Peripheral Zne Card Cmpatible with Standard r Dide Bases Up t * devices per circuit (*device range dependant) Individually Cnfigured Zne circuits Shrt = Alarm Optin Intrinsic Safety Optin Nn-latching Optin (frm 50-06 nwards) Alarm Verificatin Optin (frm 50-07b nwards) Current Limited Zne circuits (48mA under Shrt Circuit) Vltage Regulated Zne Circuits S.M.A.R.T. Pwer Management The peratin and functins described in this manual are available frm Sftware Versin Mx5000-050-04 nwards. www.advancedc.cm
Specificatins: Mdels, Sales Order Parts: Applicatins / Limitatins: Cards must be munted lcally t their pwer supply Earth Mnitring circuit must be disabled if perating n the same grund plane as the Fire Panel Vlt free ( Mnitr / Reset Input) Cmpatibility: Mx-5000 Range f Fire Panels Exp-006 Active End f Line Mdule Requires PC Cnfig Tl Versin 6. Onwards fr access t all the cnfiguratin ptins. Requires Panel Versin 50-06 Onwards fr access t the fllwing functinality Class A znes Nn-Latching zne cnfiguratin Requires Panel Versin 50-07b, And Card Firmware Versin.05, Onwards fr access t the fllwing functinality Alarm Verificatin Requires Panel Versin 50-08 Onwards fr access t the fllwing functinality Cnfigurable EOL Item Applicable Standards Specificatin Details EN54-, EN54-8 Operating Temperature -5 C t 40 C Relative Humidity PCB D.C. Supply 95% Nn Cndensing (maximum) mm H x 05mm W x 6mm L 50 grams (assembled with tp plate) (7V t 8V) DC Min Quiescent Current 00mA (Vs =, 8 Znes = Min Lad, EOL = 6K8) Max Quiescent Current Max Current (O/Ps On) Max Alarm Current Zne Circuits Available Zne Current (Iz) Limit 0mA (Vs =, 8 Znes = Max Lad, EOL = 6K8, s Off) 5mA (Vs =, 8 Znes = Max Lad, EOL = 6K8, s On) 00mA (Vs =, 8 Znes = Max Alarm Lad, s On) 8 Radial (Class B) / 4 Lp (Class A), Cnventinal 48mA, Under Shrt Circuit Zne Vltage (Vz) ± 5% Max Line Resistance Radial Zne EOL Mnitr Input Mnitr EOL PBUS EOL Outputs R Cnfigurable (6K8, 4K7 r K9), Advanced Exp-006 AEOL Mdule Vlt Free 0K 50R SELV, Change Over As ur plicy is ne f cnstant prduct imprvement the right is therefre reserved t mdify prduct specificatins withut prir ntice www.advancedc.cm
Table f Cntents Page INTRODUCTION... 4 GENERAL INSTALLATION & OPERATION... 4. MODULE OVERVIEW... 4. BASIC CONFIGURATION... 5. OPERATING MODES... 6.. Mnitr... 6.4 WIRING CONFIGURATION... 7.4. Lp (Class A) Zne Wiring... 7.4. Radial (Class B) Zne Wiring... 7.4. 485 Cmms Wiring... 8.4.4 Supply Wiring... 8.5 DETECTOR PATIBILITY... 9.5. Radial (Class B)... 9.5. Ring (Class A)... 0 CARD CONFIGURATION SETUP.... ADDING A CARD TO THE DESIGN.... OUTPUT CONFIGURATION... INPUT CONFIGURATION... 4 GENERAL TES... www.advancedc.cm
Intrductin The, n-bard I/O mdule, is an internal peripheral fr use with the Mx-5000 range f fire alarm cntrl panels Each card prvides mnitring f up t 8 Radial, r 4 Lp, cnventinal zne circuits. Cards are prtcl Independent. Up t 6 cards may be cnnected t a panel, allwing fr an extra 8 cnventinal zne circuits, and 48 Outputs. Easily cnfigured with the PC Cnfiguratin Tl Can be set t Stand Alne mde and perate independently frm the Fire Panel; using the n-bard relays t reprt Fire, Fault & Earth Fault cnditins. General Installatin & Operatin. Mdule Overview The Mxp-56 Peripheral Zne card ffers 8 individually cnfigurable cnventinal zne circuits, and cnfigurable relay utputs; as well as including an Earth Mnitr circuit in the event that the card is munted remtely t its parent Fire Panel. With up t 6 cards supprted, this allws up t 8 cnventinal zne circuits and an extra 48 SELV relay utputs t be perated frm a single Fire Panel. Each Mxp-56 unit can be cnfigured t perate in either radial (class B) r ring (class A) mde. In radial (class B) mde: Up t 8 Cnventinal znes are supprted per card The EOL can be cnfigured t use a 6K8, 4K7 r K9 EOL (single setting fr all znes). Znes wrk with standard r Schttky dide bases. Cmplies with applicable standard EN54-. Can be cnfigured fr peratin with Intrinsically Safe znes In ring (class A) mde: Up t 4 Cnventinal znes are supprted per card Maximises cverage prtectin (in the event f zne faults). Cmplies with applicable standard EN54-. See Wiring Cnfiguratin fr further details. Cards are generally intended t wrk with an Mx5000 fire panel which is cmmnly referred t as wrking in Peripheral Bus mde; but can als be cnfigured t perate in a Stand Alne mde were cnnectin t a rd party panel is required. See Operating Mdes fr further details. In Peripheral Bus mde, zne behaviur and relay settings are individually cnfigured using the PC Cnfiguratin tl. See Card Cnfiguratin Setup fr further details. A dedicated Mnitr input is prvided t reprt faults back t the parent fire Panel when perating in PBUS mde. In Stand Alne mde this input is used t reset the card in rder t clear latched alarm cnditins. The Mxp-56 Peripheral Zne card makes use f Sftware Mnitring And Real Time Pwer Management techniques in rder t minimise pwer requirements under fault cnditins (such as shrt circuits acrss multiple znes), r when driving int Zne Circuits under Alarm cnditins. The result is lwer pwer requirements, and increased battery life. Requires an Exp-006 Active End f Line Mdule, sld separately. Requires an aprpriate barrier mdule. EN54- cmpliance is nt supprted n I.S znes 4 www.advancedc.cm
. Basic Cnfiguratin Each card cnnected t the 485 Cmmunicatin Line must have its wn address. This address shuld be set s that it matches the crrespnding card within the Advanced PC Cnfig Tl design. Cnfiguratin Defaults: - Earth Mnitr Disabled: This is the required cnditin if the card is expected t share a grund plane with the parent fire Panel, r any ther card which als prvides earth mnitring capabilities. Fr example, if multiple Zne cards are lcated in a remte enclsure, that requires earth mnitring; nly f the cards shuld be set t mnitring mde. Slide switch t the ON psitin t enable the earth mnitr circuit. - Radial (Class B) peratin. Slide switch t the ON psitin t put card int Lp (Class A) mde. - Stand Alne Mde. Slide PBUS switch t the ON psitin t enable Peripheral Bus Mde. In Peripheral Bus mde the card address is set using the Address switches (as depicted abve). In Stand Alne mde the address switches are used t cnfigure the EOL setting: Bit 0 Bit EOL Setting Off Off Default EOL (6K8) On Off 4K7 Off On K9 On On Nt Used (defaults t 6K8) Nte: Bits and current have n functin when perating in stand alne mde. www.advancedc.cm 5
. Operating Mdes The Mxp-56 has peratin mdes: - Stand Alne Mde (DIP Switch Default): The card is cnnected t a rd party Fire Panel via vlt-free relay cnnectins The card uses fllwing default prcessing rules: In Class B: Zne ID Latching Alarm Verificatin Shrt is Fire I.S Mde 4 5 6 7 8 In Class A: Zne ID Latching Alarm Verificatin Shrt is Fire 4 Feature supprted n this zne I.S Mde Unused zne circuits shuld have EOLs fitted (r lp wiring if running in class A) in rder t avid incrrectly reprting faults. The n-bard relays are used t interface t the utside wrld and infrm external mnitring equipment f Fire (relay ), Fault (fail safe peratin) (relay ), and Earth (relay ) Fault cnditins. The signalling relays are glbal t all znes, s while a Fire r Fault can be reprted it cannt be tied-in t any ne particular zne circuit n the card. Therefre in stand alne mde nly ne zne circuit shuld be used fr detectin purpses, r cnversely all zne circuits n the card shuld be perating in the same physical detectin zne. - Peripheral Bus Mde:.. Mnitr The card requires an Mx5000 Fire Panel in rder t perate. In this mde the card prvides maximum flexibility, with the ability t cnfigure each zne independently via the Advanced Cnfiguratin tl. N need t fit EOLs (r lp wiring if running in Class A) n unused znes; unused znes are disabled by the Fire Panel t reduce current drain. Cnfigurable utputs (via Advanced Cnfiguratin tl) The behaviur f the Mnitr input changes depending n the run mde f the card. - In Stand Alne mde the input is used t issue the reset cmmand t the card - In Peripheral Bus mde the input acts as a mnitr. Line State Reset Input Interpretatin Mnitr State EOL Present Nrmal Operatin Mnitr Ok EOL Missing Nrmal Operatin Mnitr Fault Shrt Reset (enfrced n release) Mnitr Fault 6 www.advancedc.cm
.4 Wiring Cnfiguratin.4. Lp (Class A) Zne Wiring Z Z Z Z 4 Out In Out Out Out In In In Lp (Class A) Zne Using Standard Bases [A] + + + + - - - - Lp (Class A) 4 Wire Device Zne Withut Zne Supply Mnitring.4. Radial (Class B) Zne Wiring Z Z Z Z 4 Z 5 Z 6 Z 7 Z 8 Radial (Class B) Zne Using Standard Bases Radial (Class B) Zne Using Dide Bases EOL AEOL Exp-006 + + + + - - - - EOL Radial (Class B) 4 Wire Device Zne Withut Zne Supply Mnitring Ntes: - Fr cmpliance with EN54- an AEOL (Exp-006) must be used with radial znes, regardless f the type f base in use. Please nte that nt all detectin devices are cmpatible with the AEOL (Exp-006) mdule (please refer t - If an AEOL (Exp-006) is in use the EOL cnfiguratin must be set t 6K8. - Up t three 4-wire znes can be supprted using the n-bard relays (in PBUS mde) - If perating in Stand Alne Mde the n-bard relays becme purpse specific and therefre cannt be used in 4-Wire device cnfiguratins. www.advancedc.cm 7
.4. 485 Cmms Wiring Z Z Z Z 4 Z 5 Z 6 Z 7 Z 8 Z Z Z Z 4 [A] Z Z Z Z 4 Z 5 Z 6 Z 7 Z 8 Z Z Z Z 4 [A] Z Z Z Z 4 Z 5 Z 6 Z 7 Z 8 Z Z Z Z 4 [A] Frm Fire Panel 50R EOL.4.4 Supply Wiring Supply wiring with lcal mnitring. Z Z Z Z 4 Z 5 Z 6 Z 7 Z 8 Z Z Z Z 4 [A] Z Z Z Z 4 Z 5 Z 6 Z 7 Z 8 Z Z Z Z 4 [A] Z Z Z Z 4 Z 5 Z 6 Z 7 Z 8 Z Z Z Z 4 [A] 0K 0K GND Fault 0K Ntes: - D nt cnnect multiple mnitr inputs in parallel - Unused Mnitr I/Ps shuld be fitted with a 0K resistr Supply wiring with Remte mnitring. Z Z Z Z 4 Z 5 Z 6 Z 7 Z 8 Z Z Z Z 4 [A] Z Z Z Z 4 Z 5 Z 6 Z 7 Z 8 Z Z Z Z 4 [A] Z Z Z Z 4 Z 5 Z 6 Z 7 Z 8 Z Z Z Z 4 [A] GND Fault 0K 0K 0K Supervising Cm T Peripheral / Lp Input Mdule 8 www.advancedc.cm
.5 Detectr Cmpatibility Table Legend: Nrmal Devices using standard bases wired in a Lp (n EOL required) r Devices using standard bases with an EOL Resistance SD Devices using Shttkey dide bases and an Advanced Active EOL mdule. Value represents the maximum number f devices (+) that can be lst befre zne evaluatin is cmprmised. IS Devices used in a Radial Intrinsic Safety Zne using a 00R Zener Barrier mdule, and an EOL resistance; nly applicable t I.S. capable devices. Nte(s): Tables assume that all devices in a zne are f the same family and type. If mixed families and/r types are used the maximum device quiescent lad shuld be kept t less than ma. An Exp-006 (Active EOL mdule) is required fr Partial Open circuit detectin (EN54-) n Radial (Class B) znes..5. Radial (Class B) Hchiki Maximum Devices Exp-006 Device Type Nrmal SD IS Cmpatible SRA-ET Beam 7 7 0 Yes SPB-ET Beam 0 Yes SPC-ET Beam 0 0 0 Yes SLR-E Optical 0 Yes DCD-AE Heat (RfR/ 60deg) 0 Yes DCD-CE Heat (RfR/ 90deg) 0 Yes HF-4 UV flame DFG-60E Heat (waterprf) 0 0 Yes Yes DFJ-AE Heat (60 deg) 0 Yes DFJ-CE Heat (90 deg) 0 Yes DCD-E-IS RR Heat Yes SLR-E-IS Pht Yes Apll Maximum Devices Exp-006 Device Type Nrmal SD IS Cmpatible Orbis - full range All 7 0 Yes Orbis Optical I.S. Pht 9 Yes Orbis Multi I.S. Pht(with heat) 9 Yes Orbis Heat I.S. Heat Yes Series65 55000-5/6/7 Optical 4 0 Yes Series65 55000-/7//7 Heat (Standard) 4 0 Yes Series65 55000-0//5/6 Heat (LED flash) 4 Series65 55000-0//5/6 Heat (LED flash) 4 0 0 Yes Yes Series65 55000-5-t-0 In 4 0 Yes Nittan Maximum Devices Exp-006 Device Type Nrmal SD IS Cmpatible Sensrtec (0R base) All (except UV) 5 0 Yes Sensrtec (0R base) All (except UV) 7 0 Yes Sensrtec NFD-68P (0R base) UV flame 5 0 Yes Sensrtec NFD-68P (0R base) UV flame 0 Yes Evlutin EVC-P Pht 0 Yes Evlutin EVC-H-A/ EVC-H-C Heat 0 Yes www.advancedc.cm 9
Argus Aurra Maximum Devices Exp-006 Device Type Nrmal SD IS Cmpatible S00 (0R / 0R bases) Pht 0 0 0 N S00 (0R / 0R bases) Pht/Heat 0 0 N S00 (0R / 0R bases) High temp heat 0 0 N S400 (0R / 0R bases) Heat 0 0 N 0-S000-ADV (0R / 0R bases) Pht 0 0 0 N 0-S000-ADV (0R / 0R bases) Pht/Heat 0 0 N 0-S500-ADV (0R / 0R bases) Heat/High Temp 0 0 N System Sensr Maximum Devices Exp-006 Device Type Nrmal SD IS Cmpatible ECO00 (standard base - n resistr) Pht/ Heat 0 0 N ECO00 (standard base - n resistr) Pht 0 0 N ECO004T Heat 0 0 N ECO005 (standard base - n resistr) Heat (RfR) 0 0 N 5TEM (standard base - n resistr) Pht/ Heat 0 0 N 5E (standard base - n resistr) Pht 0 0 N 55TE (standard base - n resistr) Heat (58deg) 0 0 N 45E (standard base - n resistr) Heat (78deg) 0 0 N 55E (standard base - n resistr) Heat (RfR) 0 0 N.5. Ring (Class A) Nittan Device Type Maximum Devices Sensrtec (0R base - n resistr) All (except UV) Sensrtec NFD-68P (0R base - n resistr) UV flame Argus Aurra Device Type Maximum Devices S00 (0R base - n resistr) Pht S00 (0R base - n resistr) Pht/Heat S00 (0R base - n resistr) High temp heat S400 (0R base - n resistr) Heat 0-S000-ADV (0R base - n resistr) Pht 0-S000-ADV (0R base - n resistr) Pht/Heat 0-S500-ADV (0R base - n resistr) Heat/High Temp System Sensr Device Type Maximum Devices ECO00 (standard base - n resistr) Pht/ Heat ECO00 (standard base - n resistr) Pht ECO004T Heat ECO005 (standard base - n resistr) Heat (RfR) 5TEM (standard base - n resistr) Pht/ Heat 5E (standard base - n resistr) Pht 55TE (standard base - n resistr) Heat (58deg) 45E (standard base - n resistr) Heat (78deg) 55E (standard base - n resistr) Heat (RfR) 0 www.advancedc.cm
Card Cnfiguratin Setup. Adding a Card t the Design Expand the Panel (in the Site List ) and select the Peripheral Bus nde; this will bring up a list f available cards that can be cnnected t the peripheral bus in the Device Selectr. Unlike mst peripheral devices the PC4 is represented twice in the Device Selectr Select the desired peratin mde (Class A / B) and add it t the design. The device shuld be added t the same address as the ne set n the card. The selected peratin mde shuld match the mde set n the card; failure t d s will result in a type change errr being reprted against that card, after uplad.. Output Cnfiguratin Output cnfiguratin is perfrmed alng the same line as any ther utput device/pint. If the card is perating in stand-alne mde (but still present in the design, and cnnected t the peripheral bus) these utput settings will have n effect n the relay behaviur. www.advancedc.cm
. Input Cnfiguratin Pint Optins fr Fire Actin Pint Optins fr Nn-Fire Actins Input cnfiguratin is perfrmed alng the same line as cnfiguring any lp device. Setting the Input Actin t N Actin has the fllwing impact: - Input is disabled at the hardware end (verall pwer cnsumptin is reduced) - End f Line resistrs are nt required fr unused inputs. Each Zne circuit can be individually cnfigured t treat shrt circuits as activating/qualifying cnditins; this is dne via the Shrt Circuit Qualifies Actin checkbx. Each Zne circuit can be individually cnfigured t perate in Intrinsically Safe mde; which is intended fr use nly with an apprpriate I.S Barrier and I.S. Devices. Each zne can be cnfigured fr Alarm Verificatin by setting the Cmfirmatin Filter ptin. T get this ptin the Cnfirmatin Filter must first be enabled under Panel Details General Optins Each Zne can be cnfigure fr Latching r nn latching peratin. Nn Latching znes will reassert an active cnditin 0 secnds after activatin. The default sequence is as fllws: Activatin 0s Reassert Delay s Reset 5s Zne Evaluatin Inhibit Full Mnitring The Zne EOL selectin is an ptin cmmn t all the znes in a card, setting a zne t 6K8 will change the setting n all ther znes fr that card. www.advancedc.cm
4 General Ntes The DC pwer t the Mxp-56 card must always be lcal t the card. ATTENTION OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC SENSITIVE DEVICES This equipment is cnstructed with static sensitive cmpnents. Observe anti-static precautins at all times when handling printed circuit bards. Wear an anti-static earth strap cnnected t panel enclsure earth pint. The unit must be grunded; this is nrmally achieved via the screw terminals used t secure the card t the enclsure. Shuld this nt be the case, a dedicated grund must be prvided. Must be Grunded www.advancedc.cm
This page is intentinally left blank. 4 www.advancedc.cm
USER TES www.advancedc.cm
Dc Number: 680-88 Revisin: First Issued: 0D 0-mm-dd Advanced Electrnics Ltd Mrland Way, Cramlingtn, Nrthumberland, NE WE UK Tel: +44 (0)670 707 Fax: +44 (0)670 707 Email: sales@advancedc.cm Web: www.advancedc.cm www.advancedc.cm