.Clairbois, J.Beaumont, M.Garai, G.Schupp, A new in-situ method for the acoustic performance of road traffic noise reducing devices, In Proc. Euro-Noise '98, pp. 813-818, 1998 [3] F. Anfosso, M. Garai, J.-P. Clairbois, Adrienne: une méthode européenne pour la qualification sur site des écrans antibruit, Bullettin de Liason des Ponts et Chausées, Vol. 225, 2000 [4] EN 1793-1, Road traffic noise reducing devices - Test methods for determining the acoustic performance - Part 1: Intrinsic characteristics of sound absorption, 1997 [5] EN 1793-3, Road traffic noise reducing devices - Test methods for determining the acoustic performance - Part 3: Normalized traffic noise spectrum, 1997 [6] ISO 354, Acoustics - Measurement of sound absorption in a reverberation room, 1985 [7] ISO 11654, Acoustics - Sound absorbers for use buildings - Rating of sound absorption, 1997

000059.doc/5 Fig. 1. Sound reflection index and sound reflection coefficient values for barrier CON4: ( ) laboratory measurements; ( ) outdoor measurements. Fig. 2. Sound reflection index and sound reflection coefficient values for barrier MET2: ( ) laboratory measurements; ( ) outdoor measurements.