EUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS. FCP 2008 testing procedures FCP acoustical test method pag. 1

Similar documents
Sound Rating of Ducted Air Moving and Conditioning Equipment

The diagram below. to the by the. outlet into. calculation. Since TRANSMISSION VIA STRUCTURE. Vibration Via Supports Duct Breakout

Air distribution systems. Linear whirl outlet WL...

VK2 volume flow controller Overview

ECMA Measurement of airborne noise emitted and structure-borne vibration induced by small air-moving devices Part 1: Airborne noise measurement

BNA Series. PLENUM FAN with Backward Wheels

ISO INTERNATIONAL STANDARD. Acoustics Acoustic insulation for pipes, valves and flanges

Addendum to ARI Standard , Air Terminals September 2002

ISO 5136 INTERNATIONAL STANDARD. Acoustics Determination of sound power radiated into a duct by fans and other air-moving devices In-duct method

DETERMINATION OF AIRBORNE SOUND POWER LEVELS EMITTED BY GEAR UNITS

Turbines and turbine sets Measurement of emitted airborne noise Engineering/survey method

Operation and sound power characteristics of cooling fans in surrounding structures

ISO INTERNATIONAL STANDARD

Sound power level measurement in diffuse field for not movable sources or emitting prominent discrete tones

Air distribution systems. Radial outlet RA-N2...

WISE Damper. Active damper for Swegon s WISE System for demand-controlled ventilation QUICK FACTS

Standard ECMA-108 3rd Edition - December Measurement of High-frequency Noise emitted by Information Technology and Telecommunications Equipment

Standard Test Method for Measuring Acoustical and Airflow Performance of Duct Liner Materials and Prefabricated Silencers 1

Ecolibrium. All natural. A new style for supermarkets? THE OFFICIAL JOURNAL OF AIRAH AUGUST 2017 VOLUME 16.7 RRP $14.95

BV SERIES. VERTICAL BLOWER COIL UNITS Nominal Sizes 2 thru 10 Ton

ISO 3741 INTERNATIONAL STANDARD

TFI Report Sound Absorption Impact Sound Insulation

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

TFI Report Sound Absorption Impact Sound Insulation

Twin City Fan Companies. Fan System Effects

Standard Practices for Air Speed Calibration Testing

VRF Technical Data Book

TFI Report Sound Absorption Impact Sound Insulation

Test Report. RI Acoustic Lab. Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier. 20 Feb. 07

CNA-CNB. Centrifugal fans

Method of Measuring Machinery Sound Within an Equipment Space

Circular air volume controller RWOA

ISO INTERNATIONAL STANDARD

INTERNATIONAL STANDARD

LINEAR SOURCES WITH NON-LINEAR DISTRIBUTION OF SOUND ENERGY. Miroslav Kučera, Richard Nový, Jiří Bašta

Measurement of Acoustic Properties of light weight concrete SL-Deck

TFI Report Sound Absorption Impact Sound Insulation

COMPARISON OF THE METHODS TO CALIBRATE THE DIFFUSE FIELD SENSITIVITY OF LABORATORY STAND- ARD MICROPHONE

Test Report EN (2008)

Air distribution systems. Adjustable induction outlet IN-V...

EXPLODED DIAGRAM - PARTS VIEW

XHDU Cassette type fan-coils for double/four pipe connections 1,98-14 kw HYDRONIC TERMINALS

Two mark questions and answers UNIT I BASIC CONCEPT AND FIRST LAW SVCET

FAN TERMINOLOGY. t = 1.2 kg/m 3 (Standard air density at 20 C and 1013mb. V = duct air velocity, m/s.

Evaluation of standards for transmission loss tests

Krantz Components. Twist outlet DD-N... for ceiling installation. Air distribution systems

Mechanical flow-rate controllers

Worth noting. Introduction. Key figures. lindab architect. Picture 1. Architect Circum, Luna and Prisma.

Supply air beam. Contact, Overview, Index. Guideline heating and cooling. Plexus. Professor / Professor Plus. Premum / Premax / Solus.

Slot diffusers. Slot diffusers, Round duct diffusers. Slot diffusers. Slot diffusers LD-13, LD-14

Krantz. RL-C2 radial slot outlet. Air distribution systems

EXPERIMENTAL INVESTIGATION OF NOISE PARAMETERS IN HVAC SYSTEMS

Product Data. CAPVU Evaporator Coil A Coil --- Uncased Upflow, Downflow CAPVU

Rectangular air volume controller RWPA

Laboratory for Acoustics. Determination of the sound insulation of sliding door constructions, manufactured by Metaflex

Nozzles. About Lindab. Comfort and Design. Product overview / symbols. Theory. Ceiling diffusers. Ceiling diffusers - visible.

MODEL: WB009GMFI19HLD (120V) Wall Mount DC Inverter Fan Coil Unit 9,000 BTUH

Part 2: Methods for special reverberation test rooms

Air distribution systems. Adjustable radial outlet RA-V...

Influence of Geometry of Channel on the Flow Noise Parameters

Consultancy Report Ref: 9383-R01

Technology. Table of contents. Terms Terms and conversion factors Formula collection Fans, general Audio report...

CDD/CDR. Circular ceiling diffuser for supply air QUICK FACTS

variable flow dampers

Krantz Components. Variable twist outlet with guide ring DD-VL... jet straightener DD-VG... Air distribution systems

LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION COEFFICIENTS OF OSCAR EVO-PANELS

Krantz. Variable twist outlet with guide ring DD-VL... jet straightener DD-VG... Air distribution systems

Supply air beam. Contact, Overview, Index. Guideline heating and cooling. Plexus. Professor / Professor Plus. Premum / Premax / Solus.

DBS315 1-phase SIDE CHANNEL BLOWERS

Report. Draft. Laboratory for Acoustics

Review of Anemometer Calibration Standards

Air distribution systems. Jet nozzle DW-N2... Swivel jet nozzle DW-V2... Twist nozzle DW-V2-...-DR

ALUMINIUM CENTRIFUGAL FANS. 4 x M6 x OUTLET x M6 x 20

ALUMINIUM CENTRIFUGAL FANS x M6 x x M6 x 16

Introduction to Acoustics Exercises

Testing Procedure: AS ISO

Sound Power Measurement of Domestic Boilers

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 7MM TESTED WITH A 20MM AIR GAP IN A REVERBERATION ROOM.

AC axial compact fan

Swirl Diffuser. Type SDW T 2.2/1/B/1. recommended for room heights from approx m

ISO INTERNATIONAL STANDARD

2/S12 DIFFUSER FOR HORIZONTAL OR VERTICAL DISCHARGE DHV. v 3.3 (en)

Sound power level determinations at laboratory and field environments: An experimental comparison

NEO-V. Smoke Control Damper SMOKE CONTROL FUNCTION APPLICATION DESCRIPTION. in libraries of

CDD/CDR. Single cone ceiling diffusers for supply air. Quick facts. Quick guide CDD/CDR A I R F L O W - S O U N D L E V E L

R- 410A R-22 Size (tons) Shipping Weight (lbs) WLAU184AA 1-1/ WLAU182AA 1-1/ WLAU244AA. Model /2

Treatment of Tonal Sound in the Development of Fan Sound Ratings

Swirl Diffusers Type DLA 7 and DLA 8

Sound-Absorbing and Insulating Enclosures for Ultrasonic Range

ALC. ALBATROSS Supply air terminal for large airflows

CONFIGURABLE CROSS-FLOW HEAT RECOVERY UNITS CADB/T-N Series

Product Data. CNPVP, CNRVP, CNPVT, CNRVT, CNPVU, CNRVU Evaporator Coil N Coil Cased and Uncased Upflow, Downflow

THE ACOUSTIC IMPEDANCE MEASUREMNET SYSTEM USING TWO MICROPHONES

IS INTERNATIONAL STANDARD. Acoustics - Determination of sound power levels of noise sources using sound intensity - Part 2:

MEASUREMENTS OF SOUND ABSORPTION TIMBERCRETE

Air Cooler Industry AC-LN 1-7 / ACA-LN 2-7 / ACAF-LN 2-7

SVH with HYDROVAR (HVL range)

Modeling and simulation of windows with noise mitigation and natural ventilation

ISO 354 INTERNATIONAL STANDARD. Acoustics Measurement of sound absorption in a reverberation room

THE ENERGY 68,SAVING TDVI. exible Combine Modular 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP 60, 62, 64, 66 HP

Transcription:

EUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS FCP 2008 testing procedures FCP acoustical test method pag. 1

CONTENTS 1 - PURPOSE... 3 2 - NORMATIVE REFERENCES... 3 3 - DEFINITIONS... 3 3.1 - Ducted Fan Coil Unit... 3 3.2 - Sound Pressure: p... 3 3.3 - Sound Power: w... 3 3.4 - Sound Pressure level Lp... 3 3.5 - Sound Power level Lw... 3 3.6 - Frequency range of interest... 4 3.7 - Reverberant sound field... 4 4 - TEST METHOD... 4 5 - TEST SET-UP... 4 5.1 - Reverberation room... 4 5.2 - Equipment location... 4 5.3 - Operating conditions... 5 6 - TEST PROCEDURE... 5 6.1 - Measurement of sound pressure level... 5 6.2 - Measurement of background noise and reference sound source... 5 6.3 - Additional quantities to be measured... 6 6.4 - Calculation of sound power level... 6 7 - UNCERTAINTIES OF MEASUREMENTS... 6 8 - PRESENTATION OF THE RESULTS... 6 FCP 2008 testing procedures FCP acoustical test method pag. 2

1 - PURPOSE The purpose of this document is to describe the measurement method of Ducted Fan Coil Units sound power level, at speeds of choice with an available static pressure equal to 50 Pa at medium speed. The sound power levels are calculated in frequency bands from sound pressure level measurements in a double reverberation room. The test results describe the performance of the FC in the real condition of build installation where, as usual, the static pressure is fixed at medium speed. 2 - NORMATIVE REFERENCES - ISO 3741:1999 Acoustics -- Determination of sound power levels of noise sources using sound pressure - Precision methods for reverberation rooms - EN 1397:2001 Heat Exchangers Hydronic room fan coil units Test procedure for establishing the performances 3 - DEFINITIONS 3.1 - Ducted Fan Coil Unit the ducted FC is a factory-made assembly which provides the functions of cooling and/or heating air using hot or chilled water with air flow to the room ensured by one or more electrically driven fans. Fan Coil Units may be of the chassis style, concealed within the building structure with ducting appropriately connected to the inlet and/or outlet of the unit. The principal components are: one or more heat exchangers one or more fans with electric motors an appropriate enclosure condensed water collecting facilities when cooling air filter discharge plenum 3.2 - Sound Pressure: p Fluctuating pressure added to the static pressure by the presence of a sound. 3.3 - Sound Power: w Total sound energy radiated by the UUT per time unit. 3.4 - Sound Pressure level Lp L p = 20 1og 10 ( P/Po) (db) (1) where: P is the mean square sound pressure (Pa) Po is the reference sound pressure (2*10-5 Pa) 3.5 - Sound Power level Lw L w = 10 1og 10 (W/Wo) (db) (2) where: W is the sound power (W) is the reference sound power (1 picowatt) W o FCP 2008 testing procedures FCP acoustical test method pag. 3

3.6 - Frequency range of interest The frequency range of interest includes the one-third octave bands with centre frequencies between 100 and 10000 Hz. 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 6300 8000 10000 3.7 - Reverberant sound field The portion of the sound field in the test room over which the influence of sound received directly from the source is negligible. 4 - TEST METHOD It is generally recognized that the sound spectrum of fan coil units contains sometimes discrete frequency components. The testing method allows therefore the determination of the sound power of sources emitting discrete frequency sounds, in compliance with ISO 3741 requirements. 5 - TEST SET-UP 5.1 - Reverberation room Sound measurements of ducted Fan Coil Units are performed in a double reverberation room, which shall be qualified for the measurement of broad-band noise according to the Standard ISO 3741 (appendix E). Since the sound spectrum of fan coil units usually contains discrete frequency components it would be useful to qualify the room for the measurement of this type of noise always in agreement with the Standard ISO 3741 (appendix A). 5.2 - Equipment location In the inlet, radiated and outlet sound power level measurements of ducted FC, the unit shall be installed as similar as possible like shown on Figure 1. DISCHARGE REVERBERATION CHAMBER SUCTION REVERBERATION CHAMBER OUTLET SOUND POWER INLET + RADIATED SOUND POWER Figure 1 : Scheme of installation of ducted FC in the reverberation rooms N.B. the insulation partition between the reverberation rooms is built by high density material (> 50 kg/m 3 ) and shall have a deepth of at least 200 mm. The outlet ducts (for lateral and frontal spigot units) shall have the following characteristics: - they shall contain all the spigots of the discharge plenum of the unit. FCP 2008 testing procedures FCP acoustical test method pag. 4

- the minimum distance between the lateral outlet spigot and the side plenum wall shall be 0,5 x hydraulic diameter - the maximum discharge plenum height shall be lower than 1,25 x the unit height - the angle of the restriction between the discharge plenum and the damper must lower than 15 - the discharge plenum length must be longer than two hydraulic diameters (of the rectangular plenum section) defined in the ISO 5801 standard - they shall be acoustically insulated - No flexible pipes shall be used in the acoustical measurements set-up N.B. see 6.2 paragraph of Eurovent 6/10 document figures There should not be any additional resistance on the UUT air suction except the normal operating filters included by the manufacturer. 5.3 - Operating conditions Acoustical measurements of Ducted Fan Coil Unit shall be carried out in compliance with the following requirements: - at 20 ± 5 C, in isotherm and stationary conditions - at zero heat load - at the operating conditions measured in the air flow-rate test - the speeds of choice has to be hard wired to the motor fan - discharge plenum installed - air filter installed The electrical wiring shall assure the control and the stability of the normal supply voltage of the equipment. The fan impeller speed at maximum speed shall be measured and considered as a parameter fixing the working point and it shall not vary more than 1% in 15 minutes after at least half an hour of work at maximum speed. In order not to introduce external noise, during the acoustic tests, the working conditions recorded during the air-flow rate test (available static pressure and rotational speed) shall be performed by using the reconditioning blowers of the reverberation rooms. 6 - TEST PROCEDURE 6.1 - Measurement of sound pressure level The sound pressure level spectrum of the unit in one-third frequency bands shall be measured in sequence for each speed of choice. Between the measurements it is important to wait some time to have more stability in the operating conditions written above. If the sound pressure level spectrum contains some discrete frequency components in one or more bands, this shall be recorded and written in the test report. 6.2 - Measurement of background noise and reference sound source The background noise in one-third frequency bands shall be measured for each speed of choice without the equipment running while the reconditioning system is set as for the sound pressure level acquisition of the unit for each speed of choice. Between the measurements it is important to wait some time to have more stability in the operating conditions written above. This background noise shall be at least 6dB below the sound pressure level measured in each frequency band of the frequency range of interest.the corrections for background noise shall be calculated according to the ISO Standard 3741 Paragraph 8.1.4. FCP 2008 testing procedures FCP acoustical test method pag. 5

If the comparison method is used, the reference sound source sound pressure level with the reconditiong system set used for the maximum speed of choice for each chamber shall be measured. 6.3 - Additional quantities to be measured In addition to the quantities defined in the acoustical standard required for the calculation of emitted sound power, all the parameters that allow the determination of the operating point of the fan coil unit on test shall be measured. In particular shall be measured the following parameters: Rotational speed Supply voltage Current Power input Dry and Wet bulb temperatures of each room Barometric pressure Differential pressure in the inlet chamber Available static pressure at the discharge air-way cross section of the unit 6.4 - Calculation of sound power level The sound power level of the unit shall be calculated in each one-third octave frequency band from the sound pressure level measured in the reverberation room as described in the comparison method of ISO 3741, where the measured sound pressure levels are compared with the sound pressure levels produced in the same room by a reference sound source of known sound power output. In the comparison method, all of the measured one-third octave band sound pressure level data shall be converted to one-third octave band sound power levels using the following formula. L w(n) = L p(n) + [L wr(n) L pr(n) ] (3) where: L w(n) is the test unit sound power level, db, in the n th one-third octave band L p(n) is the test unit measured sound pressure level, db, in the n th one-third octave band L wr(n) is the RSS sound power level, db, in the n th one-third octave band L pr(n) is the RSS measured sound pressure level, db, in the n th one-third octave band 7 - UNCERTAINTIES OF MEASUREMENTS The uncertainties of measurement shall not exceed the values specified in the ISO 3741 standard. 8 - PRESENTATION OF THE RESULTS The test report shall include: - Sound power levels per one-third octave band for all the operating points of the ducted Fan Coil Unit. In detail, the following characteristics shall be reported: inlet + casing radiated sound power level spectrum outlet sound power level spectrum - A weighted sound power level expressed in db (A) calculated from the spectrum according to ISO 3741 Annex F for all sound powers measured. FCP 2008 testing procedures FCP acoustical test method pag. 6