CIGRE US National Committee 2015 Grid of the Future Symposium. Setting-less Protection: Laboratory Experiments and Field Trials

Similar documents
TRANSMISSION lines are important components of modern

PROTECTION OF SYNCHRONOUS GENERATORS AND INDUCTION GENERATORS

Trajectory Sensitivity Analysis as a Means of Performing Dynamic Load Sensitivity Studies in Power System Planning

Implementing an Intelligent Error Back Propagation (EBP) Relay in PSCAD TM /EMTDC 4.2.1

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications

A New Novel of transverse differential protection Scheme

Module 3 : Sequence Components and Fault Analysis

High Impedance Faults Detection Technique Based on Wavelet Transform

Railway Research. Study of Superconducting Fault Current Limiter Device in a AC Railway System. 1. Introduction. International Journal of

ELG4112. Electromechanical Systems and Mechatronics

Hybrid Time Domain Simulation: Application to Fault Induced Delayed Voltage Recovery (FIDVR)

Optimal PMU Placement for Power System State Estimation with Random Communication Packet Losses

Stability, Protection and Control of Systems with High Penetration of Converter Interfaced Generation

A Comprehensive Approach for Bulk Power System Reliability Assessment

A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2

Fine Tuning Of State Estimator Using Phasor Values From Pmu s

PMU-Based Distributed State Estimation with the SuperCalibrator PSERC Seminar June 17, 2008

Adaptive Distance Relaying Scheme for Power Swing Tripping Prevention

Basics of Electric Circuits

Bulk Power System Reliability Assessment Considering Protection System Hidden Failures

Secured Busbar Differential Protection Using A Computationally Efficient Dot Product Technique

STATE ESTIMATION IN DISTRIBUTION SYSTEMS

Field-Circuit Coupling Applied to Inductive Fault Current Limiters

PMU-Based Power System Real-Time Stability Monitoring. Chen-Ching Liu Boeing Distinguished Professor Director, ESI Center

URTDSM Initiative in India and Controlled Islanding using PMU Measurements

T-PRO Application in Reactor Protection Using Neutral Differential and Timed Over-Current Back-up Protection

Reactive Power Solutions

Fault Location in Distribution Feeders with Distributed Generation using Positive Sequence Apparent Impedance

State Estimation and Power Flow Analysis of Power Systems

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

A Power System Dynamic Simulation Program Using MATLAB/ Simulink

APPLICATIONS OF CONTROLLABLE SERIES CAPACITORS FOR DAMPING OF POWER SWINGS *

ELECTRICAL ENGINEERING

AVOLTAGE SAG is a short-duration reduction in rms

Introduction to State Estimation of Power Systems ECG 740

The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of Unbalanced Three Phases Electrical Distribution System

Optimal PMU Placement

Reliability Assessment and Modeling of Cyber Enabled Power Systems with Renewable Sources and Energy Storage

An Efficient Decoupled Power Flow Control Method by use of Phase Shifting Transformers

Grid Issues and Challenges Addressed by High Temperature Superconductor (HTS) Technology

Research on the Effect of Substation Main Wiring on the Power System Reliability Yuxin Zhao 1, a, Tao Liu 2,b and Yanxin Shi 3,c

Power System Security. S. Chakrabarti

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

URD Cable Fault Prediction Model

ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I

Simulation study on operating chara. Author(s) Shirai, Y; Taguchi, M; Shiotsu, M; IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY (2003), 13(2): 18

Modeling of Transmission Line and Substation for Insulation Coordination Studies

Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs

Study of Time Correlation Between Lightning Data Recorded by LLS and Relay Protection

Working Active Power Concept in a Three Phase System

THREE-PHASE CIRCUITS

New Tools for Analysing Power System Dynamics

Effect of core balance current transformer errors on sensitive earth-fault protection in compensated MV networks

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

A PROPOSED STRATEGY FOR CAPACITOR ALLOCATION IN RADIAL DISTRIBUTION FEEDERS

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

NCEES Fundamentals of Engineering (FE) Examination ELECTRICAL EXAM SPECIFICATIONS

Harmonic Modeling of Networks

Fault Calculation Methods

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

NEW DESIGN OF GROUND FAULT PROTECTION

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers

A Generalized Admittance Based Method for Fault Location Analysis of Distribution System

GMD Impacts on Power System Voltage Stability. Komal S. Shetye Research Engineer University of Illinois at Urbana-Champaign

Dynamic state based on autoregressive model for outgoing line of high voltage stations

Transmission and Dispatching Operations Manual

Mitigating Subsynchronous resonance torques using dynamic braking resistor S. Helmy and Amged S. El-Wakeel M. Abdel Rahman and M. A. L.

Study of Transient Behaviour of the Capacitor Voltage Transformer

Comparing the Impact of HEMP Electric Field Waveforms on a Synthetic Grid

Microgrid Modeling Needs: Safety and Dynamic Interaction of Distributed Energy Resources

Critical clearing time evaluation of Nigerian 330kV transmission system

Study on Identification of Harmonic Contributions Between Utility and Customer

Simultaneous placement of Distributed Generation and D-Statcom in a radial distribution system using Loss Sensitivity Factor

Module 6 : Preventive, Emergency and Restorative Control. Lecture 27 : Normal and Alert State in a Power System. Objectives

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

Electromagnetic Torque From Event Report Data A Measure of Machine Performance

EE Branch GATE Paper 2010

High Voltage Capacitors Designed to Avoid Catastrophic Failure Modes

Measurements and Electrical Equivalent Model of Polymer PTC as a Function of Joule Heating Energy

Chapter 1W Basic Electromagnetic Concepts

MAY/JUNE 2006 Question & Model Answer IN BASIC ELECTRICITY 194

LO 1: Three Phase Circuits

Risk Based Maintenance. Breakers using

Magnetic Cores Modeling for Ferroresonance Computations using the Harmonic Balance Method

Wavelet Entropy Based Algorithm for Fault Detection and Classification in FACTS Compensated Transmission Line

KINGS COLLEGE OF ENGINEERING Punalkulam

PATTERN RECOGNITION FOR PARTIAL DISCHARGE DIAGNOSIS OF POWER TRANSFORMER

Determination of Fault Location in Shunt Capacitor Bank through Compensated Neutral Current

An Equivalent Circuit Formulation of the Power Flow Problem with Current and Voltage State Variables

Work, Energy and Power

Superconducting Fault Current Limiter in DC Systems with MLI Fed to IM

A COMPUTER PROGRAM FOR SHORT CIRCUIT ANALYSIS OF ELECTRIC POWER SYSTEMS

Electrical and Magnetic Modelling of a Power Transformer: A Bond Graph Approach

Two-Layer Network Equivalent for Electromagnetic Transients

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study.

Correlation between Lightning Impacts and Outages of Transmission Lines. H-D. BETZ Nowcast GmbH Munich Germany

Power Engineering II. Fundamental terms and definitions

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY /$ IEEE

Transcription:

http : //www.cigre.org CIGRE US National Committee 2015 Grid of the Future Symposium Setting-less Protection: Laboratory Experiments and Field Trials A. P. MELIOPOULOS, G.J. COKKINIDES Georgia Institute of Technology USA P.T. MYRDA Electric Power Research Institute USA B. FARDANESH, G. STEFOPOULOS New York Power Authority USA C. VOURNAS National Technical University GREECE I INTRODUCTION The numerical relay increased its domination to the point that today has almost completely displaced electromechanical and solid state relays. The capabilities of the numerical relays are not fully utilized today; specifically, by and large, they simply mimic the logics that were developed for the electromechanical relays but with much more flexibility. Recent developments towards the digital substation make the numerical relays logical nodes in an automated system that integrates the functions of protection, SCADA, control, and communications. These approaches indicate the recognition that numerical relays offer much more than simply mimicking protection functions of the past. Yet, the logical nodes use the same protection functions, as presently done by numerical relays. Figure 1: Comparison of Estimation Based Protection to Differential Protection In the last few years we have proposed, laboratory tested and validated a new protection approach based on dynamic state estimation. The basic idea of the dynamic state estimation based protection (aka setting-less protection) has been inspired from the differential protection function and can be considered as an extension and generalization of differential protection. A conceptual illustration of the DSE based protection is illustrated in Figure 1. In current differential protection the electric currents at all terminals of a protection zone are measured sakis.m@gatech.edu

and their weighted sum must be equal to zero (generalized Kirchoff s current law). Thus the current differential protection function consists of measuring the sum of the currents and as long as it is zero or near zero no action is taken. The DSE based protection uses as many measurements as available and compares the measurements to the physical laws that the protection zone must obey (not only KCL but KVL, magnetic flux laws, thermodynamic laws, and other as applicable). This comparison is done in a systematic way via dynamic state estimation. The DSE based protection requires measurements in the protection zone (the more the better), a high fidelity dynamic model of the protected zone, and a dynamic state estimation algorithm. All existing measurements in the protection zone are utilized (currents and voltages at the terminals of the protection zone, as well as voltages and currents inside the protection zone, as in capacitor protection, or speed and torque in case of rotating machinery or other internal measurements including thermal measurements). The dynamic model of the device (physical laws such as KCL, KVL, magnetic flux laws, motion laws, thermodynamic laws, etc.) is used to provide the inter-relationship of all measured quantities to the state of the protected zone. When there is no fault within the protection zone, the measurements should satisfy the dynamic model of the protection zone. A systematic way to verify that the measurements satisfy the mathematical model is a dynamic state estimation procedure. The resulting method is a Dynamic State Estimation Based Protection (EBP). When an internal fault occurs, even high impedance faults or faults along a coil, etc., the dynamic state estimation reliably detects the abnormality, by computing the measurements/model discrepancy, and a trip signal can be issued. Because of the ability of the dynamic state estimation to detect even small differences between the measurements and the model, the selectivity and sensitivity of the EBP is very high. II DESCRIPTION OF EBP The estimation based protective relay (EBP) requires the following: (a) the dynamic model of the protected component (zone); (b) Dynamic State Estimation process to test the consistency between the measurements and the model; (c) trip logic of the relay. These steps are discussed next. A. Dynamic Model of the Protected Component The dynamic model of the protected component consists of a set of differential and algebraic equations. In our EBP method the quadratization process is utilized to reduce all high order nonlinearities of the device model to second order or less by introducing additional variables. By this process we can write the quadratized dynamic model (QDM) of any protection zone (component) in an object-oriented way, which means that all component models have the same syntax. The object-oriented modeling approach leads to standardization of the analytics of the EBP relay for any component. The syntax of the measurement model is (the derivations can be found in [7]): M T i dx( t) z( x) = Ymx x( t) + x( t) Fmx x( t) + Dmx + Cm + η t dt M ( ) where x( t) is the state variables, z( t ) is the measurements, η ( t) is the measurement errors. The other elements of the model are parameter matrices and vectors of the specific component. B. Dynamic State Estimation Process A mathematically rigorous and systematic method to test the consistency between the measurements and the model, is by means of the Dynamic State Estimation. There are several (2) 1

ways to formulate this problem. In this paper we convert the dynamical equations into discrete time equations via the quadratic integration method yielding the Algebraic Quadratic Companion Form (AQCF). Note that the AQCF include variables at both time t and t m and past history terms at time t-h. The syntax of the AQCF for the measurements is: M T i z(x) = Yeqx x( t, tm ) + x( t, tm ) Feqx x( t, tm ) + bz ( t h) (4) M where tm = t h / 2 is the mid point between time t and t h, and h is the DSE time step. Details of the integration and derivation can be found in [7]. Next, the states of the component are estimated by minimizing the sum of the squared normalized errors, i.e. the weighted least square method is employed. The optimization problem is: Minimize M M T T i T i (5) J ( x) = η ( t) η ( t) = Yeqx x( t, tm ) + x( t, tm ) Feqx x ( t, tm) + bz ( t h) z(x) W Yeqx x( t, tm ) + x( t, tm ) Feqx x ( t, tm) + bz ( t h) z(x) M M 2 where = diag {,1/ σ i, } W L L and σ i is the standard deviation of the measurement error. The solution of the above optimization problem is given with the following iterative algorithm: M ν + 1 ν T 1 T ν ν T i ν ν x = x ( H WH ) H W Yeqxx ( t, tm ) + x ( t, tm ) Feqx x ( t, tm ) + bz ( t h) z(x ) M where H is the Jacobean matrix: M T ν i i ν H = Ym, x + ( x ) Fm, x + Fm, x ( x ) M C. Relay Trip Logic The consistency between the measurements and the model is tested by examing whether the residuals of the Dynamic State Estimation (the differences between the actual and the estimated measurements) is comparable to the measurement errors. If the errors are much larger than the metering errors, we can conclude that the component model has changed and there must be an internal fault. A systematic way to quantify this comparison is to use the chisquare test [13]. The chi-square test provides the probability that there is no internal fault. A zero probability indicates an internal fault. The trip logic uses an integral of the probablity. The parameters of the integral are user selected. For example the parameters can be so selected as to issue a trip command if the probability remains zero for 1.5 cycles. III EXAMPLE RESULTS For the purpose of comparing the performance of the DSE based protection method with legacy protection functions, an event involving a ground fault at the coil of a transfomer 5% from the neutral. The selected legacy protection function is the differential function. The settings of differential protection are : pickup current ; and differential ratio threshold. The transformer under protection is a 750kVA 7.98kV/0.277kV single-phase saturable transformer. T (6) (7) 2

The transfomer operates normally when at time t = 3.5s, a 5% turn-ground fault near the neutral terminal of transformer happens on the secondary windings. The performance of the settingless proetction and differential protection are discussed next. Setting-less Protection : The results of proposed setting-less protection are shown in Figure 2. The residual and Chi-square are very small while the confidence level (probability) is 100% during normal operation, indicating that transformer is in a good health condition. When the 5% turn-ground internal fault happens at time t=3.5s, the residual and Chi-square decrease rapidly and the confidence level drops to zero. The zero confidence level indicates abnormalities inside the transformer and protection actions should be taken. It is noticed that confidence level is oscillating during the fault period since the internal fault is too small. An integral function is applied to smooth the waveform and a trip decision is taken to protect the transformer, as shown in the figure. 11.42 kv -11.42 kv Actual_Measurement_Voltage_XFMRH_A (V) 67.55 A Actual_Measurement_Current_XFMRH_A (A) -67.51 A 45.57 ma Residual_Actual_Measurement_Current_XFMRH_A (A) -45.55 ma 34.92 Chi_Square 0.266 m 100.00 Confidence_Level 48.25 u 1.000 Trip_Decision 0.000 55.98 us Execution_time (s) 12.60 us 2.045 s 4.500 s Figure 2: Setting-less Protection for Turn-ground Fault 5% from Neutral Differential Protection : The results for the differential protection are shown in Figure 3. At the beginning the differential protection scheme detects almost zero operating current when the transformer is operating normally. At time t = 3.5s, the breaker B2 is suddenly closed and an operating current occurs at the primary side of the transformer. However, the operating current is very small and the maximum differential index K is about 6.2%. The detected differential index K is smaller than the setting (20%). The differential scheme fails to alert the relay about this internal fault. As a consequence, the transformer is not tripped and the fault continues to damage the transfomer. In this example, the setting-less protection method provides better protections than traditional methods. The setting-less protection method provides dependable and secure protection for transformer with additional benefits, such as fast computing speed, and simple settings. The method has been implemented in an object oriented manner where each measurement is an object in a specific syntax. The measurement objects are automatically generated from the dynamical model of the protection zone. The dynamic state estimation is automatically 3

executed using the measurement objects and the dynamic state estimation algorithm. Three algorithms have been tested (Extended Kalman Filter, Constrained Optimization and Unconstrained Optimization). 5.870 A Differential_Current (A) -3.673 A 2.968 A Fundamental_I_op (A) 1.728 A 47.79 A Restraint_I_res (A) 45.85 A 6.211 % Diff_Ratio_Index (%) 3.768 % 1.000 u Trip_Decision -1.000 u 2.074 s 4.500 s Figure 3: Differential Protection for Turn-ground Fault 5% from Neutral IV LABORATORY TESTS The method described in this paper has been extensively tested in the laboratory at Georgia Tech for a variety of protection zones. The laboratory setup is illustrated in Figure 4. Figure IV: Lab Implementation Illustration As illustrated in Figure 4, the WinXFM program generates digital streaming waveforms representing the terminal voltages and currents of the protection zone (power system component) to the NI 32 channel DC/AC converter. Omicron amplifiers receive the analog 4

signals from the NI DC/AC converter and amplify these signals to a range comparable to real output of CTs/PTs (for voltages around 50V and for currents around 5A). The electrical output (voltages and currents) of the Omicron amplifiers are fed into merging units from Reason and GE. The setting-less relay is connected to the process bus and receives data from the merging units. The computer communicates with the merging units with IEC 61850-8-1 and IEC 61850-9-2. It performs the dynamic state estimation and the protection logic. It has been demonstrated that the dynamic state estimation can be performed within the time of consecutive samples. As a matter of fact the algorithms have been streamlined and optimized to the point that the dynamic state estimation is performed in a fraction of the time between samples, even for high sampling rates. We have tested the algorithms with sampling rates of 12 ks/sec. V FIELD DEMONSTRATIONS Presently, we have initiated a project, supported by NYSERDA, for field demonstration of the technology on a 765/345/13.8 kv autotransformer and a 765 kv transmission line. The selected architecture is based on merging units with a process bus and the EBP relay will be connected to the process bus. The EBP will be in monitoring mode only and the data will be stored. Field testing results are not available yet since this project just started. Field results and experience will be reported in future papers. VI ACKNOWLEDGMENT This work is supported by NYSERDA, EPRI and PSERC. Their support is greatly appreciated. VII REFERENCES 1. Mathews, C. A. An improved transformer differential relay, in Electrical Engineering vol.73, no.7, pp.648-648, 1954. 2. Chiesa, N. and H.K. Høidalen, H. K. Novel approach for reducing transformer inrush currents: laboratory measurements, analytical interpretation and simulation studies, in IEEE Transaction on Power Delivery, vol. 25, no. 4, pp. 2609-2616, 2010. 3. M-C. Shin, C-W. Park and J-H. Kim, Fuzzy logic-based relaying for large power transformer protection, in IEEE Transaction on Power Delivery, vol. 18, no. 3, pp. 718-724, 2003. 4. A. Guzmán, N. Fischer, and C. Labuschagne, Improvements in transformer protection and control, in IEEE 62nd Annual Conference for Protective Relay Engineers, pp. 563-579, 2009. 5. A. P. Meliopoulos, G. J. Cokkinides, Z. Tan, S. Choi, Y. Lee, and P. Myrda, Setting-less protection: Feasibility study, in Proceeding of 2013 46 th Hawaii International Conference on System Sciences (HICSS), Maui, HI, USA, Jan. 2013, pp. 2345 2353. 6. R. Huang, E. Farantatos, G. J. Cokkinides, and A. P. S. Meliopoulos, "Substation based dynamic state estimator - numerical experiment," in Proc. IEEE Power Engineering Society Transmission and Distribution Conference and Exposition, New Orleans, 2010. 7. A. P. S. Meliopoulos, G. J. Cokkinides, C. Hedrington, and T. L. Conrad, "The supercalibrator - A fully distributed state estimator," in Proceeding of IEEE Power Engineering Society General Meeting, 2010. 8. F. C. Schweppe, R. D. Masiello, "A Tracking Static State Estimator," IEEE Transactions on Power Apparatus and Systems, vol. PAS-90, pp. 1025-1033, 1971. 5