Procedure To Be Adopted When Working on High Voltage Mechanically Switched Capacitors with Damping Network (MSCDN)

Similar documents
STATE OF COLORADO DESIGN CRITERIA FOR POTABLE WATER SYSTEMS WATER QUALITY CONTROL DIVISION. Price: $5.00. Revised March 31, 1997

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

WCAP-AS5H Aluminum Electrolytic Capacitors

Lamp and Control Panel (Lamp Panel)

SMD Switch SI-C3436A General specification. Soldering conditions Reflow Soldering condition. Standard Reel Dimensions (mm) Packing specification

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

An Introduction to Insulation Resistance Testing

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM

CRTE Power Capacitors

Electronics Capacitors

Facilities Management

CAPACITORS, FIXED, TUBULAR, POROUS TANTALUM CATHODE AND ANODE, GELLED ELECTROLYTE, HERMETICALLY SEALED BASED ON TYPE ST79

Safety Precautions WARNING If critical situations that could lead to user s death or serious injury is assumed by mishandling of the product.

UNIT G485 Module Capacitors PRACTICE QUESTIONS (4)

Model M3484 Industrial Line Noise Filter Module Customer Reference Manual

ENERGY AND TIME CONSTANTS IN RC CIRCUITS By: Iwana Loveu Student No Lab Section: 0003 Date: February 8, 2004

AN922 Application note

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL

Physics Investigation 10 Teacher Manual

Lab 3 - Capacitors. Stony Brook Physics Laboratory Manuals. Equipment

Conductive Polymer Capacitors

MM74C906 Hex Open Drain N-Channel Buffers


Ultra-Small Footprint N-Channel FemtoFET MOSFET Test EVM

As light level increases, resistance decreases. As temperature increases, resistance decreases. Voltage across capacitor increases with time LDR

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals.

16 Appendix 16 Electrical Research Association Report

Trade of Electrician Standards Based Apprenticeship Capacitance Phase 2 Module No. 2.1 Unit No COURSE NOTES

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid

Electric Double Layer Capacitors Product Specification. To. : DATE : SPECIFICATION WRITTEN CHECKED APPROVED

Film Capacitors. EMI suppression capacitors. Date: June 2018

AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS. October, 1999 IM No

Remote Display Unit. Installers Handbook Copyright 2001 AirSense Technology Ltd. LM Remote Display Unit Installers Handbook Issue 1.

MM74C00 MM74C02 MM74C04 Quad 2-Input NAND Gate Quad 2-Input NOR Gate Hex Inverter

5-V Low-Drop Fixed Voltage Regulator TLE 4269

CD4028BC BCD-to-Decimal Decoder

5-V Low Drop Fixed Voltage Regulator TLE 4279

S-882Z Series ULTRA-LOW VOLTAGE OPERATION CHARGE PUMP IC FOR STEP-UP DC-DC CONVERTER STARTUP. Rev.1.2_00. Features. Applications.

Responsibilities: Effective Date: November Revision Date: February 8, VP, Facilities and Construction Management. Issuing Authority:

Lab 4 RC Circuits. Name. Partner s Name. I. Introduction/Theory

Surface Mount Multilayer Ceramic Chip Capacitors with Integrated Resistor for High Pulse Current Applications

Figure 1: Capacitor circuit

Transient thermal measurements and thermal equivalent circuit models

ELECTRIC CURRENTS D R M A R T A S T A S I A K D E P A R T M E N T O F C Y T O B I O L O G Y A N D P R O T E O M I C S

Surface Mount Multilayer Ceramic Chip Capacitors for Safety Certified Applications

This chip is used for: power module BSM 75GD120DN2. Emitter pad size 8 x ( 2.99 x 1.97 ) Thickness 200 µm. Wafer size 150 mm

University of TN Chattanooga Physics 1040L 8/18/2012 PHYSICS 1040L LAB LAB 4: R.C. TIME CONSTANT LAB

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity

Dual 3-channel analog multiplexer/demultiplexer with supplementary switches

2-input AND gate with open-drain output. The 74AHC1G09 is a high-speed Si-gate CMOS device.

Product Specification

User Manual VX4750 Function Generator Module

PRODUCT SPECIFICATION FREQUENCY COMPONENTS. ZTB Series CERAMIC RESONATOR SPECIFICATION. MOBICON HOLDINGS LTD. Prepared By Sign.

SPECIFICATION FOR APPROVAL INDEX

Hazard Communication

HV CAPACITOR SCREENING PROCEDURE FOR THE GYROSCOPE SUSPENSION SYSTEM (GSS) HV AMP/BRIDGE (HVA) BOARD. GP-B Procedure P0688 Rev -

CL-L102-C7D. 1. Scope of Application. These specifications apply to LED package, model CL-L102-C7D. 2. Part code

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018

Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION. on the given range of performed tests

STM1831. Voltage detector with sense input and external delay capacitor. Features. Applications

5-V Low Drop Fixed Voltage Regulator TLE

Section 7 DOES ALL MATTER CONTAIN CHARGE? WHAT ARE ELECTRONS?

This chip is used for: power modules. Applications: drives G. Mechanical Parameters Raster size 9.47 x 12.08

Double Layer Capacitors. PN: NEX_ series & NED_ series

Surface Mount RF Schottky Barrier Diodes. Technical Data. GUx. HSMS-281x Series

Low Drop Voltage Regulator TLE

Part Number Order Number Package Marking Supplying Form PG2417T6M-E2 CAUTION

SGM800 Low-Power, SOT µp Reset Circuit with Capacitor-Adjustable Reset Timeout Delay

[1] (b) Fig. 1.1 shows a circuit consisting of a resistor and a capacitor of capacitance 4.5 μf. Fig. 1.1

CD40106BC Hex Schmitt Trigger

TEA10402V15A0 Engineering Specification

Silicon N-channel dual gate MOS-FET IMPORTANT NOTICE. use

Pursuant to Section 205 of the Federal Power Act ( FPA ) 1 and the Commission s

Northwest Hydro Tech Session_2017

5-V Low Drop Voltage Regulator TLE 4290

This chip is used for: power modules. Applications: drives G. Mechanical Parameters Raster size x 13.63

After publication, this Indian Standard will supersede the following Indian Standards:

Fig. 1 CMOS Transistor Circuits (a) Inverter Out = NOT In, (b) NOR-gate C = NOT (A or B)

R a t i o n a l i s e d B r a k e A c t u a t o r s

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9

MM74C14 Hex Schmitt Trigger

Figure 1. (a) An alternating current power supply provides a current that keeps switching direction.

Double Layer Capacitors

UNISONIC TECHNOLOGIES CO., LTD LM78XX

Report No 247/ This Report consists of 41 pages

FLT5A FLT5A. abc. abc. Thermometer User Guide. Thermometer User Guide. Internet:

METALLIZED POLYPROPYLENE AC FILTERING CAPACITORS

Regulations concerning protection of Bjørnøya Nature Reserve in Svalbard

Self-Testing Prevectron 2 Millenium Lightning Conductor Set-up and Installation Manual

Tantalum chip capacitors

Service Information Letter SIL # 017

Low Drop Voltage Regulator TLE 4296

HEF4028B. 1. General description. 2. Features. 3. Applications. 4. Ordering information. BCD to decimal decoder

Health, Safety, Security and Environment

BUSHING AND HV CURRENT TRANSFORMER ON-LINE MONITORING USING M4000 ANALYZER. Victor Sokolov and Vladimir Prikhodko ZTZ-Service Co, Ukraine

Never switch on the equipment without the assistants explicit authorization!

3 CONDUCTIVE POLYMER ALUMINUM ELECTROLYTIC CAPACITORS

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

74HC2G34; 74HCT2G34. The 74HC2G34; 74HCT2G34 is a high-speed Si-gate CMOS device. The 74HC2G34; 74HCT2G34 provides two buffers.

Transcription:

1. SCOPE This document details the procedures to be adopted when working on High Voltage Mechanically Switched Capacitors with. 2. ISSUE RECORD This is a Reference document. The current version is held on the EN Document Library. It is your responsibility to ensure you work to the current version. Issue Date Issue No. Author Amendment Details October 2012 1 William Bennett Initial Issue November 2017 2 Allan Holton Remove requirement for Fixed Drain Earth and additional Safety Document. Updated photo of Discharge Stick. 3. ISSUE AUTHORITY Author Owner Issue Authority Name: Allan Holton Title: Lead Plant & Overhead Line Engineer Name: Gary Evans Title: Operational Assurance Manager Name: Ross Galbraith Title: Health & Safety Director 4. REVIEW... Date: 30th... January 2018 This is a Reference document which has a 5 year retention period after which a reminder will be issued to review and extend retention or archive. The proposed revision date can be viewed in the Management Safety Procedures Document Index DOC-00-238. 5. DISTRIBUTION This document is part of the Management Safety Procedures but does not have a maintained distribution list. SP Power Systems Limited Page 1 of 13 MSP 2.12

6. CONTENTS 1. SCOPE... 1 2. ISSUE RECORD... 1 3. ISSUE AUTHORITY... 1 4. REVIEW... 1 5. DISTRIBUTION... 1 6. CONTENTS... 2 7. REFERENCE DOCUMENTS... 3 8. DEFINITIONS... 3 9. HANDLING STORAGE AND TRANSPORTATION OF CAPACITOR UNITS... 6 10. PROCEDURE FOR WORK ON HIGH VOLTAGE MECHANICALLY SWITCHED CAPACITORS WITH DAMPING NETWORK (MSCDN). GENERAL REQUIREMENTS FOR ALL WORK (CAPACITOR, REACTOR, RESISTOR)... 6 11. PROCEDURE FOR WORK OR TESTING ON CAPACITOR BANK ASSOCIATED WITH MSCDN... 7 12. PRECAUTIONS FOR WORKING ON A REACTOR ASSOCIATED WITH MSCDN... 8 13. ADDITIONAL PRECAUTIONS FOR WORKING ON A RESISTOR ASSOCIATED WITH A MSCDN... 8 14. PERFORMING CAPACITOR MEASUREMENTS... 8 15. PROCEDURE TO BE APPLIED WHEN CAPACITOR UNIT HAS DISRUPTIVELY FAILED. 8 16. DIAGRAMS... 9 SP Power Systems Limited Page 2 of 13 MSP 2.12

7. REFERENCE DOCUMENTS PSSI 11 (OPSAF-10-011) High Voltage Static Capacitors 8. DEFINITIONS For the purpose of this Management Safety Procedure the following definitions apply: MSCDN (Fig 1) Manually Switched Capacitor with Damping Network Capacitor Bank (Fig 2) An assembly of one or more Capacitor Stack(s) forming the static capacitor installation. Capacitor Stack (Fig 2) An assembly of Capacitor Rack(s) connected together. If the equipment consists of only one Capacitor Rack the term Capacitor Stack will also apply. A Capacitor Stack may contain Capacitor Unit(s) from one or more discrete components of the static Capacitor Bank, e.g. the main and auxiliary capacitors, resistors and air-cooled reactors. Capacitor Rack (Fig 2) An individual framework containing Capacitor Unit(s) connected together. Capacitor Unit (Fig 2) An assembly of one or more capacitor elements in the same container with terminals brought out by one or more bushings. Discharge Stick (Fig 5) An Approved device for the purpose of discharging a Capacitor Unit, which may be charged. Rack Earth(s) (Fig 4) Fixed or Portable Earthing Devices provided for the purpose of earthing and/or short-circuiting Capacitor units or groups and the Capacitor Rack or frame supporting them. The term Rack Earth includes Frame Earths. Short-Circuiting Lead (Figs 6 and 7) An Approved lead used for short-circuiting an individual Capacitor Unit. This can be a clip-on short used during the disconnection of a Capacitor Unit or a bolt-on short used during removal transportation and storage. Rack Earth Spigot (Fig 9) Earthing point positioned at the end of each Capacitor Rack for the purpose of connecting Rack Earths. SP Power Systems Limited Page 3 of 13 MSP 2.12

CAPACITOR STACK RESISTOR REACTOR (Fig 1) Typical layout of MSCDN showing components. SP Power Systems Limited Page 4 of 13 MSP 2.12

CAPACITOR BANK CAPACITOR STACK CAPACITOR RACK CAPACITOR UNIT (Fig 2) Typical layout of Capacitor Bank showing components. SP Power Systems Limited Page 5 of 13 MSP 2.12

9. HANDLING STORAGE AND TRANSPORTATION OF CAPACITOR UNITS 9.1 Capacitor Units that are to be disconnected from Capacitor Stacks shall be short-circuited using a short-circuiting lead and remain short-circuited during transportation and storage. 9.2 Where there is a potential for Capacitor Units to become charged they shall not be handled unless they are short-circuited. 9.3 Before the application of a Short-Circuiting Lead to a Capacitor Unit the Capacitor Unit shall be discharged using a Discharge Stick(s). 9.4 If a clip-on Short-Circuiting Lead has been applied then before a Capacitor Unit is removed from a Capacitor Rack the clip-on lead shall be replaced by a bolt-on Short-Circuiting Lead. 10. PROCEDURE FOR WORK ON HIGH VOLTAGE MECHANICALLY SWITCHED CAPACITORS WITH DAMPING NETWORK (MSCDN). GENERAL REQUIREMENTS FOR ALL WORK (CAPACITOR, REACTOR, RESISTOR) 10.1 The Capacitor Bank shall be Isolated, Points of Isolation established and Primary Earths applied. 10.2 The Control Person shall ensure that the time delay between de-energisation and the first Primary Earth being applied via the earth switch is a minimum of 20 minutes. This is to allow sufficient time for the Capacitor Bank to discharge via the Capacitor Unit discharge resistors. 10.3 Only when Isolation has been completed and Primary Earths applied can access to the MSCDN enclosure be gained by the use of a Castell key arrangement and demarcation erected in accordance with PSSI 6 (OPSAF-10-006). 10.4 A Permit for Work shall be issued. 10.5 Apply a Drain Earth between the capacitor and the reactor on all three phases. (See Fig 3) 10.6 At no time shall a distance of 0.8m be encroached to any High Voltage conductor until earths are applied and capacitors discharged. On all Capacitor Stacks, apply Rack Earths and discharge the capacitor connections in a sequential manner from ground level up to a height of 3m. The sequence to be followed is: (i) On the first Capacitor Stack earth the lowest Rack Earth Spigot using a Rack Earth. The Rack Earth shall be applied using an Approved earthing rod. (ii) Discharge all of the Capacitor Units on this Capacitor Rack using a Discharge Stick connected to the substation earth tape, the two crook ends of the Discharge Sticks being applied to the capacitor terminal bushings to short out Capacitor Unit terminals. (iii) Earth the next lowest Rack Earth Spigot and discharge the Capacitor Units in that Capacitor Bank. (iv) Apply the same principle to Capacitor Rack(s) in the same Capacitor Stack up to 3m from ground level. As this process extends up the Capacitor Stack the Discharge Stick may be connected to an earthed Rack Earth Spigot if this is more convenient, providing the distance of 0.8m is not encroached to any High SP Power Systems Limited Page 6 of 13 MSP 2.12

Voltage apparatus that is either not Earthed or, as in the case of Capacitor Units, not discharged. (v) Complete this sequence for the remaining Capacitor Stack(s) 11. PROCEDURE FOR WORK OR TESTING ON CAPACITOR BANK ASSOCIATED WITH MSCDN In addition to the completion of section 10 above the following shall be carried out to all phases of the Capacitor Bank: 11.1 If work is to be performed on any Capacitor Bank component then an Earthing Schedule shall be issued by the Senior Authorised Person stating where Drain Earths and Rack Earths are to be applied and where the Discharge Stick needs to be used. The positions for the application of Rack Earths shall include: (i) On the Capacitor Stack to be worked on all Rack Earth Spigots from ground level to the one above the point of work. (ii) Additional points where a disconnection is planned to ensure either side of the disconnection point remains connected to earth. (iii) Any additional position as deemed necessary by the Senior Authorised Person. 11.2 A Permit for Work or Sanction for Test shall be issued for the capacitor components on which work or testing is to be carried out. In addition to the positions of the Primary Earth(s) the Safety Document shall also record the positions of the Rack Earths and Drain Earths; it may do this by including a cross-reference to the Earthing Schedule. 11.3 Before performing any work on a Capacitor Bank the recipient of the Safety Document shall ensure that: (i) Capacitor Banks are visually inspected at a distance greater than 0.8m from exposed capacitor components in order to identify any abnormal Capacitor Unit(s). (ii) Drain Earths and Rack Earths are applied in accordance with the issued Safety Document and Earthing Schedule where applicable. (iii) Capacitor Unit(s) in a parallel group are discharged using a Discharge Stick connected to the Rack Earth Spigot, the crook ends of the Discharge Stick being applied to the capacitor terminal bushings. The Discharge Sticks shall be operated by the recipient of the Safety Document or a Person under his Personal Supervision. At no time shall a distance of 0.8m be encroached to any High Voltage apparatus until earths are applied and capacitors discharged as described above. SP Power Systems Limited Page 7 of 13 MSP 2.12

11.4 When testing requires the removal of earths and special requirements to allow subsequent access to Capacitor Units, these actions shall be carried out by, or under the Personal Supervision of, a Senior Authorised Person under a Sanction for Test. 11.5 When working on any Capacitor Rack all Capacitor Racks from ground level to the one above that to be worked on shall be discharged. (See Fig 4). 11.6 When any Person is in contact with a Capacitor Unit, the Capacitor Unit shall remain shorted by the Short Circuiting Lead unless the testing process requires the Short Circuiting Lead to be removed. 11.7 On completion of testing, Capacitor Units shall be discharged using a Discharge Stick by a Senior Authorised Person or under the Personal Supervision of a Senior Authorised Person and all Short Circuiting Lead(s) re-applied. 12. PRECAUTIONS FOR WORKING ON A REACTOR ASSOCIATED WITH MSCDN The requirements of Section 10 above shall be fulfilled, no additional precautions are required. 13. ADDITIONAL PRECAUTIONS FOR WORKING ON A RESISTOR ASSOCIATED WITH A MSCDN In addition to the completion of Section 10 above the following shall be carried out: 13.1 A Drain Earth(s) shall be connected at the input terminals to the resistor that are not already connected to earth. 14. PERFORMING CAPACITOR MEASUREMENTS In addition to the completion of Section 10 and 11 above the following shall be carried out: 14.1 Before and after performing capacitance measurements, the Capacitor Unit(s) in a parallel group shall be discharged using a Discharge Stick by a Senior Authorised Person or under the Personal Supervision of a Senior Authorised Person and all Short Circuiting Lead(s) re-applied. 15. PROCEDURE TO BE APPLIED WHEN CAPACITOR UNIT HAS DISRUPTIVELY FAILED Industry experience of Capacitor Unit(s) suggests that there may not be visible signs of disruption on the Capacitor Unit case or bushings. Abnormal capacitor failures are Capacitor Units showing signs of excessive bulging, major leaks or broken bushings. On this type of failure there could be an open circuit on the bushing connection lead internally within the Capacitor Unit. In this situation a dangerous voltage may be present on the lead or if the lead was to come into contact with the casing it could make the casing Live at some point during removal or transportation. Where there is no cause for concern that an open circuit exists, the Capacitor Unit shall be removed using the procedure described in section 10 and 11 above. Where there is evidence to suggest that the bushing has been damaged and an open circuit may exist in the Capacitor Unit casing then an Approved Procedure shall be written. A person with specialist knowledge of capacitors, their construction, failure modes and removal from service shall be consulted. SP Power Systems Limited Page 8 of 13 MSP 2.12

16. DIAGRAMS (Fig 3) The position of Drain Earths between any Capacitor Bank and any Reactor. SP Power Systems Limited Page 9 of 13 MSP 2.12

Capacitor Rack to be worked on Rack Earth Spigot Rack Earths connected to Substation earth bar. (Fig 4) Diagram showing discharge & shorting arrangements SP Power Systems Limited Page 10 of 13 MSP 2.12

Minimum 0.8m (Fig 5) Discharge Stick. The Discharge Stick comprises two identical sticks minimum length 0.8m beyond the hand grip, with leads connected to a common clamp for attaching to the substation earth tape or Rack Earth Spigot which itself has been earthed. This enables the terminals of Capacitor Units to be shorted together and discharged simultaneously. (Fig 6) Temporary Short- Circuiting Lead applied to Capacitor Unit before disconnecting capacitor unit. SP Power Systems Limited Page 11 of 13 MSP 2.12

(Fig 7) Bolted Short- Circuiting Lead applied to Capacitor Unit. (Fig 8) Capacitor Unit can now be removed. SP Power Systems Limited Page 12 of 13 MSP 2.12

(Fig 9) Rack Earth Spigot, showing Rack Earth applied SP Power Systems Limited Page 13 of 13 MSP 2.12